Upload
others
View
6
Download
0
Embed Size (px)
Citation preview
Evaluation of Water Additives for Fire Control and Vapor
Mitigation – Two and Three Dimensional Class B Fire
Tests
Matthew E. Benfer and Joseph L. Scheffey
March 5, 2015
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
Phase I study conducted in 2013 evaluated water
additives for use in fire control and vapor mitigation:
Comprehensive literature review
Identification of agents marketed as water additives
Intended to clarify fire protection benefit of water
additives
Outlined performance criteria for water additives as
established in NFPA 18A
Developed test plan for deep seated Class A fires and
2D/3D Class B fire for comparative performance of
water additives
BACKGROUND
2
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
NFPA 18 – Standard on Wetting Agents (1st Edition, 1951)
• Wetting agents reduce surface tension and increase ability to
penetrate and spread
• UL Listings
NFPA 18A – Standard on Water Additives (1st Edition,
2007)
• Water additives suppress, cool, mitigate fire and/or vapors,
and/or provides insulating properties for fuels. They also might
provide enhanced cooling, emulsification, and foaming
characteristics
• No UL Listing
UL 162 – Standard for Safety of Foam Equipment and
Liquid Concentrates
• For foams with expansion ratio of 20:1 or less and used for fire
extinguishment; film forming
BACKGROUND
3
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
This project was carried out under a Fire Protection Research Foundation grant with the following sponsoring organizations:
David Miller, AEGIS Insurance
John Reiter, AES Global Insurance
James Biggins, Global Risk Consultants
Michael Greiner, Hazard Control Technologies
Robert Taylor, PRB Coal Users Group
Blake Shugarman, Underwriters Laboratories
Tracy Browder, Xcel Energy
Steven Behrens, XL Global Asset Protection
The Project Technical Panel also included:
Jeff Harrington, Harrington Group
Joseph Senecal, Kidde Fenwal
Don Birchler, FP&C Consultants
Benjamin Truchot, Ineris
Ken Dungan, Risk Technologies
TECHNICAL PANEL
4
www.jensenhughes.comwww.jensenhughes.com
Coal and Power Industry
Concern that current systems unable to
provide recommended 0.3 gpm/ft2 from
NFPA 850
Interest of utilities to back fit agents into
existing systems to upgrade performance
Prior demonstrations of water additives
showed better performance than water on
2D pool fire
MOTIVATION
5
www.jensenhughes.comwww.jensenhughes.com
To provide comparative performance
between plain water and water additives for:
• Extinguishment
• Fire control
• Threat reduction
To determine whether water additives are
effective on 3D running fuel fires
To evaluate Class B test methods for water
additives
OBJECTIVES
6
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
Class B scenarios were of most interest
Selected scenarios associated with real-life
conditions:
• 2D pool
• 3D running fuel fire
• Combined scenario: 2D pool and 3D running fuel fire
All tests conducted at Underwriters Laboratories in
Northbrook, IL
Optimized approach used; budget restrictions
prevented full parametric assessment
Each test ran once
APPROACH
7
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
Selection criteria:
• Different extinguishing characteristics compared
to traditional foams
• UL listed as Wetting Agents
• NOT UL listed as Foam Liquid Concentrates
All agents tested “blind”
All agents donated by manufacturer
Three agents and water evaluated
AGENTS
8
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
AGENTS
9
Agent
Recommended
Concentration
for Testing
UL Class B
Concentration
(NFPA 18 Wetting
Agent)
Manufacturer
Description
A 3% 6%Agent rapidly cools fire and surrounding
structures, encapsulates fuel, and interrupts
the free radical chain reaction.
B 0.5% 0.5%
Agent works by absorbing the energy of the
fire, cooling the fuel, blanketing the fuel to
eliminate oxygen, and renders Class B fuels
non-flammable.
C 6% 6%
Agent works by encapsulating the oxygen
molecules to starve the fire, chemically
shearing hydrocarbon strings to render the
fuel inert. Agent acts as a scrubber,
knocking smoke and soot to the ground.
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
Modified UL 162 sprinkler test
• Test pan: 50 ft2 (7.07 ft x 7.07 ft)
• Nozzles: 15 ft to centerline of piping
• Sprinkler grid: 4 sprinklers near corners of pan
• Upright, open-head sprinklers used
Rationale
• Sprinkler test design vs. water
spray/optimized approach
• Closely resembles an actual installation
• Readily available and used by the test lab
WATER ADDITIVE SYSTEM
10
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
WATER ADDITIVE SYSTEM
11
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
Application rates varied by changing spacing, k-
factor, and pressure
Agents pre-mixed (by weight), pumped from 2,000
gal reservoir
Water provided by UL fire pumps
0.3 gpm/ft2 baseline (ordinary hazard application
rate)
WATER ADDITIVE SYSTEM
12
Application
Rate
(gpm/ft2)
Sprinkler
Spacing
(ft)
k-factor of
sprinkler
(gpm/psi1/2)
Approx. Nozzle
Pressure
(psi)
Nominal
Flowrate of 4
Sprinklers
(gpm)
0.16 12 5.6 17 92
0.22 12 8.0 16 128
0.30 10 8.0 14 120
0.45 10 8.0 32 180
www.jensenhughes.comwww.jensenhughes.com
FIRE SCENARIOS
2D Pan
3D Running Fuel Cascade
Combined 2D Pan + 3D
Cascade
13
www.jensenhughes.comwww.jensenhughes.com
FIRE SCENARIOS
Small amount of heptane used to initiate fire
Pre-Burn Times:• 2D Pan
– 30 seconds after full involvement of pan
• 3D Cascade – 1 minute after cascade pan fully involved, then fuel flow
initiated
– 30 seconds after cascade trays fully involved
• Combined 2D Pan and 3D Cascade– 1 minute after cascade pan fully involved, 2D pan lit and
fuel flow initiated
– 30 seconds after cascade trays fully involved, suppression system activated.
14
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
Application Rate
90% Control Time (Visually Assessed)• 2D Fire – 90% of pan area
extinguished
• 3D Fire - (a) no trays burning, fire just in cascade pan; or, (b) if bottom cascade pan extinguished, fire on just one tray
• 2D/3D Fire - both the 2D and 3D criteria achieved
Extinguishment Time
(Visually Assessed)
Flame Height Reduction
Heat Flux Reduction
MEASURES OF PERFORMANCE
15
2D+3D
3D
2D
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
Flame height indicator in plane of pan
IR camera
Two video cameras
Total heat flux gauges (10 ft and 20 ft from
pan edge)
Thermocouples near ceiling
Flowrate through sprinkler piping
INSTRUMENTATION
16
www.jensenhughes.comwww.jensenhughes.com
RESULTS – 2D PAN
17
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
All three agents and water tested at 0.3
gpm/ft2
• All agents extinguished the fire at this rate
• Water only able to achieve 90% control
All agents significantly quicker than water for• Achieving 90% control
• Reducing flame height and heat flux by 90%
Water extinguished at 0.45 gpm/ft2
Agents B and C successful at 0.16 gpm/ft2
Agent A successful at 0.22 gpm/ft2
RESULTS – 2D PAN
18
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
RESULTS – 2D PAN
19
Test Agent
Sprinkler
Application
Rate
(gpm/ft2)
Extinguished?
Time to
90%
Control
(sec)
Time to
Extinguishment
(sec)
Time to
90% Flame
Height
Reduction
(sec)
Time to
90%
Reduction
in Heat
Flux – 10ft
(sec)
2 Water 0.45 Yes 85 153 35 23
1 Water 0.3 No 480 NA 510 191
3 A 0.3 Yes 131 157 80 17
8 B 0.3 Yes 39 50 50 18
15 C 0.3 Yes 22 29 29 16
7 A 0.22 Yes 180 243 215 19
6 A 0.16 No NA NA NA 40
11 B 0.16 Yes 95 98 100 23
18 C 0.16 Yes 43 62 29 29
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
RESULTS – 2D PAN
20
Test Agent
Sprinkler
Application
Rate
(gpm/ft2)
Extinguished?
Time to
90%
Control
(sec)
Time to
Extinguishment
(sec)
Time to
90% Flame
Height
Reduction
(sec)
Time to
90%
Reduction
in Heat
Flux – 10ft
(sec)
2 Water 0.45 Yes 85 153 35 23
1 Water 0.3 No 480 NA 510 191
3 A 0.3 Yes 131 157 80 17
8 B 0.3 Yes 39 50 50 18
15 C 0.3 Yes 22 29 29 16
7 A 0.22 Yes 180 243 215 19
6 A 0.16 No NA NA NA 40
11 B 0.16 Yes 95 98 100 23
18 C 0.16 Yes 43 62 29 29
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
RESULTS – 2D PAN (Test 15)
21
www.jensenhughes.comwww.jensenhughes.com
RESULTS – 3D CASCADE
22
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
All three agents and water tested at 0.3
gpm/ft2
• Only Agent B extinguished the fire at this rate
• Agent C able to achieve 90% control
Water unable to achieve 90% control at
0.45 gpm/ft2
Agent C also tested at 0.22 gpm/ft2
• Unable to control or extinguish
All agents and water at all flow rates able
to reduce heat flux by 90%
RESULTS – 3D CASCADE
23
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
RESULTS – 3D CASCADE
24
Test Agent
Sprinkler
Application
Rate
(gpm/ft2)
Extinguished?
Time to
90%
Control
(sec)
Time to
Extinguishment
(sec)
Time to
90% Flame
Height
Reduction
(sec)
Time to
90%
Reduction
in Heat
Flux – 10ft
(sec)
14 Water 0.45 No NA NA 314 44
13 Water 0.3 No NA NA NA 222
4 A 0.3 No NA NA NA 42
9 B 0.3 Yes 264 274 160 49
16 C 0.3 No 275 NA 150 52
19 C 0.22 No NA NA 365 252
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
RESULTS – 3D CASCADE
25
Test Agent
Sprinkler
Application
Rate
(gpm/ft2)
Extinguished?
Time to
90%
Control
(sec)
Time to
Extinguishment
(sec)
Time to
90% Flame
Height
Reduction
(sec)
Time to
90%
Reduction
in Heat
Flux – 10ft
(sec)
14 Water 0.45 No NA NA 314 44
13 Water 0.3 No NA NA NA 222
4 A 0.3 No NA NA NA 42
9 B 0.3 Yes 264 274 160 49
16 C 0.3 No 275 NA 150 52
19 C 0.22 No NA NA 365 252
www.jensenhughes.comwww.jensenhughes.com
RESULTS – COMBINED 2D
PAN AND 3D CASCADE
26
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
All three agents tested at 0.3 gpm/ft2
• Agents B and C extinguished the fire at this rate
• Agent A was not able to achieve 90% control
• Water alone was not tested
Agent B tested at 0.22 gpm/ft2
• Unable to achieve 90% control
All agents at all flow rates able to
reduce heat flux by 90%
RESULTS – 2D PAN & 3D CASCADE
27
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
RESULTS – 2D PAN & 3D CASCADE
28
Test Agent
Sprinkler
Application
Rate
(gpm/ft2)
Extinguished?
Time to
90%
Control
(sec)
Time to
Extinguishment
(sec)
Time to
90% Flame
Height
Reduction
(sec)
Time to
90%
Reduction
in Heat
Flux – 10ft
(sec)
5 A 0.3 No NA NA NA 129
10 B 0.3 Yes 320 329 70 69
17 C 0.3 Yes 185 197 196* 129
12 B 0.22 No NA NA 458 88
* - Interpolated
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
AGENT CHARACTERISTICS
29
A
B
C
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
EXTINGUISHMENT COMPARISON
30
Agent
Agent
Concentration
Lowest Application Rate with
Extinguishment
(gpm/ft2)
2D 3D 2D+3D
Water - 0.45DNE
(0.45)NT
A 3% 0.22DNE
(0.3)
DNE
(0.3)
B 0.5% 0.16 0.3 0.3
C 6% 0.16DNE
(0.3)A 0.3
DNE – Did not extinguish (highest application rate tested in parentheses).
NT – Not tested.
A – Test at 0.3 gpm/ft2 achieved 90% control.
www.jensenhughes.comwww.jensenhughes.com
Test scenarios acceptable
2D Fire extinguished by all agents and
water.
• 0.45 gpm/ft2 water application rate greater than
0.25 gpm/ft2 NFPA 850 baseline for boiler front oil
fires
Water failed to extinguish 3D and 2D+3D
fire scenarios
Two of the three agents extinguished fires
including the 3D cascade
CONCLUSION
31
www.jensenhughes.comwww.jensenhughes.com
Water additives provided quicker
reduction in thermal threats compared
to water
Water additives superior to plain water
Performance differences observed
between the water additives tested• Possibly attributed to different physio-chemical properties
(evaluation out of scope)
CONCLUSION
32
www.jensenhughes.comwww.jensenhughes.com
The authors would like to thank the NFPA Research
Foundation personnel and project Technical Panel for
their assistance in guiding the test planning and
advising the test group.
The authors would like to also thank the water additive
manufacturers for the donations of their agents for
testing. In addition, the authors would like to thank the
staff at the Underwriters Laboratory Fire Test Lab for
their facility and support in testing.
ACKNOWLEDGEMENTS
33
www.jensenhughes.comwww.jensenhughes.comwww.jensenhughes.com
ContactMatthew E. Benfer
+1 410-737-8677
For More Information Visit
www.jensenhughes.com
QUESTIONS?
34