Upload
prashantsingh04
View
224
Download
0
Embed Size (px)
Citation preview
7/29/2019 Fault Analysis SC 2012
1/29
Fault Analysis
Symmetrical Components
1
7/29/2019 Fault Analysis SC 2012
2/29
Fault Analysis
The cause of electric power system faults is
insulation breakdown
This breakdown can be due to a variety of
different factors: Lightning.
wires blowing together in the wind.
animals or plants coming in contact with thewires.
salt spray or pollution on insulators.2
7/29/2019 Fault Analysis SC 2012
3/29
Fault Types
There are two main types of faults Symmetric faults: system remains balanced; these faults
are relatively rare, but are the easiest to analyze so well
consider them first.
Un-symmetric faults: system is no longer balanced; very
common, but more difficult to analyze.
The most common type of fault on a three phase system by
far is the single line-to-ground (SLG), followed by the line-to-
line faults (LL), double line-to-ground (DLG) faults, and
balanced three phase faults. 3
7/29/2019 Fault Analysis SC 2012
4/29
Fault Analysis
Fault currents cause equipment damage due to both
thermal and mechanical processes.
Goal of fault analysis is to determine the magnitudes
of the currents present during the fault.
need to determine the maximum current to insure
devices can survive the fault.
need to determine the maximum current the circuit
breakers (CBs) need to interrupt to correctly size the
CBs. 4
7/29/2019 Fault Analysis SC 2012
5/29
Fault Analysis Solution Techniques
Circuit models used during the fault allow the network to berepresented as a linear circuit
There are two main methods for solving for fault currents:
1. Direct method: Use pre-fault conditions to solve for the
internal machine voltages; then apply fault and solve
directly.
2. Superposition: Fault is represented by two opposing
voltage sources; solve system by superposition.
5
7/29/2019 Fault Analysis SC 2012
6/29
Analysis of Un-Symmetric Systems
Except for the balanced three-phase fault, faults result in
an unbalanced system.
The most common types of faults are single line-ground
(SLG) and line-line (LL). Other types are double line-
ground (DLG), open conductor, and balanced three phase.
System is only unbalanced at point of fault!
The easiest method to analyze unbalanced systemoperation due to faults is through the use ofSymmetrical
Components6
7/29/2019 Fault Analysis SC 2012
7/29
Symmetric Components
The key idea of symmetrical component analysis is to
decompose the system into three sequence networks.
The networks are then coupled only at the point of the
unbalance (i.e., the fault)
The three sequence networks are known as the
positive sequence (this is the one weve been using).
negative sequence.
zero sequence.
7
7/29/2019 Fault Analysis SC 2012
8/29
Positive Sequence Sets
The positive sequence sets
have three phase
currents/voltages with
equal magnitude, with
phase b lagging phase a by
120, and phase c lagging
phase b by 120.
Weve been studying
positive sequence sets.Positive sequence sets
have zero neutral current
8
7/29/2019 Fault Analysis SC 2012
9/29
Negative Sequence Sets
The negative sequence sets
have three phase
currents/voltages with
equal magnitude, with
phase b leading phase a by
120, and phase c leading
phase b by 120.
Negative sequence sets are
similar to positive
sequence, except the phase
order is reversed
Negative sequence sets
have zero neutral current
7/29/2019 Fault Analysis SC 2012
10/29
Zero Sequence Sets
Zero sequence sets have three
values with equal magnitude and
angle.
Zero sequence sets have neutralcurrent
Zero Sequence vectors with
Zero phase shift.
7/29/2019 Fault Analysis SC 2012
11/29
Sequence Set Representation
Any arbitrary set of three phasors, say Ia, Ib, Ic can berepresented as a sum of the three sequence sets
0
0
0
0 0 0
where
, , is the zero sequence set
, , is the positive sequence set
, , is the negative sequence set
a a a a
b b b b
c c c c
a b c
a b c
a b c
I I I I
I I I I
I I I I
I I I
I I I
I I I
11
7/29/2019 Fault Analysis SC 2012
12/29
Conversion from Sequence to Phase
0a
2 3 3
0 0 0a b c
2
Only three of the sequence values are unique,I , , ; the others are determined as follows:
1 120 0 1
I I I (since by definition they are all equal)
a a
b a c a b a c
I I
I I I I I I I
2
0
0 + 2 2a a
2 2
1 1 1 11 1I 1 I 1
1 1
a
aa
b a a
c a
I
III I I
I I
=
12
7/29/2019 Fault Analysis SC 2012
13/29
Conversion Sequence to Phase
2
2
0 0
Define the symmetrical components transformationmatrix
1 1 1
11
Then
aa
b a s
c a
I II
I I I
I I I
A
I A A A I
13
7/29/2019 Fault Analysis SC 2012
14/29
Conversion Phase to Sequence
1
1 2
2
By taking the inverse we can convert from thephase values to the sequence values
1 1 11
with 13
1
Sequence sets can be used with voltages as well
as with currents
s
I A I
A
14
7/29/2019 Fault Analysis SC 2012
15/29
Example
1 2s
2
0
Let
Then
1 1 1 0 01
13
6.121
a
b
c
V
V
V
V
V A V
15
7/29/2019 Fault Analysis SC 2012
16/29
Example
0
2
2
10 0
Let 10
Then
1 1 1 10 0
1 101
s
s
I
I
I
I
I AI
16
7/29/2019 Fault Analysis SC 2012
17/29
Power in Symmetrical Components
The total power in a three-phase network is given in
terms of phase variables by
where the asterisk denotes complex conjugation. We can show that the
corresponding expression in terms of sequence variables is given by
The total power is three times the sum of powers in individual
sequence networks.
17
7/29/2019 Fault Analysis SC 2012
18/29
Use of Symmetrical Components
Consider the following wye-connected load:
( )
( )
( )
n a b c
ag a y n n
ag Y n a n b n c
bg n a Y n b n c
cg n a n b Y n c
I I I I
V I Z I Z
V Z Z I Z I Z I
V Z I Z Z I Z I
V Z I Z I Z Z I
ag y n n n a
bg n y n n b
ccg n n y n
V Z Z Z Z I
V Z Z Z Z I
IV Z Z Z Z
18
7/29/2019 Fault Analysis SC 2012
19/29
Use of Symmetrical Components
1
1
3 0 0
0 0
0 0
ag y n n na
bg n y n n b
ccg n n y n
s s
s s s s
y n
y
y
V Z Z Z Z I
V Z Z Z Z I
IV Z Z Z Z
Z Z
Z
Z
V Z I V A V I A I
A V Z A I V A Z A I
A Z A
19
7/29/2019 Fault Analysis SC 2012
20/29
Networks are Now Decoupled
0 0
0 0
3 0 0
0 0
0 0
Systems are decoupled
( 3 )
y n
y
y
y n y
y
V IZ Z
V Z I
ZV I
V Z Z I V Z I
V Z I
20
7/29/2019 Fault Analysis SC 2012
21/29
Grounding
When studying unbalanced system operation how asystem is grounded can have a major impact on the fault
flows
Ground current only impacts zero sequence system
In previous example if load was ungrounded the zero
sequence network is (with Zn equal infinity):
21
7/29/2019 Fault Analysis SC 2012
22/29
Grounding, contd
Voltages are always defined as a voltage difference.
The ground is used to establish the zero voltage
reference point
ground need not be the actual ground (e.g., an
airplane)
During balanced system operation we can ignore the
ground since there is no neutral current
There are two primary reasons for grounding electrical
systems
1. safety
2. protect equipment 22
7/29/2019 Fault Analysis SC 2012
23/29
Sequence diagrams for generators
Key point: generators only produce positive sequence voltages; therefore
only the positive sequence has a voltage source.
During a fault Z+ ZXd. The zero sequence impedance is
usually substantially smaller. The value of Zn depends on
whether the generator is grounded.
23
7/29/2019 Fault Analysis SC 2012
24/29
Sequence diagrams for Transformers
The positive and negative sequence diagrams for transformers are similar to those for
transmission lines.
The zero sequence network depends upon both how the transformer is grounded and
its type of connection. The easiest to understand is a double grounded wye-wye
24
7/29/2019 Fault Analysis SC 2012
25/29
Transformer Sequence Diagrams
25
7/29/2019 Fault Analysis SC 2012
26/29
Unbalanced Fault Analysis
The first step in the analysis of unbalanced faults is to assemble
the three sequence networks.
For example, for the following power system lets develop the
sequence networks.
26
7/29/2019 Fault Analysis SC 2012
27/29
Sequence Diagrams
Positive Sequence Network
Negative Sequence Network
27
7/29/2019 Fault Analysis SC 2012
28/29
Negative Sequence Network
28
7/29/2019 Fault Analysis SC 2012
29/29
Zero Sequence Network
29