Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Evaluating Data Center Indoor Air Quality
Benjamin Chu
Lawrence Berkeley National Laboratory
Environmental Energy Technologies Division
• Data centers must run 24 hours a day.
• Data centers consume large amounts of energy (60 TWh/year) [1].
• 1.5% of the total electricity generated in the US.
• Chillers are a significant energy consumer in data centers (25%) [2].
Data Center Energy Use
LBNL, 2007, Report to Congress on Server and Data
Center Energy Efficiency Public Law 109-431Greenberg et al, 2006, Best Practices for Data Centers
• Turn off the chillers and bring in cool outside air.
• This reduction of operating hours lowers the energy costs.
• Problem: Bringing in outside air increases indoor particle concentrations.
AHUCRAC
AHU
Cold Air
Warm Air
Outside AirCRAC
AHU
office
zone
Rocklin
data center
Walnut Creek
data center
Sunnyvale
data center
Air Side Economizers
Shehabi et al, 2008, Particle Concentrations in Data Centers
Tschudi et al, 2006, Measuring and Managing Data-Center Energy Use
• Contaminants can:
– Corrode metal contacts.
– Bridge the electrical isolation between conductors.
• Objective: Find out how economizers impact indoor air quality.
Particulate Matter
http://www.isa.org/Template.cfm?Section=Article_Index1&template=
/ContentManagement/ContentDisplay.cfm&ContentID=26843
Corrosion coupons used to gauge corrosion rates.
Aerosol Analysis
• Count and identify particles in indoor and
outdoor air.
• Optical measurement devices:
– Aerodynamic particle sizer (APS)
– Optical particle counter (OPC)
– Condensation particle counter (CPC)
– Aethalometer
Chemical Analysis
• Collect indoor and outdoor particles for analysis.
• Two different setups:
– An annular denuder, followed by Teflon, nylon and cellulose filters.
– Two quartz filters.
• Nitrates, sulfates and ammonia are of interest because they are hygroscopic.
• Chemical speciation by ion chromatography.
Quartz Filter Denuder
Size Resolved Data for 7/30/08-8/1/08
0
50000
100000
150000
200000
250000
4:48 PM
8:18 PM
11:48 PM
3:18 AM
6:48 AM
10:18 AM
1:48 PM
5:18 PM
8:48 PM
12:18 AM
3:48 AM
7:18 AM
10:48 AM
2:18 PM
Co
un
ts
Time (hh:mm)
0.5-0.7 microns
Outdoor
Indoor
020000400006000080000
100000120000
4:48 PM
8:18 PM
11:48 PM
3:18 AM
6:48 AM
10:18 AM
1:48 PM
5:18 PM
8:48 PM
12:18 AM
3:48 AM
7:18 AM
10:48 AM
2:18 PM
Co
un
ts
Time (hh:mm)
0.7-1 microns
Outdoor
Indoor
Indoor to Outdoor Concentration Ratio
Carbon Data for 8/4/08-8/5/08
Carbon Data for 8/4/08-8/5/08
Particle Concentrations for 7/31/08-8/1/08
Discussion and Conclusion
• When the economizer is on, there is an increase of particle counts and concentrations of indoor air.
• When it is turned off, the concentrations of indoor air decrease because of recirculation.
• Concentrations are lower than EPA standards for particulate matter smaller than 2.5 μm diameter (15.0 μg/m³).
•DOE Office of Science, LBNL Center for Science and
Engineering Education.
•Ashok Gadgil, Srirupa Ganguly, Arman Shehabi,
Doug Sullivan, Lara Gundel, Melissa Lunden and
Dennis DiBartholomeo.
Acknowledgements
• Create a model of economizer cost implications in different climates.
• SF6 is released as a tracer to measure the particle diffusion.
• Portable ambient air analyzers are used to track the diffusion rate.
• Corrosion coupons measure the corrosion rate of the electronic circuits.
Modeling and Further Work
[1] LBNL, 2007, Report to Congress on Server and Data Center Energy Efficiency Public Law 109-431
[2] Greenberg et al, 2006, Best Practices for Data Centers
[3] Shehabi et al, 2008, Particle Concentrations in Data Centers
[4] Tschudi et al, 2006, Measuring and Managing Data-Center Energy Use
References