Evolution of Facebook’sdata center design

Veerendra Mulay, PhDStrategic Engineering and Development

Page 3: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

1 Introduction

2 Electrical design

3 Mechanical design

4 Design evolution

5 RDDC

Agenda

Page 4: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Introduction

Page 5: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Facebook Greenfield DatacenterGoal Design and build the most efficient datacenter eco-system possible

Control Application Server configuration Datacenter design

Sites Prineville, OR Forest City, NC Luleå, Sweden Altoona, IA

Page 6: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Prineville, OR

Page 7: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Forest City, NC

Page 8: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Luleå, Sweden

Page 9: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Altoona, IA

Page 10: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Electrical design

Page 11: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Electrical Overview Eliminate 480V to 208V transformation Used 480/277VAC distribution to IT equipment

Remove centralized UPS Implemented 48VDC UPS System

Result a highly efficient electrical system and small failure domain

Page 12: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Typical Power Prineville Power

Utility Transformer480/277 VAC

99.999%Availability

Total loss up to server:

2% loss

6% - 12% loss

3% loss

208/120VAC

AC/DC

DC/AC

ASTS/PDU

SERVER PS

StandbyGenerator

10% loss(assuming 90% plus PS)

Utility Transformer480/277 VAC

99.9999% Availability

2% loss

480/277VAC

Total loss up to server:

FB SERVER PS

StandbyGenerator

48VDC DC UPS(Stand-by)

5.5% loss

UPS480VAC

21% to 27% 7.5%

Page 13: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

DC UPS Backup Scheme

Server PS

Back-up Converter

48VDC-12VDC

AC to DC

277VAC-12VDC

12VDC

MOBO

48VDC Standby

277VAC48VDC

Battery Charger

4x12V Batt

4x12V Batt

4x12V Batt

4x12V Batt

4x12V Batt

48VDC Battery CabinetNormal Power

Backup Power

Page 14: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Battery Cabinet

Custom DC UPS

56kW or 85kW

480VAC, 3-phase input

45 second back-up

20 sealed VRLA batteries

Battery Validation System

Six 48VDC Output

Two 50A 48VDC aux outputs

Page 15: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Reactor Power Panel Custom Fabricated RPP

Delivers 165kW, 480/277V, 3-phase to CAB level

Contains Cam-Lock connector for maintenance wrap around

Line Reactor

Reduces short circuit current < 10kA

Corrects leading power factor towards unity (3% improvement)

Reduces THD for improved electrical system performance (iTHD 2% improvement)

Power consumption = 360 Watt

Page 16: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Mechanical design

Page 17: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Overview

Removed Centralized chiller plant HVAC ductwork

System Basis of Design ASHRAE Weather Data: N=50 years TC9.9 2008: Recommended Envelopes

Built-up penthouse air handling system

Server waste heat is used for office space heating

Page 18: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Typical Datacenter Cooling

Forest City Datacenter Cooling

Ductless Return Air

Fan Wall

Misting System

100% Outside Air Intake

DUCTLESSSUPPLY

Return Air

Filter Wall

Return Air Plenum

Ductless Relief Air

Relief Air

DATA CENTER

SUPPLY DUCT

CT CHILLER AHUDATA CENTER

Return Ductwork

DX System

Prineville Datacenter Cooling

Page 19: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Fan Wall

Misting System

100% Outside

Air Intake

Hot AisleReturn Air

Filter Wall

Relief Air Corridor

CommonReturn Air Plenum

Relief Air Fan

Supply Air Corridor

Data Center

Mixed Air Corridor

Server Cabinets

Server Cabinets

Hot Aisle

Hot Aisle Relief Air

Hot AisleCommonCold Aisle

PRN1 Datacenter Cooling

Page 20: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Outside air intake corridorVertical drainable louvers

Page 21: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Air mixing section Evaporative cooling / humidification corridor

Page 22: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

DX Cooling CoilForest City Only

50 year extreme weather conditions

Page 23: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design
Page 24: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design
Page 25: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Fan array outlet / supply air corridorFan wall array inlet corridor

Page 26: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Cold aisle pressurization –ductless supply

Page 27: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design
Page 28: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design
Page 29: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Design evolution

Page 30: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

80ºF inlet

65% humidity

20ºF ΔT

PRN1A1B

85ºF inlet

80% humidity

22ºF ΔT

85ºF inlet

90% humidity

22ºF ΔT

85ºF inlet

80% humidity

22ºF ΔT

PRN1C1D FRC1A1B LLA1A1B

Basis of Design Comparison

Page 31: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Wetted Media

Page 32: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Typical Generator Topology

Page 33: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

LLA Reduced Generator Topology

Page 34: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Rapid Deployment Data Center

Page 35: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

RDDCFLAT PACKEDPANELIZED ASSEMBLIES

PRE MANUFACTURED UNIT ASSEMBLIES

Page 36: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

RDDC Pre-fab Assemblies

Page 37: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

A

MECH UNITS

MECH UNITS

BELECSKIDS

MECH UNITS

MECH UNITS

RDDC building plans

Page 38: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

RDDC

▪ Unitized IT Modules

Page 39: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

RDDC

▪ Section

Unit IT Unit IT a b c

Page 40: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

RDDC

▪ Power Modules

Page 41: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Luleå, Sweden

Page 42: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

RDDC Flat Pack Solution

Page 43: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

RA

CK

RA

CK

16’-0”16’-0”

14’-0

”14

’-0”

12’-0”12’-0”

Flat pack solution

Page 44: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Flat pack solution

Page 45: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

RA

CK

RA

CK

Flat pack solution

Page 46: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

Leaner simplification

Page 47: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design
Page 48: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

ALTOONA

Page 49: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design

www.opencompute.org

Page 50: Evolution of Facebook’s - IDCQUAN.com · Evolution of Facebook’s data center design Veerendra Mulay, PhD Strategic Engineering and Development. 1 Introduction 2 Electrical design