Applied Materials | Hannover Fair 2015

Impedance on Demand

Solid State SSFCL Superconducting SCFCL

Superconducting and Solid-State Electronic

Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

Dr. Detlev Kirsten & Herbert Piereder

Page 2: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Contents

The Fault Current Challenge

Fault Current Limiters

Applied Materials

Projects

2

Page 3: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

The Fault Current Challenge

3

Generation Transmission Distribution Customers

New Energy Sources

Renewable Power – Wind, Solar, Biomass

Increased Grid Meshing for Reliability and

Power Quality

Distributed Generation

Increased Load

Transportation - Electric Cars, Trains

Urbanization - Population Growth

Modern Conveniences

More Demanding Operations

Increased Duty Cycles

Disappearing Off-Peak Periods

Aging Infrastructure

Trends in Electricity networks increase Fault Current Levels

Page 4: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Split

the network

G

Generator Feed Transformer Feed

Bus Coupling

Sensitive Loads

Conventional Fault Current Mitigation

4

Upgrade

Circuit Breakers

Install

Reactors

Install High

ImpedanceTransformers

132kV

33kV

220/380kV

110kV

Page 5: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

G

Generator Feed Transformer Feed

Bus Coupling

Sensitive Loads

Use of Fault Current Limiters

5

FCL Fault Current Limiter

132kV

33kV

220/380kV

110kV

Page 6: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Desired Characteristics of an Ideal FCL

Increase the impedance on the

line well before the first fault peak

(when the most damage occurs)

In normal operation, it is virtually

"transparent“ (no power or voltage

loss) to the network

Diminish the fault current by at

least a factor of 2 for its duration

Return the source impedance to

its original value when fault is

cleared

Normal Load Current Prospective Fault Current Limited Fault Current

Recovery Fault Normal Operation

Fault Inception

Without FCL (Prospective Fault Current)

Typical current waveforms due to fault

Curr

en

t

Fault C

learing

td (Fault duration time) tr (recovery time)

Fault Current Limiters Reduce Fault Currents Without the Need for Mitigation

6

Page 7: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Fault Current Limiter Solution Platform

Transmission System FCL

– Superconducting Fault Current Limiter (SCFCL)

– 66 kV to 230 kV transmission voltage levels

Distribution System FCL

– Solid State Fault Current Limiter (SSFCL)

– Up to 66 kV distribution voltage levels

Proprietary Design Features

– FCL units can withstand long duration faults and remain in parallel with shunt for

extended periods.

– Solid-State Devices are protected against known failure modes including

cascading failures due to aging and timing differences.

– Modular design allows FCL components (shunt, FCL unit, instruments,

cryogenics) to be separated to accommodate site conditions.

– Modular design allows easy spares provisioning of field replaceable units.

– SC and SS elements can be upgraded or repurposed as requirements change.

Shunt Reactor, ZSH = RSH + j XSH

SC unit

Superconductor Unit

ZSC = RSC + j XSC

ISH

ISC

Shunt Reactor, ZSH = RSH + j XSH

SS unit

Solid State Unit

ZSS = RSS + j XSS

ISH

ISS

SCFCL

SSFCL

7

Page 8: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Common Operating Principles

Normal Operation

– Load current flows through FCL unit.

– FCL introduces nearly zero impedance and voltage drop.

– System ( FCL unit, shunt, remaining components) is designed to

handle the maximum load current at all times – even under

contingencies.

Fault Condition

– FCL unit responds to fault current. – Superconducting material

quenches or solid-state path switches; both insert high resistance in

≈ 0.001second.

– Load transfers to high-impedance shunt path that limits fault

current.

Post-Fault

– Recovery is fast and automatic after fault clears.

– SCFCL transitions (recovers) under load in about 3 seconds.

– SSFCL switches in milliseconds (Programmable delay can be

incorporated)

8

Shunt Reactor

FCL Unit

Shunt Reactor

FCL unit

Shunt Reactor

FCL Unit

Page 9: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Leveraging HV and High Power Expertise

Display Energy and

Environmental

Solutions

Semiconductor Applied Global

Services

The world experts in semiconductor fabrication

9

Page 10: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

The Global Strength of Applied Materials

10

Stock Ticker: Nasdaq: AMAT

Market Cap: $29.6 billion

Fiscal 2014 Revenue: $9.1 billion

Fiscal 2014 R&D: $1.4 billion

Founded: November 10, 1967

Headquarters: Santa Clara, California

Global Presence: 81 locations in

18 countries

Fortune 500 Ranking: 302

RD&E and/or

Manufacturing Centers:

China, Germany, Israel, Italy,

Singapore, Taiwan, United States

Employees*: ~14,000 worldwide

Patents: ~10,500 issued

Page 11: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Applied Materials FCL Progress

11

2013

Santa Clara 11kV

SCFCL

Central Hudson 13kV SCFCL 15 Faults

AusNet 22kV SSFCL

2014 2015 2016

Thailand 22kV SSFCL

Thailand 115kV SCFCL

US 115kV SCFCL

Ireland 220kV SCFCL

Installed Planned

Contract Signed

Commercial Terms Agreed

Commercial Terms agreed

Commercial Terms

agreed

UK 6kV SSFCL Detailed spec in progress

Page 12: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

SCFCL and SSFCL Extensively Tested

-75

-50

-25

0

25

50

75

100

125

150

175

60 80 100 120 140 160 180 200 220 240

Curr

ent [

kA],

Volta

ge [k

V]

Time [ms]

KEMA Test Trial #46 - 12.5 kV and 56 kA rms (150 kA peak) Prospective Fault Current, limited to 24 kA rms (65 kA

peak), 56 % Current Reduction

Prospective Fault Current [kA] Limited Current[kA]

Superconductor Current [kA] Shunt Current [kA]

Voltage [kV]

Tested for many weeks at full-power at KEMA, Chalfont,

Pennsylvania, USA

“Lifetime” tested for hundreds of bus faults

SCFCL fully qualified against relevant IEEE Standards for 230kV

employment – Demonstrated at over 400kV

SSFCL fully qualified for 45 kV employment – Demonstrated at over

66 kV

Tested to failure to verify reliability and DFMEA Data

Failures are predictable and benign –

Grid remains protected with no cascading or induced secondary

failures

Automatic Recovery under load validated

High-Level DFMEA performed by Core Engineering Team

66 unique failure modes Identified

11 mitigated through design changes

55 mitigated through redundancy

No FCL

With FCL

Under all scenarios power flows and the Grid remains protected

-20

-10

0

10

20

30

40

50

60

70

80

0 10 20 30 40 50 60 70 80 90 100

Curr

ent

[kA

]

Time [ms]

KEMA Trial #32 - SSFCL at 6.35 kV (11 kV system), 26 kA prospective fault current limited to 7.94 kA

(69.5% reduction)

Prospective Fault Current [kA] Limited Fault Current [kA]

No FCL With FCL

12

Page 13: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

SCFCL - 15kV for Silicon Valley Power, CA, US

Normal Operation

– Voltage = 15 kV class

– Load current = 1000A

Fault Current limitation

– 23 kA to 11.5 kA ( at 50%

reduction)

– Or 5 kA to 3.5 kA (at 30%

reduction)

Recovery Under Load (RUL)

– 1 to 3.5 seconds depending on the

fault current level

Installation

– At Applied Materials industrial

substation supplied by Silicon

Valley Power (SVP) – Santa Clara

– Commissioned in July 2013

13

Reactors,

Instrumentation and

other devices under

test

Cryostat –

Superconductor Unit Cryogenics –

Cooling system

Page 14: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Superconducting Unit

• Neutral to Ground Configuration

• Redundant safety features

Normal Operation

Voltage = 15 kV class

Load current = 400A

Installation

Central Hudson’s Knapps Corner Substation; Poughkeepsie NY

Performance

Limited 15 faults since commissioned June 2014

Refrigeration Units (2)

• N+1 Redundant

• Environmental enclosure

SCFCL - 15kV for Central Hudson, NY, US

14

Page 15: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

SSFCL - 22kV Solution for AusNet, AU

Mitigates Brushfires caused by short-circuited lines

Connected Neutral-to-Ground

Limits 3-8 kA faults to 6, 40, or 70 A Peak (within <1ms)

Fast subsequent reduction to < 2 A

15

Page 16: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015 16

SCFCL - 115kV solution for Thailand

2 x 115kV/50%

800A

Gas Insulated

Switchgear

Compact Design

LN2 tank outside

accessible

Interconnects 8th Power Block at

generating site without exceeding fault

current duty

Page 17: Fault Current Limiters - Deutsche Messe AGfiles.messe.de/abstracts/65705_3_Applied_Materials_HMI_150414_DK.pdfFault Current Limiter Solution Platform Transmission System FCL –Superconducting

© Applied Materials | Hannover Fair 2015

Summary

Platform of Fault Current Limiting Solutions ranging from 6kV to 230kV

Modular concept with independent designs for

– Power switching functionality (=superconductors or solid state power electronics)

– Current limiting properties (=shunt reactor)

Fast deployment – less outage time

– redeployable

FCLs increase network safety and reliability.

FCLs facilitate meshed network operation and connection of generation.

FCLs sustain network stability and prevent network losses.

FCLs provide impedance when it is needed!

17