LT Panels
Supply , erection , testing and commissioning of cubicle floor mounting type distribution
panels fabricated in standard sections comprising of TPN Aluminium busbars of suitable
current rating for main and interconnecting busbars with busbars of equal size in all
phases with Full the size of phase as neutral made out of 2mm thick sheet steel for load
bearing mebers and 1.6mm thick sheet steel for non load bearing members, reinforced
angle iron frame work equipped with busbar chambers and cable chamber. The panel
shall be designed for IP42 unless otherwise specified. The power control centre shall
comprise incoming and outgoing air circuit breakers / MCCBs as given below
including all accessories like fuses interlocks etc. The incoming ACB shall be designed
for busduct entry. The incoming / outgoing ACB / MCCB shall be suitable for bottom
/ top entry only. All outgoing feeders shall be suitable for connecting GI armoured cable
and with suitable gland plate of removable type . The distribution panel shall be complete
with earthing feeder identification markers, cable identifications, danger caution boards ,
floor mounting channels .The complete board shall be manufactured as per the
standard practice & shall meet the requirements of Local CEIG and other relevant
authorities . The rate shall be for the complete board including supply of all components ,
hardwares etc. including all connected civil works & as per specifications. Nos 1
Incomer
800 Amps Breaker MDO
Microprocessor based protection release with adjustable over load, adjustable short
circuit with adjustable time delay, instantaneous short circuit ( >15 In), adustable earth
fault with adjustable time delay protection, external CT for earth fault protection. Motor /
closing coil / shunt trip coil shall be 230V AC. Under voltage coil shall be 415V/220V AC, safety
shutter & door interlock shall be provided.
1 no. of Electronic energy meter with RS485 communication port, Nos 1
MCCB
Outgoing 630 Amps MCCB
O/C ,S/S ,E/F WITH METRING METER WITH ANALOG AMMETER AND VOLTMETER Nos 1
250Amps Nos 2
O/C ,S/S ,E/F WITH METRING METER WITH ANALOG AMMETER AND VOLTMETER
100 amps MCCB Nos 8
O/C ,S/S ,E/F WITH METRING METER WITH ANALOG AMMETER AND VOLTMETER
Supply , erection , testing and commissioning of cubicle floor mounting type distribution
panels fabricated in standard sections comprising of TPN Aluminium busbars of suitable
current rating for main and interconnecting busbars with busbars of equal size in all
phases with Full the size of phase as neutral made out of 2mm thick sheet steel for load
bearing mebers and 1.6mm thick sheet steel for non load bearing members, reinforced
angle iron frame work equipped with busbar chambers and cable chamber. The panel
shall be designed for IP42 unless otherwise specified. The power control centre shall
comprise incoming and outgoing air circuit breakers / MCCBs as given below
including all accessories like fuses interlocks etc. The incoming ACB shall be designed
for busduct entry. The incoming / outgoing ACB / MCCB shall be suitable for bottom
/ top entry only. All outgoing feeders shall be suitable for connecting GI armoured cable
and with suitable gland plate of removable type . The distribution panel shall be complete
BOQ for LT panels
with earthing feeder identification markers, cable identifications, danger caution boards ,
floor mounting channels .The complete board shall be manufactured as per the
standard practice & shall meet the requirements of Local CEIG and other relevant
authorities . The rate shall be for the complete board including supply of all components ,
hardwares etc. including all connected civil works & as per specifications.
630 Amps MCCB microprocesor based Nos 1
1 no. of Electronic energy meter with RS485 communication port
O/C ,S/S ,E/F WITH METRING METER WITH ANALOG AMMETER AND VOLTMETER
250 Amps MCCB thermoelectric based Nos 2
Outgoing 100 Amps MCCB Thermoelectric based Nos 6
Outgoing 63 Amps MCCB thermoelectric based Nos 2