If you can read this Click on the icon to choose a picture or Reset the slide. To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the ‘Reset’ button on the ‘Home’ ribbon (next to the font choice box) If you can read this Click on the icon to choose a picture or Reset the slide. To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the ‘Reset’ button on the ‘Home’ ribbon (next to the font choice box) Johnson Controls — Exterior Fire Protection for High-Rise Buildings Pedriant Peña Advance R&D Manager, Innovation and New Ventures Johnson Controls, Fire Suppression Products SUBDET 2018

Exterior Fire Protection for High-Rise Buildings

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Exterior Fire Protection for High-Rise Buildings

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

Johnson Controls —

Exterior Fire Protection for High-Rise Buildings

Pedriant PeñaAdvance R&D Manager, Innovation and New VenturesJohnson Controls, Fire Suppression Products

SUBDET 2018

Page 2: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —2

Worldwide Problem for Tall Buildings Increased number of fires spreading on high rise buildings

SUBDET 2018

Page 3: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —3

Time is critical Address Downtown Hotel, Dubai 1, January 2016 – 14 people injured

+ 80 seconds

4 floors on fire 20 floors on fire

SUBDET 2018

Page 4: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —4

Height, Accessibility and Response Time

Fire reported to start on 20th

floor, at approx. 60 m (200 ft)

Best equipped fire service can reach 60 m (200 ft)

External fires difficult to fight from the inside

What about response time?

Address Downtown Hotel, Dubai 1, January 2016 – 14 people injured

120 m

60 m

240 m

180 m

300 m

1X

2X

3X

4X

5X

SUBDET 2018

Page 5: Exterior Fire Protection for High-Rise Buildings

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

System Overview

Autonomous Fire Suppression System

Page 6: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —6

Functional Requirements

1. Speed detect and deploy against incipient fires in secondsFire service often takes minutes to respond and longer to become operational

2. Fight fires at any height Fire service hose can reach ~60m (~200 ft)

3. Large coverage areaAt least 50 m wide by 60 m high (20 stories)

4. Use a small amount of “agent” Utilize typical NFPA 14 standpipe water supply –e.g. 2000 lpm (500 gpm)

5. Minimize structural & architectural impact 1X

2X

3X

4X

120 m

60 m

240 m

180 m

300 m…

5X

SUBDET 2018

Page 7: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —7

System Components

SUBDET 2018

2 x Array IR Flame Detectors installed outside of the building

Robotic Monitor & Extension Boomconcealed in the building

Deluge Valve with Remote Resetting Trimto open and close the water supply to the monitor

PLC & Softwareautonomously controls and positions the system

Graphical User Interface & Web Server (Optional)allows control from PC and smartphones

Page 8: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —8

System Operation

SUBDET 2018

Autonomously detects and tracks the 3D location of up to 4 fires simultaneously, recalculating position 10 times per second

Within Seconds, extends Boom and autonomously directs a high volume of water onto the fire.

Goes into standby mode when flames are no longer detected.

Detect & Locate Aim & Suppress Remote Reset & Standby

Page 9: Exterior Fire Protection for High-Rise Buildings

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

Test Program Overview

Fire Performance Evaluation

Page 10: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —10

Test Program Overview

SP Test Method 5483 Validate targeting performance Validate suppression performance

Testing Laboratory Thomas Bell-Wright International Consultants

(TBWIC) in Dubai, UAE

Associate Laboratory Research Institute of Sweden (RISE)

M

HR HR

VU

RV

DR

SUBDET 2018

Page 11: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —11

Test Setup

SUBDET 2018

Page 12: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —12

Test Setup

SUBDET 2018

Page 13: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —13

The wall represents part of the coverage area

SUBDET 2018

System coverage area

DET 1

DET 2

M

Page 14: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —14

The wall represents part of the coverage area

SUBDET 2018

System coverage area

DET 1

DET 2

M

Page 15: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —15

The wall represents part of the coverage area

SUBDET 2018

System coverage area

DET 1

DET 2

M

Page 16: Exterior Fire Protection for High-Rise Buildings

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

Test Series 1: Targeting Performance

Fire Performance Evaluation

Page 17: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —17

Test Series 1: Targeting Performance Goal: Validate fire detection and targeting performance within coverage area

Performance criteria: Automatic detection and response to fire source Water delivery to fire source with visible suppression

SUBDET 2018

Page 18: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —18

Test Series 1: Test Variables Fire location: Based on coverage area

Pressure: 5 to 8 bar (72.5 to 116 psi)

K-factor: 374, 460 lpm/bar^0.5 (26, 30 gpm/psi^0.5)

SUBDET 2018

Page 19: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —19

Test Series 1: Fuel Package

SUBDET 2018

Flat panel fire: 600 x 1200 x 50 mm mineral foam insulation panels soaked in 2.5 L of naptha

3D pan fire: 841 x 594 x 130mm (w x l x depth) pan with 2.5 L of naptha installed on ledge

Page 20: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —20

Test Series 1 (VIDEO PLACE HOLDER)

SUBDET 2018

Page 21: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —21

Test Series 1: Results A total of 28 test conducted Time to detection Average: 10 s Minimum: 6 s Maximum: 19 s

Water delivery time Average: 12 s Minimum: 6 s Maximum: 28 s

All targets were highly suppressed or extinguished

SUBDET 2018

Page 22: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —22

Test Series 1: Results continued

Pressure (bar)

Orifice Size

Reference Flow (LPM) HR (m) VUR

(m)VDR* (m)

5K26 838 20 20 40

25 15 40

K30 967 20 25 4030 20 40

6K26 918 23 22 40

28 17 40

K30 1059 23 25 4032 20 40

7K26 992 27 23 40

32 18 40

K30 1144 27 25 4033 20 40

8K26 1060 30 25 40

35 20 40

K30 1223 30 25 4035 20 40

M

HR HR

VU

RV

DR

SUBDET 2018

Page 23: Exterior Fire Protection for High-Rise Buildings

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

If you can read this Click on the icon

to choose a picture or

Reset the slide.To Reset: Right click on the slide thumbnail and select ‘reset slide’ or choose the

‘Reset’ button on the ‘Home’ ribbon (next to the font

choice box)

Test Series 2: Suppression Performance

Fire Performance Evaluation

Page 24: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —24

Test Series 2: Suppression Performance Goals: Validate ability to contain a fire and

prevent fire spread for realistic façade system

Achieve comparable performance to successful assembly test (NFPA 285, BS 8414, SP 105, etc.)

Performance criteria: Limit damage and flame spread to

below bottom of second window

SUBDET 2018

Page 25: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —25

Test Series 2: Test Variables

SUBDET 2018

Fire attack: vertical downward, diagonal downward, horizontal

Settings: Minimum pressure / flow to reach target location

Test specimen: 4mm thick PE core ACP installed in an “open configuration”

Page 26: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —26

Test Series 2: Fuel Package

SUBDET 2018

SP105 heptane trays in combustion chamber (15 - 20 minute sustained burn time)

Page 27: Exterior Fire Protection for High-Rise Buildings

CAVITY

Page 28: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —28

Test Series 2: Free-burn (VIDEO PLACE HOLDER)

SUBDET 2018

Page 29: Exterior Fire Protection for High-Rise Buildings

Test Series 2: Suppression Performance(VIDEO PLACE HOLDER)

Page 30: Exterior Fire Protection for High-Rise Buildings

Detection as soon as the flames are out of the combustion chamberTime: 5m 25s

Page 31: Exterior Fire Protection for High-Rise Buildings

10 minutes

Page 32: Exterior Fire Protection for High-Rise Buildings

15 minutes

Page 33: Exterior Fire Protection for High-Rise Buildings

Damage after 17 minutes with active fire suppression

Page 34: Exterior Fire Protection for High-Rise Buildings

Damage after 6 minutes of Free Burn(manually suppressed for safety reasons)

Page 35: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —35

Test Series 2: Results

SUBDET 2018

Page 36: Exterior Fire Protection for High-Rise Buildings

Johnson Controls —36

Conclusions

1. Rapid detection and location of incipient stage fires is possible at over 50m

2. Early intervention with water can prevent PE panel delamination, contain fires

3. … at any height

SUBDET 2018

Page 37: Exterior Fire Protection for High-Rise Buildings