POWER PLANTFEED WATER CONTAMINATION
MONITORING- EARLY
DETECTION ACTIONS - EFFECTS
8/11/2019 Feed Water Contamination
2/13
MONITORING
ANALYSERS CATION CONDUCTIVITY PH MONITORING CONDUCTIVITY SILICA RESIDUAL OXYGEN SODIUM CHLORIDE
8/11/2019 Feed Water Contamination
3/13
CATION CONDUCTIVITY
The online measurement of conductivity afterwater has passed through a column ofstrongly acidic cation-exchange resin is used toindicate the presence of potentially corrosiveionic contaminants. The technique may bereferred to as cation conductivity or acid
conductivity in some documentation.
8/11/2019 Feed Water Contamination
4/13
8/11/2019 Feed Water Contamination
5/13
Thus, conductivity after cationexchange is extremely effective forrapidly indicating the onset of
condenser leakage, particularly atseawater-cooled plants, and alsofor detecting contaminated
makeup water
8/11/2019 Feed Water Contamination
6/13
PH MONITORING
Turbine condensate Lab Feed water online & Lab Drum online & lab
8/11/2019 Feed Water Contamination
7/13
Other Analyzers for monitoring
Total conductivity Drum water
Silica drum saturated steam Dissolved oxygen turbine condensate-Lab Sodium tracer turbine condensate- not
installed in Khobar Plants Chloride tracer live steam not installed in
Khobar Plants
8/11/2019 Feed Water Contamination
8/13
Early detection of condenser leak
TC cation conductivity Feed water conductivity Live steam conductivity
Off scale > 1 s/cm Off scale > 1 s/cm Off scale > 0.5 s/cm
8/11/2019 Feed Water Contamination
9/13
CCR operator role
TC cation conductivity High & off sacle Alert CRS & Lab
After few minutes if feed water Cationconductivity started raising raise alarm toLab & CRS.
Simultaneous raise of live steam Cationconductive increase above 0.2 s/cm confirmscontamination in the system
8/11/2019 Feed Water Contamination
10/13
SCE INVESTIGATION As soon as TC cation conductivity is Off scale
contact lab and arrange to take sample of Turbinecondensate, Feed water and Live steam samplessame time .
Take control of the unit and watch all parameters As soon as Feed water, Economiser & Live steam
Cation conductivities start increasing take
following action- Do not wait for lab result Live steam conductivity raise will result in brine
condensate Conductivity raise.
Inform lab about the contamination for fast action
8/11/2019 Feed Water Contamination
11/13
SCE IMMEDIATE ACTIONS
Arrange to take CPP in service Takes time Inform local operator to reject Turbine
condensate maximum possible Open CBD maximum of 10 % Simultaneously reduce TG load fast and desal
load ( 65%) As soon boiler load is sufficiently reduced ( 350
t/hr) , close all attemparation valve (RL54/55/56 )TO STOP CONTAMINATING LIVE STEAM
8/11/2019 Feed Water Contamination
12/13
SCE ACTION Contd,
If needed stop top burners to control Livesteam temperatures.
Reject turbine condensate completely toreject and close RM26S201/RM23S401.
Watch drum pH and feed water pH- anydrastic lowering of pH must be informed toLab for corrective action to improve pH
Watch drum conductivity fast raising mustbe informed to lab
8/11/2019 Feed Water Contamination
13/13
Chemical Symbol Maximum Concentration
(ppm)
Sodium sulphite NA2SO 3 1.0
Sodium chloride NaCl 10.0
Sodium phosphate NA3PO 4 25.0
Sodium sulphate NA2SO 4 25.0
Silica oxide SiO 2 0.20
Maximum Allowable Impurities in Boiler Water