Fcu M Leaflet

Embed Size (px)

Citation preview

  • 7/30/2019 Fcu M Leaflet

    1/11

    FAN COIL M SERIES FC 245/AE

    Ceiling Concealed MCW

    Ducted MCC

    Ceiling Cassette MCK

    Wall Mounted MWM

  • 7/30/2019 Fcu M Leaflet

    2/11

    Note: Air flow and Performances referred to EUROVENT 6/3 conditions:

    1. Cooling: Air temperature entering the unit: 27C d.b.; 19C w.b.; water inlet temperature: 7C; T 5K.2. Heating: Air temperature entering the unit: 20C; water inlet temperature: 50C; water flow rate same as for cooling mode

    3. Heating (auxiliary coil): Air temperature entering the unit: 20C; water inlet temperature: 70C; T 5K.

    Model 200C 300C 400C 600C 800C 1000C 1200C

    m3/h (max.) 408 595 765 1138 1427 1699 2175

    m3/h (med.) 306 459 663 901 1155 1308 1750Air flow rate (1)

    m3/h (min.) 204 340 510 731 952 1054 1444

    kW (max.) 2,3 3,4 4,2 6,5 8,2 9,2 11,9

    kW (med.) 1,9 2,8 3,7 5,6 7,1 8,1 10,6Total coolingcapacity (1)

    kW (min.) 1,6 2,4 3,2 5,0 6,1 7,2 8,9

    kW (max.) 1,5 2,3 2,9 4,4 5,4 6,2 8,0

    kW (med.) 1,3 2,0 2,6 3,7 4,6 5,3 7,0Sensible coolingcapacity (1)

    kW (min.) 1,0 1,5 2,1 3,2 3,8 4,6 5,6

    Water flow rateL/h

    420 600 780 1080 1740 1800 2280Pressure drop kPa 16 13 22 47 33 26 45

    W (max.) 3,9 5,7 7,5 11,3 14,2 15,8 20,5

    W (med.) 3,4 4,8 6,6 9,5 12,1 13,1 17,4Total heatingcapacity (2)

    W (min.) 2,8 4,1 5,4 8,3 10,8 11,6 15,1

    W (max.) 2,6 3,4 5,0 6,0 6,7 9,1 10,2

    W (med.) 2,1 2,9 4,5 5,1 5,8 7,7 8,9

    Total heatingcapacity auxiliarycoil (3) W (min.) 1,6 2,3 3,8 4,5 5,1 6,6 7,8

    Static pressure Pa 60 60 60 60 60 60 60

    Water flow rate L/h 420 600 780 1080 1740 1800 2280

    Pressure drop kPa 16 13 22 47 33 26 45

    Power supply 230V 1 ph 50 Hz

    Power input W 51 69 83 149 205 219 281

    Absorbed current A 0,22 0,29 0,36 0,64 0,93 1,04 1,22Connection inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4

    The high external static pressure makes units

    ideal for both ducted and free air delivery

    applications.

    MCW are able to satisfy every requirement in

    terms of air conditioning in wide space

    requiring the ceiling installation.

    The quite contained height makes units ideal

    for false ceiling installation even in vin buildings

    with narrow ceiling spaces

    Concealed

  • 7/30/2019 Fcu M Leaflet

    3/11

    Model 200C 300C 400C 600C 800C 1000C 1200C

    dB (A) (max) 36,0 37,0 37,0 39,0 39,0 39,0 40,0

    dB (A) (med) 35,0 35,0 35,0 36,0 37,0 38,0 36,0

    dB (A) (min) 34,0 34,0 34,0 35,0 35,0 35,0 35,0

    Model 200C 300C 400C 600C 800C 1000C 1200C

    Height mm 251 251 251 251 251 251 251Length mm 714 884 1014 1214 1464 1564 1824

    Width mm 490 490 490 490 490 490 490

    Weight Kg 19 22 26 30 41 44 46

    The extremely compact and lightweight design

    facilitates the delivery and installation of units.

    Height is barely 251mm allowing the installation

    in all false ceiling types.

    Water connection sides can be changed easily in

    the field

  • 7/30/2019 Fcu M Leaflet

    4/11

    Note: Air flow and Performances referred to EUROVENT 6/3 conditions:

    1. Cooling: Air temperature entering the unit: 27C d.b.; 19C w.b.; water inlet temperature: 7C; T 5K.2. Heating: Air temperature entering the unit: 20C; water inlet temperature: 50C; water flow rate same as for cooling mode

    Model 010CW 015CW 020CW 025CW 030CW 040CW 050CW 060CW

    m3/h (max.) 510 730 1050 1430 1750 1960 2620 3380

    m3/h (med.) 480 530 1040 1340 1390 1740 2430 3110Air flow rate (1)

    m3/h (min.) 410 460 850 1090 1120 1430 2210 2770

    kW (max.) 2,66 4,78 6,02 7,25 8,77 11,3 14,5 17,53

    kW (med.) 2,64 3,78 5,98 6,93 7,43 10,42 13,78 16,51Total coolingcapacity (1)

    kW (min.) 2,54 3,39 5,17 5,97 6,3 9,05 12,87 15,14

    kW (max.) 2,04 3,52 4,36 5,31 6,52 8,47 10,74 12,75

    kW (med.) 1,98 2,7 4,33 5,06 5,46 7,71 10,13 11,96Sensible coolingcapacity (1)

    kW (min.) 1,83 2,39 3,69 4,32 4,6 6,58 9,39 10,92

    Water flow rate L/h 455 819 1031 1242 1503 1936 2490 3004

    Pressure drop kPa 14 45 86 125 86 79 56 81

    W (max.) 3,34 5,22 6,44 7,85 9,72 12,8 16,33 19,33

    W (med.) 3,2 3,98 6,39 7,46 8,1 11,64 15,38 18,1Total heatingcapacity (2)

    W (min.) 2,85 3,52 5,43 6,34 6,78 9,92 14,25 16,5

    Static pressure Pa 50 50 50 50 150 150 150 150

    Water flow rate L/h 455 819 1031 1242 1503 1936 2490 3004

    Pressure drop kPa 12 24 74 99 53 58 43 62

    Power supply 230V 1 ph 50 Hz

    Power input W 71 102 148 173 421 550 670 748Absorbed current A 0,30 0,43 0,65 0,74 1,90 2,60 2,90 3,20

    Connection inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

    The new line of Ducted fan coils units, offers a

    wide range of solutions to air distribution

    problems applicable on both new and refurbished

    buildings, independently on the rooms volume.

    Multiple rooms can be cooled together with only

    one unit and the conditioned air can be effectively

    distributed to every corner of the room through

    ducting

  • 7/30/2019 Fcu M Leaflet

    5/11

    Model 010CW 015CW 020CW 025CW 030CW 040CW 050CW 060CW

    dB (A) (max) 33,0 37,0 38,0 40,0 49,0 51,0 53,0 55,0

    dB (A) (med) 31,0 34,0 35,0 37,0 45,0 47,0 50,0 52,0

    dB (A) (min) 30,0 32,0 33,0 35,0 43,0 45,0 46,0 50,0

    Model 010CW 015CW 020CW 025CW 030CW 040CW 050CW 060CW

    Height mm 261 261 261 261 370 370 370 370Length mm 765 905 1065 1200 919 1039 1289 1489

    Width mm 411 411 411 411 589 589 589 589

    Weight Kg 17 21 22 25 39 42 54 62

    MCC units are specifically designed for inside ceiling

    installation. Air mixing is well distributed in all space granting

    the best comfort.

    The small height makes unit ideal for inside ceiling

    installations where space is limited.

    A double drain pan prevents condensation drops

  • 7/30/2019 Fcu M Leaflet

    6/11

    Note: Air flow and Performances referred to EUROVENT 6/3 conditions:

    1. Cooling: Air temperature entering the unit: 27C d.b.; 19C w.b.; water inlet temperature: 7C; T 5K.2. Heating: Air temperature entering the unit: 20C; water inlet temperature: 50C; water flow rate same as for cooling mode

    Model 15BW 20BW 25BW 30BW 020AW 025AW 030AW 040AW 050AW

    m3/h (max.) 730 730 850 1030 1310 1380 1560 1740 1840

    m3/h (med.) 630 630 770 920 1130 1180 1320 1540 1680Air flow rate (1)

    m3/h (min.) 530 530 660 810 1070 1070 1210 1340 1540

    kW (max.) 3,7 5,0 5,9 6,8 7,2 8,4 9,6 10,7 11,9

    kW (med.) 3,4 4,4 5,4 6,3 6,5 7,5 8,4 9,8 11,1Total coolingcapacity (1)

    kW (min.) 3,0 3,8 4,8 5,6 6,2 6,9 7,8 8,8 10,4

    kW (max.) 2,9 3,5 4,1 4,8 5,3 6,1 6,8 7,7 8,4kW (med.) 2,6 3,1 3,8 4,4 4,7 5,4 6,0 7,0 7,8

    Sensible coolingcapacity (1)

    kW (min.) 2,3 2,7 3,3 3,9 4,5 5,0 5,6 6,2 7,3

    Water flow rate L/h 640 855 1007 1172 1239 1436 1636 1840 2041

    Pressure drop kPa 28 49 82 111 38 51 65 80 97

    W (max.) 4,3 5,3 6,1 7,0 7,9 8,9 10,0 11,1 11,8

    W (med.) 3,8 4,6 5,6 6,3 7,0 7,8 8,7 10,0 10,9Total heatingcapacity (2)

    W (min.) 3,3 4,0 4,9 5,7 6,7 7,2 8,1 8,9 10,2

    Water flow rate L/h 640 855 1007 1172 1239 1436 1636 1840 2041

    Pressure drop kPa 24 43 71 96 33 44 56 69 84

    Power supply 230V 1ph 50 Hz

    Power input W 72 72 79 108 127 151 164 192 253

    Absorbed current A 0,31 0,31 0,33 0,45 0,53 0,65 0,69 0,80 1,08

    Connection inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4

    The new McQuay range of fan coils cassette

    offers an excellent conditioning comfort with an

    extremely easy installation.

    The elegant styled cabinet easily harmonizes

    with all interior fashion design while the

    attractive grille fully integrates the unit both on

    standard panel and on inside ceiling.

  • 7/30/2019 Fcu M Leaflet

    7/11

    Model 15BW 20BW 25BW 30BW 020AW 025AW 030AW 040AW 050AW

    dB (A) (max) 41,0 44,0 44,0 47,0 42,0 45,0 49,0 51,0 53,0

    dB (A) (med) 39,0 41,0 40,0 44,0 39,0 42,0 45,0 48,0 52,0

    dB (A) (min) 38,0 39,0 38,0 40,0 37,0 40,0 43,0 46,0 50,0

    Model 15BW 20BW 25BW 30BW 020AW 025AW 030AW 040AW 050AW

    Height mm 293 293 293 293 335 335 335 335 335Length mm 650 650 650 650 820 820 820 820 820

    Width mm 650 650 650 650 820 820 820 820 820

    Weight Kg 33 33 34 35 35 36 39 42 44

    The anti-fungus and dual action ionizer/deodoriser

    filters enhance the air quality.

    Detection and diagnosis of any faults occurring in the

    unit is possible by blinking of the LED lights.

    Flexible control type selection in accordance with the

    installation requirement

    The unit comes with a builtin high head drain pump.Condensate water can be

    pumped up to 500mm anddrain out smoothly

    The 4 way air discharge andair-swing function will greatlyimprove the air distributionand circulation in the room.Innovative design of highlyefficient turbo fan producing

    air circulation in alldirections

  • 7/30/2019 Fcu M Leaflet

    8/11

    Note: Air flow and Performances referred to EUROVENT 6/3 conditions:

    1. Cooling: Air temperature entering the unit: 27C d.b.; 19C w.b.; water inlet temperature: 7C; T 5K.2. Heating: Air temperature entering the unit: 20C; water inlet temperature: 50C; water flow rate same as for cooling mode

    Model 005FW 007FW 010FW 15FW 20FW 25FW

    m3/h (max.) 340 340 460 510 820 990

    m3/h (med.) 290 290 400 460 730 830Air flow rate (1)

    m3/h (min.) 240 240 330 390 630 650

    kW (max.) 1,4 2,0 2,8 3,5 5,0 6,2

    kW (med.) 1,3 1,8 2,6 3,2 4,9 5,4Total coolingcapacity (1)

    kW (min.) 1,1 1,6 2,2 2,8 4,3 4,4

    kW (max.) 1,2 1,5 2,1 2,5 3,7 4,5kW (med.) 1,1 1,3 1,9 2,3 3,5 3,9

    Sensible coolingcapacity (1)

    kW (min.) 0,9 1,2 1,6 2,0 3,1 3,2

    Water flow rate L/h 214 304 436 553 839 925

    Pressure drop kPa 3 6 15 25 27 18

    W (max.) 2,2 2,4 3,5 4,0 5,7 7,0

    W (med.) 1,9 2,1 3,1 3,6 5,1 6,0Total heatingcapacity (2)

    W (min.) 1,6 1,8 2,6 3,1 4,5 4,8

    Water flow rate L/h 214 304 436 553 839 925

    Pressure drop kPa 3 5 13 21 23 16

    Power supply 230V 1 ph 50 Hz

    Power input W 23 23 25 25 53 57

    Absorbed current A 0,10 0,10 0,11 0,11 0,23 0,24

    Connection inches 1/2 1/2 1/2 1/2 1/2 1/2

    The Wall Mounted unit has an aesthetically

    stylish outlook and an elegant design easy to use

    where necessary to combine high performance

    and precise interior decoration.

    The swing mode enables the air to be distributed

    to every corner of the room. While providing a

    high flow rate, the random-pitched fan blade

    helps to reduce the air noise level.

  • 7/30/2019 Fcu M Leaflet

    9/11

    Model 005FW 007FW 010FW 15FW 20FW 25FW

    dB (A) (max) 38,0 38,0 38,0 38,0 45,0 47,0

    dB (A) (med) 34,0 34,0 34,0 35,0 42,0 44,0

    dB (A) (min) 30,0 30,0 30,0 31,0 39,0 42,0

    Model 005FW 007FW 010FW 15FW 20FW 25FW

    Height mm 290 290 290 290 306 306Length mm 815 815 815 815 1062 1062

    Width mm 179 179 179 179 202 202

    Weight Kg 10 11 12 12 15 15

    Dehumidification mode: a computerized control

    dehumidifies the surrounding without much change in

    temperature.

    The air intake grille can be easily removed and

    washed with clean water.

    3-stage air filtration:1) Antifungus filter to remove dust in

    the air as well as bacteriaproliferation

    2) Ionizing filter to positively charge dustparticles (0,01 micron) in the air whilethe negatively charged dust collectorattracts them

    3) Deodorizing filter to minimizeunpleasant odors from sweat, cigarettesetc.

    The compact LCD transmitter is able tooperate the air conditioner unit within thedistance of 9 meters. Fan motor speedcan be set at low/medium/high orautomatic. Sleep mode automaticallyincreases set temperature since roomtemperature is lower at night thusachieving comfort surrounding. Air flowdirection can be controlledautomatically. Room temperature iscontrolled by electronic thermostat. Theunit can be preset to on and offautomatically for maximum of 15 hoursby using timer on/off.

  • 7/30/2019 Fcu M Leaflet

    10/11

    MONITORING OF FCUSSTATUS AND OVERRIDEFCUSSETTING (ALL,GROUP OR INDIVIDUAL)

    MONITORING OF MINI CHILLER STATUS

    DETERMINATION OF MINI CHILLER RUNNING MODE(BASED ONFCUSREQUEST)

    ALARM MINI CHILLER AND/ORFCUFAULT

    ALARM HISTORY

    SMART START(START CHILLER EARLIER BEFORE SCHEDULE)

    TIME SCHEDULE:7DAYS TIMER SCHEDULE,4 TIMERS IN EACH DAY

    HOLIDAY SCHEDULE

    Maximises EfficiencyReduces CostsSaves Energy

    TTThhheee iiinnnttteeelllllliiigggeeennntttcccooonnntttrrrooolllttthhhaaatttfffuuullllllyyyiiinnnttteeegggrrraaattteeesss ttthhheee

    sssyyysssttteeemmmCCChhhiiilllllleeerrr+++ FFFaaannn CCCoooiiilllmmmaaakkkiiinnngggeeeaaasssyyyiiitttsss

    cccooommmpppllleeettteee cccooonnntttrrrooolll

  • 7/30/2019 Fcu M Leaflet

    11/11

    We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.

    McQuay Italia S.P.A.S.S. Nettunense, km 12+300 00040 Cecchina (Roma) Italia Tel. (06) 937311 Fax (06) 9374014 E-mail: [email protected]