34
Evaluation of Water Additives for Fire Control and Vapor Mitigation Two and Three Dimensional Class B Fire Tests Matthew E. Benfer and Joseph L. Scheffey March 5, 2015

Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

Evaluation of Water Additives for Fire Control and Vapor

Mitigation – Two and Three Dimensional Class B Fire

Tests

Matthew E. Benfer and Joseph L. Scheffey

March 5, 2015

Page 2: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

Phase I study conducted in 2013 evaluated water

additives for use in fire control and vapor mitigation:

Comprehensive literature review

Identification of agents marketed as water additives

Intended to clarify fire protection benefit of water

additives

Outlined performance criteria for water additives as

established in NFPA 18A

Developed test plan for deep seated Class A fires and

2D/3D Class B fire for comparative performance of

water additives

BACKGROUND

2

Page 3: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

NFPA 18 – Standard on Wetting Agents (1st Edition, 1951)

• Wetting agents reduce surface tension and increase ability to

penetrate and spread

• UL Listings

NFPA 18A – Standard on Water Additives (1st Edition,

2007)

• Water additives suppress, cool, mitigate fire and/or vapors,

and/or provides insulating properties for fuels. They also might

provide enhanced cooling, emulsification, and foaming

characteristics

• No UL Listing

UL 162 – Standard for Safety of Foam Equipment and

Liquid Concentrates

• For foams with expansion ratio of 20:1 or less and used for fire

extinguishment; film forming

BACKGROUND

3

Page 4: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

This project was carried out under a Fire Protection Research Foundation grant with the following sponsoring organizations:

David Miller, AEGIS Insurance

John Reiter, AES Global Insurance

James Biggins, Global Risk Consultants

Michael Greiner, Hazard Control Technologies

Robert Taylor, PRB Coal Users Group

Blake Shugarman, Underwriters Laboratories

Tracy Browder, Xcel Energy

Steven Behrens, XL Global Asset Protection

The Project Technical Panel also included:

Jeff Harrington, Harrington Group

Joseph Senecal, Kidde Fenwal

Don Birchler, FP&C Consultants

Benjamin Truchot, Ineris

Ken Dungan, Risk Technologies

TECHNICAL PANEL

4

Page 5: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

Coal and Power Industry

Concern that current systems unable to

provide recommended 0.3 gpm/ft2 from

NFPA 850

Interest of utilities to back fit agents into

existing systems to upgrade performance

Prior demonstrations of water additives

showed better performance than water on

2D pool fire

MOTIVATION

5

Page 6: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

To provide comparative performance

between plain water and water additives for:

• Extinguishment

• Fire control

• Threat reduction

To determine whether water additives are

effective on 3D running fuel fires

To evaluate Class B test methods for water

additives

OBJECTIVES

6

Page 7: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

Class B scenarios were of most interest

Selected scenarios associated with real-life

conditions:

• 2D pool

• 3D running fuel fire

• Combined scenario: 2D pool and 3D running fuel fire

All tests conducted at Underwriters Laboratories in

Northbrook, IL

Optimized approach used; budget restrictions

prevented full parametric assessment

Each test ran once

APPROACH

7

Page 8: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

Selection criteria:

• Different extinguishing characteristics compared

to traditional foams

• UL listed as Wetting Agents

• NOT UL listed as Foam Liquid Concentrates

All agents tested “blind”

All agents donated by manufacturer

Three agents and water evaluated

AGENTS

8

Page 9: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

AGENTS

9

Agent

Recommended

Concentration

for Testing

UL Class B

Concentration

(NFPA 18 Wetting

Agent)

Manufacturer

Description

A 3% 6%Agent rapidly cools fire and surrounding

structures, encapsulates fuel, and interrupts

the free radical chain reaction.

B 0.5% 0.5%

Agent works by absorbing the energy of the

fire, cooling the fuel, blanketing the fuel to

eliminate oxygen, and renders Class B fuels

non-flammable.

C 6% 6%

Agent works by encapsulating the oxygen

molecules to starve the fire, chemically

shearing hydrocarbon strings to render the

fuel inert. Agent acts as a scrubber,

knocking smoke and soot to the ground.

Page 10: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

Modified UL 162 sprinkler test

• Test pan: 50 ft2 (7.07 ft x 7.07 ft)

• Nozzles: 15 ft to centerline of piping

• Sprinkler grid: 4 sprinklers near corners of pan

• Upright, open-head sprinklers used

Rationale

• Sprinkler test design vs. water

spray/optimized approach

• Closely resembles an actual installation

• Readily available and used by the test lab

WATER ADDITIVE SYSTEM

10

Page 11: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

WATER ADDITIVE SYSTEM

11

Page 12: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

Application rates varied by changing spacing, k-

factor, and pressure

Agents pre-mixed (by weight), pumped from 2,000

gal reservoir

Water provided by UL fire pumps

0.3 gpm/ft2 baseline (ordinary hazard application

rate)

WATER ADDITIVE SYSTEM

12

Application

Rate

(gpm/ft2)

Sprinkler

Spacing

(ft)

k-factor of

sprinkler

(gpm/psi1/2)

Approx. Nozzle

Pressure

(psi)

Nominal

Flowrate of 4

Sprinklers

(gpm)

0.16 12 5.6 17 92

0.22 12 8.0 16 128

0.30 10 8.0 14 120

0.45 10 8.0 32 180

Page 13: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

FIRE SCENARIOS

2D Pan

3D Running Fuel Cascade

Combined 2D Pan + 3D

Cascade

13

Page 14: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

FIRE SCENARIOS

Small amount of heptane used to initiate fire

Pre-Burn Times:• 2D Pan

– 30 seconds after full involvement of pan

• 3D Cascade – 1 minute after cascade pan fully involved, then fuel flow

initiated

– 30 seconds after cascade trays fully involved

• Combined 2D Pan and 3D Cascade– 1 minute after cascade pan fully involved, 2D pan lit and

fuel flow initiated

– 30 seconds after cascade trays fully involved, suppression system activated.

14

Page 15: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

Application Rate

90% Control Time (Visually Assessed)• 2D Fire – 90% of pan area

extinguished

• 3D Fire - (a) no trays burning, fire just in cascade pan; or, (b) if bottom cascade pan extinguished, fire on just one tray

• 2D/3D Fire - both the 2D and 3D criteria achieved

Extinguishment Time

(Visually Assessed)

Flame Height Reduction

Heat Flux Reduction

MEASURES OF PERFORMANCE

15

2D+3D

3D

2D

Page 16: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

Flame height indicator in plane of pan

IR camera

Two video cameras

Total heat flux gauges (10 ft and 20 ft from

pan edge)

Thermocouples near ceiling

Flowrate through sprinkler piping

INSTRUMENTATION

16

Page 17: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

RESULTS – 2D PAN

17

Page 18: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

All three agents and water tested at 0.3

gpm/ft2

• All agents extinguished the fire at this rate

• Water only able to achieve 90% control

All agents significantly quicker than water for• Achieving 90% control

• Reducing flame height and heat flux by 90%

Water extinguished at 0.45 gpm/ft2

Agents B and C successful at 0.16 gpm/ft2

Agent A successful at 0.22 gpm/ft2

RESULTS – 2D PAN

18

Page 19: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

RESULTS – 2D PAN

19

Test Agent

Sprinkler

Application

Rate

(gpm/ft2)

Extinguished?

Time to

90%

Control

(sec)

Time to

Extinguishment

(sec)

Time to

90% Flame

Height

Reduction

(sec)

Time to

90%

Reduction

in Heat

Flux – 10ft

(sec)

2 Water 0.45 Yes 85 153 35 23

1 Water 0.3 No 480 NA 510 191

3 A 0.3 Yes 131 157 80 17

8 B 0.3 Yes 39 50 50 18

15 C 0.3 Yes 22 29 29 16

7 A 0.22 Yes 180 243 215 19

6 A 0.16 No NA NA NA 40

11 B 0.16 Yes 95 98 100 23

18 C 0.16 Yes 43 62 29 29

Page 20: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

RESULTS – 2D PAN

20

Test Agent

Sprinkler

Application

Rate

(gpm/ft2)

Extinguished?

Time to

90%

Control

(sec)

Time to

Extinguishment

(sec)

Time to

90% Flame

Height

Reduction

(sec)

Time to

90%

Reduction

in Heat

Flux – 10ft

(sec)

2 Water 0.45 Yes 85 153 35 23

1 Water 0.3 No 480 NA 510 191

3 A 0.3 Yes 131 157 80 17

8 B 0.3 Yes 39 50 50 18

15 C 0.3 Yes 22 29 29 16

7 A 0.22 Yes 180 243 215 19

6 A 0.16 No NA NA NA 40

11 B 0.16 Yes 95 98 100 23

18 C 0.16 Yes 43 62 29 29

Page 21: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

RESULTS – 2D PAN (Test 15)

21

Page 22: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

RESULTS – 3D CASCADE

22

Page 23: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

All three agents and water tested at 0.3

gpm/ft2

• Only Agent B extinguished the fire at this rate

• Agent C able to achieve 90% control

Water unable to achieve 90% control at

0.45 gpm/ft2

Agent C also tested at 0.22 gpm/ft2

• Unable to control or extinguish

All agents and water at all flow rates able

to reduce heat flux by 90%

RESULTS – 3D CASCADE

23

Page 24: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

RESULTS – 3D CASCADE

24

Test Agent

Sprinkler

Application

Rate

(gpm/ft2)

Extinguished?

Time to

90%

Control

(sec)

Time to

Extinguishment

(sec)

Time to

90% Flame

Height

Reduction

(sec)

Time to

90%

Reduction

in Heat

Flux – 10ft

(sec)

14 Water 0.45 No NA NA 314 44

13 Water 0.3 No NA NA NA 222

4 A 0.3 No NA NA NA 42

9 B 0.3 Yes 264 274 160 49

16 C 0.3 No 275 NA 150 52

19 C 0.22 No NA NA 365 252

Page 25: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

RESULTS – 3D CASCADE

25

Test Agent

Sprinkler

Application

Rate

(gpm/ft2)

Extinguished?

Time to

90%

Control

(sec)

Time to

Extinguishment

(sec)

Time to

90% Flame

Height

Reduction

(sec)

Time to

90%

Reduction

in Heat

Flux – 10ft

(sec)

14 Water 0.45 No NA NA 314 44

13 Water 0.3 No NA NA NA 222

4 A 0.3 No NA NA NA 42

9 B 0.3 Yes 264 274 160 49

16 C 0.3 No 275 NA 150 52

19 C 0.22 No NA NA 365 252

Page 26: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

RESULTS – COMBINED 2D

PAN AND 3D CASCADE

26

Page 27: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

All three agents tested at 0.3 gpm/ft2

• Agents B and C extinguished the fire at this rate

• Agent A was not able to achieve 90% control

• Water alone was not tested

Agent B tested at 0.22 gpm/ft2

• Unable to achieve 90% control

All agents at all flow rates able to

reduce heat flux by 90%

RESULTS – 2D PAN & 3D CASCADE

27

Page 28: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

RESULTS – 2D PAN & 3D CASCADE

28

Test Agent

Sprinkler

Application

Rate

(gpm/ft2)

Extinguished?

Time to

90%

Control

(sec)

Time to

Extinguishment

(sec)

Time to

90% Flame

Height

Reduction

(sec)

Time to

90%

Reduction

in Heat

Flux – 10ft

(sec)

5 A 0.3 No NA NA NA 129

10 B 0.3 Yes 320 329 70 69

17 C 0.3 Yes 185 197 196* 129

12 B 0.22 No NA NA 458 88

* - Interpolated

Page 29: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

AGENT CHARACTERISTICS

29

A

B

C

Page 30: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

EXTINGUISHMENT COMPARISON

30

Agent

Agent

Concentration

Lowest Application Rate with

Extinguishment

(gpm/ft2)

2D 3D 2D+3D

Water - 0.45DNE

(0.45)NT

A 3% 0.22DNE

(0.3)

DNE

(0.3)

B 0.5% 0.16 0.3 0.3

C 6% 0.16DNE

(0.3)A 0.3

DNE – Did not extinguish (highest application rate tested in parentheses).

NT – Not tested.

A – Test at 0.3 gpm/ft2 achieved 90% control.

Page 31: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

Test scenarios acceptable

2D Fire extinguished by all agents and

water.

• 0.45 gpm/ft2 water application rate greater than

0.25 gpm/ft2 NFPA 850 baseline for boiler front oil

fires

Water failed to extinguish 3D and 2D+3D

fire scenarios

Two of the three agents extinguished fires

including the 3D cascade

CONCLUSION

31

Page 32: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

Water additives provided quicker

reduction in thermal threats compared

to water

Water additives superior to plain water

Performance differences observed

between the water additives tested• Possibly attributed to different physio-chemical properties

(evaluation out of scope)

CONCLUSION

32

Page 33: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.com

The authors would like to thank the NFPA Research

Foundation personnel and project Technical Panel for

their assistance in guiding the test planning and

advising the test group.

The authors would like to also thank the water additive

manufacturers for the donations of their agents for

testing. In addition, the authors would like to thank the

staff at the Underwriters Laboratory Fire Test Lab for

their facility and support in testing.

ACKNOWLEDGEMENTS

33

Page 34: Evaluation of Water Additives for Fire Control and Vapor … · 2019. 7. 19. · NFPA 18 –Standard on Wetting Agents (1st Edition, 1951) •Wetting agents reduce surface tension

www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com

ContactMatthew E. Benfer

+1 410-737-8677

[email protected]

For More Information Visit

www.jensenhughes.com

QUESTIONS?

34