Feeders Protection Schemes.
2 - Transformers Protection Schemes.
3 - Bus Bar Protection Schemes.
4 - Generators Protection Schemes.
Types and voltage level of Feeders
A O. H. T. Lines
500 KV O. H. T Line
400 KV O. H. T Line
275 KV O. H. T Line
220 KV O. H. T Line
132 KV O. H. T Line
66 KV O. H. T Line
33 KV O. H. T Line
22 KV O. H. T Line
11 KV O. H. T Line
B U. G. Cables
275 KV U. G. Cable
220 KV U. G. Cable
132 KV U. G. Cable
66 KV U. G. Cable
33 KV U. G. Cable
11 KV U. G. Cable
8/3/2019 Feeders Protection Schemes
http://slidepdf.com/reader/full/feeders-protection-schemes 2/9
500, 400, 275 and 220 KV O.H.T. Lines
Protection Schemes
Main (A) Protection:
Distance Protection Permissive Over Reach Scheme. (POTT)
Main (B) Protection:
Distance Protection Permissive Under Reach Scheme. (PUTT)
Backup Protection:
I.D.M.T Directional O/C & E/F Relay.
Circuit Breaker Fail to Tripe.
Inter Trip.
SF6 Pressure Low Trip
Cable Oil Pressure Low Trip (For Cable Tail )
Drawing : single Line diagram for
protection scheme Click Here
132 and 66 KV O.H.T. Lines
Protection Schemes
Main Protection:
Distance Protection Permissive Under Reach Scheme. (PUTT)
Back up Protection:
I.D.M.T Directional O/C & E/F Relay.
Circuit Breaker Fail To Tripe.
Inter Trip.
SF6 Pressure Low Trip
Cable Oil Pressure Low Trip (For Cable Tail)
Drawing : single Line diagram for
8/3/2019 Feeders Protection Schemes
http://slidepdf.com/reader/full/feeders-protection-schemes 3/9
protection scheme Click Here
33 and 22 KV O.H.T. Lines
Protection Schemes
I.D.M.T Direction O/C & EF Relay
I.D.M.T Non Direction O/C & EF Relay
11 KV O.H.T. Lines
Protection Schemes
I.D.M.T Direction O/C & EF Relay
275, 220 U.G.C. Line
Protection Scheme
Main (A) Protection:
Differential Protection (Solkor R)
Main (B) Protection:
Distance Protection Permissive Over Reach Scheme. (POTT) With Carrier Signal through Pilot Cable
Back up Protection:
I.D.M.T Directional O/C & E/F Relay.
Circuit Breaker Fail to Tripe
Inter Trip.
SF6 Pressure Low Trip
Cable Oil Pressure Low Trip
8/3/2019 Feeders Protection Schemes
http://slidepdf.com/reader/full/feeders-protection-schemes 4/9
132, and 66 KV U.G.C. Line
Protection Scheme
Main Protection:
Differential Protection (Solkor R)
Back up Protection:
I.D.M.T Directional O/C & E/F Relay.
Circuit Breaker Fail to Tripe.
Inter Trip (Through Pilot Cable).
SF6 Pressure Low Trip
Cable Oil Pressure Low Trip
33, 22 KV U.G.C. Line
Protection Scheme
Main Protection:
Differential Protection (Solkor R)
Back up Protection:
I.D.M.T Directional O/C & E/F Relay.
I.D.M.T Non Directional O/C & E/F Relay.
Cable Oil Pressure Low Trip.
11 KV U.G.C. Line
Protection Scheme
Main Protection:
Differential Protection (Solkor R)
Back up Protection:
I.D.M.T Non Directional O/C & E/F Relay.
8/3/2019 Feeders Protection Schemes
http://slidepdf.com/reader/full/feeders-protection-schemes 5/9
Some types of power transformers
300 MVA. 3 Winding Power Transformer
275 KV / 132 KV / 33 KV. (Y.Y.).
75 MVA. & 45 MVA. 2 Winding Power Transformer 1
32 KV / 33 KV.
30 MVA 2 Winding Power Transformer
132 KV / 11 KV.
20 MVA & 15 MVA 2 Winding Power Transformer
33 KV / 11 KV.
Drawing : single Line diagram for
protection scheme Click Here
300 MVA 3 Winding Power Transformer
Protection Scheme.
Main (A&B) Protection:
1. Differential Protection.
2. Restricted Earth Fault Protection. (both at 275 kv and 132 kv)
side neutral of the star winding.
BackupProtection:
C.B Fail to trip.
I.D.M.T Non Direction O/C & E/F relay on 300 KV side
I.D.M.T Direction O/C & E/F relay on 132 KV side
Inter Trip (through pilot cable).
Buchhols Trip.
Tap Changer Buchhols Trip.
8/3/2019 Feeders Protection Schemes
http://slidepdf.com/reader/full/feeders-protection-schemes 6/9
Oil Temperature Trip.
Winding Temperature Trip.
Cable oil pressure Low Trip. (for cable tails )
SF6 pressure Low Trip.
75, 45 And 30 MVA- 2 Winding Power Transformer
Protection Scheme.
Main (A) Protection:
1. Differential Protection.
2. Restricted Earth Fault Protection.
(At the neutral of the LV. Winding).
Backup Protection:
Stand-By Earth Fault relay at the neutral of LV. Winding.
C.B Fail to trip. (For 132 KV. C.B only)
I.D.M.T Non Direction O/C & E/F relay on 132 KV side
Inter Trip (through pilot cable).
Buchhols Trip.
Tap Changer Buchhols Trip.
Winding Temperature Trip.
Cable oil pressure Low Trip. (For cable tails)
20 & 15 MVA- 33 / 11 KV, 2 Winding Power Transformer
Protection Scheme.
Main (A) Protection:
1. Differential Protection.
8/3/2019 Feeders Protection Schemes
http://slidepdf.com/reader/full/feeders-protection-schemes 7/9
2. Restricted Earth Fault Protection.
(At the neutral of the LV. Winding).
Backup Protection:
Stand-By Earth Fault relay at the neutral of LV. Winding.
I.D.M.T Non Direction O/C & E/F relay on 33 KV side
Inter Trip (through pilot cable).
Buchhols Trip.
Bus-Bar Protection Schemes.
500, 400, 275, 220 and 132 KV. Bus-Bar Protection Scheme.
- Differential Protection For each section of bus-bar.
- SF6 Pressure low Trip.
66 and 33 KV. Bus-Bar Protection Scheme.
- Differential Protection For each section of bus-bar or Arc protection or Micro switch protection.
- SF6 Pressure low Trip.
22 and 11 KV BUS-Bar Protection Scheme.
- Arc protection or Micro switches protection.
500, 400, 275, and 220 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
- C.B Fail to Trip.
- SF6 Pressure Trip.
8/3/2019 Feeders Protection Schemes
http://slidepdf.com/reader/full/feeders-protection-schemes 8/9
- Inter Trip (through pilot cable).
132 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
- C.B Fail to Trip.
33 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
11 KV BB section & BB couplers protection scheme.
- I.D.M.T Non Directional O/C & E/F Relay.
Shunt Reactor Protection Scheme.
275 &132 KV. Shunt Reactor Protection Scheme.
I.D.M.T Non Direction O/C & E/F relay.
Inter Trip (through pilot cable SHR connected through cable C.B. for 132 kV only).
Buchhols Trip.
Oil Temperature Trip.
Winding Temperature Trip.
Cable oil pressure Low Trip. (For cable tails)
SF6 pressure Low Trip.
C.B Fail to trip. (For 132 KV. C.B only).
33 KV. Shunt Reactor Protection Scheme for both connected
to 33 KV Bus-Bar or to tertiary of 300 MVA Transformer.
8/3/2019 Feeders Protection Schemes
http://slidepdf.com/reader/full/feeders-protection-schemes 9/9
I.D.M.T Non Direction O/C & E/F relay.
Buchhols Trip.
Oil Temperature Trip.
Winding Temperature Trip.