  • S.T.A.R. Faulted Circuit Indicator (Electrostatic Reset Type)

    Cooper Power Systems

    Continuous Withstand Load: Operating Temperature: -40C to +85C Reset Time Accuracy: Current Reset: Trip Current Level: Factory Preset (High and Low) Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles per IEEE 495 Std -1986 standard Battery: 1000 hours continuous 2.4 Ah Lithium Ion Battery (Internal, non-

    replaceable). Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: Can be equipped with an LED in addition to the Fis heye display. manufacturer's comment: Cooper Power Systems S.T.A.R. Electrostatic Reset

    (ER) faulted circuit indicators are designed to quickly and easily locate faulted sections of overhead distribution systems. These faulted circuit indicators (FCIs) can be installed on overhead distribution lines and derive their power from the voltage gradient between the line and the ground plane. This voltage gradient provides a reliable source for operating and resetting the fault indicator when compared to current reset devices which are subject to system loading variations. Electrostatic Reset FCIs provide a reliable means of fault location and isolation. In addition, they eliminate fault chasing methods which are costly and time consuming, and very stressful on system components exposed to the fault currents. Electrostatic Reset fault indicators have been designed to operate primarily on uninsulated, unshielded cable but may also be used on an unshielded insulated cable such as tree wire.

    Read More

    S.T.A.R. Faulted Circuit Indicators (Manual Reset Type)

    Cooper Power Systems

    Continuous Withstand Load: Operating Temperature: -40C to +85C Reset Time Accuracy: Current Reset: Trip Current Level: Factory Preset (High and Low) Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles per ANSI/IEEE 495-1986 Battery: Two 1.2 AH Lithium Ion Batteries (20 Year Shelf Life) Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C:

  • Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: Cooper Power Systems S.T.A.R.Manual Reset

    (MR) faulted circuit indicators are designed to quickly and easily locate faulted sections of cable on distribution systems. These faulted circuit indicators (FCIs) can be installed on padmounted distribution transformers, sector cabinets,switchgear, and overhead distribution lines. Manual Reset FCIs provide a reliable means of fault location and isolation. In addition, they eliminate fault chasing methods which are costly and time consuming, and very stressful on system components exposed to the fault currents. Manual Reset faulted circuit indicators are designed to operate on overhead uninsulated,unshielded cable and unshielded insulated cable (such as tree wire), as well as concentric neutral and other cable, in underground, padmount and vault applications.

    Read More

    S.T.A.R.Faulted Circuit Indicators PATHFINDER (Variable Trip Electrostatic Reset Type)

    Cooper Power Systems

    Continuous Withstand Load: Operating Temperature: -40C to +85C Reset Time Accuracy: Current Reset: Trip Current Level: 100 A rise within 6-cycles Trip Accuracy: Fault Withstand: 25 kA for 10 cycles per ANSI/IEEE 495-1986 Battery:

    2.4 Ah Lithium Ion Battery (internal, non-replaceable) 2.4 Ah Lithium Ion Battery (replaceable battery, optional)

    Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment:

    Cooper Power Systems S.T.A.R. PATHFINDER Variable Trip Electrostatic Reset faulted circuit indicators (FCI) are designed to quickly and easily locate faulted sections of overhead distribution systems. These FCIs can be installed on overhead uninsulated, unshielded cable, or unshielded insulated cable such as tree wire. The removable pads allow the Variable Trip Electrostatic Reset FCI to be used on a wide range of cable diameters.

  • S.T.A.R. PATHFINDER Electrostatic Reset FCIs feature a voltage and current sensing design, which indicates a fault when a significant rise in current, followed by a loss of voltage, is detected. Hence, there is no need to specify a particular trip rating when ordering the PATHFINDER Electrostatic Reset FCI. This design ensures fast,reliable and accurate operation.

    A long-life Lithium Ion battery provides power to indicate the faulted conditions using a highly visible FISHEYEdisplay. The battery provides power to the FCI only when a fault occurs, turning the FISHEYE display. This ensures maximum battery life.

    The standard SEVT unit will remain in the tripped position for a period of four hours following restoration of normal system voltage after a fault has occurred. Reset times of 24-hours and 4-minutes are also available. This allows time for operators to interrogate the unit. After the factory-programmed reset period, the unit will return to the black or normal position. If the system power is not restored, the FCI remains in the tripped position indefinitely, but can be reset manually using the manual testing/reset tool, SMRT. The unit can also be manually reset following restoration of system power, before the reset time has expired.

    The PATHFINDER Electrostatic Reset FCI will reset automatically when installed on a live circuit. The unit can also be reset manually, and requires no charge-up time if installed on a de-energized circuit. Thus, the Variable Trip Type ER FCI is ideal for permanent installations, or as a temporary testtool.

    Read More

    AutoRANGER Overhead, Variable Trip, Timed Reset: Type AR-OH

    E O Schweitzer Manufacturing Division of SEL

    Continuous Withstand Load: Operating Temperature: Temperature Range: -40 to +85C Reset Time Accuracy: Current Reset: Trip Current Level: Trip Accuracy: Fault Withstand: 25 kA for 10 cycles Battery: 3.6 V high-capacity lithium battery with a 15 year life expectancy Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: The AutoRANGER is a self-adjusting fault indicator.

    It automatically selects one of eight discrete trip values based on the sampled load current of the circuit to which it is applied.

  • Read More

    BEACON Electrostatic Reset: Type BER

    E O Schweitzer Manufacturing Division of SEL

    Continuous Withstand Load: Operating Temperature: Temperature Range: -40 to +85C Reset Time Accuracy: Current Reset: Trip Current Level: Nominal Trip Ratings: 50 to 1200 A Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles at 60 Hz Battery: 3.6 V high-capacity lithium battery with a 20-year shelf life Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment:

    Key Features

    o Dual-display FCI incorporates LED with a reflective red mechanical target (the largest in the industry) to provide excellent visual indication, even in low light conditions.

    o 1,200 flashing hours standard; 3,000 flashing hours with the nonreplaceable battery.

    o The mechanical target continues to provide indication regardless of battery status.

    o Automatic reset upon restoration of system voltage. o Daylight Restraint conserves battery life by activating the LED only in

    reduced ambient light conditions. o Apply at strategic intervals along overhead conductors and at

    midfeeder disconnects to minimize fault-finding time and optimize reliability statistics.

    o Inrush restraint feature prevents false tripping during recloser operations.

    Read More

    BEACON Field-Programmable Timed Reset: Type BTRIP

    E O Schweitzer Manufacturing Division of SEL

    Continuous Withstand Load: Operating Temperature: Temperature Range: -40 to +85C Reset Time Accuracy:

  • Current Reset: Trip Current Level: Trip Ratings: Programmable options from 50 A to 1200 A Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles Battery: 3.6 V high-capacity 8.5 Ah lithium battery with a 20-year shelf life Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: Use the CRSRTT tool (included) to program, field-

    test, and manually reset the BTRIP.

    Read More

    BEACON Timed Reset: Type BTRI_IR

    E O Schweitzer Manufacturing Division of SEL

    Continuous Withstand Load: Operating Temperature: Temperature Range: -40 to +85C Reset Time Accuracy: Current Reset: Trip Current Level: Nominal Trip Ratings: 50 to 1200 A Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles at 60 Hz Battery:

    Power Source: High-capacity 3.6 V lithium battery

    o Replaceable Battery: 1200-hour flashing life (2.4 Ah cell) o Nonreplaceable Battery: 3000-hour flashing life (8.5 Ah cell)

    Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: Use the CRSRTT tool (sold separately) to field-test

    and manually reset the BTRI_IR.

    Read More

    Current Reset Type: Type 1CRD

    E O Schweitzer Manufacturing Division of SEL

    Continuous Withstand Load: Operating Temperature: Temperature Range: -40 to +85C

  • Reset Time Accuracy: Current Reset: 3 A Trip Current Level: Nominal Trip Ratings: 400 and 800 A Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles Battery: No battery necessary. Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: The CRD Fault Indicator is easy to install on an

    overhead line using a single hot stick.

    Read More

    Overhead Electrostatic Reset: Type ERL

    E O Schweitzer Manufacturing Division of SEL

    Continuous Withstand Load: Operating Temperature: Temperature Range: -40 to +85C Reset Time Accuracy: Current Reset: Trip Current Level: Nominal Trip Ratings: 50 to 1200 A Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles at 60 Hz Battery: No battery to replace or monitor. Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options:

    o "DT 24 ms Delayed Trip o CC Constant Calibration o S Snap Action Clamp o Consult EOS for additional features

    manufacturer's comment:

    Key Features

    o Automatically resets upon restoration of system voltage. o Applied at strategic intervals along overhead conductors and at

    midfeeder disconnects to minimize fault-finding time and optimize reliability statistics.

    o Inrush restraint feature prevents false tripping during recloser operations.

  • o The reflective red target (the largest display in the industry) is easy to spot both at night and during the day.

    o Zero maintenance: no battery to replace or monitor. o Models with the snap action clamp option are applicable on live-front

    switchgearsimply install the ERL onto the barrel of the cable termination lug.

    Read More

    ADAPTIVE TRIP Faulted Circuit Indicators - Series 1547

    Joslyn Hi-Voltage

    Continuous Withstand Load: Operating Temperature:

    Sensor: -50C to +90C Indicator: -40C to +85C

    Reset Time Accuracy: Current Reset:

    o 1.625 in. sensor with U-lamination: 1.0 A o 2.1875 in. sensor with U-lamination 1.5 A o 1.625 in. sensor w/o U-lamination 2.0 A o 2.1875 in. sensor w/o U-lamination 3.0 A

    Trip Current Level: Trip Accuracy: Fault Withstand: 25 kA for 10 cycles per ANSI/IEEE 495-1986 Battery: Lithium cell, 800 hours of operation, rated for 10 year life. Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment:

    Features

    o Reduces Inventory o Rate of Change Trip Function o Faulted Circuit Indicators instructions o Coordinates with Current-Limiting Fuses o Low Current Reset (1 Amp Available) o Flag-Type, High Intensity LED, or Fiber Optic Cable Display o SCADA Output o Integral Radio Transmitter Option

    Read More

    Current Reset Fault Indicators - Series 1514

  • Joslyn Hi-Voltage

    Continuous Withstand Load: 1000 A Operating Temperature: Operating Temperature: -40 to +85C Reset Time Accuracy: Current Reset: Factory preset for 1.2, 1.5, 3.0 and 5.0A Trip Current Level: Factory preset from 50 to 1500A Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles per Battery:

    o Rated Battery Life: 10 years (long life lithium cell)

    Model 1514B/1515B, - 800 hours of operation Model 1514D - 300 hours of operation

    o Flag/LED Operating Life @ 23C: o Strobe Operating Life @ 23C: o Radio Operating Life @ 23C: o Conductor Diameter Range: o options:

    Current Inrush Restraint: Avoids false trips caused by line energization or reclosure operations

    Time-Delayed Reset: Offered with or without current reset override

    Manual Reset: Available on all Series 1514 fault indicators Flag or LED Display: Flag - Black (normal position),

    fluorescent orange (fault position). LED - Red, high intensity signal flashes every 2 seconds. (LED requires lithium battery)

    SCADA: Latching or momentary N.C. output available with flag display. 3A @ 125 Vac, 250 Vac 1/10 HP @ 250 Vac.

    Integral Radio Transmitter Fiber Optics: A remote 10 ft. fiber optic cable display provides

    isolation for signal transmission of trip and reset operations. o manufacturer's comment:

    Trip Current Rating - Selection of the trip current rating should be at least 3 times the expected full load current.

    Reset Current Rating - Ensures reset on lightly loaded feeders. Use of a fault indicator with 1.2A reset is recommended

    Read More

    Overhead Faulted Circuit Indicators - Series 1548

    Joslyn Hi-Voltage

    Continuous Withstand Load: 1000 A Operating Temperature: Operating Temperature: -40 to +85C Reset Time Accuracy: Reset Time Accuracy: +/- 10%

  • Current Reset: o 1548FH standard: 3 Amps Minimum o 1548GH special: 8 Amps Minimum

    Trip Current Level: Fixed Trip Current Level: 50 to 1500A Trip Accuracy: 10% Fault Withstand: 25 kA for 10 cycles (per ANSI/IEEE 495-1986) Battery: Replaceable, 10+ yr Lithium Cell (Flag model non-replaceable) Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: From 0.14 to 1.20 inches. options:

    o Temporary/permanent fault indication. o Instantaneous recloser coordination feature. o Backfeed Restraint utilizing a delay trip scheme

    (requires protective device to pass 2 cycles minimum of fault current before closing).

    ACCESORIES:

    o Manual test and reset tool AT2186-10 o Radio receivers

    Read More

    FCI 333 Series (LED Type 333-1, 333-4, 333-6)

    Power Delivery Products Inc

    Continuous Withstand Load: Operating Temperature: Reset Time Accuracy: Current Reset: Trip Current Level: 60 amps to 2000 amps Trip Accuracy: Fault Withstand: Battery: Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: Armed and Ready.

    Read More

    FCI Load Tracker (Low Profile)

  • Power Delivery Products Inc

    Continuous Withstand Load: Operating Temperature: Reset Time Accuracy: Current Reset: Trip Current Level: Trip Accuracy: Fault Withstand: Battery: Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: Low trip option manufacturer's comment:

    o Self Powered o Easy to Install

    Read More

    Load Tracker (Directional Fault Indicator)

    Power Delivery Products Inc

    Continuous Withstand Load: 25,000 amps sym. RMS / 170 msec. Operating Temperature: -40 to +85 C Reset Time Accuracy: Current Reset: 5 Amps Small Core / 10 Amps Large Core Trip Current Level: 200A Min. to 3 to 5 Times Load (200A DEFAULT) Trip Accuracy: Fault Withstand: Battery: Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: 0.85 inches to 2.37 inches options: Red or Green LED Fault Indication, Elbow or Cable Mounted manufacturer's comment: Could be used in underground application too.

    Hotstick applied, one size fits all, close proximity immunity and automatic reset.

    o Automatic In-Rush Restraint o Load Tracking above 40 Amps o 900 flashing hours o One size for all circuits o Elbow or Cable Mounted o Lightweight = 10 ounces o Closed Core CT Design

  • o Self Powered o Manual Test and Reset o Hot stick applied o 5 minute installation time o Self adjusting to load current

    Read More

    OH Load Tracker (Navigator Load Memory)

    Power Delivery Products Inc

    Continuous Withstand Load: 25,000 A / 1 second sym. RMS Operating Temperature: -40 to +85 C Reset Time Accuracy: Current Reset: > 3 A load current Trip Current Level: 100 amps Trip Accuracy: Fault Withstand: Battery: Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: 0.3 inches to 1.15 inches options: manufacturer's comment:

    o 72 Hour Hold High Load Memory o Highest Daytime Visibility o Low Battery Indication o Manual, Time and/or Current Reset

    Read More

    Radio Type Remote Faulted Circuit Indicator-Navigator Radio FCI (RTU or SCADA Interface)

    Power Delivery Products Inc

    Continuous Withstand Load: Operating Temperature: Reset Time Accuracy: Current Reset: Trip Current Level: Trip Accuracy: Fault Withstand: Battery: Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C:

  • Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: FCI Navigator Radio Type FCIs can be configured

    in a variety of ways to address phase reporting or three way group circuit reporting.

    o Transmitter Integral to FCI o Low Battery Remote Reporting o Communication Flexibility

    Read More

    Radio Type Remote Faulted Circuit Indicator-UG Fault Indicator (Distribution Automation Relay)

    Power Delivery Products Inc

    Continuous Withstand Load: Operating Temperature: Reset Time Accuracy: Current Reset: Trip Current Level: Trip Accuracy: Fault Withstand: Battery: Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment:

    o UG SCADA fault reporting o RTU Interface o Low Power Consumption o Economica

    Read More

    Overhead Line Fault Indicator

    Thomas & Betts Corp, Utility Products Group

    Continuous Withstand Load: Operating Temperature: -40CTo +85C Reset Time Accuracy: Current Reset: Trip Current Level: Low, 400 Amp; High, 800 Amp Trip Accuracy:

  • Fault Withstand: Battery: 3.6 volt Lithium Thyonil Chloride Battery

    Battery Capacity 2.4 Ah Battery Operating Life 1200 Flash Hours Minimum Battery Storage Life 15-20 Years

    Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: Time Reset with LED Display Indicator auto-resets

    to normal after a four-hour time duration. Indicator may also be manually reset using an FTT test tool.

    Read More

    Overhead Line Fault Indicator

    Thomas & Betts Corp, Utility Products Group

    Continuous Withstand Load: Operating Temperature: -40C To +85C Reset Time Accuracy: Current Reset: Trip Current Level: Low, 400 Amp; High, 800 Amp Trip Accuracy: Fault Withstand: Battery: Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: Voltage Reset with Flag Display. Indicator auto-

    resets to normal after system voltage restoration. Reset requires 5kV minimum voltage to operate. Reset operation time is proportional to system voltage.

    Read More

    Overhead Line Fault Indicator

    Thomas & Betts Corp, Utility Products Group

    Continuous Withstand Load: Operating Temperature: -40C To +85C Reset Time Accuracy:

  • Current Reset: Trip Current Level: Low, 400 Amp; High, 800 Amp Trip Accuracy: Fault Withstand: Battery: 3.6 volt Lithium Thyonil Chloride Battery

    Battery Capacity 2.4 Ah Battery Operating Life 1200 Flash Hours Minimum Battery Storage Life 15-20 Years

    Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: Voltage Reset with LED Display. Indicator auto-

    resets to normal after system voltage restoration. Reset requires 5kV minimum voltage to operate. Reset operation time is proportional to system voltage.

    Read More

    Overhead Line Fault Indicator

    Thomas & Betts Corp, Utility Products Group

    Continuous Withstand Load: Operating Temperature: -40C To +85C Reset Time Accuracy: Current Reset: Trip Current Level: Low, 400 Amp; High, 800 Amp Trip Accuracy: Fault Withstand: Battery: 3.6 volt Lithium Thyonil Chloride Battery

    Battery Capacity 2.4 Ah Battery Operating Life 1200 Flash Hours Minimum Battery Storage Life 15-20 Years

    Flag/LED Operating Life @ 23C: Strobe Operating Life @ 23C: Radio Operating Life @ 23C: Conductor Diameter Range: options: manufacturer's comment: Voltage Operated, Time Reset, LED Display

    Indicator auto-resets after a four-hour time duration. Longer time resets are available upon request.

    Read More