21
1 DICIEMBRE 2020 Fenton process as effective treatment of aqueous effluents of a pharmaceutical plant: Operation and performance.

Fenton process as effective treatment of aqueous effluents

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Fenton process as effective treatment of aqueous effluents

1

DICIEMBRE 2020

Fenton process as effective treatment

of aqueous effluents of a

pharmaceutical plant: Operation and

performance.

Page 2: Fenton process as effective treatment of aqueous effluents

22

INDICE

• INTRODUCCIÓN.

• DESCRIPCIÓN DE PLANTA DE TRATAMIENTO. ETAPAS DE

TRATAMIENTO.

• DATOS DEL PROCESO Y CARACTERÍSTICAS DEL VERTIDO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Page 3: Fenton process as effective treatment of aqueous effluents

33

DICIEMBRE 2020

• INTRODUCCIÓN.

Page 4: Fenton process as effective treatment of aqueous effluents

44

INTRODUCCIÓN. LABORATORIOS SERVIER.

ACTIVIDAD

La actividad industrial de SERVIER es la

fabricación de materias primas de base para la

industria farmacéutica.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

PROCESOS PRODUCTIVOS.

En el proceso de producción de los productos

farmacéuticos de base se desarrollan las

siguientes etapas comunes en todos ellos

Page 5: Fenton process as effective treatment of aqueous effluents

55

INTRODUCCIÓN. TRATAMIENTO FENTON

TRATAMIENTO DE OXIDACIÓN HÚMEDA CON PERÓXIDO.

✓ Laboratorios Servier cuenta con este tratamiento desde 2005.

✓ Proceso de oxidación avanzada.

✓ Radicales libres OH, con alto caracter oxidante. Oxidación muy active con

los compuestos orgánicos de alto peso molecular.

✓ Reactivo principal: Peróxido de hidrógeno.

✓ Reactivos secundarios, catalizadores que favorecen la reacción Fenton.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Page 6: Fenton process as effective treatment of aqueous effluents

66

INTRODUCCIÓN. TRATAMIENTO FENTON

CARACTERISTICAS DEL VERTIDO

Los procesos generadores de vertidos son principalmente los siguientes:

✓ Procesos productivos.

✓ Procesos auxiliares.

✓ Procesos de mantenimiento.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Page 7: Fenton process as effective treatment of aqueous effluents

77

DICIEMBRE 2020

• DESCRIPCIÓN DE PLANTA DE TRATAMIENTO. ETAPAS

Page 8: Fenton process as effective treatment of aqueous effluents

88

DESCRIPCIÓN DE PLANTA DE TRATAMIENTO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Lineas de tratamiento

Page 9: Fenton process as effective treatment of aqueous effluents

99

DESCRIPCIÓN DE PLANTA DE TRATAMIENTO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

ACTUALIZAR

DESBASTESEPARADOR

DE ACEITE Y

GRASAS

ALJIBES T-

12A,

T-12B

HOMOGENIZACIÓN

BALSA Nº 1

Agua a

tratar

Sosa 30%

Zona de Balsas-Pretratamiento

Page 10: Fenton process as effective treatment of aqueous effluents

1010

DESCRIPCIÓN DE PLANTA DE TRATAMIENTO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Proceso OHP

TANQUE DE

ACIDIFICACION

REACTOR

OHP

Agua

procedente

de Balsa nº 1

Ácido

sulfúrico

Catalizador

Agua

oxigenada

Page 11: Fenton process as effective treatment of aqueous effluents

1111

DESCRIPCIÓN DE PLANTA DE TRATAMIENTO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

NEUTRALIZACIÓNFLOCULACIÓN -

COAGULACIÓN

DECANTADOR DE

LODOSBALSA DE

HOMOGENIZACIÓN

Físico-Químico

Polielectrolito

Sosa 30%

Proceso

OHP

Page 12: Fenton process as effective treatment of aqueous effluents

1212

DESCRIPCIÓN DE PLANTA DE TRATAMIENTO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

DECANTADOR

DE LODOS

ESPESADOR DE

FANGOS

BALSA DE

HOMOGENIZACIÓN

BALSA Nº 2ACONDICIONAMIEN

TO DE FANGOSFILTRO PRENSA

Tratamiento de Lodos

Proceso

Físico-químico

Lodos

Agua

tratada

Page 13: Fenton process as effective treatment of aqueous effluents

1313

DESCRIPCIÓN DE PLANTA DE TRATAMIENTO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Page 14: Fenton process as effective treatment of aqueous effluents

1414

DESCRIPCIÓN DE PLANTA DE TRATAMIENTO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Page 15: Fenton process as effective treatment of aqueous effluents

1515

DESCRIPCIÓN DE PLANTA DE TRATAMIENTO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Page 16: Fenton process as effective treatment of aqueous effluents

1616

DICIEMBRE 2020

• DATOS DEL PROCESO Y CARACTERÍSTICAS DEL

VERTIDO

Page 17: Fenton process as effective treatment of aqueous effluents

1717

DATOS DEL PROCESO Y CARACTERÍSTICAS DEL VERTIDO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

✓ Caudal medio de tratamiento: 3 m3/h

✓ DQO de entrada (mg O2/l) : 9.000 ( entre 6.000 y 12.000)

✓ pH: 7 – 9

✓ Conductivity: 15.000 µS

Si el vertido no cumple estas condiciones de partida (Alta

DQO) o debido a la existencia de compuestos como

cianuros o CMR, éstos son gestionados externamiente con

Gestores de Residuos Autorizados.

CARACTERÍSTICAS DE VERTIDO ENTRADA A LA DEPURADORA.

Page 18: Fenton process as effective treatment of aqueous effluents

1818

✓ Tiempo de residencia: 60 min

✓ Temperatura 120ºC

✓ Presión 1,5 bar

✓ pH: 3

CONDICIONES DE REACCIÓN

DATOS DEL PROCESO Y CARACTERÍSTICAS DEL VERTIDO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

Page 19: Fenton process as effective treatment of aqueous effluents

1919

CONSUMO DE REACTIVOS.

DATOS DEL PROCESO Y CARACTERÍSTICAS DEL VERTIDO.

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

✓ Peróxido de Hidrógeno 3,6 l / kg DQO eliminated

✓ Sulfato Ferroso (Fe SO4+7H2O) 0,025 kg / kg DQO eliminated

✓ Sulfato Cuprico (CuSO4+5H2O) 0,0017 kg / kg DQO eliminated

✓ Acido Sulfúrico 98 % (H2SO4) 0,069 kg / kg DQO eliminated

✓ Hidróxido Sódico en solución 30 % (Na OH) 0,335 kg / kg DQO eliminated

Page 20: Fenton process as effective treatment of aqueous effluents

2020

CARACTERÍSTICAS DEL AGUA TRATADA

DATOS DEL PROCESO Y CARACTERÍSTICAS DEL VERTIDO

FENTON PROCESS AS EFFECTIVE TREATMENT OF AQUEOUS EFFLUENTS OF A PHARMACEUTICAL PLANT: OPERATION AND PERFORMANCE

✓ DQO (mg O2/l) 1.058

✓ pH : 7 – 9

✓ Conductiviidad (µS): 5.500

✓ Cobre (Cu2+) (ppm): 1

✓ Hierro (Fe2+ / Fe3+) (ppm): 3

✓ Solidos en suspensión (ppm): 60

✓ DQO (mg O2/l) 2000

✓ pH : 6 – 9,5

✓ Conductividad (µS): 20.000

✓ Cobre (Cu2+) (ppm): 5

✓ Hierro (Fe2+ / Fe3+) (ppm): 25

✓ Sólidos en suspensión (ppm): 600

LIMITES LEGALES AAI

Page 21: Fenton process as effective treatment of aqueous effluents

21

www.servier.com

HSE Department