6
1 Occupancy Sensor OCS 100W • Setup Guide The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual-technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to detect the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves. The PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the ambient room temperature. The OCS 100W has a 24 VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy output connections. Front Panel Features Ultrasonic Sensors Green LED (status indicator) Red LED (status indicator) Infrared/Photocell Sensor and Lens Removable Front Cover Figure 1. OCS 100W Front Panel Features Control A B 123 4 123 4 Blue Timer Test Button Blue Photocell Dial Notch Green Ultrasonic Range Dial Red Infrared Sensitivity Dial DIP Switches (B) DIP Switches (A) Figure 2. OCS 100W Controls DIP Switches (B) B OPERATION OFF ON 1 Timer Setting (B1 and B2 switches must be set together) 8 minutes: OFF* 4 minutes: OFF 15 minutes: ON 30 minutes: ON 2 OFF * ON OFF ON 3 Timer adjust Automatic Manual* 4 Sensitivity adjust Automatic Manual* *Default Blue Timer Test Button Push in to enable 8 second timer test mode. This will last for 1 hour. Then automatically resets to the dip switch settings. Push and hold until the red LED flashes to return the 8 second timer to the dip switch timer settings. Red Infrared Sensitivity Dial — Adjust this dial to increase or decrease infrared sensitivity. Turn counter clockwise (CCW) to decrease sensitivity. Turn clockwise (CW) to increase sensitivity. Factory default is 75%. Ultrasonic Sensors — Detect movement in the room, based on ultrasonic waves. Green LED (status indicator) — Flashes when the ultrasonic sensors detect occupancy. Infrared/Photocell Sensor and Lens — Diffracts the incoming light and directs the light to the infrared/photocell sensor. Red LED (status indicator) — Flashes when the infrared sensor detects occupancy. Removable Front Cover — Conceals all controls and DIP switches. DIP Switches (A) A OPERATION OFF ON 1 Not used Not used* Not used 2 Not used Not used* Not used 3 LED indicators LEDs enabled* LEDs disabled 4 Automatic adjust reset Toggle to reset (Default: OFF) *Default

Extron OCS 100W Setup Guide R T T: Go to www .e xtr on.com o r the complete user guide installation instructions, and specifications. Occupancy Sensor OCS 100W • Setup Guide The

  • Upload
    lythuy

  • View
    224

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Extron OCS 100W Setup Guide R T T: Go to www .e xtr on.com o r the complete user guide installation instructions, and specifications. Occupancy Sensor OCS 100W • Setup Guide The

1

IMPORTANT:

Go to www.extron.com for the

complete user guide, installation

instructions, and specifications.

Occupancy Sensor OCS 100W • Setup Guide

The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual-technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to detect the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves. The PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the ambient room temperature.

The OCS 100W has a 24 VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy output connections.

Front Panel Features

A B

12

34

12

34

Blue Timer Test ButtonBlue Photocell Dial

Notch

Green Ultrasonic Range DialRed Infrared Sensitivity Dial

UltrasonicSensors

Green LED(status indicator)

Red LED(status indicator)

Infrared/PhotocellSensor and Lens

Removable Front Cover

DIP Switches (B)DIP Switches (A)

Figure 1. OCS 100W Front Panel Features

Control

A B

12

34

12

34

Blue Timer Test ButtonBlue Photocell Dial

Notch

Green Ultrasonic Range DialRed Infrared Sensitivity Dial

UltrasonicSensors

Green LED(status indicator)

Red LED(status indicator)

Infrared/PhotocellSensor and Lens

Removable Front Cover

DIP Switches (B)DIP Switches (A)

Figure 2. OCS 100W Controls

• DIP Switches (B) —

B OPERATION OFF ON

1 Timer Setting(B1 and B2 switches must be set together)

8 minutes: OFF*

4 minutes: OFF

15 minutes: ON

30 minutes:ON

2 OFF * ON OFF ON

3 Timer adjust Automatic Manual*

4 Sensitivity adjust Automatic Manual*

*Default

• Blue Timer Test Button —

• Push in to enable 8 second timer test mode. This will last for 1 hour. Then automatically resets to the dip switch settings.

• Push and hold until the red LED flashes to return the 8 second timer to the dip switch timer settings.

• Red Infrared Sensitivity Dial — Adjust this dial to increase or decrease infrared sensitivity.

• Turn counter clockwise (CCW) to decrease sensitivity.

• Turn clockwise (CW) to increase sensitivity.

• Factory default is 75%.

• Ultrasonic Sensors — Detect movement in the room, based on ultrasonic waves.

• Green LED (status indicator) — Flashes when the ultrasonic sensors detect occupancy.

• Infrared/Photocell Sensor and Lens — Diffracts the incoming light and directs the light to the infrared/photocell sensor.

• Red LED (status indicator) — Flashes when the infrared sensor detects occupancy.

• Removable Front Cover — Conceals all controls and DIP switches.

1

2 • DIP Switches (A) —

A OPERATION OFF ON

1 Not used Not used* Not used

2 Not used Not used* Not used

3 LED indicators LEDs enabled* LEDs disabled

4 Automatic adjust reset

Toggle to reset (Default: OFF)

*Default

Page 2: Extron OCS 100W Setup Guide R T T: Go to www .e xtr on.com o r the complete user guide installation instructions, and specifications. Occupancy Sensor OCS 100W • Setup Guide The

2

Occupancy Sensor OCS 100W • Setup Guide (Continued)

• Green Ultrasonic Range Dial (see figure 2 on the previous page) — Adjust this dial to increase or decrease ultrasonic sensitivity.

• Turn counter clockwise (CCW) to decrease sensitivity.

• Turn clockwise (CW) to increase sensitivity.

• Factory default is 50%.

• Blue Photocell Dial — Photocell prevents the sensor from triggering on when the area is adequately lit with natural light and when motion is detected. The sensor must be mounted directly over an area that is representative of the average, natural room lighting. Before setting the photocell control, wait until the natural light is brightest (optional). Adjust this dial to increase or decrease photocell sensitivity.

• Turn counter clockwise to decrease photocell sensitivity.

• Turn clockwise to increase photocell sensitivity.

• Factory default is 100% (full clockwise).

• Full counter clockwise — Photocell is disabled.

• Range — 10 to 1000 LUX

Sensor Placement and Installation OptionsWhen placing the sensor in a room, be sure the sensor is not aimed out through a door. The sensor can detect hallway traffic, causing false triggers. PIR sensors trigger in response to changes in the amount of IR arriving from any of their segments of view within a direct line of sight from the sensor. US sensors trigger in response to changes in the frequency of reflected ultrasonic waves, caused by movement within the space.

NOTE: See Troubleshooting on page 5 if you experience false triggers.

Installation OptionsRotation

60˚

80˚

Ceiling Mount Wall Mount Top ViewCorner Mount

Sensor Placement

Wrong

Correct Hallway

Figure 3. Sensor Placement and Installation Diagrams

Sensor Coverage

32'(10 m)

23'(7 m)

32'(10 m)

23'(7 m)

40'(12 m)

20'(6 m)

40' (12 m) MajorMotion Coverage

20' (6 m) MinorMotion Coverage

10' (3 m) MountingHeight

Sensor CoverageUS Minor Motion

US Major Motion

IR Minor Motion

IR Major MotionFigure 4. Sensor Coverage Diagrams

3

4

Page 3: Extron OCS 100W Setup Guide R T T: Go to www .e xtr on.com o r the complete user guide installation instructions, and specifications. Occupancy Sensor OCS 100W • Setup Guide The

3

OCS 100W Parts

Pull

CoverBody

BracketCover

WiringHarness

MountingBracket

Mounting Bolt,Washer and Nut. (2)

Figure 5. OCS 100W Parts

Installation

Pull

CoverBody

BracketCover

WiringHarness

MountingBracket

Mounting Bolt,Washer and nut. (2)

Insert wiring throughMounting Bracket.

Wall

Building Wiring

1

“POP”

Snap sensor onto mounting post.

5“SNAP”

Push

Replace Cover.

7

Wall

WiringHarness

Secure MountingBracket to the wall.

Connect building wiring toWiring Harness with includedwire nuts.

2

3

PositionLockingScrew

Loosen Tighten

Plug Wiring Harness into connector locatedon the left side, opposite exit slot and place wiring under wire tabs. Align sensor and tightenposition locking screw.

6

32'23'

32'23'

40'

20'

40' - 0" Major Coverage

20' - 0" Minor Motion Coverage

10' - 0"MountingHeight

Sensory CoverageUS Minor Motion

US Major Motion

IR Minor Motion

IR Major Motion

Snap Bracket Cover in place toconceal wiring and MountingBracket.

4

Bracket Cover

Figure 6. OCS 100W Installation

ATTENTION:• All structural steps and electrical installation must be performed by qualified personnel in accordance with local and national

building codes and electrical codes.

• Toute étape structurelle et installation électrique, doit être effectuée par un personnel qualifié, conformément aux codes du bâtiment, aux codes incendie et sécurité, et aux codes électriques, locaux et nationaux.

5

6

Page 4: Extron OCS 100W Setup Guide R T T: Go to www .e xtr on.com o r the complete user guide installation instructions, and specifications. Occupancy Sensor OCS 100W • Setup Guide The

4

Occupancy Sensor OCS 100W • Setup Guide (Continued)

OCS 100W Wiring

ExtronIPCP PRO 550Control Processor

Dual Zone

Single Zone

RO 550

LAN

IPCP PRO 550

MAC: 00-05-A6-XX-XX-XX

S/N: ####### E######

00-05-A6-XX-XX-XX

5A MAX

100-240V ~ 50-60Hz1 1 2 3 72 1 2 3 4 1 2 3 4 PWR OUT = 9W

eBUS+V +S -S GTx Rx G Tx Rx G Tx Rx G Tx Rx G S G S G S G S GRTSCTS

SWITCHED 12 VDC40W MAX TOTAL

3 4 84 5 6 5 6 7 8 5 6 7 8 321 4 G

FLEX I/ORELAYSIR/SERIALCOM12 VDCS G S G S G S GTx Rx G Tx Rx G Tx Rx G Tx Rx G RTSCTS

ECM DIO8

BUS ID

eBU

S+

V O

UT

24G

G-S

+S

+V

DIG

ITA

L I/

O1

23

4G

G6

57

8

LSB

MSB

ExtronECM DIO8eBUS Control Module

ExtronPC 1224Power Module

ExtronOCS 100WOccupancySensor 2

ExtronOCS 100WOccupancySensor

ExtronOCS 100WOccupancySensor 1

Control Signal #2 (Blue)

Control Signal #1 (Blue)

Sensor with 12 VDCPower Supply

Sensor with 24 VDCPower Supply

Control Signal #1 (Blue)

Ground(Black)

Ground(Black)

Ground (Black)

Ground (Black)

+24 V (Red)

+24 V (Red)

+12 V (Red)

Extron Extron

Extron

E t

1.25

A M

AX75

mA

MAX

1.5 A MAX

PC 1224

33-2665-01 Bwww.extron.com

24V

O

UT

12V

O

UT12V

IN

Figure 7. OCS 100W Wiring Diagram

PC 1224 Wiring

ATTENTION:

• Do not connect power until you have read the ATTENTIONS: notices on the next page.

• Ne branchez pas l’alimentation avant d’avoir lu les mises en garde «ATTENTIONS:» de la page suivante.

• Remove power from the system before making any connections.

• Mettez le système hors tension avant d’effectuer tout raccordement.

The OCS 100W requires 24 VDC. If the sensors are connected to a device that does not provide 24 VDC:

1. Connect a 12 VDC power source to the 12 VDC input on the supplied PC 1224 power converter, using a 2-pole captive screw connector (see image on the right).

2. Wire the PC 1224 24 VDC 2-pole captive screw connector to the black and red wires on the OCS 100W.

A 12 VDC pass-through is available to power additional 12 VDC devices.

7

ExtronPC 1224Power Module

12 V PowerSource

AdditionalDevices

OccupancySensor

1.25

A M

AX75

mA

MAX

1.5 A MAX

PC 1224

33-2665-01 Bwww.extron.com

24V

O

UT

12V

O

UT12V

IN

Connections

Black Ground

Red +24 VDC

Blue Occupancy control output

Gray Occupancy and photocell control output

NOTE: Gray wire is used when the control system needs to know when the area is adequately lit with natural light and when motion is detected (for example, automatic lighting through Extron control system).

Relay Contacts

Blue/White

Common

Black/White

Normally closed when unoccupied

Yellow/White

Normally open when unoccupied

NOTE: Relay contacts could be used to trigger third party devices, such as HVAC, based on occupancy.

NOTE: The Ground dash line is optional.

Page 5: Extron OCS 100W Setup Guide R T T: Go to www .e xtr on.com o r the complete user guide installation instructions, and specifications. Occupancy Sensor OCS 100W • Setup Guide The

5

Troubleshooting

Problem Possible Cause Test Solution

Sensor remains on. Constant noise. Reduce both green and red knobs by 15% and remove noise source.

Move sensor to a less noisy area within the room.

Sensor remains on too long. Timer setting too high. Check dip switch settings. Reduce timer setting.

Hallway traffic turns sensor on.

Infrared sensor can see into the hallway.

Put sensor in timer test mode and walk the hallway.

Move sensor, so it cannot see into the hallway.

Safety Instructions

For information on safety guidelines, regulatory compliances, EMI/EMF compatibility, accessibility, and related topics, see the Extron Safety and Regulatory Compliance Guide on the Extron website.

FCC Class A Notice

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. The Class A limits provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause interference. This interference must be corrected at the expense of the user.

NOTE: For more information on safety guidelines, regulatory compliances, EMI/EMF compatibility, accessibility, and related topics, see the Extron Safety and Regulatory Compliance Guide on the Extron website.

Power Attentions

ATTENTIONS:• These products are intended for use with a UL Listed LPS type power source.

• Ces produits doivent être utilisés avec une source d’alimentation de type LPS certifiée UL.

• Use of a non-LPS or unlisted power supply will void all regulatory compliance certification.

• L’utilisation d’une source d’alimentation non-listée ou non-listée LPS annulera toute certification de conformité réglementaire.

• Unless otherwise stated, the AC/DC adapters are not suitable for use in air handling spaces or in wall cavities. The power supply is to be located within the same vicinity as the Extron AV processing equipment in an ordinary location, Pollution Degree 2, secured to the equipment rack within the dedicated closet, podium, or desk.

• Sauf mention contraire, les adaptateurs CA/CC ne conviennent pas à une utilisation dans les espaces d’aération ou dans les cavités murales. La source d’alimentation doit être placée à proximité de l’équipement Extron dans un emplacement ordinaire soumis à un degré de pollution de catégorie II, solidement fixé au rack d’équipement d’une baie technique, d’un pupitre, ou d’un bureau.

• The installation must always be in accordance with the applicable provisions of National Electrical Code ANSI/NFPA 70, article 725 and the Canadian Electrical Code part 1, section 16.

• Cette installation doit toujours être conforme aux dispositions applicables du Code américain de l’électricité (National Electrical Code) ANSI/NFPA 70, article 725, et du Code canadien de l’électricité, partie 1, section 16.

• The power supply shall not be permanently fixed to building structure or similar structure.

• La source d’alimentation ne devra pas être fixée de façon permanente à la structure de bâtiment ou à d’autres structures similaires.

Page 6: Extron OCS 100W Setup Guide R T T: Go to www .e xtr on.com o r the complete user guide installation instructions, and specifications. Occupancy Sensor OCS 100W • Setup Guide The

68-3155-50 Rev. D11 17

© 2017 Extron Electronics All rights reserved. All trademarks mentioned are the property of their respective owners. www.extron.com