EURO-DIESEL DYNAMIC ROTARY UPS - DRUPS
PRESENTATION TO IDEAL SOLUTIONS
OMAN
JULY 2018
Bernard Hanssens
AGENDA
1. COMPANY PRESENTATION
2. DRUPS SYSTEM
3. DRUPS – ADDED VALUE FOR THE CLIENTS
4. DRUPS CONFIGURATIONS
5. DRUPS APPLICATIONS
6. LOCAL PRESENCE IN ME – AFTER SALES SUPPORT
7. EURO-DIESEL REFERENCE IN ME
8. SOME SPECIAL INTERNATIONAL REFERENCES
EURO DIESEL Template
2
1. COMPANY PRESENTATION
3
EURO-DIESEL HQ, BELGIUM
EURO DIESEL Template
4
EURO-DIESEL
France
Holland
Belgium
• Private company
• Factory in Belgium and Germany
• Established in 1989
• 330 Employees
• 12 offices: Belgium (HQ), Germany, UK, France, USA, Singapore, Turkey, Chili, Russia, Brazil, Qatar, UAE + Presence in KSA
• Worldwide presence
• 24/7 After Sales service support worldwide
• Focus on power quality solutions
WORLDWIDE PRESENCE
EURO DIESEL Template
5
EURO-DIESEL
Distributors
THE FACTORY
EURO DIESEL Template
6
The Facility:
• 6300 M²
• Production capacity > 300 systems
• 18 Test stands
• Indoor enclosure assembly
• 50 & 60 Hz testing
• Load banks > 18 MW
• Load banks & recordings, software operated
ISO CERTIFIED
EURO DIESEL Template
7
2. DRUPS SYSTEM
8
Static vs Dynamic UPS Solution
9
Mains
Diesel Generator System
ATS STATIC UPS POWER DISTRIBUTION PANELS
BATTERY ROOM
Load
NO-BREAK KS®
CHOKE COIL
INSTALLATION OF A DRUPS
EURO DIESEL Template
11
IN A ROOM:
IN A FACTORY-BUILT ENCLOSURE:
DRUPS – HOW IT WORKS
12
DRUPS – CONTROL PANEL
13
DRUPS – CONTROL PANEL
14
3. DRUPS – ADDED VALUE
15
SIMPLE DESIGN
EURO DIESEL Template
16
SIMPLE ELECTRICAL DESIGN
SIMPLE DESIGN
EURO DIESEL Template
17
SIMPLE MECHANICAL INSTALLATION
Static UPS Modules Air Conditioning
PFC
Standby Battery Rooms
Spark-proof Lighting
Fire Protection & Security
Standby Generator
DRUPS = 1 SIMPLE MACHINE
STATIC UPS =
MANY ELEMENTS REQUIRED
REPLACE THEM ALL BY 1 DRUPS
REDUCED FOOTPRINT
EURO DIESEL Template
18
COST SAVINGS
• No Standby Battery rooms and related infrastructure: Air conditioning for battery rooms
Special fire protection system
Spark proof lighting
…
• No Static UPS Modules
• No Capacitor banks
• No separate standby Generator
• Reduced cabling costs
• Saving on building costs
EURO DIESEL Template
19
LOW CAPEX
COST SAVINGS
• No A/C, hence reduced utility bills
• Continuous power factor correction, hence reduced electricity bills
• Eliminate the need to replace S-UPS batteries every 3-5 years
• Reduced maintenance DRUPS = low maintenance, mainly bearings greasing
First overhaul after 10 years of operations only
EURO DIESEL Template
20
LOW OPEX
COST SAVINGS - TCO
EURO DIESEL Template
21
HIGH RELIABILITY
• For a single unit:
• For a N+1 installation:
EURO DIESEL Template
22
SEE MTBF CALCULATIONS
OTHER BENEFITS
EURO DIESEL Template
23
USING EURO-DIESEL DRUPS
• SUSTAINABILITY (GREEN BUILDING CERTIFICATION)
• INCREASED PUE
• GUARANTEED DIESEL ENGINE START
• PROTECT BOTH IT AND MECHANICAL LOADS
• AVAILABILITY IN THE REGION AND IN THE COUNTRY
4. DRUPS CONFIGURATIONS
24
DRUPS CONFIGURATIONS
EURO DIESEL Template
25
NO-BREAK KS® - SINGLE SYSTEM
DRUPS CONFIGURATIONS
EURO DIESEL Template
26
NO-BREAK KS® - DUAL OUTPUT
DRUPS CONFIGURATIONS
EURO DIESEL Template
27
NO-BREAK KS® - LV PARALLEL
DRUPS CONFIGURATIONS
EURO DIESEL Template
28
NO-BREAK KS® - MV PARALLEL
DRUPS CONFIGURATIONS
EURO DIESEL Template
29
NO-BREAK KS® - DISTRIBUTED REDUNDANT
DRUPS CONFIGURATIONS
EURO DIESEL Template
30
NO-BREAK KS® - IP STAR BUS CONFIGURATION
DRUPS CONFIGURATIONS
EURO DIESEL Template
31
UPTIME DESIGN CRITERIA
DRUPS CONFIGURATIONS
EURO DIESEL Template
32
NO-BREAK KS® - EXAMPLE OF TIER III
DRUPS CONFIGURATIONS
EURO DIESEL Template
33
NO-BREAK KS® - EXAMPLE OF TIER IV
DRUPS CONFIGURATIONS
EURO DIESEL Template
34
NO-BREAK KS® - EXAMPLE OF TIER IV – CISCO DATA CENTER
5. DRUPS APPLICATIONS
35
DRUPS APPLICATIONS
EURO DIESEL Template
36
TYPICAL SECTORS
• Datacenters
• Hospitals
• Traffic Control Rooms
• Airports
• Industrial Plants
• High technology
• Power range for a single unit : 200 kVA -> 3000 kVA
• No limitation on total system rating. Ex : 26 x 2000KVA = 52 MVA
TYPICAL POWER RANGES
6. LOCAL PRESENCE IN KSA AFTER SALES SUPPORT
37
EURO-DIESEL MIDDLE EAST
EURO DIESEL Template
38
EURO-DIESEL MIDDLE EAST
2. Qatar office:
The Gate Tower 2
Suite 706
Tel: +974 4020 6030
Activities:
- Storage of critical spare parts and consumables
- Operations & Maintenance
- Supervision of installation
- Pre-sales and post-sales engineering support
Main office locations:
1. Main office:
Jebel Ali Free Zone
Dubai, UAE
Tel: +971 4 886 1010
Email: [email protected]
3. Local presence in KSA
Ahmad Khatib, Country Manager
Tel: +966 53 944 5526
Email: [email protected]
AFTER SALES - OPS SUPPORT
EURO DIESEL Template
39
EURO-DIESEL LLC helpdesk
Back Office Support HQ
Local Service Technician
Automated transfer
Site
Vis
it
To BMS or Site Operator
Automatically Generated E-mails
Remote Analysis Loging KS Vision
E-mail, text message or Telephone
Call for 2nd line support
ALARM OR EVENT
AFTER SALES - OPS SUPPORT
EURO DIESEL Template
40
Services • Monitoring of quality control service sheets
to assist in identifying problems proactively
• Recording of Machine history in a Global Service Database (worldwide)
• Full archives over its product life
• Manage preventive programs during 25 years life expectancy
• Follow up each individual machine
• Inform the customer in advance
• Analyze local situation
7. EURO-DIESEL EFERENCES IN THE MIDDLE-EAST
41
INSTALLED BASE ACROSS CONTINENTS ˃ 1.600.000KVA
668.035 KVA in Europe 103.409 KVA in North America
146.160 KVA in Latin America
119.200 KVA in Africa
141.100 KVA in the Middle East
419.200 KVA in Asia Pacific
24.880 KVA in Russia
1000+
RECENT REFERENCES IN THE MIDDLE EAST
EURO DIESEL Template
43
UAE • MAKTOUM INTL
AIRPORT
KSA - JEDDAH • JEDDAH MUNICIPALITY
DATA CENTER
KSA - RIYADH • IMAM UNIVERSITY
DATA CENTER
KSA - JUBAIL • POLISILICON PLAN
OMAN • TRA DATA CENTER
KSA - RIYADH • SIMAH
DATA CENTER
UAE • ETISALAT KHALIFA ‘A’
DATA CENTER
KSA - JEDDAH • KING ABDULAZIZ INT’L
AIRPORT
QATAR • MEEZA MV2 DATA
CENTER
KSA - RIYADH • MOFA
DATA CENTER
KSA – KING ABDULAZIZ INT’L AIRPORT
EURO DIESEL Template
44
KEY FACTS
• International Airport in Jeddah
• DRUPS protecting the 2 main DATA CENTERS on the airport
• 12 x DRUPS - 2000kVA – 400V – 60Hz
• 50°C environment
• Mechanical + IT loads
EURO-DIESEL SCOPE
• DRUPS Supply, design & supply of ventilation systems
• On-site installation assistance, commissioning, training
KSA – JEDDAH MUNICIPALITY
EURO DIESEL Template
45
KEY FACTS
• Tier 3 Data Center
• JM Headquarter Data Center
• 2 x DRUPS - 500kVA – 415V – 60Hz
• 50°C environment
• Containerized solution
EURO-DIESEL SCOPE
• DRUPS + ventilation systems + containerization
• Supply, on-site assistance, commissioning
• Operations & maintenance
KSA – IMAM UNIVERSITY
EURO DIESEL Template
46
KEY FACTS
• Tier 2 Data Center
• University Data Center
• 1 x DRUPS - 500kVA – 415V – 60Hz
• 50°C environment
• Containerized solution
EURO-DIESEL SCOPE
• DRUPS + ventilation systems + containerization
• Supply, on-site assistance, commissioning
• Operations & maintenance
KSA – SIMAH DATA CENTER
EURO DIESEL Template
47
KEY FACTS
• Tier 4 Data Center
• Banking institution
• 2 x DRUPS - 800kVA – 380V – 60Hz
• 50°C environment
• Containerized solution
EURO-DIESEL SCOPE
• DRUPS + ventilation systems + containerization
• Supply, on-site assistance, commissioning
• Operations & maintenance
KSA – MOFA DATA CENTER
EURO DIESEL Template
48
KEY FACTS
• Tier 3 Data Center
• 2 x DRUPS - 1250kVA – 380V – 60Hz
• 50°C environment
• Containerized solution
EURO-DIESEL SCOPE
• DRUPS + ventilation system + containerization
• Supply, on-site assistance, commissioning
• Operations & maintenance
KSA – JUBAIL POLISILICON PLANT
EURO DIESEL Template
49
KEY FACTS
• Polisilicon Factory
• 2 x DRUPS - 3000kVA – 400V – 60Hz
• 50°C environment
• Mechanical + IT loads
• Dual output solution:
• 1500kVA Critical Load
• 1500kVA Non-Critical Load
EURO-DIESEL SCOPE
• DRUPS Supply
• on-site assistance, commissioning
UAE ABU DHABI – ETISALAT
EURO DIESEL Template
50
KEY FACTS
• Tier 3 Data Center
• Telecom company
• 16 x DRUPS - 2500kVA – 400V – 50Hz
• 2 Phase (4 + 12)
• 50°C environment
ED’S SCOPE
• Supply & commissioning
• Supervision of installation
• Maintenance
UAE – MAKTOUM INT’L AIRPORT
EURO DIESEL Template
51
KEY FACTS
• Protection of Airfield Lighting Systems
• 2 x DRUPS – 1000/2000kVA – 400V – 50Hz
• Phase 1 of 5
• 50°C environment
ED’S SCOPE
• Supply, commissioning, training,
maintenance assistance
OMAN – TELECOM REGULATORY AUTHORITY
EURO DIESEL Template
52
KEY FACTS
• Tier 2 Data Center
• TRA Head Quarter Data Center
• 1 x DRUPS - 1900kVA – 415V – 50Hz
• 50°C environment
ED’S SCOPE
• DRUPS + ventilation systems
• Supply, on-site assistance, commissioning
• Long-Term Operations & maintenance
QATAR – MEEZA MV2
EURO DIESEL Template
53
KEY FACTS
• Tier 3 Data Center
• Co-location & IT Services
• 10,000 m2 D.C. space
• 10 x DRUPS - 1600kVA – 415V – 50Hz
• 50°C environment
• Continuous power ED’S SCOPE
• DRUPS + ventilation systems
• Supply, on-site assistance, commissioning
• Long-term contract for operations & maintenance on site
8. SPECIAL REFERENCES
54
Medicare References
EURO DIESEL Template
55
800 kVA | LFKK Hospital, Linz, Austria 630 kVA | St. Michel Hospital, Belgium 250 kVA | AOKH, Austria
3 MVA | Hospital Bologna, Italy 630 kVA | Hospital Ambroise Pare, Marseille, France
Multi MVA Data Centre References
EURO DIESEL Template
56
17 MVA | Data Centre, France 12 MVA | Data Centre, Germany 13.2 MVA | Data Centre, S. Africa
12 MVA | Data Centre, UK 52 MVA | Global SwitchData Centre, Canary Wharf, UK
IT Centre References
EURO DIESEL Template
57
6 MVA | ECMWF, Reading, UK
12.4MV | Nankang Software Park, Taiwan 12 MVA | Citigroup, London, UK
Critical Process Industry References
EURO DIESEL Template
58
9.8 MVA | ATMEL, France 15 MVA | Texas Instruments, The Philippines
10.2 MVA | Semiconductor FAB GSMC, China 30.7 MVA | TFT/LCD FAB, Taiwan
Telecommunication References
EURO DIESEL Template
59
3.2 MVA | Swisscom, Olten, Switzerland 250 kVA | Telecom Italia, Roma, Italy
4.5 MVA | Fucino National Space Center, Aquila, Italy
250 kVA | British Telecom
Portsmouth , UK
Aviation & Traffic Control References
EURO DIESEL Template
60
2.3MV | Liège Airport, Belgium 3 MVA | New Bangkok Airport, Thailand
7 MVA | Dubai International Airport, UAE 3.5 MVA | Airport Madrid Barajas, Spain
Ascenty 20MVA Data Center – Sao Paulo - Brasil
EURO DIESEL Template
61