46
fÅÉ båÖáåÉÉêáåÖ bñÅÉääÉåÅÉ dÉåÉÖä~ÅÉ dbkbo^qlop cNR ~åÇ cPM `çåíê~ÅíçêÛë ã~åì~ä j~åì~ä cçê cNR ~åÇ cPM J jáää W OMMUÓNN L jçÇ W slJMR

F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

  • Upload
    others

  • View
    17

  • Download
    0

Embed Size (px)

Citation preview

Page 1: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

==

fÅÉ=båÖáåÉÉêáåÖ=bñÅÉääÉåÅÉ= =

dÉåÉÖä~ÅÉ= == dbkbo^qlop=cNR=~åÇ=cPM== `çåíê~ÅíçêÛë=ã~åì~ä== =j~åì~ä=cçê=cNR=~åÇ=cPM=J=jáää=W=OMMUÓNN=L=jçÇ=W=slJMR=

Page 2: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important
Page 3: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

1

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

Table of contents

Table of contents1. General .................................................................................. 4

1.1 Introduction to this notice ................................................................41.2 Warning ............................................................................................41.3 Where can you fi nd the information you need? ...............................4

2. Safety rules ............................................................................ 52.1 Meaning of the danger pictograms ...................................................52.2 Qualifi cation and training of personnel ............................................52.3 Danger in the event of non-observance of the safety rules ..............52.4 Operating range ................................................................................5

3. Safety and Environmental Instructions ............................. 63.1 Safety rules .......................................................................................63.2 Protection of the Environment ..........................................................6

4. Safety of pressure vessel ..................................................... 75. Installation and Handling of the F15 and F30 ..................... 86. Dimensions and Connections of the F15 and F30 ............. 9

6.1 Positioning the machine .................................................................106.2 Mountings .......................................................................................106.3 Ice level safety detection ................................................................ 11

7. Connections ....................................................................... 127.1 Specifi cations .................................................................................127.2 Hydraulic connections ....................................................................137.3 Electrical connection .......................................................................137.4 Connections to the refrigerating circuit ...........................................15

8. Initial start up ....................................................................... 168.1 Checks and adjustments ................................................................168.2 Recommended uses .......................................................................188.3 Start-up report ................................................................................18

9. Operation ............................................................................. 199.1 Principle of operation ......................................................................199.2 Electrical sequences .......................................................................209.3 Refrigeration operation ...................................................................22

Page 4: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

2

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

Table of contents

10. Addition of salt .................................................................. 2310.1 The salt dosing tube ....................................................................2310.2 The dosing pump .........................................................................24

11. Options ............................................................................... 2611.1 Electrical terminal box ...................................................................2611.2 «ILD» Ice level detector (regulation) .............................................2611.3 Remote Control .............................................................................26

12. Maintenance ..................................................................... 2712.1 Maintenance schedule ..................................................................2712.2 Routine maintenance ....................................................................2812.3 Replacement of worn parts ..........................................................29

13. F15 and F30 Refrigeration Diagrams .............................. 3014. Troubleshooting ................................................................ 3115. Exploded view ................................................................... 32

15.1 F15 Generator ..............................................................................3215.2 F30 Generator ..............................................................................33

16. Commissioning Check List .............................................. 3417. Operational Measurement sheet ...................................... 36

17.1 Measurement Points for F15 or F30 Generator ............................3718. Adjustment of torque limiter ............................................ 3819. Adaptating of Water Pump ............................................... 3920. Adjustment of Rubber Wipers Blade ............................... 4021. Electrical connexion of the ILD ........................................ 4122. Adjusting the Reamer ....................................................... 42

Page 5: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

3

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

Type / Model

Pression de service Max. (PS)Max. working

Intensité maxi. / max.

Charge fluide maxi Max. refrigerant

N° construction / Serial

Puissance installée Installed

Fluide / Fluid

Tension (V) - Phases Voltage (V) - Phases

Fréquence / Frequency

GEA Geneglace s.a.s.9 rue des orfèvres44840 Les Sorinières - France+33 (0)2.51.19.10.51

Kg

A

Bar

kVA

Date

Hz

IDENTIFICATION

Introduction Your GENEGLACE ice machine has been designed and manufactured in accordance with current regulations; built with the greatest care, it has been subjected to a test for long-lasting quality. Nevertheless, if you discover a manu-facturing fault and in order to protect your GENEGLACE machine, please do not attempt a repair but contact us as soon as possible.Any reproduction of all or part of this notice is subject to prior permission.The information contained in this notice is subject to modifi cation without prior notice.In order to update the present notice, please advise us by return of any errors or misunderstandings that may have slipped in.GENEGLACE cannot be held responsible for damage or problems in operation occurring with GENEGLACE machines as a result of use outside the operating or safety limits or even the use of options or consumable items other than those approved by GENEGLACE.

IDENTIFICATION

Manufacturer Plaque

Page 6: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

4

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

1. General

1.1 Introduction to this noticeYour GENEGLACE ice machine has been designed and manufactured in accordance with current regulations; built with the greatest care, it has been subjected to a test for long-lasting quality. Nevertheless, if you discover a manu-facturing fault and in order to protect your GENEGLACE machine, please do not attempt a repair but contact us as soon as possible.

1.2 Warning- Any reproduction of all or part of this notice is subject to prior permission.

- The information contained in this notice is subject to modifi cation without prior notice.

- In order to update the present notice, please advise us by return of any errors or misunderstandings that may have slipped in.

- GENEGLACE cannot be held responsible for damage or problems in operation occurring with GENEGLACE machines as a result of use outside the operating or safety limits or even the use of options or consumable items other than those approved by GENEGLACE.

1.3 Where can you fi nd the informa- tion you need? After reading the safety instructions, the «Handling» section gives a list of the items that should come with your GENEGLACE, as well as instructions concerning handling with complete safety.

The layout will tell you about : the overall dimensions of your GENEGLACE, the procedure to follow for choosing the best location for it in relation to its environment and fi nally all information concerning accessibility for future service and maintenance.

«Connections» : In order to make all the hydraulic, elec-trical and cooling connections correctly, this section will give you some useful advice regarding the procedures for the connections.

To ensure that your GENEGLACE starts successfully the fi rst time and not handling it incorrectly, refer to the «Initial Start Up Sheets» as well as this section 8.

The «Operation»: section describes in detail all the operational features, factory settings and adjustments to be carried out.

The «“Service, Maintenance and Fault Rectifi cation»: section will help you, by following its advice, to keep your GENEGLACE in optimum working condition for as long as possible.

Throughout this notice, you will fi nd boxes such as :

NoteA note provides certain general information

relevant to the subject treated.

TipThe tip suggests procedures enabling you to surmount

or get round any diffi culties that may arise.

ImportantThis inset is intended to draw the attention of the reader to particular points that could be relevant

to the safety of the operator or the machine.

General

Read the safety instructions carefully before working on the ice machine.

Important

Page 7: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

5

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

2. Safety rulesThis notice contains important rules to be observed con-cerning safety, installation, operation and maintenance of ice machines and their scrapping. And for this reason it must be read before any handling. In addition, a copy of the «Notice for Users», including the safety rules, must be continuously available to the user at the place of operation of the GENEGLACE.

An information board, indicating the type, identifi cation number and certain operating and safety features of your GENEGLACE machine must always be visible and under no circumstances must it be removed.

The safety rules contained in this notice, as well as the national or local requirements for the prevention of ac-cidents must also be observed.

2.1 Meaning of the danger pictograms

The safety rules appearing in GENEGLACE notices which, if not observed, could result in body injury, are preceded by the following symbols :

These symbols are also placed directly on the machine (or on certain spare parts), as well as arrows indicating the direction of rotation which must be observed.You must ensure that all these markings remain legible.Non-observance of these safety or operating instructions can result in equipment damage or incorrect operation of the machine, this instruction must be taken seriously.

2.3 Danger in the event of non- observance of the safety rulesNon-observance of the safety rules can also result in physical danger, equipment danger or pollution of the environment.Failure to observe the safety rules will result in the loss of rights to damages or compensation.

2.4 Operating range

Electrical supply : as indicated on the manufacturer’s rating plate and in accordance with current standards.

Safety rules

General danger

Risk of burning

Electrical danger

Chemical danger

Danger of damage due to pressure

Escape of gas

ImportantYour GENEGLACE is designed to operate within the

following limits : Type of fl uid : R22 & R 404A

(for other fl uids : consult us) Maximum working pressure (MWR) See page 7 Ambient air temperature : + 5 to + 35°C

(dry bulb) Minimum evaporating temperature : - 25°C Temperature of water to be frozen : + 5 to + 25°C Mains water pressure : 2 to 4 barHardness of mains water: TH 15 to 20° French°

Acidity of mains water : PH 7/8 Sodium chloride content : about 100 g/m³. Electrical protection : IP 44

Any use of the GENEGLACE machine outside these limits could result in malfunctions, or even damage.

Altitude : if greater than 500 m, consult us.

All installation and servicing is to be performed by qua-lifi ed personnel in compliance with all relevant practices and safety procedures.

Note that all local and regional regulations and safety standards, such as EN378, must be taken into account when designing, connecting and running the system.

Concerning accessibility to the machine by the public, the operator is responsible for protecting himself against any accident that may occur associated with its mechanical, electrical or chemical operation.

2.2 Qualifi cation and training of personnel

Page 8: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

6

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

3.1 Safety rules

Starting and stopping a GENEGLACE.Use the switch provided for this purpose on the electrical terminal box.

CAUTIONWhen stopping, the rotating part of the generator maintains a residual rotation that may cause an

accident.

If it is diffi cult to reach the Start/Stop switch (machine mounted high up), request a remote control at a more convenient height.If it is necessary to switch the machine off, use the isolating switch on the electrical terminal box (three phase). Lock the equipment with a padlock on the isolating switch to prevent inadvertent starting of the machine.

The principal area of danger is located inside the ice maker itself, enclosed by an upper cover and a base cover.

It is dangerous to place the hands or any object into this area while the rotating part is turning, for example during a normal cleaning operation of the water system.It is recommended that the machine be stopped and switched off for cleaning or that the emergency switch on the upper part is used.

If the rotating part is driven by a reduction gear and a motor through a belt, a guard that can removed by using tools is provided. Operation of the machine without this guard is prohibited.

The operation of manual valves is strictly reserved for maintenance personnel with the necessary skills (risk of spurting of fl uids under pressure).

In the event of a general power failure, protect yourself against any risk when the power returns (unintended start-ing): keep personnel away from dangerous areas.

Operation of the machine without the original safety equip-ment is prohibited: torque limiter, electrical protection, pressostats, thermostats, transmission guards, etc. These devices must be maintained in working condition and the pictograms indicating the dangers must remain visible.

The drawing below indicates the principal dangerous areas of the GENEGLACE.

3. Safety and Environmental Instructions

3.2 Protection of the EnvironmentMaterials and fl uids resulting from the disposal of ma-chines must be treated via the approved channels in accordance with current regulations.

Safety and Environmental Instructions

Within the directives of the “MONTREAL PROTOCOL”, any service work that might place the cooling system in communication with the atmosphere must be performed by skilled personnel.

The use of a mains socket or an upstream isolating switch is prohibited.

Before operating, switch off the installationBefore operating, switch off the installation. All other maintenance, if required, shall be done by a qualifi ed engineer.

Page 9: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

7

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

4. Safety of pressure vessel

Safety of pressure vessel

4.1.1 Service instructions

The GENEGLACE ice generators are pressure vessels, to be incorporated into refrigeration systems complying with EC Machines Directive 98/79/EEC. Their use is only permitted if they have been incorporated in refrigeration systems complying with the present instruction and if the refrigeration systems fully comply with current local regulations.

F15 and F30 generators are designed and built using good engineering practice in accordance with article 3§3 of Directive 97/23/EC relating to the construction of pressure vessels.

4.1.1.1 Residual Danger

Pressure vessels can be a source of unavoidable residual danger. Anyone working on such equipment must therefore carefully read this service instruction and must take into consideration:the precautions to be taken against accidents, generally recognised safety rules, EU directives and any special requirements of the country concerned.

4.1.1.2 Location

When used in extreme conditions (for example, in an aggressive atmosphere, in extreme outside temperatures, etc.) take adequate protective measures. Where appropriate, it is advisable to consult Geneglace.

Warning !

Geneglace ice generators are designed to be installed in the “low pressure” sides of refrigeration systems.

Geneglace equipment must not be used as a storage reservoir for coolant.

4.1.2 Protection against exceeding permissible limits

Permissible limits for GENEGLACE « generator only » type pressure vessels

Type (bar) MWP

Groupof

Refrigerant

T°Min

°C / °F

T°Max

°C / °F

Maximumcharge

KgF15 1,5 F30 15 2 -30 / -22 +45 / +113 2,5

4.1.3 Pressure relief valve

All systems must be designed and operated so that the maximum working pressure (MWP) in pressure vessels cannot be exceeded. Pressure relief valves are obligatory and must be correctly rated and installed by installer (not inclued in the standard scope of supply).

4.1.4 Safety cut-out device

In accordance with current local regulations, safety cut-out devices must be fitted to limit the pressure or temperature (thermostats and safety pressure regulators).

Page 10: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

8

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

5. Installation and Handling of the F15 and F30

Installation and Handling of the F15 and F30

50 kg

BA C

H1

I

L

H2/H

3

D2

DE

F

D1

Ea

c

K,Øi

ØG1 2

a

b

3

ØG

K,Øi

Net weightInstallation

Minimum clearance for service

Handling

Tightness seal around the boring1 Raising of the floor to avoid accidental water leaks in the storage2 Provision should be made in the insulation to enable fixing the ice level detector3 Dimensions of the base without insulationB,E Minimum clearance for reducer removalD1 Minimum clearance for reamer removalD2 Ice chuteG Two fixation screws 8 x 40 mmK

We advise to foresee enough space around the system for its inspection and maintenance

* Dimensions in mm

A 300

C 500D 600

F 300

D1 300D2 460

H1 430H2 600H3 600

LI

GB

E

ba

ci

240505080

8

400520

360

390

GENEGLACE s.a.s.

Tél. +33-(0)2-51-19-10-51

Installation and handling GTI.001A

Fax +33-(0)2-40-05-73-81

ZAC de la Forêt - 9, rue des Orfèvres44840 Les Sorinières - France

COMMERCIAL LAND-BASEDGenerator F15

Edition date

GENEGLACE may change this document whitout prior notice

29/01/2009 JPM 0.0V

90 kg

BA C

H1

I

L

H2/H

3

D 2

DE

F

D1

a

c

K,Øi

ØG1 2

b

3a

Net weightInstallation

Minimum clearance for service

Handling

Tightness seal around the boring1 Raising of the floor to avoid accidental water leaks in the storage2 Provision should be made in the insulation to enable fixing the ice level detector3 Dimensions of the base without insulationB,E Minimum clearance for reducer removalD1 Minimum clearance for reamer removalD2 Ice chuteG Two fixation screws 8 x 40 mmK

We advise to foresee enough space around the system for its inspection and maintenance

* Dimensions in mm

A 500

C 300D 700

F 500

D1 300D2 500

H1 500H2 690H3 700

LI

GB

E

ba

ci

340202020

8

500650

470

470

GENEGLACE s.a.s.

Tél. +33-(0)2-51-19-10-51

Installation and handling GTI.001A

Fax +33-(0)2-40-05-73-81

ZAC de la Forêt - 9, rue des Orfèvres44840 Les Sorinières - France

COMMERCIAL LAND-BASEDGenerator F30

Edition date

GENEGLACE may change this document whitout prior notice

29/01/2009 JPM 0.0V

Page 11: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

9

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

6. Dimensions and Connections of the F15 and F30

Dimensions and Connections of the F15 and F30

Generator F15

Minimal clearance for disassembly: See Installation and handling section

mmLength

Item Description Qty.Dimensions Overall Open crate Full crateDimensions Item

WidthHeight

Volume

Net weightGross weigh

Max. water flow 19 l/h Water pressure 2 -> 4 barMaximum working pressure 2 MPa (PED 97/23 CE)

mmmm

m3

kgkg

0,12 0,72 0,99

Electrical connections

Other specifications

Refrigerating connections

Hydraulic connections

400520

600

9008001000

10009001100

50115 1255050 50

E Horizontal heat exchanger (loose)

1

F Ice detection flag (safety) 1

ConnectionsItem Description Qty. Type MaterialDimensionsA Generator water supply 1 Plain ends tube Chromed brass10/12 mmA, or 1 Threated Chromed brass1/2 " gazB Overflow 1 Plain ends tube Plastic pipe20/22 mm

ConnectionsItem Description Qty. Type MaterialDimensionsE1 Heat exchanger-suction line 1 O.D.F. Copper7/8 " E2 Heat exchanger-liquid line 1 O.D.F. Copper3/8 " H Suction 1 Plain ends tube Steel26,7 x 2,9 mmJ Liquid inlet 1 Flare Brass3/8 "

Item Description Qty. Nominal power Nominal amperage

Power supply

1 x 90 W 1 x 0,62 AReamer motor 1F1 400 V - 3 - 50 Hz1 x 70 W 1 x 0,35 APump 1F2 230 V - 1 - 50 Hz

Torque limitor switch 1F3 -Ice level safety switch (supplied) 1F4 -

* Dimensions in mmLI

H1 430H2 600

600400520

H3

Dimensions GENEGLACE s.a.s.

Tél. +33-(0)2-51-19-10-51

Dimensions and connections GTE.001A

Fax +33-(0)2-40-05-73-81

ZAC de la Forêt - 9, rue des Orfèvres44840 Les Sorinières - France

COMMERCIAL LAND-BASEDGenerator F15

Edition date

Cancels and replaces the document of 20/08/2004GENEGLACE may change this document whitout prior notice

29/01/2009 JPM 0.0V

Generator F30

Minimal clearance for disassembly: See Installation and handling section!

mmLength

Item Description Qty.Dimensions Overall Open crate Full crateDimensions Item

WidthHeight

Volume

Net weightGross weigh

Max. water flow 50 l/h Water pressure 2 -> 4 barMaximum working pressure 1,5 MPa (PED 97/23 CE)

mmmm

m3

kgkg

0,23 0,72 0,99

Electrical connections

Other specifications

Refrigerating connections

Hydraulic connections

500650

700

9008001000

10009001100

90155 1659090 90

E Horizontal heat exchanger (loose)

1

F Ice detection flag (safety) 1

ConnectionsItem Description Qty. Type MaterialDimensionsA Generator water supply 1 Plain ends tube Chromed brass10/12 mmA, or 1 Threated Chromed brass1/2 " gazB Overflow 1 Plain ends tube Plastic pipe20/22 mm

ConnectionsItem Description Qty. Type MaterialDimensionsE1 Heat exchanger-suction line 1 O.D.F. Copper7/8 " E2 Heat exchanger-liquid line 1 O.D.F. Copper3/8 " H Suction 1 Plain ends tube Steel26,7 x 2,9 mmJ Liquid inlet 1 Flare Brass3/8 "

Item Description Qty. Nominal power Nominal amperage

Power supply

1 x 90 W 1 x 0,62 AReamer motor 1F1 400 V - 3 - 50 Hz1 x 70 W 1 x 0,35 APump 1F2 230 V - 1 - 50 Hz

Torque limitor switch 1F3 -Ice level safety switch (supplied) 1F4 -

* Dimensions in mmLI

H1 500H2 690

700500650

H3

Dimensions GENEGLACE s.a.s.

Tél. +33-(0)2-51-19-10-51

Dimensions and connections GTE.001A

Fax +33-(0)2-40-05-73-81

ZAC de la Forêt - 9, rue des Orfèvres44840 Les Sorinières - France

COMMERCIAL LAND-BASEDGenerator F30

Edition date

Cancels and replaces the document of 20/08/2004GENEGLACE may change this document whitout prior notice

29/01/2009 JPM 0.0V

Page 12: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

10

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

10 cm mini

12345

6.1 Positioning the machine

- Place the generator on a level, fl at surface.

- The generator must be located in a position protected from bad weather, water spray or any other liquid and in a non-aggressive environment.

- Position the generator so as to maintain adequate ac- cess for upkeep and maintenance (see Installation Handling - free access)

- The generator must be mounted suffi ciently high, in order to permit suitable storage for its daily production of ice (e.g. cold chamber, static or orbital silo, etc.).

- Avoid locating the ice output in the air fl ow from an evaporator.

- Do not reduce the cross section of the ice output.

NoteIn order to facilitate all upkeep and maintenance work on the generator, (such as regular greasing of the bearings of the shaft and the reamer), provide

accessibility below and above the machine.

Fig 512. Optional chute, easily removable for mainte -nance of generator.

ImportantRisks of freezing during machine downtime : protect the base of the pump and valve fl oat by

means of a heater housed in the base. This device will only be effective for an air tem-perature of - 10°C to + 5°Cmaximum for a period of 12 to 24 h. Beyond that, it is preferable to drain the machine if it is stopped. Also protect the water

supply pipework

NoteWhen fi tting a heater resistance, provide a circuit breaker for protection and a thermostat

to monitor the ambient air temperature.

6.2 Mountings

The opening in the generator mounting must be at least equal to the diameter «G» of the ice chute.

ImportantDo not forget to add a silicone seal all round the base of the generator to prevent water entering the

ice storage area.

The unit is mounted by the bottom of the base using the two holes provided for the purpose. Fibre seals ensure the mountings are watertight.

Positioning the machine

Ice overfl ow

area

Access toemergency

switch

Maxi 45°

ChutePVC

1 Cap 2 Lag screw 3 Fibre seal 4 Pin 5 Silicone seal

Mounting

In concreteIn woodf

Page 13: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

11

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

6.3 Ice level safety detection

The ice level safety detection, consisting of a blade and a probe, is delivered not fi tted with your GENEGLACE.

ImportantThis safety system does not control the ice maker. The ice maker does not re-start automatically after the bin is emplied.

It must be associated with a manual reset device in accordance with electrical diagram 534004.

In order to prevent direct action due to ice fl akes falling on the switch “fi nger” : - the blade must be screwed into the lower end of the central shaft and positioned opposite the reamer, (see drawing opposite).

- the switch and its end must be positioned in line nith and underneath on of the supporting arm of the cen- tral bearing of the generator.

In the case of an insulated wall, we recommend the following method of fi xing :

Positioning the machine

Stainless steel threaded rod

Stainless steellock nut

Stainless steel washer

3 mm - 1/27 inch Ice level safety switch

Page 14: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

12

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

7. Connections

7.1 Specifi cations

Connections - Specifi cations

Specifications Units F15 F30

Dimensions Length x width x height mm 520 x 400 x 600 650 x 500 x 700 Net weight Kg 50 90 Sound level dBa < 70 < 70

Fluid load of R22 or R404A kg 1.5 2,5

Conditions of operation R22 R404a R22 R404a R22 R404a Frequency of power supply Hz 50 60 50 60 50 60 50 60 50 60 50 60 Production of temperature of water to be frozen of +15°C kg/24h 450 450 450 450 650 650 650 650 950 950 950 950

Reamer Speed r.p.h 62 75 62 75 70 75 70 75 98 83 98 83 Thickness of ice flakes mm 1.9 1.8 1.9 1.8 1.9 1.7 1.9 1.7 1.8 2 1.8 2 Evaporation temperature at the generator °C -18 -17 -20 -19 -20 -18 -22 -20 -23 -21 -23 -23

Required refrigeration power KW 2.33 2.33 2.33 2.33 3.4 3.4 3.4 3.4 4.9 4.9 4.9 4.9

Thermostatic expansion valve Type TX2 TS2 TX2 TS2 TX2 TS2 Orifice No. 2 3 2 3 2 4

Electrical supply V 400V 3 phase + N - 50 Hz / 60 Hz Power of reducer motor W 90 Three 90 Three Pump power (single phase) W 70 70 Switches Torque limiter I S L (supplied not fitted) Electrical diagrams Power + control, Part no.: 535003 Electrical diagrams for ice level detection

With manual resetting, Part no.: 535004 With automatic resetting, Part no.: 535005

Refrigerant connections Liquid supply inches 3/8’’ brass nut

Inlet mm 26.9 x 2.65 smooth steel 26.9 x 2.65 smooth steel

Exchanger (supplied not fitted) inches Inlet 7/8’’ Inlet 1 7/8’’ inches Liquid 3/8’’ Liquid 1/2’’

Hydraulic Water supply connection mm 15/21 threaded connector or 10 x 12 smooth brass Overflow connection mm 20 x 22 smooth steel Water flow rate required (Max) L/h 21 50 Water pressure required bar 2 to 4

Page 15: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

13

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

7.2 Hydraulic connections

RecommendationRisk of frost : fi t the water supply and overfl ow pipes with a device (insulation and/or heater) to protect them

against freezing.

7.2.1 Connection to the water supply

The water supply should preferably be connected by a fl exible hose to the 15/21 threaded connector + fl ange. Rigid pipe can also be used soldered to the 10/12 smooth brass connector.

NoteIt is a good idea to fi t a shutoff valve in the water in

order to make maintenance operations easier.

When tightening the fl ange connector, hold the fl oat valve so that its water outlet is perpendicular to the bottom of the base and the rod and fl oat valve can move freely up and down.

ImportantIn order to prevent malfunctions of your

GENEGLACE and from a food hygiene point of view, it is a good idea to fi t a water fi lter or purifi er

as required.

In fact, fi ltering the water supply may considerably slow down the deposition of impurities in your GENEGLACE, but not scale formation. For this reason, when the hard-ness of the water is too high, the use of a softener is required.

ImportantIn order to prevent malfunctions of your

GENEGLACE it is a good idea to fi t a device for pro-tection against falls in pressure or water fl ow rate.

7.2.2 Overfl ow connectionIn the event of malfunction of the fl oat valve, the ex-cess water escapes through the overfl ow. The overfl ow therefore prevents any overfl ow of water through the ice descent hole and thus into the ice store.

The overfl ow water must fl ow into the drains as required by the regulations.The drain pipe must not have a rising portion that could prevent the natural fl ow of water, and its slope must be suffi cient.

7.3 Electrical connectionThe type of electrical power supply is stated on the rating plate attached to the generator.Ensure that the electrical supply for your GENEGLACE complies with the regulations in force and in the following respects :

voltage (Volts) three phase or single phase + Earth frequency (Hz) installed power (KVA) nominal current (A)

ImportantThe cross section of the electrical supply cable must be adequate for the installed power of the machine (see rating plate) and comply with cur-rent standards. An electrical protection device complying with current standards must be fi tted to protect the various parts of the machine. Using the electrical diagram of the machine, check the polarity of the electrical connection of single phase

generators.

Hydraulic and Electrical connections

An electrical control box is obligatory to control the opera-tion of the generator. The electrical sequences and cur-rent regulations must be followed (refer to the functional diagram section).

The water consumption of your GENEGLACE is equal to its ice production

the water supply pressure must be between 2 bar mini-mum and 4 bar maximum. The water fl ow rate must al-ways be constant and greater than that due to the water consumption of your GENEGLACE. If this is not the case, the installation of a pump and reservoir and/or an expan-sion valve is essential.

Page 16: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

14

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

W2 U2 V2

W1 U1 V1

U1 V1 W1

10 f

13 21

14 22

13 21

14 22

7.3.1 Reamer motor In the case of a three phase supply, connect as appropriate for the characteristics of the electrical supply. The motors are supplied connected in star.

Where the electrical supply is single phase, 220 Volt, the reamer motor is fi tted with a 10 μf capacitor.Connect as follows :

If the moving parts assembly does not rotate in the direc-tion indicated by the arrow on the top, connect the phase to W1.

7.3.2 Water pump The water pump operates from 220 Volts, single phase and is fi tted in advance with a 3 m cable.However if the cable has to be changed, the connections must be as follows :

7.3.3 Torque limiter switchThe drawing below shows the position of the torque limiter switch when the generator is operating normally.

7.3.4 High level safety switchThe drawing below shows the position of the high level safety switch when the generator is operating normally.

NoteIn all the above cases, do not forget to connect

the earth terminals.

Electrical connection

Neutral Phase

Neutral (blue)

Phase (brown)

Earth (green /yellow)

Faultindication

Action on safetychannel

Earth

Earth

Earth

Earth

Operate the switch for manual resetting and indication

Page 17: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

15

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

3

4

2

1

7.4 Connections to the refrigerating circuit

7.4.1 General topics concerning the liquid and suction pipes

ImportantEvery precaution must be taken to ensure that the refrigerant piping is clean and free from moisture

and enhances oil return to the compressor.

Concerning the suction pipe, as far as possible the loss of pressure between the generator and the compressor must not exceed a value corresponding to a variation of about 1 to 2°C in the temperature of the saturated fl uid.

7.4.2 Generator and refrigerating system located at the same level

F15 and F30 generators are fi tted with a thermostatic ex-pansion valve. A heat exchanger is supplied not mounted with the generator. Install it according to the diagram below, horizontally and close to the generator.

The diameters of pipes «section 7» can be retained for a maximum developed length of 6 m.

7.4.3 Generator and refrigerant systems located at different levelsIn the case where the compressor and the generator are mounted at different levels, certain precautions concerning the piping must be taken into account.

7.4.3.1 Suction pipe The suction pipe must be arranged with a slope descend-ing towards the compressor and any part of the piping that could constitute a fl uid trap must be avoided.Wherever the suction piping has to rise, a siphon must be provided to form an oil trap at the output from the evapora-tor. It is advisable to install a double siphon three metres from the rising piping.Regarding the section of suction piping sloping towards the compressor, a reverse siphon must be placed at the top in order to prevent any return behind of oil.

Where the suction piping is very long, it is recommended, after a section of ascending piping of suffi cient size to en-sure the correct oil carry-over, that a change is made to a larger cross section in order to minimise pressure drop.The suction piping must be thermally insulated in accord-ance with current technology.The thermal insulation must have a thickness of at least 13 mm and must tight to vapour migration (this is to prevent rotting of the insulating material).

7.4.3.2 Liquid pipe

Any gas trap must be avoided, that is any section of pip-ing in an inverted «U» so as not to interrupt the fl ow of liquid.A solenoid valve on the liquid line must shut off the supply of refrigerant fl uid from the generator in order to avoid any risk of liquid fl uid fl owing into the compressor.Where the difference in level is greater than about 5 m, it is recommended that the liquid pipe is increased in size. In this case, it is possible that the selection of the expan-sion valve may have to be reconsidered, no longer taking into account the condensation pressure but the pressure existing upstream of the expansion valve.

Connections to the refrigerating circuit

Refer to the section «Safety Concerning Pressu-rised Equipment».

4 m/s or more

4 m/s or more

8 to 12 m/sMax3 m

Max3 m

10 hourbulb

Suction

HP Fluid

Insulation

0,5 %

0,5 %

– Supplied with the generator

- - - To be fitted on site

1 Thermostatic expansion valve

3 Evaporating pressure regulator (if required)

2 Heat exchanger F15 - 7/8 - 3/8 F30 - 1"1/8 - ½

4 Liquid solenoide valve

Page 18: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

16

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

M

1 2 3 4 5 6

R

8. Initial start upThis section gives the chronological order of the checks and actions to be carried out before, during and after the initial start up of your GENEGLACE in complete safety.This is why, before operation of your GENEGLACE, we invite you to refer to the recommendations suggested in this section, by ticking X the boxes corresponding to the checks you carry out. (See section‘’Commissioning Check List’’).

8.1 Checks and adjustments8.1.1 Hydraulics

Ensure that the water fl ow rate is greater than the quantity of water required for maximum production of your GENEGLACE and that the water quality is as required.

Check that the water supply pressure of your ma- chine lies between 2 and 4 bar.

Check, by pressing on the valve fl oat, that water is reaching the base.

8.1.1.1 Presetting the fl oat valveThe fl oat valve has two basic settings.The fi rst setting is the level of water in the base. The level must be suffi cient to prevent cavitation of the pump through lack of water on the one hand and to prevent overfl ow on the other hand.The second setting is for the water fl ow rate, which must correspond to the quantity of water necessary for the maximum ice production rate of your GENEGLACE.

Fig. 7111. Illustration of the fl oat valve in its closed and open positions.

♦ Setting the level

By turning the screw 6, adjust the water level in the base while observing the following dimensions :

Once the adjustment of the water level in the base has been completed, lock the setting with the lock nut 5.

♦ Adjusting the fl ow rate

♦ Measure

Adjusting the fl ow rate of the fl oat valve must be carried out when its fl ow rate is not suffi cient to provide the water required for the production of ice in your GENEGLACE.In this case :

shut-off the water supply and remove the inlet connector of the machine.

Unlock the nut 2, (see fi g. 7111) Unscrew adjustment 1 in the housing 3 to increase

the fl ow rate. Lock the setting by locking the nut 2 on the housing

3, the normal setting of dimension R varies from 1 to 3 mm.

Adjust the water level

To prevent fl ooding of the ice container if the fl oat valve sticks open, check, with the machine stopped, that the fl ow rate of the valve when the fl oat is completely submerged does not exceed the capacity of the overfl ow.

If, after 1 hour of operation, the level in the base is lower than the minimum level, increase the fl ow rate of the valve as described above

TipAt the fi rst start up, submerge the fl oat to obtain a water level close to the overfl ow, in order to assist priming of the pump.

Initial start up

Water level in the ‘’Base’’ F15 / F30

Maximum shut-off level 50 mm

Minimum operating level 40 mm

Stroke

Page 19: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

17

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

8.1.3.2 Levels in the distribution tank

The water level must be a minimum of 15mm and a maximum of 1mm below the dent at the top of the upper water tray.In this case, check that the water reaches the overfl ow pipe of the distribution tank and is continuously removed by it.

Correct level (minimum 15 mm)

If the water level in the distribution tank is too low, raise the overfl ow pipe or refer to the section «Adapting of the water pump».

If the water level in the distribution tray is much too high, check that the holes in the tank are not blocked or fi le down the base of the overfl ow pipe or refer to the section « Adapting of the water pump».

8.1.2 Electrical systemWe checked previously that the water pump was function-ing correctly.

Adjust all the circuit breakers to the values corre- sponding to the nominal current consumed by their respective motors.

Adjust or preset the time delays. Checking the reamer motor :

Check that the motor is correctly coupled.energise the motor from a separate supply to check :

that the direction of rotation of the rotating parts is the same as that shown by the arrow marked on the top of the generator

that the speed of rotation of the reamer corresponds to the production rate of the machine (see “Specifi cations”)

Note The speed of the reamer is the number of complete revolutions made by all the rotating

parts in one hour.

At the same time, check the operation of the torque limiter by causing it to trip.

To do this it is suffi cient to trip the torque limiter by manually moving the roller of its microswitch. To reset the limiter, hold the reamer motor with both hands and turn it a few degrees in a clockwise direction

Fig.712. Illustration of resetting the torque limiter after trip-ping.

Check the operation of the high level safety switch by tripping it.

8.1.3 Refrigerating checks

8.1.3.1Before initial start up

Check for leaks in the refrigerating system. Ensure that the expansion bulb is correctly located

on the suction pipe, is held securely and is well insulated.

In the case of an independent refrigerating system, that is a generator connected to a compressor alone,the fl uid charge of the generator is indicated in the section (“Specifi cations” under “Connections”). The installer must provide the charge for the remain- der of the system.

Initial start up

For generators F15 and F30, the water level in the up-per water distribution tray is obtained by the fl ow rate of the water pump and the regulation of its over fl ow tube.In order to check the water level, switch on the pump alone after checking that the water level in the base is suffi cient.

Tripping the torque limiter

Resetting thetorque limiter

Overfl ow pipe

Dent

Page 20: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

18

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

8.1.3.2 Starting your ice machine Check that the starting procedure of your

GENEGLACE is carried out as described in the sec- tion ‘’ Diagram of operation’’.

Check that the distribution tank is correctly fi lled with water.

Adjust the back pressure valve to the reference suction pressure for your GENEGLACE (in the case of connection to central refrigeration plant).

Adjust the superheater 4 to 6 °K see section ‘’Adjus- ting the expansion’’.

Check the correct oil carry-over to the compressor (in the case of refrigerating system with a dedi- cated compressor).

After a few minutes of operation, check that ice is forming over the full height of the drum swept by the reamer.

If this is not the case, see the section ‘’Faults’’.

8.1.4 Other checks Check that the ice is stripped correctly.

If after a few minutes of operation the generator makes a signifi cant noise when the ice is stripped or the ice has diffi culty in releasing itself, see sections ‘’Faults and Addition of salt’’.

Check that the wipers are performing their function (no water fl owing into the ice store). To adjust the wipers see section’’ Adjusting the wipers’’.

Check, by simulating the presence of ice while pressing on the switch, that the ice safety detector is operational.

If required, adjust the salt dosage. See section ‘’Addition of salt’’.

ImportantThe high ice safety detector is, as its name indi-cates, a safety device for the generator and not a control device. For this reason, it should never be used for the purpose of controling the quantity of

ice in the bin.

8.1.4.1 Addition of salt

Check that the salt addition system is operating correctly.

8.2 Recommended uses

In the case of an independent refrigerating system, leave the power supply of the system switched on during periods of stoppage : the crankase heater must remain live.

In the same case, after a long period without electrical power, power on at least 3 hours before starting-up.

Avoid short duration run and stop periods. It is preferable to leave the machine operating for 4 hours rather than short-cycling it 4 times 1 hour on and 1 hour off.

During prolonged stoppages (more than a week), it is advisable to run the machine for 1 hour without adding salt and to drain and dry the base.

Management of a stock of ice : The basis for calculating the effective volume is : 500 kg about of freshly fl aked ice for 1m3 of storage.

To keep the ice fresh, do not keep it for more than 2 days.

The ice storage container must be emptied at least once a week so that the user has no diffi culty in extracting the ice. There is also a risk of damage to the GENEGLACE, by a build-up of ice in the generator.

8.3 Start-up reportA start-up report at the initial start up will :

- enable you to check the correct operation of your installation by noting a few key points of operation.- Open all right for warrantly.

You will fi nd an initial start up report at the end of this notice, it has four headings.

- Points to note : description of the inspection or check to be carried out.

- Values : generally a physical quantity to be measured and entered or a box to be ticked as checked.

- Where to note : the exact location of the note or check to be made in relation to the fl uid diagram attached to the note.

- How to note : for the purpose of helping you to make the most accurate note possible by means of a precise procedure.

Initial start up

Page 21: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

19

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

F

E

D

C

B

A

L

K

J

P

O

N

H

G

I

M

D

R S

B

Q

E

M

C1

C2

9. Operation

9.1 Principle of operation

9.1.1 Description of generator

Fig.1 Simplifi ed exploded view of a generator

Fig.2 Simplifi ed exploded view of a generator, and an illustration of the water distribution seen from above.

The water distributed by the tray B fl ows copiously and continuously over the internal surface of the stationary drum F, inside which a low temperature refrigerant fl uid circulates inside the double wall E. The insulation G of the drum ensures heat exchanger withf the water only.

Part of this water M is frozen and the excess returns via the lower water pan H into the base O, where the level P is kept constant by means of a fl oat valve (not shown). This water circulated by the pump N.

A helical reamer D, driven through a reduction gear A, sweeps the surface L, when the coat of iceis thick enough, the reamer starts rotating and harvesting the ice by ap-plying pressure on it.

The torque limiter K switches off the electrical supply to the motor-gearbox when in the event of mechanical overbad.

The thickness and quantity of ice produced by the genera-tor depends on : - The refrigerating power applied to the generator - The speed of rotation of the reamer.

ImportantThe thickness of the ice does not depend on the spacing of the reamer from the drum. IT IS DANGER-OUS TO SPACE THE REAMER AWAY FROM THE DRUM this can cause : fatigue of the bearings, tripping of the torque limiter, slugging and oil departure that

could destroy the compressor.

In the factory, the reamer is set as close as possible to the drum : a distance of less than 0,4 mm, for a proper operation.

The sprayed area Q is bounded by two wipers C1 and C2, which surround the reamer D. The purpose of wiper C1, situated before the reamer, is to dry the ice before the latter reaches the subcooling zone S. The area R for stripping the ice is located between one blade of the reamer D and the rear wiper C2.

The purpose of this wiper is to remove the residues of ice which may have remained on the drum after the passage of the reamer. There is no fl ow of water in the areas R and S. So the perfectly dry ice I is stripped in the area R and falls into the storage bin under the machine. However, for the rear wiper to effectively clean the surface, it must be adjusted in such a way that a thin trickle of water fl ows along its forward face in contact with the surface (1 mm approx.), as shown on fi g 2

NoteThe reamer speed is set in the factory and cannot be changed without the risk of causing operating

problems.

Operation

Thin trickle of water

Page 22: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

20

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

9.2 Electrical sequencesWhen starting the ice machine, with the compressor work-ing, only the solenoid valve for the water supply is open.After the time delay T1 of between 1 and 3 minutes, the water pump and the reamer start, the ice machine is then in its normal operating confi guration.

If the torque limiter trips, the solenoid valve, the reamer motor and the water pump stop immediately.When the torque limiter is reset, the start up procedure is repeated as when starting.On stoppage of the machine, the water pump and the solenoid valve cut out while the reamer continues to rotate for 3 minutes.

In the case where the system for adding salt comprises a dosing pump, its operation will be slaved to that of the functioning is dependent on that of the fl uid solenoid valve.

Electrical sequences

Time delay T1 : Time required to fi ll the cylinder with refrigerant before starting production. (15s to180s).Ice safety detector : Safety blade + Switch (Reset by Manual Electrical Switch).Time delay T.KA1 : Time required for cleaning the cylinder after stopping the generator. (180s).Do not install a pump-down on generators F15 and 30.

Fig. Block diagram of the electrical box available as an optional extra for a generator connected to a central refrigeration system.

Basic diagram F15 or F30

On / Off Switch 10

Liquid Solenoid Valve 1

0

Motor Gearbox 1

0 T1 T.KA1

Water Pump 1

0 T1

F15 or F30

Power on 10

Reset Switch 1

0

Run Relay 1

0

On / Off Switch 1

0

Torque Limiter or I.L.S Or 1 Reducer Thermal Relay 0

Liquid Solenoid Valve 1

0

Motor Gearbox 1

0 T1 T1 T.KA1

Water Pump 10

T1 T1

9.2.1 Central installation where one compressor is serving several evaporators an/or ice generators

T1 = time required after activation of the solenoid valve to fi ll 75 % of the cylinder with refrigerant.

Page 23: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

21

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

9.2.2 When the compressor serves a single ice generator

9.2.3 Automatic starting and stopping

Ice production can be controlled by a clock. The start time is estimated according to the capacity of the ice bin (500 Kg of ice approx.per cubic meter) and the hourly production rate of the machine.

ImportantIn order to avoid short cycles that could damage your GENEGLACE, the ice level detector

switch must be associated with manual or time-delayed resetting.

The electro-mechanical ice level detector (a blade driven by a micro-motor) is the most commonly used. In order to avoid short cycles, also use the terminal box 534004 requiring manual resetting or 534005 permitting time-delayed resetting T2.

If the ice level detector or the clock trip, the solenoid valve and the water pump stop immediately while the reamer continues to rotate for 3 minutes.

When this safety device is reset, the start up procedure is repeated as when starting.

Electrical sequences

When starting the ice generator, the compressor, the liquid feed solenoid valve, water pump and reamer begin working simultaneously. If the condensing unit is outside there may be a delay of a few seconds before the reamer and the pump start. (This is to ensure that at least 3/4 of the height of the generator is frozen at the start). On the diagrams according to T1 a question mark has (?), this suggests that it is not always necessary to install it, if the condensation unit is near the generator.

F15 or F30

On / Off Switch 10

Liquid Solenoid Valve 1

0

Motor Gearbox 1

0 T1 ? T.KA1

Water Pump 1

0 T1 ?

F15 or F30

On / Off Switch 10

Clock 1

0

Ice level safety 1

0

Liquid Solenoid Valve 1

0 T2

Motor Gearbox 1

0 T1 ? T.KA1 T1 ? T.KA1

Water Pump 1

0 T1 ? T1 ?

Page 24: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

22

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

°C

P

+

-

9.3 Refrigeration operation

As we saw in the section ‘’Description of operation’’, the refrigerant fl uid circulates freely in the double wall :

After expansion, the refrigerant is injected through the injector in the lower part of the drum.The fl uid occupies the complete double wall where it changes from a liquid to a gaseous state.The consequence of this evaporation is to absorb the heat introduced by the water fl owing against the inner of the drum, where it is converted into ice. All the heat is exchanged through the inner wall, and the refrigerant cannot contact the water to be frozen at any time.

The refrigerant is circulated and regenerated by a con-denser system.

ImportantThe refrigerating power applied to the generator must

be close to that recommended by GENEGLACE.

Too low or too high a refrigerating power may cause serious malfunctions.

In order to ensure trouble-free operation of the ice machine, the fl ow of refrigerant fl uid injected into the generator at reduced pressure must be perfectly controlled in order to obtain optimum and constant fi lling of the generator.

9.3.1 Adjustment of expansion valveThe thermostatic expansion valve must only be adjust-ed when the refrigerant has been correctly loaded and the condensation pressure is constant and close to the average operating conditions.

The following depend directly on correct adjustment of the expansion valve :

- the fi lling of the generator with refrigerant fl uid and thus the production of ice.- the evaporation pressure.- the superheat of suction gas.- the oil carry-over to compressor.

Indirectly, misadjustment of the superheat may have me-chanical consequences for the generator itself and also to the compressor.The thermostatic expansion valve is adjusted according to the superheat.

NoteIf the refrigerating power is too great, a back pres-sure valve must be used which can be adjusted (together with the expansion valve) to the suction

operating pressure.

9.3.1.1 Superheater

Fig. 842. Illustration of adjustment of the superheat.

The value to be obtained for the superheater must be between 4 and 6 K.

The superheater ensures icing of the drum over its full height and appropriate oil carry-oil to the compressorl.

Too great a superheater (expansion valve too far closed) results in insuffi cient fi lling with consequent trapping of oil in the drum.The production of ice is greatly reduced.

Too small a superheater (expansion valve too far open) results in overfl owing of the liquid towards the compressor. (risk of slugging to compressor)

ImportantFor the use of any fl uid other than R22 or R404A,

consult GENEGLACE beforehand.

Refrigeration operation

The superheater is the difference between the surface temperature measured near the bulb and the temperature corresponding to the evaporation pressure taken on the suction line near the generator. Bulb position according to refrigerant see section “refrigeration diagrams”.

Page 25: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

23

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

10. Addition of saltThe operation of a fl ake ice machine is improved by adding sodium chloride to the water to be frozen.Addition of salt :

- delays the formation of scale when hard water is used.

- gives larger fl akes, with less breaking up or “snow”.

- facilitates ice harvesting and minimises the forces produced by reaction on the reamer.

In short, large fl akes of ice are produced with ‘‘smoother’’ operation.

To add the salt, two methods are proposed :

- the standard dosing system uses calibrated tablets 25 mm in diameter, as employed in water softeners for the regeneration of resins.- a dosing pump using a solution of purifi ed salt (fi ne cooking salt) dissolved in water in PVC containers.

The quantity of salt consumed is indicated in the section (Dosing Pump). 80 to 100 g of salt is added per tonne of ice, the usual quantity, to be adjusted according to the water quality.- Ice which is very broken up indicates a lack of salt which is often due to very soft water.- Ice in very large fl akes that can be detached before the passage of the reamer indicates too high a dosage.

Precautions must be taken in the use of these system :

- The tablets used in the standard dosing system must be perfectly cylindrical with at least one fl at end so they do not jam in the vertical pipe. The position of the latter must not be altered after fi lling. Adjustment of the fl ow rate is possible but requires much care.

Monthly cleaning of the base of the dosing system will keep it operating correctly.

- The purifi ed salt used with dosing pumps must be dissolved in small successive quantities to ensure a complete melting, either in cold water or preferably hot water. Final mixing, after complete fi lling of the PVC tank, will ensure a homogeneous solution.

A dosing tube is a system for adding salt, mounted in series, in the case where there is no other system avail-able for adding salt.

The dosing tube is attached by two collars to the drum of the generator.

It consists of a clear, rigid tube closed at the bottom by a drilled stopper held by a collar. A small metal tongue collects water from the fl ow at the base of the drum and conducts it to the dosing tube.

The water collected in this way penetrates between the tube and the stopper of the dosing tube, and comes into contact with the salt tablets.

This procedure generates a steady drip of salt water that passes through the hole in the base n° 3.

10.1 The salt dosing tube

The dosing tube is fi tted in a corner of the base and po-sitioned so that the base 3 is 70 mm from the bottom of the base and the tongue is directed towards the shaft. The n° 1 hole must engage with the head of the screw of the top collar.

10.1.1 Adjusting the salt dosing tubeBy raising base no. 3, or reducing the inclination of the tongue no. 4, the salt consumption is reduced (and con-versely) F15 and F30.The dosing tube of the F30 is provided with an orifi ce located in front of the tongue which by uncovering it in-creases the consumption of salt (and conversely).

ImportantThe recommended salt consumption is given in

the Dosing Pump section.

Addition of salt

N°1 Hole

Tube

Tongue N°4 N°2 Hole / F30

Base N°3

Clamp

Page 26: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

24

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

A

D

C

F

G

H

E

B

I

104 mm

226 mm

37 mm

11 mm 79 mm

218 mm

160 mm

113 mm103 mm

51,5 mm

93 mm

2,7 mm

ADFH

BDFI

25 mm

10 mm

6 cm-(2,36 inch)

The dosing pump

10.2 The dosing pump

10.2.1 Dimensions of the dosing pump

10.2.2 Connecting the dosing pumpIf your GENEGLACE is fi tted with a salt dosing tube with tablets, a dosing pump is not supplied.

Electrical connection

The dosing pump must be connected in parallel with the fl uid solenoid valve.

The electrical characteristics are as follow : Voltage : 230 - 240 VoltSingle phaseFrequency : 50 or 60 HertzPower : 28 WattNominal current : 0,50 Ampère

Hydraulic connection : proceduredwg. 652. Illustration of the connection of the dosing pump

between the brine container and the base of the generator.

A steady drip of salt solution occurs directly

into the base of the generator

The suction tube must be positioned vertically and mustn’t have any swan necks on its entire length.

Max

imum

hei

ght =

6 m

Max

imum

hei

ght =

1,5

m

Valve drain connexion(1 inch)in

ject

or p

ipe

inle

t fi lt

er

(0,4 inch)

Elect. Control boxgenerateur.

A) Fix the pump on a wall bracket type above the brine tank.

1) Fix the nut and tubing sleeve (A-D-F-H) on the suction and discharge tubes. (see the right sketch below). cuted at the required lenghts.2) screw The A nut on the B injection valve. Unscrew the HP pump dis charge cap, replace it with the 4-function valve E. The D nut is to be connected to the discharge bolt of the 4-funtion valve E. The F nut is to be connected on the pump suction bolt. To position the ceramic ballast G on the suction pipe. The H nut is to be connected to foot valve I. Connect the loose drain tube to the E valve.

3) Immerge the foot valve I in the brine tank.4) Lead the injection valve B into the generator base.

The ceramic weight (G) around the suction tube maintains the tube in the vertical position (see dwg 652) The injector pipe (B) must inject verticatly.

Hose line

Coupling nut

Tubing sleeve

Fitting

Page 27: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

25

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

3

1

2

Salt consumption

10.2.3 Salt consumptionThe production rates and the lives indicated in the table below are given for 24h/24h operation under nominal condi-tions of operation with air at +25°C and water at +15°C.This data is for a salt solution of 80 to 110 grams per tonne of ice produced.

10.2.4 Operation of the dosing pump

10.2.4.1 Operation

TipThe salt dissolves more quickly if you use

hot water.10.2.4.2 Priming the salt dosing pump

TipIf you are unable to prime the pump using the method indicated above, you can unscrew the pump inlet connector and prime the pump by

immersing the inlet pipe in the brine.

RecommendationIt is recommended that an interrupter switch be in-stalled beside the feed of the dosing pump in order to switch it off when changing the brine container

so that it does not require repriming.

“to be amended according to the quality of the water”, see limits chapter 2.4 and refer to GENEGLACE. Do not wait until the brine container

is empty before replacing it.

- apply power to the dosing pump with # 1 on/off switch

- Adjust stroke at 100 % (# 3) and the speed at 80 % (# 2).- Turn the knurled knob located on 4-way valve E for a

1/4 turn and maintain it open.until brine drips out of the draining tube (return to bin).

- After successful priming release the knurled knob.- Adjust the # 2 and # 3 knobs according to the ice maker

as per table 1.- Ensure that brine is dripping at the injection valve B.

Pump is shipped from the factory with water in the pump head to aid in priming. After a prolonged stop, remember to fi ll again the pump head with water.

The salt dosing pumps uses brine - either saturated or non-saturated.

The saturated brine is made with 10 Kg of rock salt (or salt tablets) immersed in 30 liters of water.

The non-saturated brine is made with 5 Kg of fi ne table salt diluted in 30 liters of water

Table 1 Production

Brine

Setting of the salt dosing pump

Model Kg/24h Button n°3

/Stroke

Adjustment

Button n°2 /

Speed Adjustment

Pulse intervals

< >Duration

F15350 Saturated 20 % 5 % 60 Sec. 416 Days

Non-saturated 40 % 5 % 208 Days

450 Saturated 20 % 5 % 56 Sec. 250 Days Non-saturated 40 % 5 % 125 Days

F30650 Saturated 20 % 10 % 37 Sec. 166 Days

Non-saturated 40 % 10 % 483 Days

950 Saturated 20 % 10 % 28 Sec. 125 Days Non-saturated 40 % 10 % 62 Days

Page 28: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

26

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

11. OptionsThe options cover any equipment peripheral to the ice machines connected directly with their operation and of-fered by GENEGLACE.

11.1 Electrical terminal boxYou will fi nd this in the section diagram of operation on the terminal box in option for a generator connected to a central refrigeration system.

It is suitable for a three phase + neutral supply.

11.2 «ILD» Ice level detector (regulation)11.2.1 Specifi cations

11.2.2 Principle of operationThe device includes an engine which drives a rod equipped with a sensor on one end. The assembly ro-tates continuously.When the ice reaches the sensor, the resistance causes a rotation of the motor on its axis which triggers a small switch.

This switch then cuts the supply to the “ILD” motor and also trips another changeover switch dedicated to the output signal which stops the ice machine.When the level decreases, the “ILD” motor returns to its initial position and starts to rotate again.Production of ice then becomes possible again.

11.2.3 MountingIt is important to consider the angle of slope formed by the fl aked ice in the storage container when choosing the position of the The Ice Level Detector (ILD) .

Fig. 8623. Illustration of a possible mounting of the «ILD».

11.2.4 Connection to the terminal box

ImportantIn order to avoid repeated starting of the

GENEGLACE, it is recommended that you install manual or automatic time-delayed resetting.

11.3 Remote Control

Options

The (ILD) must be positioned in such a location that it prevents ice from building-up inside the ice generator.Position the(ILD)in order to avoid a build-up of ice in the generator cylinder.

The (ILD) can be installed inside the ice storage contain-er. Every precaution must be taken to ensure that the passage of the (ILD)cable through the wall is watertight.

With this time switch you can enter several programmes to switch the ice machine on and off.

A 5 core cable is suffi cient to connect the «ILD» : 2 for the control (terminals 1 and 2) and three for the power supply (terminals 4, 5 and 6). Refer to the end of the instructions.

Supply voltage 220 volts single phase 50 Hz Consumption 3 – 4 VA Changeover switch 1 inverser - 6A - 220V Protection of housing IP 65 Rotor speed 12 r.p.m. Reinforced tube Stainless steel 28 mm diameter Retractable blade Polyamide Housing Red ABS Stuffing gland 16 mm diameter Mounting Horizontal or vertical Motor Switched off in detection position Blade Friction system

The remote control can be used to set different operating times for the GENEGLACE.

It is a digital time switch controlled by a microprocessor.

Programming instructions and a connection diagram are supplied in the remote control box.

Page 29: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

27

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

12. Maintenance

12.1 Maintenance schedule

In order to prevent faults or malfunctions, you are advised periodically to examine certain essential points of your GENEGLACE.The user guide mentions the current service and inspection operations that can be performed. To this must be added :

Maintenance

Operation Recommended

frequency

daily

Routine inspection

Compressor oil level, icing of inlet valve, temperature of casing (Base cools down when stopped), spraying of the wall of the drum, accumulation of ice on the reamer, bearings, regular consumption of salt or salt solution.

Recharge standard salt dosing system Or Filling up the brine containers for the dosing pump

depending on consumption

Cleaning standard salt dosing system monthly

Cleaning water system Base, tanks, valve operation

weekly

Grease bearings ( use greasing pump) Central shaft and reamer bearings (Food compatible grease fulfils : NSF.H1 standard), consult us if necessary

every three months

Checking operating pressures every three month

Checking operation of the torque limiter switch and the condition of the wipers every three month

Examining the gearbox (for traces of oil) occasionally

Examining the internal wall of the drum for scaling Presence of a whitish deposit on the dry wall occasionally

To control the state of refrigerating pipings as well as the insulation (oxidation - attacks chemical ---) to cure it if necessary Annual

Page 30: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

28

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

12.2 Routine maintenance12.2.2 Descaling

- Stop the machine or isolate the supply to the terminal box.

- Pour a measure of the descaler into the base tank in accordance with the table.

- Top up with water to reach the overfl ow of the base.

- Start the reducer and the pump only for about 1 to 2 hours according to scaling.

- Stop operation, drain and rinse 2 or 3 times while restarting the reducer and the pump.

Recommended descaling products - PR 5200 ST (France)

A technical data sheet accompanies each container, giving instructions for use.

THE INSTRUCTIONS MUST BE READ BEFORE USE.

Average dosage 7%

ImportantTake care that the descaler does not fall into the ice

storage container.

Routine maintenance

With time, certain problems can arise with the operation of the ice machine associated with the water quality.

The two main sources of problems are scaling and prolif-eration of micro-organisms.

In addition to the potential risks associated with public health, in both cases the operation of the ice machine can be seriously affected.

We therefore recommend a range of products for descal-ing and attacking micro-organisms.

Important

15.2.1 Anti-micro organism productPR 61 is an anti-algae sanitary decontaminant product for any microbial contamination.It is in the form of a clear liquid.- Density 1.02.- PH 7.

It is sanitary and not dangerous to use.It is not volatile.It is rapid and works on any surface.It has great powers of decontamination.It can be added to a sanitary descaler to act as both a descaler and decontaminant.It halts corrosion of the walls of systems attacked by microbial corrosion.

PR 61 consists of dimethyl benzyl ammonium chloride. This type of cationic detergent is authorised in annex 1, an approved product for cleaning equipment that may come into contact with foodstuffs. Decree of 27 October 1975.

We test all our products ourselves to ensure they meet all reliability criteria in terms of effectiveness and compatibility with GENEGLACE machines.

The use of other products (for example : hydro-chloric acid) will cause irreparable damage to

the generator.

For purposes of good hygiene and correct operation, external cleaning of the generator assembly is essen-tial. Dusting before washing by hand is recommended, in order to prevent bacteria from multiplying. Do not use a water jet, or high pressure washer.

GENERATOR F15 F30

PACK 10/12 13/14

QUANTITY (kg) 0.3 0.5

Page 31: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

29

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

12.3 Replacement of worn parts

For dismantling, reassembly and adjustment, the parts are identifi ed in the exploded views in the annex.The average frequencies are given for normal 24h/24 conditions of operation and correct preventive maintenance.

Explanatory sheets for replacement and adjustment are supplied with spare parts or on request. These are coded depending on the generator and its type.

Codifi cation example : F15/01 = F15 Generator / Replacement of the central shaft bearings.

F30/02 = F30 Generator / Centring the central shaft.

Replacement of worn parts

Part Frequency Coding of Data Sheets

Float valve When appropriate 10

Central shaft bearings About 1095 Days (3 years)

01

Centring of central shaft After replacing the bearings 02

Torque limiter 912 Days to 1095 Days 06 (2,5 to 3 years)

Wipers About 1095 Days 03 (3 years)

Water pump The bottom cover and the impeller are to be modified according to the model of the generator.

912 Days to 1095 Days,

replacement possible (2,5 to 3 years)

20

Reamer and bearings 1095 Days to 1825 Days 04/05 (3 to 5 years)

Gearbox 912 Days, replacement possible 30

Page 32: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

30

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

13. F15 and F30 Refrigeration Diagrams

F15 and F30 Refrigeration Diagrams

1

3

4

5

2

Refri

gera

ting

conn

ectio

n m

ade

To b

e pe

rform

ed o

n si

te

Wel

d

Flar

e co

nnec

tion

Scre

w c

onne

ctio

n

Flan

ge c

onne

ctio

n

Gen

erat

or F

15

1 /

Gen

erat

or 2

/ S

uctio

n 3

/ H

P liq

uid

inle

t 4

/ H

oriz

onta

l hea

t exc

hang

er (l

oose

) 5

/ T

herm

osta

tic e

xpan

sion

val

ve

GEN

EGLA

CE s

.a.s

.

Tél.

+33-

(0)2

-51-

19-1

0-51

Refri

gera

ting

sket

chG

TF.0

01A

Fax

+33-

(0)2

-40-

05-7

3-81

ZAC

de

la F

orêt

- 9,

rue

des

Orfè

vres

4484

0 Le

s So

riniè

res

- Fra

nce

COM

MER

CIAL

LAN

D-BA

SED

Gen

erat

or F

15

Editio

n da

te

GEN

EGLA

CE m

ay c

hang

e th

is d

ocum

ent w

hito

ut p

rior n

otic

e

29/0

1/20

09 J

PM0.

0V

1

3

4

5

2

Refri

gera

ting

conn

ectio

n m

ade

To b

e pe

rform

ed o

n si

te

Wel

d

Flar

e co

nnec

tion

Scre

w c

onne

ctio

n

Flan

ge c

onne

ctio

n

Gen

erat

or F

30

1 /

Gen

erat

or 2

/ S

uctio

n 3

/ H

P liq

uid

inle

t 4

/ H

oriz

onta

l hea

t exc

hang

er (l

oose

) 5

/ T

herm

osta

tic e

xpan

sion

val

ve

GEN

EGLA

CE s

.a.s

.

Tél.

+33-

(0)2

-51-

19-1

0-51

Refri

gera

ting

sket

chG

TF.0

01A

Fax

+33-

(0)2

-40-

05-7

3-81

ZAC

de

la F

orêt

- 9,

rue

des

Orfè

vres

4484

0 Le

s So

riniè

res

- Fra

nce

COM

MER

CIAL

LAN

D-BA

SED

Gen

erat

or F

30

Editio

n da

te

GEN

EGLA

CE m

ay c

hang

e th

is d

ocum

ent w

hito

ut p

rior n

otic

e

29/0

1/20

09 J

PM0.

0V

Page 33: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

31

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

14. TroubleshootingThe table below will assist you in the diagnosis of any malfunction detected

TroubleshootingOb

serv

atio

ns, s

ympt

oms

and

effe

cts

12

34

56

78

910

1112

1314

1516

1718

19LO

W P

RESS

URE

ABNO

RMAL

LY H

IGH

ALO

W P

RESS

URE

ABNO

RMAL

LY L

OW

BBU

BBLE

S IN

THE

LIQ

UID

FLO

W IN

DICA

TOR

CTO

RQUE

LIM

ITER

CUT

S O

UT (R

EAM

ER L

OCK

ED)

DLP

PRE

SSUR

E SW

ITCH

CUT

OUT

EHP

PRE

SSUR

E SW

ITCH

CUT

OUT

FRO

TATI

NG P

ART

MO

TOR

THER

MAL

CUT

OUT

GCO

NSTA

NT D

ISCH

ARG

E FR

OM

OVE

RFLO

W IN

THE

BAS

EH

NOIS

Y O

PERA

TIO

NI

UNUS

UAL

ICIN

G IN

SUC

TIO

N O

F CO

MPR

ESSO

RJ

HARD

ICE,

DO

ES N

OT

EASI

LY C

OM

E AW

AY F

ROM

THE

CYL

INDE

R, 2

THI

CKNE

SSES

KFI

NE IC

E, T

RANS

PARE

NT, M

OIS

T, H

AS C

OM

E AW

Y IN

TW

O T

HICK

NESS

ESL

GRA

NULA

R IC

E O

N O

NE S

IDE

("ORA

NGE

PEEL

")M

IRRE

GUL

AR IC

E FO

RMAT

ION,

WIT

H DR

IPS

NIC

E AC

CUM

ULAT

ED IN

THE

BO

TTO

M O

F TH

E CY

LIND

ER, T

HICK

OIC

E AC

CUM

ULAT

ING

UND

ERNE

ATH

THE

MAC

HINE

PIC

E DO

ES N

OT

COM

E AW

AY E

ASIL

Y O

R NO

T AT

ALL

WHE

N TH

E RE

AMER

OVE

RQ

ICE

VERY

THI

CK, S

OFT

, DO

ES N

OT

COM

E AW

AY F

ROM

THE

CYL

INDE

RR

ICE

VERY

FRA

GM

ENTE

DS

ROTA

TING

PAR

T M

OTO

R NO

T W

ORK

ING

TLO

W O

IL L

EVEL

IN C

OM

PRES

SOR

UO

IL L

EVEL

IN C

OM

PRES

SOR

HIG

H W

HEN

STAR

TED,

THE

N LO

WV

DRO

PE IN

ICE

PRO

DUCT

ION

RATE

WCa

uses

12

34

56

78

910

1112

1314

1516

1718

191

LACK

OF

SALT

12

TOO

MUC

H SA

LT2

3FR

ONT

WIP

ER S

ETTI

NG L

OST

OR

INCO

RREC

T (L

EAK)

34

REAR

WIP

ER S

ETTI

NG L

OST

OR

INCO

RREC

T (L

EAK)

45

BALL

CO

CK S

TUCK

IN O

PEN

POSI

TIO

N O

R NO

T CL

OSI

NG F

ULLY

? HO

LE IN

FLO

AT5

6IN

ADEQ

UATE

WAT

ER D

ISTR

IBUT

ION

: HO

LES

BLO

CKED

, LO

W P

UMPI

NG R

ATE

(UNP

RIM

ED)

67

NO W

ATER

DIS

TRIB

UTIO

N : W

ATER

CLO

SED

OFF

, BAL

L CO

CK S

TUCK

IN C

LOSE

D PO

SITI

ON,

FAU

LT IN

PUM

P7

8RE

AMER

TO

O F

AR F

ROM

CYL

INDE

R8

9CL

EARA

NCE

IN B

EARI

NGS

ON

SHAF

T, IN

CORR

ECTL

Y CE

NTRE

D9

10SC

ALE

IN C

YLIN

DER

1011

OIL

OR

LACK

OF

REFR

IGER

ANT

IN T

HE D

OUB

LE W

ALL

: EXC

ESSI

VE S

UPER

HEAT

, LEA

K, P

ARTI

AL B

LOCK

AGE

IN F

LUID

LIN

E, F

ILTE

R O

F TH

ERM

OST

ATIQ

UEEX

PANS

SIO

N VA

LVE

1112

LACK

OF

REFR

IGER

ATIN

G C

APAC

ITY

: CO

NDEN

SER

DIRT

Y, H

IGH

AMBI

ENT

TEM

PERA

TURE

, FLA

P¨VA

LVES

ON

COM

PRES

SOR

WO

RN, F

ILTE

R O

F CO

MPR

ESSO

RDI

RTY

1213

COND

ENSE

R DI

RTY,

HIG

H AM

BIEN

T TE

MPE

RATU

RE13

14TO

O L

ITTL

E A

SUPE

RHEA

T O

F TH

E EX

PANS

IO V

ALVE

1415

LACK

OF

REFR

IGER

ANT,

LEA

K15

16CO

NDEN

SATI

ON

TOO

LO

W16

17EX

CESS

IVE

REFR

IGER

ATIN

G C

APAC

ITY

(EVA

PORA

TIO

N RA

TE T

OO

LO

W)

1718

CRAN

CKAS

E HE

ATER

OF

COM

PRES

SOR

NOT

WO

RKIN

G18

19TO

RQUE

LIM

ITER

ELI

MIN

ATED

OR

INCO

RREC

TLY

SET

19

Page 34: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

32

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

15. Exploded view15.1 F15 GeneratorThis drawing is the property of Généglace, it is forbidden to reproduce it or to communicate it to a third party without our permission

Exploded view F15

Page 35: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

33

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

This drawing is the property of Généglace, it is forbidden to reproduce it or to communicate it to a third party without our permission

15.2 F30 Generator

Exploded view F30

Page 36: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

34

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

16. Commissioning Check List

Commissioning Check List

Before Start-up, refer to the safety instructions and furtherrecommendations in the installer manual

The aim of this checklist is to check the main steps ofthe installation of a generator in view of the latter’s good working order.

Tick the boxes as the check proceeds

1. Before turning the power on, check:

That the base is fixed properly and watertight (flat and level surface)

The sealing of the water tray base on its support (silicone seal around the ice outlet)

The diameter of the ice chute (where appropriate) (according to instructions)

That it is possible to remove this ice chute for future maintenance

That the ice chute is not in the flow of air of an evaporator

The position of the ice level safety pallet (F15-F30) (according to instructions)and the electric connection of the contact

The presence of the exchanger in the suction system (according to instructions)

The position of the bulb of the expansion valve (according to instructions) and the insulation thereof

The connection to the overflow tube

The flow regulation of the water float valve (at standstill) (according to instructions)

That the water float valve has remained in operating position after having been connected(according to instructions)That the water float ball has freedom of movement

The level of water in the water tray base of the generator is still (according to instructions)

The positioning of the salt doser (where appropriate) (according to instructions)

The installation of the dosing pump (where appropriate) (according to instructions)

Prepare the brine container with fine salt (if a metering pump is installed)

The connection of the reducer motor

The electrical connection of the torque limiter

The presence of a “working” timer (delay at interlock)on the reamer and water pump control (if the generator is connected to a central refrigeration system)

The presence of an “idle” timer (delay at downtime) on the reducer motor control

Page 37: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

35

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

Commissioning Check List

2. After turning the power on:

Manually activate the torque limiter then rearm it (red lever),(according to instructions) (complete standstill of the generator and generating set unit)

Check the direction of rotation of the reducer (refer to the arrow painted on the upper part – clockwise)

Check the working order and the adjustment of the dosing pump (where relevant)

Set the "work" timer to between 0 and 15 s if the machine is connected to a power station,then set the reducer motor timer to 180 s.

Preload the refrigerating circuit after vacuumizing

3. After commissioning:

After having turned on the liquid solenoid valve, time the filling time of the cylinder(see suction outlet icing) (connection to central system)

Transfer this time to the “working” time delay (adjust value if need be)

The commissioning of the reducer and pump after time delay

Adjusting the evaporating pressure reducer (where relevant)(in order to obtain the pressure recommended by GENEGLACE at the time of the order)

Set the expansion valve to 6/8K by reference to the bulb(temperature at the bulb minus the temperature of evaporation at the generator)

Adjusting the wipers (according to instructions)

The level of water in the upper basin and that of the water tray base (according to instructions)

The oil level at compressor indicator (to be monitored also later)

4. After 10 - 15 minutes’ operation, check:

The level of water in the base (according to instructions)(that no water drains out of the overflow tube)

Removal of the ice without the reducer motor gear moving

Spraying of water droplets on the strip of the salt measuring device (where relevant)

The drip of the dosing pump (where relevant)

The feedback of the oil level to the compressor indicator (according to the type of installation, extra oilmay be required)

The operating pressures (according to defined production)

Stop the generator with the I.L.D (check if installed), then the Stop button., check the level of waterin the water tray base (according to instructions) (check to make sure that no water drains out of the overflow)

Re-commission the installation and fill in the operation report sheet

Page 38: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

36

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

17. Operational Measurement sheet

Operational Measurement sheet

GENEGLACE TYPE END-USER

ICE MAKER SERIAL NUMBER CONTRACTOR

Electrical supply : frequency in Hertz FILE NUMBER

Where

Check the calibration of the tools before the operation.

START-UP DATA SHEET FOR GENEGLACE ICE GENERATOR

F15

GENERATORRefrigerant type AReamer motor amperage

A

BC

upper tray

base tray

Read on the GENEGLACE identification plate.

Read for the 3 phases with ammeter clamps.

How to checkWhereto checkCheck points

mm

cf. refrigerating sketch

Measure the water level in the upper water tray and in the

water base, when machine is in operationWater supply

mm

Z

Ice production

Show with an arrow the rotation direction of the central shaft

Measure the temperature of the water at the outlet of water

Duration of one complete reamer rotation.

from the top of the generator.

fitted on the water supply pipe.

Temperature of water supply

Reamer Direction

Rotation speed

F

°C E

By weighing the ice or by reading a water flow meter

float valve. Don't measure the temperature inside the base.

kg/h

D

D

Sec/Rnd

HHHH (tick appropriate boxes). not at all

H x a little

H x x x a lot

HIce temperature I

Irregular surface

By examinating the ice at the outlet of the generator

Make the measurement during several minutes.

(preferably use a plastic caliper square). When using a metal

caliper square you must precool it.

Granular on 1 side

Aspect of the ice flakes

°C

Wet

Thickness of ice flakes Gmm

White and opaque

Smooth surface

Transparent

Dry

Use a caliper square. The tool must not warm up the ice

Level of ice forming in the generator

the level of ice forming in the cylinder75%

50%

25%

0%

T t f th f i t

Variation +/- in %

Suction side (a) in % Opposite side (b) in %

°C

100%

Enter the level of charge in % in the left boxes

J

Use an electronic contact thermometer.K

Indiquer s'il y a des fluctuations et dans quelles proportions.

show on the drawing

And frost on the oil return heat exchanger

(a) (b)

Evaporating pressure bar NCorresponding temperature °C N

Condensing pressure bar Ocorresponding temperature °C O

M3OTHER CONTROLS

Temperature of the refrigerant °CPosition it on the suction pipe close to the bulb.

K

Read pressure with a pressure gage at the inlet of the generator.

Read pressure with a pressure gage at the outlet of the generator.

°C Measure temperature with a thermometer on the inlet of Expansion valve / liquid inlet throttle valve

Temperature of the refrigerant at the Expansion valve / liquid inlet throttle valve

Salt dosing Salt addition in operation Yes SOperating sequences of the installationAt start-up of Ice-maker … Z… the operation …

yes no

(b) indicate a value if any in the appropriate box

(a) tick the appropriate box

(a) immediate (b) delayed

bar

…of the Reamer-Motor is :

sec

Tick the appropriate box.No

…of the water pump is :

of the refrigeration is :

…of the liquid inlet Solenoid valve is:

Dia / o mm Height between the generator and the condensing unit.

Length of piping between the generator and the condensing unit.

Dia : inlet and outlet diameters of connecting pipes.

Tick the appropriate box.

Tick the appropriate box.

COMPONENTS ON THE INSTALLATIONGenerator connected to :

below the condenser

above the condenser

Refrigerant connexions

Dia / i mm

Height m

Length m

Please enclose a detailed refrigeration diagram

Generator located :

Tick the appropriate box.A central plantA dedicated compressor

Name of the engineer who

ame of the person in charge :

Please enclose a detailed refrigeration diagram.GEA GENEGLACE S.A.S.

ZAC de la forêt 9, rue des Orfèvres

44840 LES SORINIEREStel. (0) 2 51 19 10 51

fax. (0) 2 40 5 73 81e-mail. : [email protected]

signature of the person in charge, and stamp of the company :

Date :

performed this test :

Page 39: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

37

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

J D L B

PBAR°C

P BAR

K N

O

F

E

HGIF

Z

C

A

mm

H2O l/h

°C

mm

kg/h

°C

Kg

mm

M

17.1 Measurement Points for F15 or F30 Generator

Measurement Points for F15 or F30 Generator

Page 40: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

38

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

18. Adjustment of torque limiter

Adjustment of Torque Limiter

3

5

6

1

4

2

7

A

Important Before operating, switch off the installation

OPERATION OF THE TORQUE LIMITER

If the ice is not harvested correctly, the torque limiter reacts:

The stop N°2 is compressed by the arm N°1.

The head of screw no. 3 presses on the roller on the switch arm in front of it and stops the complete installation

TOOLS REQUIRED ONE CALLIPER GAUGE

ONE G-CLAMP

TWO 13 MM FLAT SPANNERS

ADJUSTMENT OF THE TORQUE LIMITER With the machine switched off and stopped, see safety instructions. Measure dimension ( A ) in the drawing above using a calliper gauge.

Subtract the following values from the measured dimension:

PACK 11 2,5 mmPACK 12 or generator F15 2,5 mmPACK 13 et 14 or generator F30 3,5 mm

Take the G-clamp and compress the stop no. 2 to obtaindimension A, minus the value chosen above. Unscrew screw no. 3 until the switch operates. Remove the G-clamp. Reset the switch (hold the motor-gearbox assembly in your hands and rotate it clockwise in order to decompress stop no. 2. The spring no. 4 facilitates this movement. Take the G-clamp and compress the stop until the switch operates. Measure dimension A which must be: dimension A minus the chosen value. Hold the head of screw no. 3 and tighten the nut no. 5.Remove the G-clamp. Reset the switch.

Page 41: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

39

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

19. Adaptating of Water Pump

Adaptating of Water PumpTh

e JB

C P1

C 22

5 pu

mp

is fi

tted

to s

ever

al G

ENEG

LACE

mod

els

of ic

e m

aker

.

It is

the

resp

onsi

bilit

y of

the

inst

alle

r to

mod

ify th

e bo

dy a

nd im

pelle

r of t

he p

ump

in a

ccor

danc

e

with

the

follo

win

g in

stru

ctio

ns :

Switc

h of

f the

pow

er b

efor

e co

mm

enci

ng w

ork.

* The

dim

ensi

ons

are

give

n fo

r inf

orm

atio

n on

ly. I

MPO

RTAN

T: T

he w

ater

leve

l in

the

dist

ribut

ion

bow

l is

obta

ined

by

the

size

of t

he

w

ater

pum

p im

pelle

r, AN

D, b

y th

e ad

just

men

t of t

he o

verfl

ow p

ipe.

Ref

er to

the

Initi

al S

tart

Up s

ectio

n in

the

inst

ruct

ions

con

cern

ed.

Cut o

ff th

e ha

tche

d po

rtion

File

the

hatc

hed

area

AF3

0 A

= 8

mm

at 5

0 Hz

F30

A =

7 m

m a

t 60

Hz *

Rem

ove

the

hatc

hed

porti

on

AF1

5 A

= 7

mm

at 5

0 Hz

F15

A =

6 m

m a

t 60

Hz *

Rem

ove

the

hatc

hed

porti

on

Rem

ove

the

base

w

hile

ta

king

car

e no

t to

dam

age

the

lugs

Lock

the

mot

or fa

n us

ing

a sc

rew

driv

er,

in

orde

r to

un

scre

w th

e im

pelle

r.

Page 42: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

40

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

20. Adjustment of Rubber Wipers Blade

Adjustment of Rubber Wipers Blade

- Both wipers are positioned in the water distribution tank and held with a flat nut and a blind nut locked together.

- Stop the machine using the main and isolating switches for safety.

- Using a 10mm box spanner to turn both the 2 nuts, turn the front wiper to position A and the rear wiper to position B. They must remain in these positions. If they do not, retighten the lock nuts at the bottom, under the collection tank.

- A very thin film of water must be visible at the rear wiper 2.

- Positions C and D cause deformation by strong pressure on the drum. Positions E and F cause water to flow into the stripping area.

- The good condition of the front wiper can be checked from below the generator.

C

1E

2D

F

Rear scraper

Front scraper

Sub-cooling Harvesting

Spraying

Thin trickle ofwater

1 2

BA

Spraying

Front wiper

Rear wiper

Page 43: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

41

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05Page

M

5

6

1

Détecteur de niveau de glaceIce level detector

ANR

2

3

Coffret électrique Terminal of electrical panel

Machine à glace / Ice machine

36

37

41

Ver

s un

Voy

ant /

Tow

ards

a li

ght i

ndic

ator

RACCORDEMENT ELECTRIQUE DE L’ANR ELECTRICAL CONNEXION OF THE ANR

CONEXIÓN ELÉCTRICA DEL ANR

4

21. Electrical connexion of the ILD

Electrical connexion of the ILD

Page 44: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

42

Contractor’s manualF15 - F30 Generators

Manual For F15 and F30 - Mill.: 2008 - 11 / Mod.: JPM 05Page

BTR

c

ae

v d

90°

Fig 1

90°

Fig 2

g

v

d

c

22. Adjusting the Reamer

Adjusting the Reamer

Important Before operating, switch off the installation

TOOLS REQUIRED:

• 1 engineer’s wedge set, 1 Allen key, 1 screwdriver, 1 extending ratchet handle, 1 bushing size 22

• Place the reamer opposite the inspection hole• Select the largest tooth on the reamer using a set of engineer’s wedges, turning them one after ano- ther perpendicular to the cylinder.( c )• Loosen the screw ( v )• Position the selected tooth ( d ) perpendicular to the cylinder• Manoeuvre the reamer axis ( a ) placing the screwdriver in one of the slots ( e ) turning in a clockwise direc- tion to distance the reamer tooth from the cylinder• Manoeuvre the reamer axis ( a ) placing the screwdriver in one of the slots ( e ) turning in an anti-clockwise direction to bring the reamer tooth towards the cylinder• Take a wedge equal to or less than 0.4mm and place it between the tooth and the cylinder.• Manoeuvre the reamer axis ( a ) placing the screwdriver in one of the slots until there is contact between the tooth/wedge/cylinder• Isolate this adjustment by locking the screw ( v ) while maintaining the axis ( a ) with a screwdriver in one of the slots• Remove the wedge by turning the reamer on itself

• To adjust the lower section of the reamer, fi rstly loo- sen the hexagonal cap screw, positioned under the arm locking he reamer axis• Repeat the same procedure on the top section, bearing in mind that the slots ( e ) are replaced with pins ( g ) which can be moved using your fi ngers • The only difference is that turning the pins in a clockwise direction brings the tooth closer to the cylinder and turning in an anti-clockwise direction distances it.• Tighten the hexagonal cap screw to lock the reamer axis once the adjustment is completed

Plan viewPre-centring pin

View from underneath

Page 45: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important
Page 46: F15 F30 GEA VO.05 - Crionovo · 5 Contractor’s manual F15 - F30 Generators Manual For F15 and F30 - Mill.: 2008 - 11 / Mod. : JPM 05 Page 2. Safety rules This notice contains important

'' Partout où vous êtes, nous avons la solution. '' '' Wherever you are, we have the solution. '' '' En cualquier parte donde esté, tenemos la solución '' '' Überall wo Sie sind, haben wir die richtige Lösung '' En qualquer parte onde voce se encontre , temos la solução ''

=

oÉÑêáÖÉê~íáçå=aáîáëáçå=çÑ=íÜÉ=db^=dêçìé=

db^=dÉåÉÖä~ÅÉ=ëK~KëK==w^`=ÇÉ=ä~=cçêÆí=Ó=V=êìÉ=ÇÉë=lêÑ≠îêÉë=Ó=QQUQM=iÉë=pçêáåá≠êÉë=Ó=cê~åÅÉ=mÜçåÉ=W=HPP=EMFORN=NV=NM=RN=J=c~ñ=W=HPP=EMFOQM=MR=TP=UN=bJã~áä=W=Åçåí~Åí]ÖÉåÉÖä~ÅÉKÅçã=Ó=ïïïKÖÉåÉÖä~ÅÉKÅçã==