Fire Alarm Control Panel
HORING LIH INDUSTRIAL CO., LTD.
CONTENTS
1.System Characteristics 1
2.Control Board Description 2334
2.1 LED Indicators2.2 Keypad Switches2.3 Access Level
3.Wiring Diagram 5
66
3.2 Zone Wiring53.1 Zone Input/Output
3.3 Alarm Bell Wiring77788
3.4 24V DC Output Wiring3.5 Dialler Relay Output Wiring3.6 Fire/Fault Relay Output Contacts3.7 AC Power Connection3.8 Dip-switch instruction
4.Operating Instructions 999
5.Maintenance Instructions 17
6.Trouble Shooting 18
7.General Specifications 20
4.1 Information Function Screen4.2 Menu Description
91111121313
1. All Status Disp.2. Memory Data Disp.3. Main Switch4. Zone Disable5. Memory Data Delete6. Set Up
VIVID32 System Characteristics
2. Available from 1 to 32 zones and modular setting enable.
3. Individual zone disable function.
4. Key switch protection for panel control switches. When the key switch is turned off, the BUZZER, BELL, EVACUATE, RESET switches will be disabled.
5. Protection for withstand voltage can reach up to 2.5KV.
6. Fire Alarm NO, NC, COM & Fault Alarm NO, NC, COM output contact points.
7. Two sets of sounder outputs.
8. Automatic dialer output.
9. LCD screen is 24-digit x 2 lines.
10. Long-term and temporary mute/silence feature.
11. Sounder open/short circuit detection.
12. Output /Input ground fault detection.
13. PCB connection fault detection.
14. Microprocessor- based & digital signal design included.
15. Membrane switch provides longer service and is waterproof, dust resistant and easy to clean.
1. In accordance with EN54 Parts 2 and 4.
1VIVID32OPERATING MANUAL
1. System Characteristics
1. Fire Alarm Indicator
2. Fault Indicator
3. CPU Fault Indicator
4. Power Normal Indicator
5. Disable Indicator
6. Information Display
7. Keyboard Enable Switch
8. “UP” Switch
9. “DOWN” Switch
10. “BACK” Switch
11. “ENTER” Switch
12. Buzzer Mute Switch
13. Alarm Bell Silence Switch
14. Evacuate Switch
15. Reset Switch
16. Zone Indicators (optional)
2VIVID32OPERATING MANUAL
3
7
6
8 9 10 11
12
16
13 14 15
54
1
9
17
25
2
10
18
26
3
11
19
27
4
12
20
28
5
13
21
29
6
14
22
30
7
15
23
31
8
16
24
32
21
2. Control Board Description
3VIVID32OPERATING MANUAL
2.1 LED Indicators1. Fire Alarm Indicator: A red light indicates the Fire Alarm Control Panel has received a fire signal.
2. Fault Indicator: A yellow light indicates a fault in the fire alarm system.
3. CPU Fault Indicator: A yellow light indicates the CPU is not normal .
4. Power Normal Indicator: A green light indicates the Fire Alarm Control Panel is in normal condition.
5. Disable Indicator: A yellow light indicates a zone han been disabled .
6. Information Display: It provides a read-out of system conditions.
2.2 Keypad Switches
7. Keyboard Enable Switch: When the switch is turned on, it means that the keyboard is enable.
8. UP Switch: Pressing this switch shows the previous item on the page. It can also be used to change the time and passwords by increasing the value progressively.
9. Down Switch: Pressing this switch shows the next item on the page. It can also be used to change the time and passwords by decreasing the value progressively.
10. Back Switch: Pressing this switch shows the previous page. When changing the setup of time and passwords, pressing this switch can shift control to the previous decimal place.
11. Enter Switch: Pressing this switch shows the next page. When changing the setup of time and passwords, pressing this switch can shift contorl to the next decimal place.
12. Buzzer Mute Switch: If there is an alarm or fault in the system, pressing this switch can disable the buzzer and the indicator can go on. When a new signal is received, the buzzer function will be restored. If the switch is pressed again, the buzzer function will be restored and the indicator will go out. If the switch is pressed for more than 2 seconds, the indicator will flash and the buzzer will remain disabled despite any new signals.
13. Alarm Bell Silence Switch: If there is an alarm or a fault in the system, pressing this switch can disable the relay output to the bells and the indicator can go on. When a new signal is received, the bell function will be restored. If the switch is pressed again, the bell function will be restored and the indicator will go out. If the switch is pressed for more than 2 seconds, the indicator will flash and the bells will remain disabled despite any new signals.
2. Control Board Description
4VIVID32OPERATING MANUAL
2.3 Access Level
14. Evacuate Switch: Press this switch, and the system can generate an alarm and activate all warning devices.
LEVEL 1Any operations on the UP, DOWN, BACK or ENTER button on the panel board can review status information.
LEVEL 2Turn the “KEYBOARD ENABLE” switch to the “ON” position to access to the LEVEL 2 sothat the BUZZER, BELL, EVACUATE, or RESET button on the control panel is available touse. In addition, Zone Disable, Date/Time, Delay Timer and Backlight Timer can be set up.
LEVEL 3In this level, all operations are based on the LEVEL 2. Enabling “Memory Data Delete”requires to input a 4-digit security code to enter LEVEL 3 in order to clear all memorydata.
LEVEL 4There is a screw (“ ” form) on the side of the panel door. It requires a Phillips screwdriverto turn on to access to LEVEL 4 to change the hardware settings of the main board, suchas DIP switch settings and JUMP settings.
15. Reset Switch: Pressing this switch can reset the panel. The rest indicators will light up and after a 5-second delay, the system will be restored to the surveillance status.
16. Zone Indicators(optional): It shows “disable” & “fault” & “fire alarm” signal in the individual loop. The light of LED is yellow or red.
It shows flash yellow light when fault loops occurred.It shows continuous yellow light when disabled loops occurred.It shows continuous red light when a fire alarm occurred.
2. Control Board Description
5VIVID32OPERATING MANUAL
3.Wiring Diagram
3.1 Zone Input/Output
24V
24V DC
+ - AUX
24V DC
+ -
4.7k
24V DC
SND1+ -
AUX
24V DC
+ -DIALLER
To Dialing RelayOutputDevice
Indicating Lamp 24Vdc Output Sounder 24Vdc Output Dialler Output Fire Relay Output Fault Relay Output
To Relay OutputDevice
FIRE
To Relay OutputDevice
FAULT
Z1 E1+ -
Z2 E2+ -
Z3 E3+ -
Z4 E4+ -
Z5 E5+ -
Z6 E6+ -
Z7 E7+ -
Z8 E8+
+ --
2k
220P
Terminal4.7k
Relay 24V
24V
6VIVID32OPERATING MANUAL
ZN .....P P P P
220 /1W 220 /1W
C.
4.7k
SND1 4.7k
SND2 4.7k
24V DC
Wiring Diagram A is a recommended connection. The maximum number ofconnected smoke detectors is 30 for each zone (not including the mechanic-type heat detectors.)
Wiring Diagram B is an improperly connected one. Do not connect a detectoror an end of resistor with another detector in paralled way.
Wiring Diagram C .When connecting a manual call point to a zone, pleaseuse a 220 Ohm resistor and install the 4.7K ohm end of line resistor.
Fire alarm control panel is equipped with two sets of Area Bells contacts.When connecting one set of bell contacts, please be sure to connect the endof resistor to avoid bell malfunction. Please install the 4.7K ohm resistoracross the unused bell contacts as well.
ZN .....A.
4.7k
ZN
B.
..... 4.7k
3.2 Zone Wiring:
3.3 Alarm Bell Wiring:
3.Wiring Diagram
7VIVID32OPERATING MANUAL
The contacts marked “24V” are controlled by the reset switch but the contacts marked “AUX” are not. When connecting the indicating lamp to the contacts,please connect the red wire to the “+” and the black wire to the “-” contact atthe same time.
The contact is connected with NO. and COM. When there is a fire alram, thesignal will go through the telephone line.
In picture A shows N.O. connection.In picture B shows N.C. connection.
3.4 24V DC Output Wiring:
3.5 Dialler Relay Output Wiring:
3.6 Fire/Fault Relay Output Contacts:
To Relay Output Device
To Relay Output Device
A.
B.
Aux
24V 24V DC
24V DC
DIALLER DialDevice
3.Wiring Diagram
8VIVID32OPERATING MANUAL
Connect the AC power supply wires to contacts 1 and 3.Connect the ground wire to contact 2.
OFF: Set the switch to OFF when the loop has connected to devices.(including detector or sounder).
ON: Set the switch to ON and loop will be setted with internal end-of-line resistor when disconnect device (including detector or sounder).
1~8: It is the place to set internal end-of-line resistor for detector (Z1~Z8).
9: It is the place to set internal end-of-line resistor for sounder.
1: 8 Zones (PCB*1)Set the switch to ON for 1st PCB.
2: 16 Zones (PCB*2)Set the switch to ON for 2nd PCB.Set the switch to OFF for 1st PCB.
3: 24 Zones (PCB*3)Set the switch to ON for 3rd PCB.Set the switch to OFF for 1st & 2nd PCB.
4: 32 Zones (PCB*4)Set the switch to ON for 4th PCB.Set the switch to OFF for 1st & 2nd & 3rd PCB.
10: PCB link detection setting.
3.7 AC Power Connection:
3.8 Dip-switch instruction
For example:
1
2
3
ON ECE
1 2 3 4 5 6 7 8 9 10
Z1 E1 E2+ -
Z2+ -
SND+ -
3.Wiring Diagram
9VIVID32OPERATING MANUAL
4.Operating Instructions
4.1 Informational Function Screen
4.2 Menu Description
Fire Alarm Control Panel is in surveillance status. Alarm=000 Fault=000 2015/01/21 16:38.58
When the control panel receives a fire alarm signal,the screen will show the total number of alarms.
Alarm=001 Fault=002 2015/01/21 16:38.58
When the control panel receives a fault signal,the screen will show the total number of faults.
Alarm=001 Fault=002 2015/01/21 16:38.58
► 1.All Status Disp.2.Memory Data Disp.
► 1.Alarm Status Disp.2.Fault Status Disp.
Main Display
1. All status Disp.2. Memory Data Disp.3. Main Switch4. Zone Disable5. Memory Data Delete6. Set Up
1.Relay Output2.Dialler3.Auto Reset
1.Alarm Status Disp.2.Fault Status Disp.3.Disable Disp.
4.Test1.Data/Time 2.Security Code3.Delay Timer4.Backlight Timer5.Zone Number
1-1. All Status Disp. - Check Alarm Data:
1. All Status Disp.
Press the“on each item.
Enter” switch to see more details
Press the“All Status Disp.
Enter” switch to enter the item 1-
Press the“Alarm Status Disp. to see more details.
Enter” switch to enter the item 1-
Alarm=000 Fault=0002015/01/21 16:38.58
10VIVID32OPERATING MANUAL
4.Operating Instructions
0001 0008 Zone Alarm 2015/01/21 16:38.58
The number in the upper left-hand corner is a sequence of signals. For example, “0001” is thefirst signal. The number in the upper middle screenshows the zone number. The upper right-hand corner shows the type of signal, Alarm or Fault.The lower screen displays the time and date ofthe event.Press the “ Up” or “ Down” switch to switchalarm information.Press the “ Back” switch to return to Alarm StatusDisp. selection list.
Press the “ Down” switch to move to item 2-Fault Status Disp. and press the “ Enter” switchto see more details.
Press the “ Back” switch to return to AlarmStatus Disp. selection list.
Press the “ Back” switch to return to AlarmStatus Disp. selection list.
1-2. All Status Disp. - Check Fault Data:
1-3. All Status Disp. - Check Disable Data:
►
1.Alarm Status Disp.2.Fault Status Disp.
► 2.Fault Status Disp.3.Disable Disp
Zone Disable : 000101 ZONE Disable
0001 AC Fault 2015/01/21 16:38.58
The number in the upper left-hand corner is a sequence of signals. For example, “0001” is thefirst signal. The upper right-hand corner shows thetype of signal (AC or DC power supply/Zone PCB/SND 1~4/5V/24V/ground fault/light board fault/open circuit/short circuit/extended board outlierdetection/CPU malfunction). The lower screendisplays the time and date of the event. Press the“ Up” or “ Down” switch to switch alarminformation.
Press the “ Down” switch to move to item 3-Disable Disp. and press the “ Enter” switch tosee more details.
The upper right-hand corner is a number of thedisabled loops.Press the“ Up” or “ Down”switch in the lower to switch the disabled loops.
11VIVID32OPERATING MANUAL
4.Operating Instructions
2. Memory Data Disp. - Check Memory Data:
3. Main Switch - Main Switch Control:
Press the“
In the upper left-hand corner is a number of theevent.(M001~255) The highest number shows themost recent event. The upper middle screen showsthe zone number. The upper right-hand shows thetype of signal. The lower screen displays the timeand date of the event.
Memory Data Disp. Press the “to enter the Memory Data Disp.
Enter” switchDown” switch to move to item 2-
Press the“3-Main Switch.
Switch selection list.Press the“
Down” switch to move to item
Enter” switch to enter the Main
Press the“the item.
item.Press the“
Up” or “ Down” switch to select
Enter”switch to enter the selection
► 2.Memory Data Disp.3.Main Switch
.M001 0008 Zone Alarm 2015/01/21 16:38.58
M002 0001 Zone Fault 2015/01/21 16:38.58
> 2.Memory Data Disp. ► 3.Main Switch
► 1.Relay Output> 2.Dialler
Press the“event.
Up” switch to check the previous
Press the“event.
Down” switch to check the next
Press the“Display selection list.
Back” switch to return to the Main
12VIVID32OPERATING MANUAL
4.Operating Instructions
3-2. Dialler- Enable or disable the fire alarm dialler output:
3-3. Auto Reset - Enable or disable the fire alarm signal latching or not latching:
3-4.Test - Check all indicators and buzzer :
4. Zone Disable - Disable Fire Alarm Zone :
Note: Enable the Test mode, and all the indicators will shine and the buzzerwill beep. After five seconds, the fire alarm control panel will automatically return to the surveillance status. If a new fire alarm signal is received during test mode, the test mode will be interruptedand the fire alarm control panel will respond to the signal.
3-1. Relay output - Enable or disable the main board relay output:Press the“
output.
Up” switch to enable the relay output. Press the“ Down” switch to disable the relay
Press the“selection list.
Enter” switch to return to Main Switch
Press the“
output.
Up” switch to enable the dialler output. Press the“ Down” switch to disable the dialler
Press the“selection list.
Enter” switch to return to Main Switch
Press the“
reset.
Up” switch to enable auto reset.Press the“ Down” switch to disable the auto
Press the“selection list.
Enter” switch to return to Main Switch
Press the“ Up” switch to enable test.
Press the“ Down” switch to disable the test.
Press the“Zone Disable.
Down” switch to move to item 4-
Press the“selection list.
Enter” switch to return to Main Switch
Press the“ Enter” switch to ener the Zone Disable.
Relay Output
> Enable Disable
Dialler Enable Disable
Auto Reset> Enable Disable
Test Enable Disable
3. Main Switch> 4. Zone Disable
Z01 Disable Enable> Z02 Disable Enable
**
Press the“the zone number.
the zones.
Display selection list.
Press the“
Press the“
Up” or “ Down” switch to select
Enter ”switch to disable or enable
Back” switch to return to the Main
13VIVID32OPERATING MANUAL
4.Operating Instructions
5. Memory Data Delete - Clear All Memory Data:
6. Set Up - Set Control Panel Other Function:
Press the“
Press the“
After the code is finished, press the“
to the next digit. Use the“to a previous digit.
Back ”switch to move
Memory Data Delete. Press the“to enter the Memory Data Delete.
Enter ”switch
switch to raise the value of the digit. Press“Down ” switch to lower the value of the digit.
Down”switch to move to item 5-
Enter ”switch to move the cursor
Enter”switch to delete the memory. Use the“ Back”
To delete the memory, input a 4-digit code, startingwith the left digit (code1). Press the“ Up ”
switch to return to the 4th digit (code 4).
After deleting, the display returns to the MainDisplay selection list.
Press the“Set up.
selection list.Press the“
Down”switch to move to item 6-
Enter ”switch to enter the Set Up
5. Memory Data Delete > 6. Set Up
Input Code:0000Code 1 ^
Input Code:0000Code 2 ^
Input Code:0000 ok?
Input Code:0000 confirm
4. Zone Disable5. Memory Date Delete
14VIVID32OPERATING MANUAL
4.Operating Instructions
6-1. Date/Time - Set up date and time:
Move the cursor to item 1-Date / Time.Press the“Set-up.
Enter”switch to enter the Date/Time
The lower right screen shows the editing item(Edit Year). Press the“value of the digit. Press“the value of the digit.
Up”switch to raise theDown”switch to lower
2015/01/21 16:40.56^ Edit Year
After setting the year, press the“ Enter”switch to edit month.
digit.Use the“ Back”switch to move to a previous
2015/01/21 16:40.56^ Edit Month
After setting the month, press the“ Enter”switch to edit day. Use the“move to a previous digit.
Back”switch to2015/01/21 16:40.56
^ Edit Day
After setting the day, press the“
Use the“digit.
Back”switch to move to a previous
Enter”switch to edit hour.2015/01/21 16:40.56
Edit Hour ^
switch to edit minute.After setting the hour, press the“
Use the“digit.
Back”switch to move to a previous
Enter”2015/01/21 16:40.56Edit Minute ^
Press“of date and time setup.
Enter”switch to complete the setup
Use the“digit.
Back”switch to move to a previous
2015/01/21 16:40.56ok?
After setup is completed, the display returnsto the Set Up selection list.
2015/01/21 16:40.56Complete
►1. Date/Time> 2. Security Code
15VIVID32OPERATING MANUAL
4.Operating Instructions
6-2. Security Code - Security code reset:Press the“
Press the“to item 2-Security Code.
Code.
Down” switch to move the cursor
Enter”switch to enter the Security►2.Security Code
3.Delay Timer
Up”switch to raise the value of thePress the“
To reset the security code, input the 4-digit originalsecurity code, starting with the left digit (code1).
digit. Press the“value of the digit.
Down”switch to lower the
Input Login Code:0000Input Code 1 ^
Press the“to the next digit. Use the“move to a previous digit.
Back” switch to Enter” switch to move the cursor
Input Login Code:0000ok?
Input a new 4-digit security code.Input Set Code:0000Input Code 1 ^
After the code is finished, press the“switch to complete the code setting.
Enter”
Use the“(code 4).
Back” switch to return to the 4th digitInput Set Code:0000
ok?
After setting up, the display returns to the Set Upselection list.
Input Set Code:0000Confirm
16VIVID32OPERATING MANUAL
4.Operating Instructions
6-3. Delay Timer - Set fire alarm signal delay time:
6-4. Backlight Timer - Set LCD backlight timer :
6-5. Zone Number & ROM Edition - Display the control panel version
Move the cursor to item 3-Delay Timer.Press the“Timer.
Enter” switch to enter the Delay
Press the“ Enter” switch to see the details.
Press the“to the Set Up selection list.*Note: Display zone data can be changed via panel
internal setting. Zone disable will also be changed.
Enter”or“ Back ”switch to back
Press the“time setup and back to the previous screen.
Enter” switch to complete the delay
Enter” switch to
Enter” switch. Press the
Up”or “ Down” switch to delay
Up”or “ Down” switch to move the
Press the“
Press the“
Use the“
Move the cursor to item 5-Zone Number.
cursor to the selection you prefer. To make theselection press the““
-Backlight Timer. Press the”enter the Backlight Timer.
Down” switch to move to item 4
time.Delay Timer (Sec) : 10 ok?
Zone Number:32Zones ROM Ver. 091813-1
►2.Security Code3.Delay Timer
Delay Timer3.►4.Backlight Timer
►4 Backlight Timer.5. Zone Number
► 10 Second20 Second
*
Press the“selection list.
Back” switch to return to the Set Up
Back” switch to return to the Set Up selection list.
17VIVID32OPERATING MANUAL
5.Maintenance Instructions
1. Normal Status:
2. Maintenance:
a. In normal operating status, the Power Normal indicator will shine.b.
Maintenance Instructions
If the equipment is installed in a public place, maintenance and testing will disturbpeople. Be sure to inform them beforehand. If the equipment is found faulty, it mustbe fixed instantly and maintained regularly. Please check the current in the powersupply of the fire alarm system, the voltage of the backup battery and also dischargetime of the backup battery. Turn to the test mode to test if all the indicators can shine and buzzers can beep.And also check to see whether any detectors/manual call points are detective or existany broken glass shields or not.Eusure that no faults in the whole wiring system.Make sure if any ground fault is in the AC input contacts.
When AC power fails, the backup battery will supply power. The Fault indictor willshine and the buzzer will sound. The system can continue monitoring for 72 hoursand sound an alarm for 30 minutes.
18VIVID32OPERATING MANUAL
6.Trouble Shooting
Normal Status: This system is composed of several devices and it will be affected bydefective and improper use of detectors, wiring, bells, and manual call points.
1.
a. Use a multi-meter to test the voltage in the AC input contacts.b. Check that the Power Normal indicator can shine or not.c. Inspect whether any fuses are burned out.d. Check that the external devices and wiring are normal or not.Fuse Function: There is a special protective function in the fuses in the panel, so do notuse unspecified or poor quality products. Faulty external wiring and poor quality productswill make fuses burn out.
2.
a. AC: Normal power 220V AC fuse (2A).
a. Check the unused zones to see if the end of line resistors have come adrift.
b. BATT: Backup battery fuse (2A).c. SND1 and SND2: Bell fuse (Auto-reset).d. AUX: Output fuse (Auto-reset).e. 24 V DC: DC power output fuse (Auto-reset).
Reasons for Burned Out Fuses and Inspection Notes:3.
False Bell Alarm: The improper wiring can make the bell sound when no alarm signal isgiven. Please remove the external wiring and then use a multi-meter to test the bell’scontacts which shouldn’t give 24V DC reading. If it meets the mentioned requirement,please check the external wiring.
4.
Zone Abnormal Status (Indicator ON ): According to the statistic, most zone faults are due to incorrect wiring. Some other reasons for fault are improper use and misconnectionto contacts.
5.
a. AC power fuse burn out: Check whether the applied power is over the specified loadand if the specification is correct. (Using a fuse lower than specified load will cause thefuse burn out)
b. Disconnect the zone wiring and connect a 4.7K ohms resistor across the contacts.The fault signal should disappear.
c. If above conditions are met, the control panel is in normal condition. The fault signal may be caused by faulty external wiring. After repairing the external wiring, you mayconnect the wiring to the control panel again.
d. Check whether the external wiring is short circuited or disconnected, detectors havecome adrift or not, and if the end of line resistor in detectors have come adrift or evenwas not installed.
e. Use a multi-meter to check that the resistance across the L(Z+) and LC(Z-) contacts isabout 4.7K ohms.
f. Disconnect the wires connected to the contacts L and LC. Make sure that the voltage across the two wire is 0 volt.
b. Backup battery fuse burn out: Check whether the polarity of the contacts is right.
Trouble Shooting
19VIVID32OPERATING MANUAL
False Zone Alarm Inspection notes: 6.
b. Disconnect the faulty zone and the Zone Alarm indicator will go out and the Zone Fault/Disable indicator will light up. If you would like to make the Zone Faulty indicator go off,you should install the end of line resistor across the L(Z+) and LC(Z-) contacts of theZone. After repairing the wiring, please reconnect the external wiring.
a. Disconnect the faulty zone and check the resistance across the L and LC wires isabout 4.7K ohms.
Trouble Shooting
6.Trouble Shooting
20VIVID32OPERATING MANUAL
7. General Specifications
General Specifications
- Main Power SourceInput Voltage 220V ACFrequency 50Hz-60HzFuse 2A
- Standby PowerBattery Consumption 8L:24V/1.2Ah;16L,24L,32L:24V/4AhCharge Voltage 24V DC/1.2AhFuse 2A
- Single LoopVoltage 20V DCTerminal Resistor 4.7KΩ
Manual Call Point Resistance 220Ω/1WMaximum sensor’s connection ( Smoke Detector) 30
- Area Sounding/ Alarm Voltage 24V DCMaximum Supply Current 2A
Fuse 2A(Auto Reset)Terminal Resistor 4.7KΩ
- Relay OutputMaximum Voltage 250V AC/30V DCMaximum Supply Current 2A(Auto Reset)
- Connecting CableCable’s Semi-Diameter 1.5mmMaximum Supply Current 2A
2
- Ambient TemperatureOperating Temperature -7℃ ~ +45℃
Storage Temperature -10℃~ +70℃
Fuse 2A(Auto Reset)
- AUX & 24V Output VoltageVoltage 24V DCMaximum Supply Current 2A
Instruction Policy (Design, Install, Plan , Usage....) EN54-14
- StandardFire Alarm Control Panel EN54-2Power Source EN54-4
Note
HORING LIH INDUSTRIAL CO., LTD.
www.horinglih.com
VIV ID32 Operating Manual