5/20/2018 Expansion&ContractionCalculationfortheChilledWaterPipes-slidepdf.com http://slidepdf.com/reader/full/expansion-contraction-calculation-for-the-chilled-water- EXPANSION & CONTRACTION CALCULATION:   BLACK CARBON STEEL PIPE: - ASTM / A53 / SCH 40. PIPING THERMAL GROWTH:- 1. THERMAL GROWTH COEFFICIENT = 0.0000125 mt / mtº c 2. OPERATING TEMPERATURE = 5.5º C 3. TEMP. AT TIME OF INSTALLATION = 4º C EXPECTED THERMAL GROWTH ( L ! L" # " T $% / $% ' L = LENGTH OF THE PIPE INSTALLE! IN THE "RI!GE. (3 MTR #  ∆T= $!IFF."ETWEEN TEMP.AT TIME OF INSTILL. %%% OPERA.TEMP#. & = THERMAL GROWTH CO%EFFICIENT $0.0000125 mt / mtº c#. EXPECTED THERMAL GROWTH ( L ! L" # " T $% / $% ' ! 3" 0.0000)*5" (4-5.5 ! 0.0*0)+ $% / $% ' ! *0.)+ $$ / $% '. W, , '%12' '26 (72,892, '26 %2, 0;;. M18.112192, $,$,% ,< %2, ;; 72,892, '26 =.4$$ >%? '% 6<,@ , 7< )0 @1. S17,% *5 A12192, $,$,% ,< '26 ! =.4" 0.;5 ! 4. $$. N$9,< 7 '26 ! *0.)+ / 4. !4.*0 ! 4 NOS

Expansion & Contraction Calculation for the Chilled Water Pipes

Embed Size (px)

DESCRIPTION

expansion and contraction cal

Citation preview

EXPANSION & CONTRACTION CALCULATION: BLACK CARBON STEEL PIPE: - ASTM / A53 / SCH 40.

PIPING THERMAL GROWTH:-

1. THERMAL GROWTH COEFFICIENT = 0.0000125 mt / mt c

2. OPERATING TEMPERATURE = 5.5 C

3. TEMP. AT TIME OF INSTALLATION = 48 C

EXPECTED THERMAL GROWTH((L)= L* * (T mt / mt c L = LENGTH OF THE PIPE INSTALLED IN THE BRIDGE. (38 MTR) (T= (DIFF.BETWEEN TEMP.AT TIME OF INSTILL. --- OPERA.TEMP). = THERMAL GROWTH CO-EFFICIENT (0.0000125 mt / mt c).

EXPECTED THERMAL GROWTH ((L) = L* * (T mt / mt c

= 38* 0.0000125* (48-5.5)

= 0.02019 mt / mt c

= 20.19 mm / mt c.

We use victaulic coupling (flexible coupling style 077).

Max.available movement per style 77 flexible coupling is 6.4mm with cut grooved pipe for 10" dia.

Safety 25%

Available movement per coupling = 6.4* 0.75 = 4.8 mm.

Number of coupling's

= 20.19 / 4.8=4.20 = 4 NOS