Upload
andreea-handabut
View
214
Download
0
Embed Size (px)
Citation preview
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
1/9
Experimental and analytical progressive collapse assessment of a steel
frame building
Brian I. Song a, Halil Sezen b,⇑
a URS Corporation, Warrenville, IL, USAb Department of Civil and Environmental Engineering and Geodetic Science, The Ohio State University, Columbus, OH, USA
a r t i c l e i n f o
Article history:
Received 19 August 2011
Revised 19 June 2012
Accepted 31 May 2013
Available online 2 July 2013
Keywords:
Progressive collapse
Steel buildings
Column failure
Load redistribution
Collapse experiment
a b s t r a c t
A field experiment and numerical simulations were performed to investigate the progressive collapse
potential of an existing steel frame building. Four first-story columns were physically removed from
the building to understand the subsequent load redistribution within the building. Experimental data
from the field tests were used to compare and verify the computational models and simulations. Due
to the scarcity of data from full-scale tests, the experimental data produced during this research is a valu-
able addition to the state of knowledge on progressive collapse of buildings. The progressive collapse
design guidelines typically recommend simplified analysis procedures involving instantaneous removal
of specified critical columns in a building. This paper investigates the effectiveness of such commonly
used progressive collapse evaluation and design methodologies through numerical simulation and exper-
imental data.
2013 Elsevier Ltd. All rights reserved.
1. Introduction
Progressive collapse is generally defined as small or local struc-
tural failure resulting in damage and failure of the adjoining mem-
bers and, in turn, causing total collapse of the building or a
disproportionately large part of it. Progressive collapse of building
structures is initiated by loss of one or more vertical load carrying
members, usually columns. After one or more columns fail, an
alternative load path is needed to transfer the load to other struc-
tural elements. If the neighboring elements are not designed to re-
sist the redistributed loads, failure will happen with further load
redistribution until equilibrium is reached, resulting in partial or
total collapse of the structure.
Progressive collapse is triggered by abnormal loading that
causes local failure of one or more columns if the building lacks
sufficient ductility, continuity and/or redundancy. The local orcomplete collapse may cause significant casualties and damage
disproportionate to the initial failure. A notable example is partial
collapse of the Ronan Point apartment building in London. An acci-
dental gas explosion in a corner kitchen on the 18th floor initiated
progressive collapse of the 24-story building in 1968. This event
triggered extensive progressive collapse research and led to devel-
opment of design guidelines for the prevention of progressive
collapse [13].
The World Trade Center 7 (WTC 7) in New York City was a 47-
story office building adjacent to the WTC towers (WTC 1 and 2)that collapsed following the terrorist attacks of September 11,
2001. WTC 7 collapsed several hours after the collapse of twin
WTC towers. The NIST report [11] concluded that: ‘‘An initial local
failure occurred at the lower floors (below floor 13) of the building
due to fire and/or debris induced structural damage of a critical
column (the initiating event) which supported a large span floor
bay with an area of about 2000 square feet. Vertical progression
of the initial local failure occurred up to the east penthouse, as
the large floor bays were unable to redistribute the loads, bringing
down the interior structure below the east penthouse. Horizontal
progression of the failure across the lower floors triggered by
damage due to the vertical failure, resulting in a disproportionate
collapse of the entire structure.’’ The FEMA 403 [6] study empha-
sized the significance of fires on the collapse. This is a good exam-ple of disproportionate collapse caused by debris and/or fire
induced failure of a column or columns in a tall steel building. In
this research, several columns were sequentially removed from a
building, which can resemble the initial debris damage and gradual
and intensifying fire damage or a various other loads.
Failure of one or more columns in a building and the resulting
progressive collapse may be a result of a variety of events with dif-
ferent loading rates, pressures or magnitudes. The magnitude and
probability of natural and man-made hazards are usually difficult
to predict. Therefore, most of the current progressive collapse
design guidelines are threat-independent and do not intend to
prevent such local damage, e.g., ACI 318 [1]. Rather, their purpose
0141-0296/$ - see front matter 2013 Elsevier Ltd. All rights reserved.http://dx.doi.org/10.1016/j.engstruct.2013.05.050
⇑ Corresponding author. Tel.: +1 614 292 1338.
E-mail addresses: [email protected] (B.I. Song), [email protected] (H. Sezen).
Engineering Structures 56 (2013) 664–672
Contents lists available at SciVerse ScienceDirect
Engineering Structures
j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / e n g s t r u c t
http://dx.doi.org/10.1016/j.engstruct.2013.05.050mailto:[email protected]:[email protected]://dx.doi.org/10.1016/j.engstruct.2013.05.050http://www.sciencedirect.com/science/journal/01410296http://www.elsevier.com/locate/engstructhttp://www.elsevier.com/locate/engstructhttp://www.sciencedirect.com/science/journal/01410296http://dx.doi.org/10.1016/j.engstruct.2013.05.050mailto:[email protected]:[email protected]://dx.doi.org/10.1016/j.engstruct.2013.05.050http://crossmark.crossref.org/dialog/?doi=10.1016/j.engstruct.2013.05.050&domain=pdf
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
2/9
is to provide a level of resistance against disproportionate collapse
and to increase the overall structural integrity. Design guidelines
typically require minimum level of redundancy, strength, ductility
and element continuity. The codes typically prescribe simplified
analysis procedures requiring instantaneous removal of certain
critical columns in a building, e.g., GSA [8]. In this paper, effective-
ness of such commonly used progressive collapse evaluation and
design methodologies is investigated through numerical simula-
tions and experimental testing of the building.
A large number of numerical studies have been conducted to
evaluate the effectiveness and consistency of the current progres-
sive collapse design guidelines. However, very limited experimen-
tal research has been performed to validate the results of these
computational studies and to verify the methodologies prescribed
in the guidelines. This is mainly because it is difficult to construct
and test full-scale building specimens and such large-scale testing
is discouragingly expensive. In this study, an existing steel frame
building, Ohio Union building, was tested by physically removing
four first-story columns. The building was instrumented and the
experiment was conducted prior to its scheduled demolition. The
building was also modeled and analyzed using the computer pro-
gram, SAP 2000 [15], following the requirements of the current
progressive collapse evaluation and design guidelines. The results
from static and dynamic analysis of the building were compared
with the experimental data.
2. Progressive collapse guidelines
American Society of Civil Engineers (ASCE 7, [3]), General Ser-
vices Administration [8], Department of Defense (Unified Facilities
Criteria, [4], and National Institute of Standards and Technology
[12] have developed criteria and guidelines to evaluate, design
and improve structural integrity and progressive collapse resis-
tance of existing and new buildings. ASCE 7 [3] provides design
load combinations including abnormal loads and associated
probabilities. It also presents general direct and indirect design ap-proaches to ensure structural integrity following local damage to a
primary load-carrying member. In this paper, the collapse resis-
tance of the test building is evaluated using the load combinations
recommended by the ASCE 7 standard and GSA guidelines [8].
General Services Administration [8] provides guidelines for
evaluation of existing buildings and design of new buildings
against progressive collapse. A simplified threat independent
methodology is recommended for buildings with fairly regular
plans and up to ten stories above ground. A linear elastic static
analysis of the building is required after the instantaneous removal
of a first story column located near the middle of longitudinal and
transverse perimeter frame or at the corner of the building. Pro-
gressive collapse and possible subsequent failure of elements are
investigated using the calculated demand-to-capacity ratio (DCR)
for each structural element. DCR is defined as the ratio of the force
(moment, shear, or axial force) calculated after the instantaneous
loss of a column and the corresponding capacity of the member.
In this study, the test building was analyzed using the load combi-
nations specified by the GSA and the corresponding DCRs were cal-
culated. The acceptance criteria provided by the GSAwas then used
to assess the potential for progressive collapse.
3. Building experiment
The Ohio Union building, shown in Fig. 1, was located on the
Ohio State University campus. The four-story moment frame build-
ing was constructed in 1950. The building included a rectangular
floor plan with three columns on each transverse axis and ninecolumns along the longitudinal axes. Column and beam section
properties and the longitudinal test frame geometry are shown
in Table 1 and Fig. 2, respectively. In Table 1, the first and last num-
bers are the depth (in inch units) and nominal weight (lb/ft) of the
columns or beams, respectively (1 in. = 25.4 mm, 1 ft = 305 mm,
and 1 lb = 4.448 N). The letters WF and B are wide-flange (WF)
shaped I-beam and light I-beam, respectively, which were com-
monly used in the 1950s [2].
Before the building’s demolition, four first-story columns were
removed in the following order: (1) two columns near the middle
of the longitudinal perimeter frame, (2) column in the building cor-
ner, and (3) column next to the corner column. As shown in Figs. 1
and 3, four of the nine exterior columns were first torched near the
top and bottom. Only a small portion of the flange was left intact
when the cross sections were cut. The middle column segment be-
tween the torched sections was then pulled out by a bulldozer
using a steel cable (Fig. 3).
The columns were removed within a very short time period
representing an instantaneous column removal as recommended
in the design guidelines. As shown in Fig. 4, 15 strain gauges were
installed on the columns and beams closely linked to the removed
columns to monitor the redistribution of gravity loads using the
change in strains measured during the removal of columns. During
the column removal process, a portable data acquisition system
and a scanner connected to a laptop computer recorded the strains.
No significant visible damage was observed in the building even
after the four columns were removed. Detailed description of the
test building, instrumentation, experimental procedure and re-
corded data can be found in Song [16].
During the field experiment, strains in members neighboring
the removed columns were measured as each column was torched
and removed. In this study, universal general purpose strain
gauges with a resistance of 120 ± 0.3% Ohms were used. All strain
values dropped to negative values after each column was torched
or removed, and then stabilized after a certain amount of time.
These negative strain values indicate that the structural members
contracted and compressed when the neighboring columns were
torched. Most of the measured strain values dropped more whenthe columns were torched than when they were removed during
the experiment. The largest drop of strain values was observed
when the last column was torched.
4. Analysis procedures and results
Numerical simulations of the test building were performed
using the computer program SAP2000 [15] to investigate the
progressive collapse performance of the building. At the time of
testing, the frames carried only dead loads due to weight of walls,
slabs, beams, and columns. In the linear static analysis, the dead
loads were multiplied by 2.0 as recommended in the GSA guide-
lines [8]. The live load was assumed to be zero in all analysesbecause the test building was not occupied, and most of the parti-
tions, furniture and other non-structural loads were removed from
the building. To calculate the dead load of the walls, densities of
glass and brick were assumed to be 2579 kg/m3 and 1920 kg/m3,
respectively. Properties of frame members were obtained from
the original structural drawings and design notes. Yield strength
of all frame members of the Ohio Union building was assumed to
be 345 MPa (50 ksi), as specified in the original design drawings.
Details of the modeling and analysis assumptions and results are
reported in Song [16] and Song et al. [17,18].
Two-dimensional (2-D) as well as three-dimensional (3-D)
models of the building were developed to analyze and compare
the progressive collapse response. Fig. 5 shows 2-D and 3-D
SAP2000 models of the Ohio Union building with frame membernumbers. As in the actual building experiment, four circled
B.I. Song, H. Sezen/ Engineering Structures 56 (2013) 664–672 665
http://-/?-http://-/?-
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
3/9
columns were sequentially removed in the following order: col-
umns 27, 22, 2, and 7.
Linear static, nonlinear static, linear dynamic, and nonlinear
dynamic analysis methods, in order of increasing complexity, can
be used to analyze a structure to investigate its structural behavior.
Researchers investigated the advantage and disadvantage of eachof these procedures for progressive collapse analysis [14]. A com-
plex analysis is desired to obtain more realistic results represent-
ing the actual nonlinear and dynamic response of the structure
during the progressive collapse. However, both GSA and DOD
guidelines recommend the simplest method, linear static, for the
progressive collapse analysis since this method is cost-effective
and easy to perform. One of the objectives of this paper is to
Fig. 1. (a) Building before demolition, (b) four first-story columns exposed, (c) columns removed, and (d) building during the gradual demolition process.
Table 1
Column and beam sections of the Ohio Union building.
Column section Beam section
Column number Column type Beam number Beam type
C1 10 WF 72 B1 24 B 76
C2 12 WF 133 B2 21 B 68
C3 12 WF 120 B3 16 B 58
C4 10 WF 100 B4 21 WF 62
C5 10 WF 89 B5 18 WF 50
C6 10 WF 54 B6 14 B 17.2
C7 10 WF 112 B7 14 B 22
C8 10 WF 60 B8 24 WF 76
C9 10 WF 33 B9 18 WF 45
Fig. 2. Longitudinal frame elevation including beam and columns sections (see Table 1).
666 B.I. Song, H. Sezen / Engineering Structures 56 (2013) 664–672
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
4/9
compare the simplest and most complicated analysis procedures
(i.e., linear static and nonlinear dynamic procedures) for the eval-uation of progressive collapse potential of the test building.
4.1. 2-D linear static analysis
Linear static analysis is a simple and commonly used method to
investigate progressive collapse potential of a building [3], and [8].
Fig. 6 shows the elastic moment diagrams after the removal of each
column from the Ohio Union building. When the first two columns
were removed, the largest bending moments were localized and
typically occurred in the members above or immediately next to
the removed columns. The maximum moments significantly in-
creased and spread within the frame when three and four columns
were removed.
Demand-to-capacity ratios (DCR) were calculated for eachframe member, and the building response was evaluated by
comparing the calculated DCR values based on the recommenda-
tions of GSA guidelines. DCR for moment is defined as the ratioof the maximum moment demand M max of the beam or column
calculated from linear elastic analysis to its expected ultimate
moment capacity M p, which is calculated as the product of plastic
section modulus and yield strength. In M p calculations for columns,
the effect of the axial load is neglected because the column axial
loads were relatively small and did not significantly affect the
moment capacity of the cross section.
DCR ¼ M maxM p
ð1Þ
Fig. 7 shows the moment diagram and the corresponding
maximum DCR values at the end of each beam and top of each
column after four columns were removed from the frame. The
columns in the top story had higher DCR values, indicating thatafter removal of columns additional loads were transferred
Fig. 3. Before and after removal of middle part of a column.
Fig. 4. Plan view of strain gauge placement in Ohio Union building with columns and beam labeled (15 strain gauges are shown in the circles).
B.I. Song, H. Sezen/ Engineering Structures 56 (2013) 664–672 667
http://-/?-http://-/?-http://-/?-
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
5/9
upward as well as to the adjacent spans. Smaller cross section
used in the top story columns is another reason for the higher
DCR values observed in the top story. As shown in Fig. 7, the
maximum DCR value of 2.83 was calculated in Column 10 in
the top story. The maximum calculated beam DCR value was0.94 in beam 63 in the third floor level.
Fig. 8 shows DCR values for each frame member for all column
removal cases. Frame member numbers up to 45 are columns, and
beams are numbered from 46 to 85 (Fig. 5a). After the first column
was removed, DCR values for all columns and beams were below
0.5. The DCR values after the loss of second column was similarto those of third column loss, all of which were less than 1.5. The
Fig. 5. (a) Two-dimensional SAP2000 model with frame member numbers and (b) three-dimensional SAP2000 model of the Ohio Union building (circled columns are
removed in the order shown).
Fig. 6. Moment diagrams: (a) after one column was removed, (b) after two columns were removed, (c) after three columns were removed, and (d) after four columns were
removed.
668 B.I. Song, H. Sezen / Engineering Structures 56 (2013) 664–672
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
6/9
DCR values for columns were remarkably increased after the fourth
column was lost. Columns were impacted more than beams when
all four columns were removed from the frame. As acceptance cri-
teria, the maximum DCR limits specified in GSA [8] are 2.0 and 3.0
for columns and beams for the test building, respectively. After all
four columns were removed, no beams and five columns (i.e., col-
umns 8, 9, 10, 20 and 25) exceeded the DCR criteria. The change in
DCR values for beams was not significant compared with that of
columns. The DCR values of beams were always less than 1.0. This
is probably due to potential redistribution of loads to the adjacent
beams in the analyzed frame.
After four columns were removed, the building was more
susceptible to progressive collapse. This was also reflected in the
maximum displacements calculated from linear static analysis.
As columns were sequentially removed, the maximum vertical dis-
placements were calculated as 11.40, 11.54, 30.73, and 17.93 cm at
the joints immediate above the first (column 27), second (column
22), third (column 2) and forth (column 7) removed columns,
respectively.
4.2. 2-D nonlinear dynamic analysis
Progressive collapse is a dynamic event involving vibration of
building elements and resulting in internal dynamic forces affected
by inertia and damping. Progressive collapse is inherently a
nonlinear event in which structural elements are stressed beyond
their elastic limit to failure. Nonlinear dynamic procedure reflectsthe dynamic and nonlinear aspects of the progressive collapse
phenomenon and therefore nonlinear dynamic analysis is more
realistic and accurate than linear static analysis.
In nonlinear dynamic analysis, a major load bearing structural
element is removed dynamically and the structural material is al-lowed to undergo nonlinear behavior. Fig. 9 illustrates the replace-
ment of a removed column by equivalent loads in nonlinear
dynamic analysis. First, the building is modeled with its dead load
assigned. After the internal (equivalent) forces in a given column
are determined from static analysis, the column is replaced with
its equivalent forces to simulate the instantaneous removal of
the column. As shown in Fig. 10, the equivalent load is first as-
signed with a uniform time history function. This corresponds to
the initial case where the column is still in place and carrying
the dead load. Then the column is suddenly removed using a step
function. The sum of a uniform time history function and the col-
umn loss function represents the column loss. This is referred to
as a time-history analysis where the response of the structure is
calculated during and after the removal of column(s) as a functionof time.
In this study, both geometric and material nonlinear behaviors
were considered in the nonlinear dynamic analysis. Material prop-
erties such as yield strength, ultimate strength, and ductility were
important parameters to design a building model. P -Delta effect
was considered as a geometric nonlinearity. Also, several dynamic
and nonlinear parameters including time step, damping ratio, and
plastic hinges was defined before performing nonlinear time his-
tory analysis.
The vertical displacements of the joints above each removed
column were calculated during and after removal of each column
in the first story. Fig. 11 shows the vertical displacement history
of Joint 1, 2, 3, and 4 above the first (column 27), second (column
22), third (column 2), and fourth (column7) removed columns,
respectively (Fig. 5a) after the removal of fourth column. The col-
umns were removed at time of 0 s and negative values indicate
0.32
0.38
0.34
2.25
2.14
2.83
1.21
1.56
2.38
0.22
0.45
0.89
1.10
0.16
1.54
1.44
2.24
0.63
0.41
0.45
0.17
0.35
0.37
0.07
0.45
0.44
0.86
0.11
0.14
0.12
0.17
0.03
0.47
0.40
0.39
0.21
0.91
0.82
0.77
0.51
0.58
0.56
0.49
0.24
0.94
0.83
0.80
0.91
0.07
0.00
0.15
0.09
0.48
0.42
0.32
0.40
0.56
0.55
0.42
0.41
0.34
0.26
0.27
0.18
Fig. 7. Moment diagram and corresponding DCR values after the loss of four columns in the Ohio Union building.
Fig. 8. Change in DCR values of each frame member for all cases.
Fig. 9. Column removal load representation for nonlinear dynamic analysis.
B.I. Song, H. Sezen/ Engineering Structures 56 (2013) 664–672 669
http://-/?-http://-/?-http://-/?-
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
7/9
downward displacements. As shown in Fig. 11, the joints above the
four removed columns settled at the permanent displacements of
6.05, 6.12, 17.93, and 9.98 cm, respectively. The maximum
transient vertical displacements calculated from 2-D nonlinear dy-
namic analysis were 7.11, 7.24, 20.47, and 11.33 cm at Joint 1, 2, 3,
and 4, respectively.
4.3. Comparison of results from 2-D and 3-D analyses
A 3-D model of the Ohio Union building was developed, and
progressive collapse analysis was performed using this model.
Fig. 12 shows a comparison of DCR values for moments determined
from 2-D and 3-D models after four columns were removed. In 2-D
linear static analysis, columns were more impacted than beams.Five columns exceeded the DCR criteria of 2.0 [8], but none for
the beams after four columns were removed. The DCR values of
all beams were less than 1.0, and the maximum DCR value ob-
served in beams was 0.94. However, DCR values calculated from
3-D linear static analysis showed an opposite trend compared to
2-D results. Beams were more influenced by the column loss. The
maximum DCR value of beams was 1.49 while that of columns
was 0.96. The reason that beams had higher DCR values than
columns in the 3-D linear static analysis was possibly due to the
larger deformation and participation of beams in the transverse
direction. It was found that beams, especially in the top story, were
significantly deformed in the transverse direction after each col-
umn removal. 2-D linear static analysis may lead to limited and
underestimated demands for beams.
More interestingly, it was observed that DCR values calculated
from the 3-D linear static analysis were smaller than those from
2-D linear static analysis for columns and most beams. As shown
in Fig. 12, all members had DCR values of less than 1.5, and satis-
fied GSA acceptance criteria of 2.0 for columns and 3.0 for beams.This could be mainly due to contribution of transverse beams. The
transverse beams can distribute loads to the connected columns
and beams in the transverse direction, leading to a decrease of
force demands in structural members.
Table 2 shows the comparison of maximum vertical displace-
ments calculated from 2-D and 3-D analyses. 3-D models showed
lower maximum displacements than 2-D models for both linear
static and nonlinear dynamic analysis. Similar to the DCR results,
the transverse beams connected to the interior columns and the
beams increased the overall resistance of structure, leading to
smaller deformations in the 3-D model. As shown in Table 2, Linear
static analysis resulted in higher maximum vertical displacements
than nonlinear dynamic analysis in both 2-D and 3-D models. For
example, the maximum vertical displacement calculated from2-D linear static analysis was 30.73 cm at Joint 3 while that from
Fig. 10. Time history function for column loss simulation.
Fig. 11. Displacement of joints above each removed column after all columns wereremoved.
Fig. 12. Comparison of DCR values determined from 2-D and 3-D linear static
analysis after removal of four columns.
670 B.I. Song, H. Sezen / Engineering Structures 56 (2013) 664–672
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
8/9
the 2-D nonlinear dynamic analysis was 20.47 cm. It seems that
the impact factor of 2 (i.e., dead loads multiplied by 2) in linear sta-tic analysis led to very conservative results. Marjanishvili reported
that a more complicated analysis method such as nonlinear dy-
namic analysis may result in less severe structural response, due
to more accurate estimates of load distribution and less stringent
evaluation criteria.
Table 3 shows plastic hinge rotations at the location where
columns were removed after four columns removal. Plastic hinge
rotation was chosen as acceptance criteria for the nonlinear
dynamic analysis [8], which also possibly evaluates whether the
moment connection of the frame is strong enough to survive the
excessive moment rotation of the joints. Plastic hinge rotation
angle for beam members on each side of the removed column
can be measuredbetween horizontal line and tangent to maximum
deflected shape, which is defined by Eq. (2).
h ¼ tan1 dmax
L
ð2Þ
where h is the maximum hinge rotation, dn the maximum displace-
ment of columns at the location where the column is removed, and
L is thebeamlength or column spacing in the longitudinal direction.
As shown in Table 3, hinge rotations calculated from the 3-D
model were smaller than those from the 2-D model, because of
lower maximum displacement values in 3-D nonlinear dynamic
analysis. The maximum plastic hinge rotation was only 1.80 at
the hinge above third removed column (Column 2) in linear static
analysis. For both 2-D and 3-D nonlinear dynamic procedure, the
values of plastic hinge rotation were much smaller than 12 of GSA [8] criteria, indicating that the Ohio Union building was not
susceptible to progressive collapse. Considering that no significant
deformations were observed during field testing, GSA criteria for
plastic deformations or hinge rotations may be more realistic than
the GSA criteria for force demands or DCR values.
4.4. Comparison of calculated and measured strains
Table 4 shows changes in strain (De) obtained from the field
test, compared with those calculated from 2-D and 3-D models.
During the field test, strain values changed as each column was
torched and removed. De (Field Test) reported in Table 4 are the
changes in strain values recorded by the strain gauges in the field
after the last column torching. De (Computational Model) is the
changes in strain values after the last column removal. De is calcu-
lated by considering the combined effect of axial load and a bend-
ing moment, both of which were determined from the SAP2000
analysis. Details of calculations and assumptions are reported in
Song [16].Total of fifteen (15) strain gauges were used in this experiment
(see Fig. 4). Table 4 compares selected strain measurements and
analytical model results. Six strain gauges were selected since
strain gauges 1, 3, 7, 10 and 12 are attached to the same columns
of the selected gauges 2, 4, 8, 9 and 11, respectively, and strain
gauges 5, 6, 13 and 14 were attached above the removed columns.
The strain gauges on the same column showed very similar strain
measurements. The strain gauge 15, attached on Beam 67, was
selected from the experimental study to compare the results from
2-D and 3-D models because it was the only strain gauge left in the
perimeter frame in the 2-D model after the four columns were
removed (location of strain gauges are shown in Fig. 4). Strain
gauges 2, 4, 8, 9 and 11 were attached on the interior columns.
As shown in Table 4, for strain gauge 15 attached on Beam 67,De calculated from the 3-D model was closer to the experimental
result than that from the 2-D model. 3-D model can account for
redistribution of the building’s weight to both exterior and interior
Table 2
Comparison of vertical displacement (cm) after all columns removal.
Joints above removed columns 2-D model 3-D model
Linear static analysis Nonlinear dynamic analysis Linear static analysis Nonlinear dynamic analysis
Maximum Permanent Maximum Permanent
Joint 1 11.40 7.11 6.05 7.85 4.22 3.66
Joint 2 11.53 7.24 6.12 7.95 4.27 3.71
Joint 3 30.73 20.47 17.93 10.03 5.64 5.08 Joint 4 17.93 11.33 9.98 7.37 3.68 3.38
Table 3
Plastic hinge rotations (h, degree) at the location where each column was removed after all columns removal.
Removed columns 2-D nonlinear dynamic analysis () 3-D nonlinear dynamic analysis ()
Joint 1 0.53 0.31
Joint 2 0.54 0.32
Joint 3 1.80 0.50
Table 4
Comparison of change in strain (De) obtained from the field test after last column torching with that calculated from 2-D and 3-D analyses after all columns removal (% difference
was indicated in parentheses).
Strain gauge Field test 2-D model 3-D model
Linear static analysis Nonlinear dynamic analysis Linear static analysis Nonlinear dynamic analysis
2 (Column) 55 106 – – 165 106 (200%) 32 106 (42%)
4 (Column) 37 106 – – 121 106 (227%) 17 106 (54%)
8 (Column) 29 106 – – 34 106 (17%) 4 106 (86%)
9 (Column) 28 106 – – 104 106 (271%) 20 106 (29%)
11 (Column) 33 106 – – 49 106 (48%) 7 106 (79%)
15 (Beam) 37 106 118 106 (219%) 64 106 (73%) 53 106 (43%) 46 106 (24%)
B.I. Song, H. Sezen/ Engineering Structures 56 (2013) 664–672 671
http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
8/15/2019 Experimental and analytical progressive collapse assessment of a steel frame building
9/9
columns and beams while only exterior members were considered
in the 2-D model. All of De values calculated from the 3-D models
were very comparable to the measured strains.
Fig. 13 compares strain values (De) measured in the field and
calculated from linear static and nonlinear dynamic analyses after
all columns were removed. For the interior columns (i.e., Strain
gauge 4) and the beam (i.e., Strain gauge 15), the measured strains
were closer to the De values calculated from the nonlinear dy-
namic analysis. The strain increments (De) calculated from the lin-
ear static analysis were much larger than the measured values. It
should be noted that the linear static analysis was performed by
amplifying the gravity (dead) loads by a factor of 2.0 following
the recommendations of GSA [8] while the unfactored dead load
was used in dynamic analysis. If the unfactored dead loads wereused in the linear static analysis, the calculated strain would be re-
duced by half to approximately 0.00006, which is still larger than
the maximum measured strain.
5. Conclusions
Progressive collapse performance of an existing steel frame
building was evaluated by physically removing four first-story col-
umns from the building and by performing linear static and nonlin-
ear dynamic analysis of the building. The following conclusions
were reached during this study based on the evaluation of experi-
mental data and structural analysis of the test building.
The measured strain data compared relatively well with the
analysis results. In particular, 3-D model was more accurate than
the 2-D model, because 3-D models can avoid overly conservative
solutions as well as account for 3-D effects such as contribution of
transverse beams to overall resistance of the frame. The 3-D model
had lower DCR values and vertical displacements than 2-D model,
which was possibly due to inclusion of transverse beams in the 3-D
model. The 3-D model is believed to be more realistic than 2-D
model for the progressive collapse analysis.
The strain values calculated from the nonlinear dynamic analy-
sis were smaller than those from the linear static analysis, and
were closer to the measured strains. Also, linear static analysis
showed higher DCR values and vertical displacements than nonlin-
ear dynamic analysis for both 2-D and 3-D models. The amplifica-
tion factor of 2 required for the dead load in linear static analysis
may lead to very conservative analysis results.
For future research, it would be better to consider the actual
material properties and connections of the building in the analyt-
ical models in order to obtain more reliable results.
Acknowledgements
This research was partially funded by the National Science
Foundation (CMMI 0745140), American Institute of Steel Construc-
tion, and URS Corporation; this is gratefully acknowledged. The
authors would like to thank SMOOT Construction, Loewendick
Demolishing Contractors, and the Ohio State University for provid-
ing access to the test building and help with the experiment.
References
[1] ACI 318-11. Building code requirements for structural concrete and
commentary. Farmington Hills, MI: American Concrete Institute (ACI); 2011.
[2] AISC. Manual of steel construction. 6th ed. American Institute of Steel
Construction (AISC); 1969.
[3] ASCE. Minimum design loads for buildings and other structures. Reston, VA:American Society of Civil Engineers (ASCE); 2005.
[4] DOD. Design of buildings to resist progressive collapse. Unified Facilities
Criteria (UFC) 4-023-03. Department of Defense (DOD); 2005.
[6] FEMA 403. World trade center building performance study: data collection,
preliminary observations and recommendation. Report: FEMA 403.
Washington, DC: Federal Emergency Management Agency (FEMA); 2002.
[8] GSA. Progressive collapse analysis and design guidelines for new federal office
buildings and major modernization projects. Washington, DC: General
Services Administration (GSA); 2003.
[11] NIST SP 1000-5. Progress report on the federal building and fire safety
investigation of the world trade center. Gaithersburg, MD: National Institute
of Standards and Technology; 2004.
[12] NIST. The collapse of the world trade center towers. Final Report.
Gaithersburg, MD: National Institute of Standards and Technology (NIST);
2005.
[13] NIST. Best practices for reducing the potential for progressive collapse in
buildings. Gaithersburg, MD: National Institute of Standards and Technology
(NIST); 2006.
[14] Powell G. Progressive collapse: case study using nonlinear analysis. ASCE
structures congress and forensic engineering symposium. New York, NY; April
20–24, 2005.
[15] SAP2000. SAP 2000 advanced structural analysis program. Version 12.
Berkeley, CA, USA: Computers and Structures, Inc. (CSI); 2009.
[16] Song BI. Experimental and analytical assessment on the progressive potential
of existing buildings. Master’s thesis. The Ohio State University; 2010. p. 125.
[17] Song B, Sezen H. Evaluation of an existing steel frame building against
progressive collapse. In: ASCE structures conference, Austin, Texas; April 30–
May 2, 2009.
[18] Song B, Sezen H, Giriunas K. Experimental and analytical assessment on
progressive collapse potential of actual steel frame buildings. In: ASCE
structures conference and North American steel construction conference,
Orlando, Florida; May 12–15, 2010.
Fig. 13. Comparison of calculated strains and strain measured by (a) Strain Gauge 4
and (b) Strain Gauge 15 after all columns were removed.
672 B.I. Song, H. Sezen / Engineering Structures 56 (2013) 664–672