19
eurammon Symposium 2015 Combined Heating and Cooling Applications in Dairy Philippe Nellissen Emerson Climate Technologies GmbH Schaffhausen, 25 th /26 th June, 2015

eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

  • Upload
    dodat

  • View
    213

  • Download
    0

Embed Size (px)

Citation preview

Page 1: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

eurammon Symposium 2015

Combined Heating and Cooling

Applications in Dairy

Philippe Nellissen

Emerson Climate Technologies GmbH

Schaffhausen, 25th/26th June, 2015

Page 2: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 2

Agenda

• What's worth for a HP success?

• Vilter Single Screw short description

• If there is hot, there is certainly also cold

• Be opportunistic in your revamping

• Be Creative and make new business Model

• Optimise your existing Installation

• Conclusions

Page 3: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 3

Where is the value for a Heat Pump ?

Equipment Capability

Heat Source

Return On Investment

End-User Vision

Heat Needs

Page 4: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 4

Source and Need

Sources Heat Pump Applications

The most interesting is when the cooling of the heat

source is part of the process !

Page 5: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 5

Vilter Single Screw Compressor: A short description

Gaterotor

Radially and Axially

Balanced main

Screw Variable

Capacity

Slide 10%

to 100%

Variable

Volume

Slide 1.2 to

7 ratio

Gaterotor

Page 6: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 6

Key features for

Refrigeration / Heat Pump application

Balanced forces - Enhancing bearing life

Parallex™ Slide Valves - Automatic capacity control

Low Maintenance

Energy Efficiency

High Temperature

up to 90°C Hot Water

High Capacity

Working pressure for Heat Pump Application

Balanced screw allows casing material for higher working pressure (Cast iron, Ductile Iron, Cast Steel)

Page 7: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 7

If there is hot, there is certainly also cold

Page 8: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 8

Be opportunistic in your revamping

The Dairy Vire Plant

THE DAIRY VIRE PLANT - 37 200 tons of Cheese

Page 9: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 9

Be opportunistic in your revamping

The Dairy Vire Plant

Chilled water @ 1°C

Heat Rejected by chilled water

production for process cooling

Hot water @ 58°C

• Clean In Place process

• Cheese ripening rooms

• General cleaning process need

• Reduce energy costs

• Heat Recovery from cooling process

Reduce CO2 emissions generated by

gas and fuel combustion

• Replace old cooling installation

Cooling capacity and hot water

generation @ -3°C/+58°C

Opportunistic !

Page 10: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 10

How? One single Installation

1380 kW

Energy usage per ton of product:

820 kWh/ton 559 kWh/ton

Return On Investment (ROI) of 2 years

-31.8%

Chilled water @ 1°C Hot water @ 58°C

1100 kW

24/7 running VSM-701

Are you OK to say

COPT=COPc+COPh ??

Page 12: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 12

Make new Business Model

Norway’s Dairy Cooperative Tine

Cooled loop @ -2°C

Heat Rejected by chilled water

production for process cooling

Hot water @ 58°C

• Clean In Place process

• General cleaning process need

• Greenhouse heating

• Heat Recovery from cooling process

• Reduce CO2 emissions by 30 - 40 %

with this new dairy

• Sell heat to Industrial Greenhouse

close to the dairy

• 5400 kW @ -5°C required refrigeration duty,

Condensing +37ºC

• 6900 kW @ 58°C water required heating duty

• 7200 kW @ 73°C water required heating duty

Page 13: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 13

Sell the heat to the Greenhouse next door ? Why not?

58°C

Plans for connecting a local business estate to the heating

network and increase the supply temperature to 73°C

within the next couple of years

First step to a Greenhouse

Second step to local business place

Added revenues, new business

Page 14: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 14

How? Two stage Installation

3 low stage (VSS-1851 ) and 2 high stage

compressors units (VSSH-791)

Payback of the plant of less than 2.5 years.

Cooling Capacity 5400 kW @ -5°C/+37ºC

Heating capacity • 7200 kW @ 73°C

water – COP 5.8

• 6900 kW @ 58°C

water – COP 9.0

Page 16: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 16

Optimise your existing Installation

Kerry Dairy

Heat Rejected by chilled water

production for process cooling Hot water @ 67°C

• Clean In Place process

• General cleaning process need

• Heat Recovery from cooling process

• Reduce CO2 emissions by 30 - 40 %

with this new dairy

Hot water from 12°C to 67°C with HP operating

conditions +28°C/+64°C and additional heat

recovery

Page 17: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 17

How? Recover as much heat as possible and a Heat Pump

VSSH-291

Water out 67°C

Additional heat recovery from cooling

installationdesuperheating, …

HX

29°C 12°C

Water in

Pre-heating with waste heat

recovery from Process

HX

62°C

Heat Recovery from

cooling installation

HX

HX

28°C

64°C

1025 kW

Seagull

Refrigeration

Ltd.

Page 18: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Schaffhausen, 25th / 26th June, 2015 Page 18

Conclusions

• Combined heating and cooling with an ammonia heat pump is a very

attractive solution among existing only heating system.

• This allows savings not only for heating cost but also

• On the total cost of energy per units manufactured

• In term of CO2 emissions,

• Low Ammonia charge (For those who would be afraid of this)

• In term water consumption

• For the future, F-Gas regulation in Europe opens large opportunities

in the replacement of existing HFC installations.

• Combined heating and cooling can be applied on any industrial

process requiring cooling and heating on different steps in their

manufacturing process.

Page 19: eurammon Symposium 2015 · eurammon Symposium 2015 ... Kerry Dairy Heat Rejected by chilled water ... • Combined heating and cooling with an ammonia heat pump is a very

Contact:

Ir. MM Philippe Nellissen

Emerson Clmiate Technologies GmbH

Pascalstrasse 65, 52076

Germany

Phone: +49 2408 929 134

Mobile: +32 476 94 34 81

Fax +49 2408 929 570

E-Mail [email protected]