8
DEPARTMENT OF THE ARMY CECW-ED U.S. Army Corps of Engineers CECW-EG Washington, DC 20314-1000 ETL 1110-2-352 Technical Letter No. 1110-2-352 31 March 1994 Engineering and Design STABILITY OF GRAVITY WALLS VERTICAL SHEAR Distribution Restriction Statement Approved for public release; distribution is unlimited.

ETL-352 Stab Grav Wall

Embed Size (px)

DESCRIPTION

letter

Citation preview

Page 1: ETL-352 Stab Grav Wall

DEPARTMENT OF THE ARMYCECW-ED U.S. Army Corps of EngineersCECW-EG Washington, DC 20314-1000 ETL 1110-2-352

Technical LetterNo. 1110-2-352 31 March 1994

Engineering and DesignSTABILITY OF GRAVITY WALLS

VERTICAL SHEAR

Distribution Restriction Statement

Approved for public release; distribution is unlimited.

Page 2: ETL-352 Stab Grav Wall

DEPARTMENT OF THE ARMY ETL 1110-2-352CECW-ED U.S. Army Corps of EngineersCECW-EG Washington, DC 20314-1000

TechnicalLetter No. 1110-2-352 31 March 1994

Engineering and DesignSTABILITY OF GRAVITY WALLS

VERTICAL SHEAR

1. Purpose

This engineer technical letter (ETL) provides guid-ance for incorporating and calculating a shear forceacting along the backs of gravity earth retaining wallswithin the procedures for analyzing the stability ofnavigation structures, including lock walls, andapproach walls. This shear force is also referred toas a "downdrag" force or "drag" force. The simpli-fied procedure described in this ETL for calculatingthe magnitude of shear force is restricted to concretegravity earth retaining walls founded on rock.

2. Applicability

This ETL applies to all HQUSACE elements, majorsubordinate commands, districts, laboratories, andfield operating activities having responsibilities forthe design and construction of civil works projects.

3. References

References are included in Appendix A.

4. Background

a. Calculation of the stability of gravity walls.

(1) A common procedure used for designing newgravity walls and for evaluating the safety of existinggravity walls is the conventional equilibrium methodof analysis. The conventional equilibrium methodinvolves assumptions regarding the loading and resist-ing forces that act on the structures. In most cases ofmassive retaining walls constructed on rock founda-tions, movements of the wall and backfill are not

sufficient to fully mobilize the shear resistance of thesoil.

(2) Past practice has been to assign at-rest lateralearth pressures against the back of the gravity walland set the interface friction between the wall and thebackfill equal to zero. Zero interface friction alongthe back of the wall corresponds to a zero shear forcealong the back of the wall. In addition, boundarywater pressures were assigned along the back, front,and base of the wall for navigation structures. Withall forces and their points of action on the free bodydiagram of the wall defined, wall stability waschecked against the recommended criteria (EM 1110-2-1605, EM 1110-2-2502, EM 1110-2-2602,ETL 1110-2-22, ETL 1110-2-256, ETL 1110-2-310).

b. Experience with existing gravity walls.Pastpractice has been to use the same stability criteria fordesigning new gravity earth retaining structures andfor reviewing the margin of safety available for exist-ing structures. Several existing structures, althoughnot meeting the referenced stability criteria (EM1110-2-1605, EM 1110-2-2502, EM 1110-2-2602,ETL 1110-2-22, ETL 1110-2-256, ETL 1110-2-310),have performed satisfactorily for many years. It maynot be necessary to improve a structure’s stability tosatisfy the referenced criteria when the remaining lifeof the structure is relatively short or when there areno indications of any stability problem. A researchinvestigation, performed as part of the Repair, Evalu-ation, Maintenance, and Rehabilitation (REMR) Pro-gram (Ebeling, Duncan, and Clough 1990; Filz andDuncan 1992), was undertaken to study the stabilityof existing concrete structures. The results of theinitial REMR research, and the experience from sub-sequent research programs (Ebeling, Duncan, andClough 1990; Filz and Duncan 1992), are describedin Sections 4c and 4d of this ETL.

Page 3: ETL-352 Stab Grav Wall

ETL 1110-2-35231 Mar 94

c. Shear force - finite element analyses.

(1) To develop an improved understanding of theinteraction between gravity walls, their foundations,and their backfills, an investigation using finite ele-ment analyses was conducted (Ebeling et al. 1992;Ebeling, Duncan, and Clough 1990). The analysesdemonstrated that the backfill settles relative to thewall and develops downward shear loads on the wall.Some examples are given in Figure 1, which showsthe results of finite element analyses of four wallsfounded on rock and retaining dry backfill. In Fig-ure 1, the magnitude of the vertical shear forceFv isexpressed in terms of a vertical shear coefficientKv,which is related to the shear force on the verticalplane through the heel of a wall by the followingequation:

(1)Fv Kv

12

γt H2

where

Fv = shear force on the vertical plane through theheel of the wall (force per unit length of wall)

Kv = vertical shear coefficient (dimensionless)

γt = total unit weight of backfill

H = wall height

(2) Analyses indicated that the gravity wallswould move only a very small amount during place-ment of the toe fills and backfills. As a result, theearth pressures on the backs and the fronts of thewalls are close to those that exist at rest. Even so,settlement of the backfill relative to the wall as it isplaced behind the wall is sufficient to generate asignificant amount of shear force on the wall. Valuesof Kv range from 0.09 to 0.21 for the four casesshown in Figure 1.

(3) Parametric studies demonstrated that the mostimportant factors influencing the value ofKv forconcrete gravity walls on rock foundations are thedepth of the backfill, the stiffness of the backfill, theinclination of the back of the wall, and the number ofsteps in the back of the wall. The following trendswere observed:

(a) For low walls, the value ofKv increases withincreasing wall height because more backfill compres-sion occurs due to self-weight of the backfill. Theresulting increase in differential movement between

Figure 1. Results of finite element analyses of four walls founded on rock retaining dry backfill

2

Page 4: ETL-352 Stab Grav Wall

ETL 1110-2-35231 Mar 94

backfill and wall causes a greater portion of theinterface strength to be mobilized. This processapproaches a limiting condition for high walls as theinterface strength becomes fully mobilized over mostof the wall-backfill contact area.

(b) As the stiffness of the backfill increases,backfill compression decreases, and the wall heightnecessary to mobilize the full interface strengthincreases. For low walls with vertical back sides, thevalue ofKv decreases as the backfill stiffnessincreases.

(c) The value ofKv decreases as the back side ofthe wall becomes inclined away from the backfill andtowards the front of the wall.

(d) The value ofKv is greater for a wall with astepped back side than for a wall with a smooth backside at the same average slope.

d. Shear force - instrumented field and modelwall measurements.

(1) Shear loads have been reported for severalinstrumented walls (Duncan, Clough, and Ebeling1990), including a lock wall 30.2 m in height andfounded on rock (Hilmer 1986). Measurements at thelock wall are reported over a 6-year period. Mobi-lized interface friction at the lock wall fluctuatesseasonally and with changes in water level inside thelocks. However, the data indicate that the shear forceis persistent over the 6-year period, and does notdecay with time. According to a conservative inter-pretation of the data, the minimum value ofKv duringthe 6-year period is about 0.18.

(2) In a recent research program conducted atVirginia Polytechnic Institute and State University(Filz and Duncan 1992), both the horizontal earthpressure force and the vertical shear force along thevertical back side of a 2.1-m- (7-ft-) high rigid retain-ing wall were measured. The research programincluded 16 tests using compacted fine sand (UnifiedSoil Classification SP) and compacted non-plasticsilty sand (SM) as backfill. Measured values ofKv

ranged from 0.11 to 0.23 (Table 8.9 in Filz andDuncan (1992)). The more compressible backfillsexhibited higherKv values. The compacted backfillswere left in place for periods ranging from 1 to14 days after completion of backfilling. Values ofKv

tended to increase with time.

5. Procedures for Calculating the VerticalShear Force

Two procedures for computing the magnitudes ofshear loads along the backs of gravity walls aredescribed in this section: a simplified procedure, anda complete soil-structure interaction analysis proce-dure using the finite element method. These proce-dures are intended only as guidelines and are notintended to replace judgment by the engineers respon-sible for the project.

a. Simplified procedure.

(1) Inclusion of a shear force on a vertical planethrough the heel of the wall, as shown in Figure 2,can be computed by use of the following equation:

(2)Fv Kv

12

γt (D1)2 γt (D1D2)

12

γb (D2)2

where

D1 = thickness of backfill above the hydrostatic watertable

D2 = thickness of submerged backfill above the baseof the wall

γb = buoyant unit weight of submerged backfill,γt - γw

γw = unit weight of water

(2) As indicated in Figure 2, the total height ofthe backfill against the wall is the sum of the thick-nessesD1 andD2:

(3)H D1 D2

(3) Equation 2 requires a value forKv. In thesimplified procedure, the value ofKv is obtained fromFigures 3 through 5 and Equation 4:

(4)Kv (1 CθCs) (Kv)vert

where

3

Page 5: ETL-352 Stab Grav Wall

ETL 1110-2-35231 Mar 94

Figure 2. Resultant earth pressure forces on a vertical plane through the heel of a gravity wallfounded on rock

Figure 3. Values of ( Kv)vert for design of gravitywalls founded on rock

Cθ = correction factor to account for inclinationof the back side of the wall

Cs = correction factor to account for steps in theback side of the wall

(Kv)vert = value ofKv for a wall with a vertical backside

Figure 4. Values of the correction factor Cθ forinclination of the back side of gravity wallsfounded on rock

(4) Figure 3 shows that the value of (Kv)vert fordesign increases with increasing wall height until alimiting value of 0.1 is reached. This limiting valuefor design is well below the actual limiting value of(Kv)vert indicated by measurements and analyses. Itwas selected conservatively so that the change toprevious design procedures (i.e.,Kv = 0) would not belarge. Even with this conservative selection of thelimiting value of (Kv)vert, significant economies can

4

Page 6: ETL-352 Stab Grav Wall

ETL 1110-2-35231 Mar 94

Figure 5. Definition sketch and values of the cor-rection factor Cs for gravity walls founded on rockwith stepped back sides

be obtained by including the vertical shear force indesign.

(5) Figure 3 also shows that the limiting value of(Kv)vert develops at lower wall heights for walls withloose backfill than for walls with dense backfill.

(6) Figures 4 and 5 show the values of the cor-rection factorsCθ andCs, respectively, that are to beapplied.

(7) An example application of the simplifiedprocedure is shown in Figure 6. It can be noted thatthe steps in the back side of the wall in Figure 6 arenot uniform. An average slope consistent with the

Figure 6. Example calculation of the vertical shearforce for a gravity wall founded on rock

definition sketch in Figure 5 is used to obtain thevalue of the correction factorCθ from Figure 4.

(8) The vertical shear force determined using thesimplified procedure can be incorporated in conven-tional equilibrium calculations. The results should bechecked against the recommended criteria (EM 1110-2-1605, EM 1110-2-2502, EM 1110-2-2602, ETL1110-2-22, ETL 1110-2-256, ETL 1110-2-310).When a toe fill of significant height exists, a verticalshear force at the toe should be included in the equi-librium calculations if a vertical shear force wasapplied to the back side of the wall. Neglecting thevertical shear force at the toe could result in uncon-servative estimates of the base contact area and themaximum bearing pressure on the foundation.

(9) Use of the simplified procedure to obtain avertical shear force for stability calculations isrestricted to gravity earth retaining walls that satisfythe following criteria:

(a) The vertical displacements within the founda-tion during construction of the wall and backfillingare negligible when compared with the vertical settle-ment within the backfill due to self-weight. Gravity-

5

Page 7: ETL-352 Stab Grav Wall

ETL 1110-2-35231 Mar 94

walls founded on competent rock foundations satisfythis criterion.

(b) The backfill soil does not creep. Compactedsoils classified as SW, SP, GW, and GP according tothe Unified Soil Classification System (AmericanSociety for Testing and Materials 1990) do not exper-ience significant creep movements. The simplifiedprocedure is also applicable to select SM backfillswith nonplastic fines that do not creep.

(c) No special features that reduce or eliminateinterface friction exist along the interface between theback of the wall and the backfill. Examples ofspecial features that would reduce interface frictioninclude bituminous coatings and synthetic barrierswith low interface friction values.

(d) The interface between the back side of thewall and the backfill is capable of developing inter-face friction values ofδ > 0.7φ, whereφ is the effec-tive angle of internal friction for the soil comprisingthe backfill. This is satisfied by SW, SP, GW, andGP backfills compacted against concrete walls. It isalso satisfied by SM backfills with nonplastic finescompacted against concrete walls.

(e) The water table within the backfill is hydro-static. If the variation of pore water pressure is nothydrostatic, the values ofD1 andD2 in Equation 3should be selected to represent the average conditionsin the backfill.

b. Soil-structure interaction analysis.

(1) A complete soil-structure interaction analysis(Ebeling 1990) for computing shear loads along the

backs of gravity walls can be accomplished using afinite element program such as SOILSTRUCT(Ebeling, Peters, and Clough 1992). Unlike conven-tional equilibrium procedures (Section 4a), an SSIanalysis does not require the use of predeterminedpressure distributions between the soil and the wall.Instead, it allows for development of these pressuresthrough soil-structure interaction by simulating thestaged construction that occurs. The computer pro-gram SOILSTRUCT can model the nonlinear stress-strain behavior of the soil, and allow for relativemovement between the soil and the structure byincorporating interface elements in the mesh.

(2) Soil-structure interaction analyses are alsoespecially useful for analyzing retaining structuresfounded on either soils or compressible rock founda-tions. Differential settlements within the foundationaffect the magnitude of the shear force that the back-fill exerts on the wall. The SSI analysis procedurehas been successfully used for a wide variety ofproblems, including the Port Allen and Old Riverlocks (Clough and Duncan 1969) and, more recently,the lock at Red River Lock and Dam No. 1 (Ebelinget al. 1993).

(3) A soil-structure interaction analysis is recom-mended for those structures for which the simplifiedprocedure is not applicable (Section 5a) or for thosecases in which a more precise evaluation of the shearforce is required. Soil-structure interaction analysesare recommended for U-frame locks, retaining struc-tures founded on soils, and structures with compli-cated geometry.

FOR THE DIRECTOR OF CIVIL WORKS:

1 Appendix PAUL D. BARBER, P.E.Chief, Engineering DivisionDirectorate of Civil Works

6

Page 8: ETL-352 Stab Grav Wall

ETL 1110-2-35231 Mar 94

APPENDIX A: REFERENCES

EM 1110-2-1605. Hydraulic Design of NavigationDams.

EM 1110-2-2502. Retaining and Flood Walls.

EM 1110-2-2602. Planning and Design of Naviga-tion Lock Walls and Appurtenances.

ETL 1110-2-22. Design of Navigation Lock GravityWalls.

ETL 1110-2-256. Sliding Stability for ConcreteStructures.

ETL 1110-2-310. Stability Criteria for ExistingConcrete Navigation Structures on Rock Foundations.

American Society for Testing and Materials (1990)."Standard Test Method for Classification of Soils forEngineering Purposes," Practice No. D2487-90, 1990Book of ASTM Standards, 04.08, pp 309-319.

Clough, G. W., and Duncan, J. M. 1969 (Sep)."Finite Element Analyses of Port Allen and Old RiverLocks," Contract Report S-69-6, U.S. Army EngineerWaterways Experiment Station, Vicksburg, MS.

Duncan, J. M., Clough, G. W., and Ebeling, R. M.1990 (Jun). "Behavior and Design of Gravity EarthRetaining Structures," invited contribution to theASCE conferenceDesign and Performance of EarthRetaining Structures, Cornell, NY.

Ebeling, R. M. 1990 (Dec). "Review of Finite Ele-ment Procedures for Earth Retaining Structures,"Miscellaneous Paper ITL-90-5, U.S. Army EngineerWaterways Experiment Station, Vicksburg, MS.

Ebeling, R. M., Clough, G. W., Duncan, J. M., andBrandon, T. L. 1992 (Mar). "Methods of Evaluatingthe Stability and Safety of Gravity Earth RetainingStructures Founded on Rock," Technical ReportREMR CS-29, U.S. Army Engineer WaterwaysExperiment Station, Vicksburg, MS.

Ebeling, R. M., Duncan, J. M., and Clough, G. W.1990 (Oct). "Methods of Evaluating the Stability andSafety of Gravity Earth Retaining Structures Foundedon Rock-Phase 2 Study," Technical Report ITL-90-7,U.S. Army Engineer Waterways Experiment Station,Vicksburg, MS.

Ebeling, R. M., Mosher, R. M., Abraham, K., andPeters, J. F. 1993 (Sept). "Soil-Structure InteractionStudy of Red River Lock and Dam No. 1 Subjectedto Sediment Loading," Technical Report ITL-93-3,U.S. Army Engineer Waterways Experiment Station,Vicksburg, MS.

Ebeling, R. M., Peters, J., and Clough, G. W. 1992(May). "Users Guide for the Incremental Construc-tion, Soil-Structure Interaction Program SOIL-STRUCT," Technical Report ITL-90-6, U.S. ArmyEngineer Waterways Experiment Station, Vicksburg,MS.

Filz, G. M., and Duncan, J. M. 1992 (Apr). "AnExperimental and Analytic Study of Earth Loads onRigid Retaining Walls," Technical Report to theU.S. Army Engineer Waterways Experiment Station,Virginia Polytechnic Institute and State University,Blacksburg, VA.

Hilmer, K. 1986. "Evaluation of a Ten-YearMeasuring Program at the Eibach Lock."

A-1