SINGLE METER PEDESTALNOT TO SCALE
EXISTINGMOBILE HOME UNIT
INSTALL 200 AMP SINGLE METER SERVICEPEDESTAL ON EXISTING CONCRETE PAD. METERSHALL FACE TOWARDS SERVICE RESIDENCE.
EXISTING J-BOX (WHEN APPLICABLE)BACK OF CURB
LOT LINE
EXISTINGMOBILE HOME UNIT
EXISTING DRIVEWAY
COVEREDCARPORT
COVEREDPATIO
ELEC
EXISTING LANDSCAPE
BUILDING ENTRYACCESS STAIRS
AC UNIT AC UNIT
INSTALL NEW 200AMP SUB-PANEL
EXISTING ELECTRICALMETER PEDESTALEXISTING BRANCH CIRCUITS SHALL BE MOVEDFROM EXISTING PEDESTAL TO NEW PANEL.
INSTALL 2-1/2" SCH 40 PVCCONDUIT W/ 18" MIN. DEPTH OF
COVER. CONNECT TO EXISTING ATPEDESTAL PAD AND CONTINUE TO
REAR OF MOBILE HOME LOT.
LANDSCAPE TO BERESTORED WITHINTRENCH LIMITS.
INSTALL 24"RADIUS PVC
SWEEP
CITY OFBOULDER CITY, NV
PUBLIC WORKSDEPARTMENT
ENGINEERINGDIVISION
STANDARD DRAWINGELECTRICAL INFRASTRUCTURE REQUIREMENTS
CREATED BY:M. GRIMESISSUE DATE:
02/20/18FILE NAME:BC-MH-Tie-in.dwgSHEET:
1 OF 7
ELECTRICAL INFRASTRUCTURE - MOBILE HOME TIE-INPEDESTAL TO MOBILE HOME - PLAN VIEW
INSTALL 200 AMP DOUBLE METER SERVICE PEDESTAL ONEXISTING CONCRETE PAD. METERS SHALL FACE TOWARDSSERVICE RESIDENCES.
DOUBLE METER PEDESTALNOT TO SCALE
ELEC
EXISTING LANDSCAPE
INSTALL (2) 2-1/2" SCH 40 PVCCONDUIT W/ 18" MIN. DEPTH OF
COVER. CONNECT TO EXISTING ATPEDESTAL PAD AND CONTINUE TOREAR OF EACH MOBILE HOME LOT.
LANDSCAPE TO BERESTORED WITHINTRENCH LIMITS.
EXISTINGMOBILE HOME UNIT
BACK OF CURB
EXISTING DRIVEWAY
COVEREDCARPORT
BUILDING ENTRYACCESS STAIRS
EXISTINGMOBILE HOME UNIT
COVEREDPATIO
AC UNIT
INSTALL NEW 200AMP SUB-PANEL
AC UNIT
INSTALL NEW 200 AMPSUB-PANEL
EXISTING ELECTRICALMETER PEDESTAL
EXISTING BRANCH CIRCUITS SHALL BE MOVEDFROM EXISTING PEDESTAL TO NEW PANEL.
EXISTING ELECTRICALMETER PEDESTAL
LOT LINE
EXISTING J-BOX (WHEN APPLICABLE)
INSTALL 24"RADIUS PVCSWEEP
CITY OFBOULDER CITY, NV
PUBLIC WORKSDEPARTMENT
ENGINEERINGDIVISION
STANDARD DRAWINGELECTRICAL INFRASTRUCTURE REQUIREMENTS
CREATED BY:M. GRIMESISSUE DATE:
02/20/18FILE NAME:BC-MH-Tie-in.dwgSHEET:
2 OF 7
ELECTRICAL INFRASTRUCTURE - MOBILE HOME TIE-INPEDESTAL TO MOBILE HOME - PLAN VIEW
SINGLE METER PEDESTALNOT TO SCALE
DOUBLE METER PEDESTALNOT TO SCALE
INSTALL 200 AMP DOUBLE METER SERVICEPEDESTAL ON EXISTING CONCRETE PAD.METERS SHALL FACE TOWARDS SERVICERESIDENCES.
COVERED PATIOEXISTING MOBILEHOME UNIT
LOT L
INE
EXISTING GROUNDING CONDUCTOR
COVERED PATIOCOVERED CARPORTEXISTING MOBILEHOME UNIT
EXISTING MOBILEHOME UNIT
LOT L
INE
INSTALL 200 AMP SINGLE METER SERVICE PEDESTALON EXISTING CONCRETE PAD. METER SHALL FACE
TOWARDS SERVICE RESIDENCE.
EXISTINGDRIVEWAY
CONNECT TO EXISTING CONDUITSAT PEDESTAL PAD AND INSTALL2-1/2" SCH 40 PVC CONDUIT.
EXISTING MOBILEHOME UNIT COVERED CARPORT
EXISTINGDRIVEWAY
CONNECT TO EXISTING CONDUIT AT PEDESTALPAD AND INSTALL 2-1/2" SCH 40 PVC CONDUIT.
EXISTING GROUNDING ROD
EXISTING GROUNDING ROD
EXISTING GROUNDING CONDUCTOR(CUSTOMER SIDE)
EXISTING GROUND
EXISTING GROUNDING CONDUCTOR(CUSTOMER SIDE)
CITY OFBOULDER CITY, NV
PUBLIC WORKSDEPARTMENT
ENGINEERINGDIVISION
CREATED BY:M. GRIMESISSUE DATE:
02/20/18FILE NAME:BC-MH-Tie-in.dwgSHEET:
3 OF 7
ELECTRICAL INFRASTRUCTURE - MOBILE HOME TIE-INPEDESTAL TO MOBILE HOME - ELEVATION VIEW (FRONT)
STANDARD DRAWINGELECTRICAL INFRASTRUCTURE REQUIREMENTS
DOUBLE METER PEDESTALNOT TO SCALE
COVERED PATIOEXISTING MOBILE
HOME UNIT
LOT L
INE
EXISTINGGROUND
COVERED PATIO
EXISTING MOBILEHOME UNIT
LOT L
INE
EXISTING GROUND
AC UNIT
AC UNIT
INSTALL NEW 200 AMPSUB-PANEL
COVERED CARPORTEXISTING MOBILE
HOME UNIT
EXISTINGDRIVEWAY
AC UNIT
INSTALL NEW200 AMPSUB-PANEL
INSTALL 18" RADIUSPVC SWEEP
INSTALL 18" RADIUSPVC SWEEPINSTALL 2-1/2" SCH 40 PVC CONDUIT
W/ 18" MIN. DEPTH OF COVER.ROUTE NEW CONDUIT TO NEW
SUB-PANEL LOCATION.
EXISTING BRANCH CIRCUITSSHALL BE MOVED FROMEXISTING PEDESTAL TONEW SUB-PANEL.
EXISTING BRANCH CIRCUITSSHALL BE MOVED FROMEXISTING PEDESTAL TO
NEW SUB-PANEL.
18" M
IN. C
OVER
18" M
IN. C
OVER
INSTALL 2-1/2" SCH 40 PVC CONDUITW/ 18" MIN. DEPTH OF COVER.ROUTE NEW CONDUIT TO NEW
SUB-PANEL LOCATION.
SINGLE METER PEDESTALNOT TO SCALE
AC UNIT
INSTALL NEW 200 AMPSUB-PANEL
COVERED CARPORTEXISTING MOBILE
HOME UNIT
EXISTINGDRIVEWAY
INSTALL 18" RADIUSPVC SWEEP
EXISTING BRANCH CIRCUITSSHALL BE MOVED FROMEXISTING PEDESTAL TONEW SUB-PANEL.
CITY OFBOULDER CITY, NV
PUBLIC WORKSDEPARTMENT
ENGINEERINGDIVISION
CREATED BY:M. GRIMESISSUE DATE:
02/20/18FILE NAME:BC-MH-Tie-in.dwgSHEET:
4 OF 7
ELECTRICAL INFRASTRUCTURE - MOBILE HOME TIE-INPEDESTAL TO MOBILE HOME - ELEVATION VIEW (BACK)
STANDARD DRAWINGELECTRICAL INFRASTRUCTURE REQUIREMENTS
EXISTING MOBILE HOME UNIT
ACCESSORYBUILDING
FINISH GRADE
FINISH GRADE
FRONT BACK
EXISTING BRANCH CIRCUITSSHALL BE MOVED FROMEXISTING PEDESTAL TONEW SUB-PANEL.
EXISTINGELECTRICALMETERPEDESTAL
INSTALL 200AMP SUB-PANEL
AC UNIT
SEE SHEET 6 FOR DETAILSON SUB-PANEL BASE AND
SUPPORT STRUCTURE
UNISTRUT SUPPORTSTRUCTURE
NEW 2-1/2" CONDUIT FROMNEW METER PEDESTAL
EXISTING BRANCH CIRCUITSMOVED FROM EXISTINGMETER PEDESTAL. CIRCUITSSHALL BE IN CONDUIT.
ALL CONDUITS SHALL BE RIGIDFROM GROUND LEVEL TOSUB-PANEL CONNECTION
CIT
Y O
FB
OU
LD
ER
CIT
Y,
NV
PU
BL
IC W
OR
KS
DE
PA
RT
ME
NT
EN
GIN
EE
RIN
GD
IVIS
ION
CREA
TED
BY:
M. G
RIM
ESIS
SUE
DATE
:
02/2
0/18
FILE
NAM
E:BC
-MH-
Tie-
in.d
wg
SHEE
T: 5 O
F 7
ELEC
TRICA
L INF
RAST
RUCT
URE
- MOB
ILE H
OME T
IE-IN
MOB
ILE H
OME
- ELE
VATIO
N VI
EW (S
IDE)
STAN
DARD
DRA
WIN
GEL
ECTR
ICAL
INFR
ASTR
UCT
URE
REQ
UIR
EMEN
TS
NEW SUB-PANEL (FRONT)NOT TO SCALE
NEW SUB-PANEL SIDENOT TO SCALE
NEW SUB-PANEL. EATONMODEL No. BR1224L200R
OR APPROVED EQUAL
VERTICAL UNISTRUTSUPPORTS
1 5/8" x 1 5/8"(BEHIND PANEL)
UNISTRUT SUPPORTS.CONTRACTOR TOCONSTRUCT SUPPORTSYSTEM TOADEQUATELY HANGPANEL. SHOPDRAWINGS REQUIREDFOR APPROVAL. ALLUNISTRUTS MUST BEGALVANIZED.
CONCRETE BASE FORUNISTRUT SUPPORTS.
SHOP DRAWINGREQUIRED.
BRANCH CIRCUITS MOVED FROM EXISTING PEDESTAL.NEW RIGID CONDUIT MAY VARY IN SIZE
AND NUMBER BASED ON EXISTING CONDITIONS.(BOTTOM KNOCKOUTS - 1/2" MIN / 1.5" MAX)
NEW 2-1/2" RIGID CONDUIT.CONTRACTOR TO PULL
WIRING FROM NEWPEDESTAL TO NEW
SUB-PANEL.2" MIN. 2" MIN.
18" M
IN.
2" MIN.
14.31" 5.19"
6" MIN. 6" MIN.
HORIZONTAL UNISTRUTSUPPORTS - 1 5/8" x 1 5/8"(BEHIND PANEL)
18" M
IN.
6" MIN.
SIDE KNOCKOUTS(2 1/2" MAX)
EXISTINGGROUND
EXISTINGGROUND
18" RADIUS PVC SWEEP
PANE
L INS
TALL
HEIG
HT PE
R NEC
.24
" FRO
M G
ROUN
D M
IN.
18.75
"
CITY OFBOULDER CITY, NV
PUBLIC WORKSDEPARTMENT
ENGINEERINGDIVISION
CREATED BY:M. GRIMESISSUE DATE:
02/20/18FILE NAME:BC-MH-Tie-in.dwgSHEET:
6 OF 7
ELECTRICAL INFRASTRUCTURE - MOBILE HOME TIE-INPANEL SUPPORT STRUCTURE DETAILS
STANDARD DRAWINGELECTRICAL INFRASTRUCTURE REQUIREMENTS
GENERAL NOTES:1. ALL INFRASTRUCTURE FROM THE METER PEDESTAL TO THE MOBILE HOME SHALL BE CONSIDERED "PRIVATE" AND WILL BECOME THE RESPONSIBILITY OF THE
MOBILE HOME PARK OR LOT OWNER. A ONE YEAR WARRANTY WILL APPLY TO ALL INSTALLED INFRASTRUCTURE. ALL INFRASTRUCTURE PRIOR TO THE METERPEDESTAL, INCLUDING THE ELECTRIC METER, IS CONSIDERED "PUBLIC". THE CITY OF BOULDER CITY WILL BE RESPONSIBLE FOR THE MAINTENANCE ANDOPERATION OF ALL PUBLIC INFRASTRUCTURE.
2. ALL ELECTRICAL INFRASTRUCTURE SHALL MEET ALL APPLICABLE CODE REQUIREMENTS OF THE 2012 EDITION OF THE NATIONAL ELECTRIC CODE (NEC).3. CONTRACTOR SHALL OBTAIN ALL APPLICABLE BUILDING PERMITS AND REGULATIONS AS REQUIRED BY THE BOULDER CITY COMMUNITY DEVELOPMENT
DEPARTMENT, BUILDING INSPECTIONS DIVISION (702-293-9282).4. CONTRACTOR TO INSTALL A 200 AMP SINGLE OR DOUBLE ELECTRICAL METER SERVICE PEDESTAL WITH PAD MOUNTING BRACKET. METER SERVICE PEDESTAL
TYPE SHALL BE PER PROJECT PLANS OR AS INDICATED BY THE DESIGNATED CITY PROJECT REPRESENTATIVE.a. 200 AMP SINGLE METER PEDESTAL - MILBANK MODEL No. U5242-O-200Sb. 200 AMP DOUBLE METER PEDESTAL - MILBANK MODEL No. MPAPD-200-MB-78-PDc. PAD MOUNTING BRACKET (SINGLE) - MILBANK MODEL No. K5410d. PAD MOUNTING BRACKET (DOUBLE) - MILBANK MODEL No. MP-PDMT-KITe. CHASEWAY COVER (SINGLE) - MILBANK MODEL No. K5745f. CHASEWAY COVER (DOUBLE) - MILBANK No. K6390
5. CONTRACTOR SHALL INSTALL SERVICE PEDESTAL MOUNTING BRACKET SO THE METER WILL FACE TOWARDS THE RESIDENCE BEING SERVICED.6. DRIVEWAY PATCHING:
a. ASPHALT - 4' WIDE MINIMUM PATCH PERPENDICULAR ACROSS DRIVEWAY.b. CONCRETE - REMOVE AND REPLACE ALL CONCRETE, IN LIKE-KIND, FROM JOINT TO JOINT.
7. ALL GROUNDING CONDUCTORS SHALL BE #4 STRANDED BARE COPPER WIRE. 20' OF WIRE COILED WITHIN THE SERVICE PEDESTAL, 5' OF WIRE COILED ABOVETHE PEDESTAL FOR PEDESTAL ATTACHMENT.
8. ALL CONDUITS SHALL HAVE PULLSTRING INSTALLED AND POLYPLUG OR CAP INSERTED ON EACH END PRIOR TO CABLE INSTALLATION.9. CABLING MUST BE PULLED FROM EXISTING J-BOX OR TRANSFORMER TO EACH METERING PEDESTAL. CABLE TYPE, SIZE, CONNECTIONS, TERMINATIONS, ETC.
ARE PER CITY OF BOULDER CITY ELECTRICAL STANDARDS.10. PERSONNEL FROM THE CITY OF BOULDER CITY PUBLIC WORKS DEPARTMENT, ELECTRIC DIVISION MAY NEED TO BE ON STANDBY WHEN CONNECTING TO
EXISTING EQUIPMENT. 48 HOUR MINIMUM NOTICE. CALL 702-293-9200 TO SCHEDULE.11. ALL LANDSCAPING DISTURBED DUE TO THE CONTRACTOR'S OPERATIONS SHALL BE RESTORED. ANY PLANTS, SHRUBS, GROUNDCOVER, OR HARDSCAPE
REMOVED FOR INSTALLATION OF CONDUIT SHALL BE REPLACED IN LIKE-KIND.12. ANY BUILDING SKIRT REMOVED OR DAMAGED DURING THE CONTRACTOR'S OPERATION SHALL BE REPLACED IN LIKE-KIND.13. TO MINIMIZE POWER OUTAGE TIME, ALL NEW INFRASTRUCTURE AS DEPICTED ON THESE DRAWINGS SHALL BE IN PLACE PRIOR TO SWITCHING THE RESIDENCE
OVER TO THE NEW POWER SYSTEM .14. AS SOME RESIDENTS DEPEND ON THE POWER FOR MEDICAL REASONS, THE CONTRACTOR MUST NOTIFY AND SCHEDULE WITH THE RESIDENT PRIOR TO
SWITCHING POWER TO THE NEW SYSTEM. PARK MANAGEMENT AND THE CITY OF BOULDER CITY MUST ALSO BE NOTIFIED OF THE SCHEDULE AS WELL. THECONTRACTOR SHALL HAVE A PLAN IN PLACE FOR BACK UP POWER OR ACCOMMODATIONS TO THE RESIDENT SHOULD UNFORESEEN ISSUES ARISE.
15. METERS TO BE INSTALLED IN PEDESTALS SHALL BE COORDINATED WITH CITY OF BOULDER CITY PUBLIC WORKS DEPARTMENT, ELECTRIC DIVISION. CALL702-293-9200 TO COORDINATE.
16. AS ELECTRICAL NEEDS AT EACH RESIDENCE WILL VARY, CONTRACTOR IS TO BID ACCORDINGLY.
CITY OFBOULDER CITY, NV
PUBLIC WORKSDEPARTMENT
ENGINEERINGDIVISION
CREATED BY:M. GRIMESISSUE DATE:
02/20/18FILE NAME:BC-MH-Tie-in.dwgSHEET:
7 OF 7
ELECTRICAL INFRASTRUCTURE - MOBILE HOME TIE-INGENERAL NOTES
STANDARD DRAWINGELECTRICAL INFRASTRUCTURE REQUIREMENTS