G U L F G R ILL Ese O.
FIREDAMPERS
FD20-VA FIRE DAMPER(VERTICAL MOUNTING)
STANDARD CONSTRUCTION
• Frame 4-7/8" wide x 20 gauge roll formedgalvanized steel.
• Blades Interlocking type, 24 gauge galvanizedsteel.
• Fusible Link: Standard for fusing temperatures of165°F. UL listed. Other fusingtemperatures are available on request.
• Mounting : Vertical.
• Fire Rating : 3 hours.
• Springs : Stainless steel closure springs.
• Finish : Mill galvanized.
Dimensional Detail
'1-+-- Fusible link
H
rt+-- Negator closurespring andblade lock
L~o---W3" U---.l 4-7/8" I--
H48" Max.
H35" Max.
Note: - Dampers for openings larger than maximum single section sizesshown above are assembled from equal size single section dampers.Wand H dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-1
FD20-HA FIRE DAMPER(HORIZONTAL MOUNTING)
STANDARD CONSTRUCTION r:
• Frame : 4-7/8" wide x 20 gauge roll formedgalvanized steel.
r-::;.;=======~'::::=----""-":::1C4-7/8"
7• Blades Interlocking type, 24 gauge
galvanized steel.
• Fusible Link : Standard for fusing temperaturesof 165°F. UL listed. Other fusingtemperatures are available onrequest.
W32" Max.
• Mounting Horizontal.
• Fire Rating 3 hours.
• Springs : Stainless steel closure springs.
• Finish : Mill galvanized.
t f3" 4-7/8"
'-- •.._-_-:...-:...~-=--=--=-_j._-.i__ tC-H--J
. Negator closurespring andblade lock
Dimensional Detail
,--..----- Fusible link
Note: - Dampers for openings larger than maximum single section sizes shownabove are assembled from equal size single section dampers.Wand H dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-2
FD20-V8 FIRE DAMPER(VERTICAL MOUNTING)
• Fusible Link: Standard for fusing temperatures 0*
of 165°F. UL listed. Other fusingtemperatures are available onrequest.
STANDARD CONSTRUCTION
• Frame : 4-7/8" wide x 20 gauge rollformed galvanized steel.
• Blades Interlocking type, 24 gaugegalvanized steel.
• Enclosure 20 gauge galvanized steel.
• Mounting Vertical.
• Fire Rating 3 hours.
• Springs : Stainless steel closure springs.
• Finish : Mill galvanized.
Dimensional Detail
""1 r 3/4'
1\I\..~
I t--
\ I0
Fusible link
Negator closurespring andblade lock
H44" Max.
H31" Max.
0*
L
Note: - Dampers for openings larger than maximum single section sizesshown above are assembled from equal size single section dampers.Wand H dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-3
FD20·HB FIRE DAMPER(HORIZONTAL MOUNTING)
STANDARD CONSTRUCTION
• Frame 4-7/8" wide x 20 gauge roll formedgalvanized steel.
• Blades Interlocking type, 24 gaugegalvanized steel.
• Enclosure 20 gauge galvanized steel.
• Fusible Link: Standard for fusing temperaturesof 165°F. UL listed. Other fusingtemperatures are available onrequest.
• Mounting Horizontal.
• Fire Rating 3 hours.
• Springs : Stainless steel closure springs.
• Finish : Mill galvanized.
Dimensional Detail
Fusible link
~3/4"'----
rlrn'n~--~~f4-7/8"
.............-;--~--I~
W40" Max.
H34" Max.
W32" Max.
o·
Note: - Dampers for openings larger than maximum single section sizesshown above are assembled from equal size single section dampers.Wand H dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-4
FD20-VC FIRE DAMPER(VERTICAL MOUNTING)
STANDARD CONSTRUCTION
• Blades Interlocking type, 24 gaugegalvanized steel.
H44" Max.
• Frame 3-5/32" wide x 20 gauge galvanizedsteel channel.
• .Enclosure 20 gauge galvanized steel.
• Fusible Link: Standard for fusing temperaturesof 165°F UL listed. Other fusingtemperatures are available onrequest. 0*
• Mounting Vertical.
• Fire Rating : 3 hours.
• Springs : Stainless steel closure springs.
• Finish Mill galvanized.
Model FD20-VC (Square or Rectangulardesign provides a nominal 100%free area Fire Damper).
Dimensional Detail
3-5/32"--i ~
Fusible link
Negator closurespring andblade lock
1-3/16"jU \'-1-3/16"
Note: - Dampers for openings larger than maximum single section sizes shownabove are assembled from equal size single section dampers.Wand H dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-5
FD20-HC FIRE DAMPER(HORIZONTAL MOUNTING)
STANDARD CONSTRUCTION
• Frame 3-5/32" wide x 20 gauge galvanizedsteel channel.
~H ~-'/' 30"Max./,
• Blades
~ /7Interlocking type, 24 gauge ~,,~~i-'
galvanized steel. ~,,\\'"f.
1~3~/1«6~"~~~~~~~==~~~~~-,n• Enclosure 20 gauge galvanized steel.
• Fusible Link: Standard for fusing temperaturesof 165°F. UL listed. Other fusingtemperatures are available onrequest.
Lo*--J
• Mounting Horizontal.
• Fire Rating 3 hours.
• Springs : Stainless steel closure springs.
• Finish Mill galvanized.
Model FD20-HC (Square or Rectangulardesign provides a nominal 100%free area Fire Damper).
Dimensional Detail
...---- Fusible link
Negator closurespring andblade lock
L3-5/32"
Note: - Dampers for openings larger than maximum single section sizes shownabove are assembled from equal size single section dampers.Wand H dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-6
FD20-VCR FIRE DAMPER(VERTICAL MOUNTING)
STANDARD CONSTRUCTION
• Blades Interlocking type, 24 gaugegalvanized steel.
• Frame 4-7/8" wide x 20 gauge roll formedgalvanized steel.
• Enclosure 20 gauge galvanized steel.
• Fusible Link: Standard for fusing temperaturesof 165°F. UL listed. Other fusingtemperatures are available onrequest.
• Mounting Vertical.
• Fire Rating 3 hours.
• Springs : Stainless steel closure springs.
• Finish Mill galvanized.
Model FD20-VCR (Round designprovides a nominal 100% free areaFire Damper).
Dimensional Detail
A~~?-~,-,
1\'-- ., 1-
Fusible link
Negator closurespring andblade lock
Note: - Dampers for openings larger than maximum single section sizes shownabove are assembled from equal size single section dampers.D dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-7
FD20-HCR FIRE DAMPER(HORIZONTAL MOUNTING)
STANDARD CONSTRUCTION
• Frame 4-7/8" wide x 20 gauge roll formedgalvanized steel.
• Blades Interlocking type, 24 gaugegalvanized steel.
L D+2-1/2"
• Enclosure 20 gauge galvanized steel.
• Fusible Link: Standard for fusing temperatures of165°F. UL listed. Other fusingtemperatures are available onrequest.
• Mounting Horizontal.
• Fire Rating 3 hours.
• Springs : Stainless steel closure springs.
• Finish Mill galvanized.
Model FD20-HCR (Round design providesa nominal 100% free area FireDamper).
Dimensional Detail
US) e In
r-r- Negator closurespring andblade lock
1/ <, IIRIIII,... "-\Um /.
I I
F ·bl r k
3"
4-7/8"
3"
Note: - Dampers for openings larger than maximum single section sizes shownabove are assembled from equal size single section dampers.D dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-8
FD20-VCO FIRE DAMPER(VERTICAL MOUNTING)
STANDARD CONSTRUCTION
• Frame 4-7/8" wide x 20 gauge roll formedgalvanized steel.
• Blades Interlocking type, 24 gaugegalvanized steel.
• Enclosure 20 gauge galvanized steel.
• Fusible Link: Standard for fusing temperaturesof 165°F. UL listed. Other fusingtemperatures are available onrequest.
• Mounting Vertical.
• Fire Rating 3 hours.
• Springs : Stainless steel closure springs.
• Finish Mill galvanized.
Model FD20-VCO (Oval design providesa nominal 100% free area FireDamper).
Dimensional Detail
I't--+-- Fusible link
L+--t-- Negator closurespring andblade lock
Note: - Dampers for openings larger than maximum single section sizes shownabove are assembled from equal size single section dampers.Wand H dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-9
FD20-HCO FIRE DAMPER(HORIZONTAL MOUNTING)
STANDARD CONSTRUCTION
• Frame 4-7/8" wide x 20 gauge roll formedgalvanized steel.
• Blades Interlocking type, 24 gaugegalvanized steel. 4-7/8"
• Enclosure 20 gauge galvanized steel. 7f• Fusible Link: Standard for fusing temperatures
of 165°F. UL listed. Other fusingtemperatures are available onrequest.
• Mounting Horizontal.
• Fire Rating : 3 hours.
• Springs : Stainless steel closure springs.
• Finish Mill galvanized.
Model FD20-HCO (Oval design providesa nominal 100% free area FireDamper).
Dimensional Detail
,------ Fusible link
Negator closurespring andblade lock
4-7/8"
3"
3"
Note: - Dampers for openings larger than maximum single section sizes shownabove are assembled from equal size single section dampers.Wand H dimension furnished approximately 1/4" undersize.
* See Fire Damper Sizing Chart, on page 15-12.
15-10
FIRE DAMPERINTERLOCKING BLADE,
CURTAIN TYPE FIRE DAMPER WITH SLEEVE.
STANDARD CONSTRUCTION
• Frame 4-7/8" wide x 20 gauge galvanizedsteel channel.
• Blades Interlocking type, 24 gaugegalvanized steel.
• Sleeves Maximum 36" length x· 20 gauge.galvanized steel.
• Enclosures : 20 gauge galvanized steel.
• Fusible Link: Standard for fusing temperaturesof 165°F. UL listed. Other fusingtemperatures are available onrequest.
• Mounting Vertical or Horizontal.
• Finish Mill galvanized.
rH
~
Model : FD25 - CR
r p---~I ",.:- ,I ~",,'lII ,I r I I'I I , I II' : I II ~, , I II I 'I I I: I ~ III I '\ I I,: ••\ I :
1"
Model : FD25 - CR
Model : FD25 - A
36" Max. •..
1H
Model : FD25 - A
r ""M"oiI I I' fI' I I II I , I II , , I
I I I I II I I I II I I : I HI " II 1\,,1 I I
~
I I ,. I II I '\ I II ' 011 ,
Model : FD25 - B
Model: 25CR Low pressure system only.W x H Dimension are equal. Diameteris always W minus 2".
Note:- No additional sleeve is required whenusing's' slip connections.
15-11
FIRE DAMPERSFD SERIES FIRE DAMPER SIZING CHART
p
qr-------,jl
~'-::::;:v..r~:::;I~
r-W+2-1/2" ~
H
r-- D+2-1/2" ~
I-" W+2-1/2" -t
H
FD2o-VAFD2o-HA
FD2D-VBFD20-HB
FD2D-VCFD20-HC
FD20-VCRFD20-HCR
FD20-VCOFD20-HCO
FD Models
FD20-VCH or D FD20-HC
Dimension FD20-VA FD20-VB FD20-VCRFD20-HA FD20-HB FD20-HCR
FD20-VCOFD20-HCO
(in.) p (in.) 0 (in.) 0 (in.)
6 1 7 - 7/16 8 - 5/87 1 - 1/4 8 - 5/8 9 - 3/48 1 - 1/4 9 - 5/8 10 - 3/49 1 - 1/2 10 - 7/8 12 - 3/6410 1 - 1/2 11 - 7/8 13 - 1/3211 1 - 3/4 13 - 1/8 14-5/1612 1 - 3/4 14 - 1/8 15 - 5/1613 1 - 3/4 15 - 1/8 16 - 9/3214 2 16 - 3/8 17 - 9/1615 2 17 - 3/8 18 - 9/1616 2 18 - 3/8 19 - 9/1617 2 - 1/4 19 - 5/8 20 - 3/418 2 - 1/4 20 - 5/8 21 - 3/419 2 - 1/2 21 - 7/8 23 - 1/3220 2 - 1/2 22 - 7/8 24 - 1/6421 2 - 3/4 24 - 3/32 25 - 9/3222 2 - 3/4 25 - 3/32 26 - 1/423 2 - 3/4 26 - 3/32 27 - 9/32.24 3 27 - 3/8 28-9/1625 3 28 - 3/8 29 - 9/1626 3 29 - 3/8 30 - 1/227 3 - 7/32 30 - 5/8 31 - 3/428 3 - 7/32 31 - 5/8 32 - 3/429 3 - 1/2 32 - 7/8 34 - 1/6430 3 - 1/2 33 - 7/8 3531 3 - 1/2 34 - 7/8 36 - 1/6432 3 - 3/4 36 - 1/16 37 - 1/433 3 - 3/4 37 - 5/64 38 - 1/434 4 38 - 3/8 39 - 1/235 4 39 - 3/8 40 - 1/236 4 40 - 5/16 41 - 1/237 4 - 1/4 41 - 9/16 42 - 3/438 4 - 1/4 42 - 9/16 43 - 3/439 4 - 1/4 43 - 5/8 44 - 3/440 4 - 1/2 44 - 7/8 4641 4 - 1/2 45 - 7/8 4742 4 - 3/4 47 - 5/64 48 - 7/3243 4 - 3/4 48 - 5/64 49 - 1/444 4 - 3/4 49 - 1/16 50 - 1/445 5 - -
46 5 - -
47 5 - 1/4 - -
48 5 - 1/4 - -
r:
15-12
FIRE DAMPERSMULTI-SECTION FIRE DAMPER
Model : FD20-VA
Model : FD20-HA
Model : FD20-HA
15-13
FIRE DAMPERSMULTI-SECTION FIRE DAMPER
o
Model: FD2o-VB
Model: FD2()-'HB
Model: FD2o-HB
15-14
FIRE DAMPERSMULTI-SECTION FIRE DAMPER
H
Model: FD20-VC
Model: FD20-HC
Model : FD20-HC
15-15
FIRE DAMPERSMULTI-SECTION FIRE DAMPER
o
D
Model: FD20-VCR
Model: FD20-HCR
15-16
FIRE DAMPERSMULTI-SECTION FIRE DAMPER
H
II '1'Jv------
Model: FD20-VCO
Model: FD20-HCO
15-17
FIRE DAMPERSPERFORMANCE DATA
0.25
en~(f) 0.2WIoZn,0 0.15rr:0wrr:::)(f) 0.10(f)Wrr:n,
0.05
Applicable to FD20-VA, VB, HA, and HB ModelsRecommended for low and medium velocities.
(91-95% FREE AREA)0.3
//~/
~
,y~~
~~I"'~'~t.>V
~~.>: 95% Max rnurnfr~
oo 490 980 1470 1960 2450
DUCT VELOCITY tprn
Applicable to FD20-VC, HC, VCR, HCR, vco, and HCa, ModelsRecommended for high velocities.
(100% FREE AREA)
0.5
OJ~ 0.4(f)WIoZa. 0.30a:0wrr:::) 0.2(f)(f)wrr:a.
0.1
0.6
///
~)~-+-
V --------:-------= (40" x WO)
I
15-18
oo 980 29401980 3920 4900
DUCT VELOCITY fpm
FIRE DAMPERSINSTALLATION INSTRUCTION
VERTICAL INSTALLATIONWALL
1-112" x 1-1/2" x 14 ga.Angles
FIRE DAMPERm>6Nou...:..iwoo:;;: Bolls & Nuls, Tack
welds or steel poprivets 12 max. cc.
1" Min. Over lap(4 sides)
on All Sides
HORIZONTAL INSTALLATION
1" Min. Over lap(4 sides)
FLOOR
1/4" Min. Clearance ----:1'T
Bolts & Nuts, Tackwelds or steel pop --r~~rivets 12 max. cc.
12"
1-112" x 1-1/2" x 14 ga.Angles
FIRE DAMPERDuct ConnectionsModel: FD20-
"HC" "HCR" "HCO"
Model: FD20-"HB" -.-u'----'r6" Max.on All Sides
Model: FD20-"HA"
NOTE: Figures show the vertical and horizontal installation details for a specific requirements forinstallation.
1. Minimum clearance of 1/4" shall be provided between the sleeve and wall or floor openings.2. Sleeve shall be of the same or heavier gauge as the duct to which is attached. Gauges shall
conform to SMACNA or ASHRAE duct standards. Sleeve shall be extended approximately 6"maximum on either side of wall or floor to facilitate the joining of the sleeve to the duct.
3. The following duct sleeve connection may be used on all systems: I. Inside Slip, II. Plain'S' S lip,III. Hemmed'S' Slip, IV.Alternate bar Slip (standard Slip), V. Reinforced standing'S' Slip, VI. SingleSlip, VII. Double'S' Slip, VIII. Cup Slip, IX. Drive Slip, X. Pocket Lock.
4. Mounting angles shall be minimum of 1-112" x 1-W' x 14 ga. fasten to sleeve only, with 1/4" dia. nutsand bolts, tack welds or pop rivets at 12" maximum spacing with a minimum of two connections oneach side, top and bottom. Mounting angles shall overlap wall a minimum of 1" on all four sides.
5. Damper shall be bolted, tack welded or screwed to sleeve on same spacing as angles.
\ \
15-19