    POWER PLANTFEED WATER CONTAMINATION

    MONITORING- EARLY

    DETECTION ACTIONS - EFFECTS

  • 8/11/2019 Feed Water Contamination

    2/13

    MONITORING

    ANALYSERS CATION CONDUCTIVITY PH MONITORING CONDUCTIVITY SILICA RESIDUAL OXYGEN SODIUM CHLORIDE

  • 8/11/2019 Feed Water Contamination

    3/13

    CATION CONDUCTIVITY

    The online measurement of conductivity afterwater has passed through a column ofstrongly acidic cation-exchange resin is used toindicate the presence of potentially corrosiveionic contaminants. The technique may bereferred to as cation conductivity or acid

    conductivity in some documentation.

  • 8/11/2019 Feed Water Contamination

    4/13

  • 8/11/2019 Feed Water Contamination

    5/13

    Thus, conductivity after cationexchange is extremely effective forrapidly indicating the onset of

    condenser leakage, particularly atseawater-cooled plants, and alsofor detecting contaminated

    makeup water

  • 8/11/2019 Feed Water Contamination

    6/13

    PH MONITORING

    Turbine condensate Lab Feed water online & Lab Drum online & lab

  • 8/11/2019 Feed Water Contamination

    7/13

    Other Analyzers for monitoring

    Total conductivity Drum water

    Silica drum saturated steam Dissolved oxygen turbine condensate-Lab Sodium tracer turbine condensate- not

    installed in Khobar Plants Chloride tracer live steam not installed in

    Khobar Plants

  • 8/11/2019 Feed Water Contamination

    8/13

    Early detection of condenser leak

    TC cation conductivity Feed water conductivity Live steam conductivity

    Off scale > 1 s/cm Off scale > 1 s/cm Off scale > 0.5 s/cm

  • 8/11/2019 Feed Water Contamination

    9/13

    CCR operator role

    TC cation conductivity High & off sacle Alert CRS & Lab

    After few minutes if feed water Cationconductivity started raising raise alarm toLab & CRS.

    Simultaneous raise of live steam Cationconductive increase above 0.2 s/cm confirmscontamination in the system

  • 8/11/2019 Feed Water Contamination

    10/13

    SCE INVESTIGATION As soon as TC cation conductivity is Off scale

    contact lab and arrange to take sample of Turbinecondensate, Feed water and Live steam samplessame time .

    Take control of the unit and watch all parameters As soon as Feed water, Economiser & Live steam

    Cation conductivities start increasing take

    following action- Do not wait for lab result Live steam conductivity raise will result in brine

    condensate Conductivity raise.

    Inform lab about the contamination for fast action

  • 8/11/2019 Feed Water Contamination

    11/13

    SCE IMMEDIATE ACTIONS

    Arrange to take CPP in service Takes time Inform local operator to reject Turbine

    condensate maximum possible Open CBD maximum of 10 % Simultaneously reduce TG load fast and desal

    load ( 65%) As soon boiler load is sufficiently reduced ( 350

    t/hr) , close all attemparation valve (RL54/55/56 )TO STOP CONTAMINATING LIVE STEAM

  • 8/11/2019 Feed Water Contamination

    12/13

    SCE ACTION Contd,

    If needed stop top burners to control Livesteam temperatures.

    Reject turbine condensate completely toreject and close RM26S201/RM23S401.

    Watch drum pH and feed water pH- anydrastic lowering of pH must be informed toLab for corrective action to improve pH

    Watch drum conductivity fast raising mustbe informed to lab

  • 8/11/2019 Feed Water Contamination

    13/13

    Chemical Symbol Maximum Concentration

    (ppm)

    Sodium sulphite NA2SO 3 1.0

    Sodium chloride NaCl 10.0

    Sodium phosphate NA3PO 4 25.0

    Sodium sulphate NA2SO 4 25.0

    Silica oxide SiO 2 0.20

    Maximum Allowable Impurities in Boiler Water