8
Knowledge sharing MARCH-2019 ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com Exterior inspection and Tests for Transformer Periodic transformer exterior inspection (visual) reveals important condition information. For example, valves positioned incorrectly, plugged radiators, stuck temperature indicator and level gauges, and noisy oil pumps or fans. Oil leaks can often be seen which indicate a potential for oil contamination, loss of insulation, or environmental problems. Transformer exterior inspection and tests Physical inspection requires staff experienced in these techniques. 1. To check: a. Oil leaks b. Oil pumps c. Fans and radiators d. Age 2. To perform: a. Infrared temperature analysis Infrared for transformer tanks Infrared for surge arresters Infrared for bushings Infrared for radiators and cooling systems b. Corona scope scan 3. Other also important inspections

Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

Knowledge sharing

MARCH-2019

ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com

Exterior inspection and Tests for Transformer

Periodic transformer exterior inspection (visual) reveals important condition information. For example,

valves positioned incorrectly, plugged radiators, stuck temperature indicator and level gauges, and noisy oil

pumps or fans. Oil leaks can often be seen which indicate a potential for oil contamination, loss of insulation,

or environmental problems.

Transformer exterior inspection and tests

Physical inspection requires staff experienced in these techniques.

1. To check:

a. Oil leaks

b. Oil pumps

c. Fans and radiators

d. Age

2. To perform:

a. Infrared temperature analysis

Infrared for transformer tanks

Infrared for surge arresters

Infrared for bushings

Infrared for radiators and cooling systems

b. Corona scope scan

3. Other also important inspections

Page 2: Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

Knowledge sharing

MARCH-2019

ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com

TO CHECK:

Oil leaks

Check the entire transformer for oil leaks. Leaks develop due to gaskets wearing out, ultraviolet exposure,

taking a “set,” or from expansion and contraction, especially after transformers have cooled, due to thermal

shrinkage of gaskets and flanges. Many leaks can be repaired by applying an epoxy or other patch. Flange

leaks may be stopped with these methods, using rubberized epoxy forced into the flange under pressure.

Very small leaks in welds and tanks may be stopped by peening with a ball-peen hammer, cleaning with the

proper solvent, and applying a “patch” of the correct epoxy. Experienced leak mitigation contractors whose

work is guaranteed may also be employed.

Some leaks may have to be welded. Welding may be performed with oil in the transformer if an experienced,

qualified, and knowledgeable welder is available. If welding with oil in the tank is the method chosen, oil

samples must be taken for DGA, both before and after welding. Welding may cause gases to appear in the

DGA and it must be determined what gases are attributed to welding and which ones to transformer

operation.

Oil pumps

If the transformer has oil pumps, check the flow indicators and pump isolation valves to ensure that oil is

circulating properly. Pump motor(s) may also have reversed rotation, and flow indicators may still show that

oil is flowing. To ensure motors are turning in the proper direction, use an ammeter to check the motor

current. Compare results with the full-load-current indicated on the motor nameplate. If the motor is

reversed, the current will be much less than the nameplate full-load-current.

Check oil pumps with a vibration analyser if they develop unusual noises. Have the DGA lab check for

dissolved metals in the oil and run a metal particle count for metals, if the bearings are suspect. This should

be performed as soon as a bearing becomes suspect.

Bad oil pump bearings can put enough metal particles into the oil to threaten transformer insulation and

cause flashover inside the tank, resulting in an explosive catastrophic failure of the transformer tank.

Page 3: Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

Knowledge sharing

MARCH-2019

ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com

Ultrasonic inspection of oil pump bearings

Fans and radiators

Inspect all isolation valves at the tops and bottoms of radiators to ensure they are open. Inspect cooling fans

and radiators for cleanliness and fans for proper rotation. Check for dirty or damaged fan blades or partially

blocked radiators.

Fans are much more efficient if the blades are clean and rotating in cool air. Normally, fans blow cool air

through the radiators and they should not be pulling air through. Check to see if fans are reversed electrically

(i.e., pulling air first through the radiators and then through the fan blades).

This means that the blades are rotating in warm air after it passes through the radiator, which is much less

efficient. Place a hand on the radiator opposite the fans. Air should be coming out of the radiator against your

hand. Watch the blades as they rotate slowly when they are starting or stopping to determine which way they

should be rotating and correct the rotation if necessary.

Age

Transformer age is an important factor to consider when identifying candidates for replacement or

rehabilitation. Age is one indicator of remaining life and upgrade potential to current state-of-the art

materials. During transformer life, structural strength and insulating properties of materials used for suppo rt

and electrical insulation (especially paper) deteriorate.

Although actual service life varies widely depending on the manufacturer, design, quality of assembly,

materials used, maintenance, and operating conditions, the expected life of a transformer is about 40

years.

Page 4: Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

Knowledge sharing

MARCH-2019

ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com

Westar Energy, Inc. 69-kV (unknown capacity MVA) single phase transformers, play an important role in this Wichita-area

switchyard. The transformers are equipped with Conservator Tanks, which was a means to allow for oil expansion and

drainage under high temperature conditions. These units are not forced air, nor forced oil, however do contain cooling tubes

and substantial height. Their age may be around the late 1930s. They are 69-kV/40-kV phase-to-ground. They appear to

have NLTC, and do not have LTC configurations.

To perform:

Infrared temperature analysis

Infrared analysis should be conducted annually while equipment is energized and under full load, if

possible. IR analysis should also be conducted after any maintenance or testing to see if connections that

were broken were re-made properly. Also, if IR is performed during factory heat run, the results can be

used as a baseline for later comparison.

Infrared for transformer tanks

Unusually high external temperatures or unusual thermal patterns of transformer tanks indicate problems

inside the transformer, such as low oil level, circulating stray currents, blocked cooling, loose shields, tap

changer problems, etc. Infrared scanning and analysisis required annually for trending purposes by

National Fire Protection Association 70B,

Abnormally high temperatures can damage or destroy transformer insulation and, thus, reduce life

expectancy. Thermal patterns of transformer tanks and radiators should be cooler at the bottom and

gradually warmer ascending to the top.

Page 5: Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

Knowledge sharing

MARCH-2019

ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com

For a normal pattern; the red spot at the top is normal showing a “hot spot” top of B phase, about 110

degrees Fahrenheit (°F). Any departure from this pattern means a probable problem which must be

investigated. An IR inspection can find over-heating conditions or incorrect thermal patterns. IR scanning and

analysis requires trained staff, experienced in these techniques.

Normal transformer infrared pattern

Infrared for surge arresters

Surge arresters should be included when infrared scanning energized transformers. Look for unusual thermal

patterns on the surface of lightning arresters. The yellow in the top right of the image is a reflection not

associated with the arrester. A temperature profile of the arrester is shown as black lines. Note the hot spot

(yellow) about a third of the way down from the top. This indicates that immediate de-energization and

replacement must be undertaken! Catastrophic failure is imminent which can destroy nearby equipment

and be hazardous to workers. Also compare thermal patterns to sister units or earlier scans of the same

arrester. Scan all high voltage connections and compare them to nearby connections for unusual

temperatures.

Infrared image of defective arrester

Page 6: Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

Knowledge sharing

MARCH-2019

ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com

Infrared for bushings

IR scans of bushings can show low oil levels which would call for immediate de-energization and

replacement. This generally means that the seal in the bushing bottom has failed, leaking oil into the

transformer. The top seal has probably also failed, allowing air and up the bushing.

Another reason a bushing can exhibit a high oil level is that the top seal is leaking – allowing water to enter.

The water migrates to the bushing bottom, displacing the oil upward.

Remember, over 90% of bushing failures are attributed to water entrance through the top seal. Bushings

commonly fail catastrophically, many times destroying the host transformer or breaker and nearby equipment

and causing hazards to workers.

Infrared image of defective bushing

Low-oil level in a high voltage transformer bushing. Compare previous IR scans of the same bushing with the

current scan.

Doble hot-collar testing possibly may show this problem. However, Doble tests are run infrequently, and

the transformer has to be out of service, under clearance, and both primary and secondary conductors

removed, while an IR scan easily can be performed at any time.

Infrared for radiators and cooling systems

Examine radiators with an IR camera and compare them with each other. A cool radiator or segment

indicates that a valve is closed or the radiator or segment is plugged. The IR image (figure 4) shows that the

cold left radiator section is valves off or plugged.

Page 7: Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

Knowledge sharing

MARCH-2019

ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com

If visual inspection shows the valves are open, the radiator or segment must be isolated, drained, removed,

and the blockage cleared. Do not allow a transformer to operate with reduced cooling which drastically

shortens transformer life.

Remember, an increased operating temperature of only 8 to 10 °C will reduce transformer life by one-half. IR

scan all cooling systems, including heat exchangers, fans, pumps, motors, etc. Check inside control panels

for overloaded wiring, loose connections, and overheated relays. Look for unusual thermal patterns and

compare similar equipment.

Infrared image showing blocked radiators

Corona Scope Scan With the transformer energized, scan the bushings and surge arresters and all high voltage connections for

unusual corona patterns. Corona should be visible only at the top of bushings and arresters, and corona at

connections should be similar to sister connections. As a bushing deteriorates due to physical defects, the

corona pattern will grow progressively larger.

When the corona pattern reaches a grounded surface (i.e., the tank or structure), a flashover will occur,

destroying the bushing or arrester and, perhaps, the transformer. The corona scope will reveal this

problem long before a flashover.

Page 8: Exterior inspection and Tests for Transformerpotentialsystem.com/admin/category/exterior... · ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai

Knowledge sharing

MARCH-2019

ADDRESS: A/215, V.M. Balakrishnan Street, Sathyamoorthy Block, Ashok Nagar, Chennai - 600083. Phone: 044-23718587: 9840938585 / 9444314624 Email: [email protected] / Web: www.potentialsystem.com

Other also important inspections

There are several required physical inspections that will not be covered here because they were addressed

previously. Be sure to inspect the following:

a. Winding temperature indicators

b. Pressure relief devices

c. Sudden pressure relay

d. Conservator bladder

e. Conservator breather and

f. Bladder failure relay

For further information please do call us…..

Also we request you to kindly share your valuable comments, suggestions and feedback to

improve us