Fgd Pds Uv Irs Flame Detector

Embed Size (px)

Citation preview

  • 7/28/2019 Fgd Pds Uv Irs Flame Detector

    1/4

    UV/IRS Flame DetectorBCR-0005-00-017

    Product Data SheetNovember 2012

    -

    -

    Net Saetys UV/IRS ( Ultraviolet/Inrared ) ame detector delivers exceptionalperormance with many distinct unctions and eatures. Two precisespectrums o radiation must be recognized and confrmed by highly tunedsensors or the UV/IRS to initiate a fre condition. This accurate and reliableame monitoring technology combined with immunity to arc welding, hotbody radiation, lightning and sunlight greatly reduces costly alse alarmswhile providing critical saety perormance to your site and personnel.

    Two Radiation Wavelengths Necessary For AlarmMinimize False Alarm Events

    Extremely Low Power Consumption Increases

    Uptime and Lowers Overall Costs

    Manual and Automatic Testing o Optical Suraces Constantly Monitors Internal Electronics

    Designed or Extreme Conditions, OperationalFrom -50C +75C

    Global Certifcations and Approvals

    Wide Voltage Range Allows For Greater Stabilityand System Compatibility

    Field-selectable Sensitivity and Delay SettingsAllows Operators To Fine Tune At Installation Site

    Wide Area Coverage, Extended Range with FastResponse Times

    Analog, Relay, RS 485 Digital Modbus, and HARTOutputs Available

    3 Year Warranty Electronics / 2 Years on Sensors

    UV/IRS Flame DetectorUltraviolet and Inrared Optical Sensors

    Enclosed in a rugged, explosion-proo housing, the Net

    Saety UV/IRS ame detector uses the latest in modular

    microprocessor and Ultraviolet/Inrared sensor technology

    delivering accurate and reliable monitoring or hydrocarbon

    based res. Its capable o stand-alone operation or can be

    connected to a variety o networked saety systems to create

    a dependable re monitoring system.

    The UV/IRS Flame Detector has many unique eatures which

    make it one o the industries best: an extra wide eld o view

    up to 120 degrees; user dened sensitivity and time delay

    settings can be completed in the eld with no special tools

    required; one o the lowest power consumption levels and

    widest voltage range available on the market; plus the option

    o a separated HART communication interace at ground level.

    Net Saety has engineered a superior UV/IR ame detector

    that is simple to operate and maintain while delivering

    all the security and perormance required or high-risk,

    industrial installations!

  • 7/28/2019 Fgd Pds Uv Irs Flame Detector

    2/4

    UV/IRS Flame DetectorBCR-0005-00-017

    Product Data SheetNovember 2012

    -

    -

    UV/IRS Flame DetectorSpecifcations

    SMART Gas Detector Series

    ANALOG RELAY HARTOperating Voltage Range 10 to 32 Vdc

    Power Consumptionat 24 Vdc*with Heater

    Nom 45 mA / 1.1 WMax 115 mA / 2.76 W*Nom 90 mA / 2.16 W* Max 165 mA / 3.96 W

    Nom 45 mA / 1.1 WMax 115 mA / 2.76 W*Nom 90 mA / 2.16 W* Max 165 mA / 3.96 W

    Nom 71 mA / 1.7 WMax 173 mA / 3.36 W

    *Nom 106 mA / 2.22 W* Max 223 mA / 5.36 W

    Power Consumptionat 32 Vdc*with Heater

    Nom 35 mA / 1.12 WMax 105 mA / 3.36 W*Nom 70 mA / 2.24 W* Max 145 mA / 4.64 W

    Nom 35 mA / 1.12 WMax 105 mA / 3.36 W*Nom 70 mA / 2.24 W* Max 145 mA / 4.64 W

    Nom 57 mA / 1.72WMax 158 mA / 5.06 W*Nom 92 mA / 2.84 W* Max 198 mA / 6.34 W

    Temperature Range Certied -40C to +75C (-40F to +167F) / Operational -50C to +75C (-58F to +167F)

    Field o View 120 degrees horizontal / 95 degrees vertical

    Spectral Range UV Radiation 185 to 260 nanometres (1850 to 2600 angstroms) | IR Radiation in the 4.4 micron range

    Time Delay Dip switch selectable to 0, 3, 5, 7 seconds

    Sensitivity Settings DIP switch selectable to 8, 16, 24 or 32 counts per second

    Response Time

  • 7/28/2019 Fgd Pds Uv Irs Flame Detector

    3/4

    UV/IRS Flame DetectorBCR-0005-00-017

    Product Data SheetNovember 2012

    -

    -

    UV/IRS Flame DetectorSpecifcations cont - Termination Boxes - Accessories

    TERMINATION BOXESClass 1, Division 1, Groups BCD - Class 1, Zone 1 -- Enclosure rated NEMA 4X, IP67(See man-0081 or ull specications)JB-MPS-A/S Termination box - Analog Output - Switch (or remote MVI testing) & Test Jacks - Aluminum or Stainless Steel

    ACCESSORIES

    LAT-120 Laser alignment tool assembly - used to dene area o coverage or all NSM ame detectors

    AIR-SHIELD Air Shield assembly (aluminum), supplied clean instrument air keeps lens clear in areas with heavy airbourne particulate

    HPT-001 HART Communicator port - Instrincially Sae connection mounts to connected JB-MPHF & JB-MPHFR

    FH-SHROUD Field o View Restrictor Anodized (Red) or S series re detectors (aluminum)

    UN-MK-41 1 Pipe Mounting kit - Stainless steel

    UN-MK-42 2 Pipe Mounting kit - Stainless steel

    UN-MK-43 3 Pipe Mounting kit - Stainless steel

    SSK-4 Sun shade kit/rain guard or S series ame, stainless steel - mounts directly to ame detector

    SSK-1 Sun shade kit or S series ame, stainless steel - mounts directly to ame detectorTL-MP-KIT Universal test lamp kit - certied rechargeable hand-held unit - produces accurate re simulation (UV and IR sources)

    TL-MP-KIT-X Universal test lamp kit [ATEX] - certied rechargeable hand-held unit - produces accurate re simulation (UV and IR sources)

    Summary o DistancesFuel Fire Size Typical Response

    n-heptane 1 x 1 < 11sec @ 140 ft.

    gasoline 1 x 1 < 6sec @ 120 ft. (< 3sec @ 50 ft.)

    methane 30 plume < 6sec @ 100 ft.

    Immunity False Alarm StimuliStimuli Immunity Range

    Direct/Indirect Sunlight total

    1500W Heater 10 t

    Halogen, Incandescent Light 3 t

    Florescent Light 10 t

    Arc Welding 30 tExample Field o View - Methane32 plume - indicated in eet - consult actory or other ame types

    I I

    6060

    I I

    60

  • 7/28/2019 Fgd Pds Uv Irs Flame Detector

    4/4

    UV/IRS Flame DetectorBCR-0005-00-017

    Product Data SheetNovember 2012

    -

    -

    HEADQUARTERS:FLAME AND GAS DETECTIONEmerson Process ManagementNet Saety Monitoring Inc.2721 Hopewell Place NECalgary, Alberta, Canada T1Y 7J7T +1 (403) 219 0688T 1 866 FIREGASF +1 (403) 219 0694www.net-saety.com

    2012 Emerson Process Management. All rights reserved.

    Emerson Process Management, Rosemount Analytical, and Net Saety Monitoring are marks o Emerson Process Management group ocompanies. All other marks are the property o their respective owners.

    The contents o this publication are presented or inormation purposes only, and while efort has been made to ensure their accuracy, they

    are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use orapplicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modiy or improve thedesigns or specications o our products at any time without notice.

    Please reer to manuals or complete specications.

    http://twitter.com/NetSafetyRAIhttp://www.youtube.com/user/NetSafetyMonitoringhttp://www.facebook.com/NetSafetyMonitoringhttp://www.linkedin.com/groups?gid=2758896&trk=hb_side_gmailto:name%40address.com?subject=Interesting%20Product%20by%20Net%20Safety%20Monitoring%20-%20Emerson%20Process%20Managementhttp://www.analyticexpert.com/