All content in this presentation is protected – © 2011 American Power Conversion Corporation How to install PowerChute Network Shutdown 3.0 on VMware ESXi – vMA 4.0 and 4.1

ESXi-PCNS 3 installaton

Embed Size (px)

Citation preview

Page 1: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

How to install PowerChute

Network Shutdown 3.0 on

VMware ESXi – vMA 4.0 and 4.1

Page 2: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

� Basic knowledge of Linux commands and Linux administration is needed before user should attempt the installation of the software.

� PowerChute Network Shutdown (PCNS) 3.0 is required.

� PowerChute Network Shutdown requires VMware Infrastructure Management Assistant (vMA) 4.0 or 4.1 install on the VMware ESXi host.

� If you need help installing vMA please contact VMware support or go to this site http://www.vmware.com/support/developer/vima/

� The vMA client requires AMD Opteron, Rev E or later CPU or Intel processors with EM64T and VT support

� You will need VMware Infrastructure Client installed on your desktop / laptop to log into the ESXi host system. You can load the client by logging into the ESXi host via a web browser.

� Communications ports TCP 3052, 6547, 80 and UDP port 3052 need to be open.

Page 3: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Installing VMWare Infrastructure

client

Page 4: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Download the

desktop client

Enter IPaddress

To load VMware desktop Infrastructure client log into the ESXi host using a web browser and the host systems IPaddress and download the client.

Page 5: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Once the client

has been installed a shortcut to the

client will be placed on the

desktop

Page 6: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Log into the host

server

Double click on the client and the login screen will launch.

Page 7: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

View of Infrastructure Client

Page 8: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Installing vMA on host and

configuring CDROM

Page 9: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

If the vMA has not been loaded go to File – Virtual Appliances - Import.If you need help installing vMA please contact VMware support or go to this site http://www.vmware.com/support/developer/vima/

Page 10: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Import from the VMware Market place: download from http://www.vmware.com/support/developer/vima/ and navigate / browse to where you downloaded the file to and import from there. Import from URL To download any files from VMware you are required to create a user account.

Page 11: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Once the vMA client has been added select it from the list of available

virtual systems to load PCNS on.

Page 12: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

If loading PCNS from CD verify that

the CD drive is

connected on the client and the CD

is loaded into the host system CD

drive.

Page 13: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Page 14: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

From the console tab log into

the client.

Page 15: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

If one has not been created, create a mount point for the CD.

sudo mkdir /mnt/cdrom

Page 16: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Change the permissions on the new mount point

sudo chmod 666 /mnt/cdrom

Page 17: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Mount the APC CD and change directory to view

the files in the ESXi directory.

sudo mount –t iso9660 /dev/cdrom /mnt/cdromcd /mnt/cdrom/ESXi

Line CommandsLine 1 sudo mount –t iso9660 /dev/cdrom /mnt/cdromLine 2 cd /mnt/cdrom/ESXi

Page 18: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Install PowerChute Network

Shutdown 3.0 on vMA

Page 19: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

From within the ESXi directory on the

APC CD run the installation script.

sudo ./install_en.sh (for English version)

NOTE: If the install files were downloaded from APC web site you will need to copy the files to atemporary directory to be uncompressed before the program can be installed. Assuming you are copying

to /tmp the commands are

sudo cp pcns30esxi.tar.gz /tmpcd /tmpsudo gunzip pcns30esxi.tar.gzsudo tar –xvf pcns30esxi.tarsudo ./install_en.sh

Page 20: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

When running the install file accept the license and answer

the installation questions as they appear on the console.

Page 21: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

When installing be sure when asked to enter the host server ipaddress, user

name, and password. This enables communication between the vMA client and the host server.

Page 22: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Once the installation is complete open web browser to configure PCNS

Page 23: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

PCNS Configuration Wizard

Page 24: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Configuration Wizard

• The first time logging into PCNS the configuration wizard is displayed automatically. This can occur after a regular install or a silent install which failed to register PCNS with a Network Management Card.

• Post install, the user will be redirected to the PCNS web user interface. If PCNS has not previously been configured, the userwill be automatically logged in and directed to configure PCNS to ensure server protection. Once the first time wizard completes, the session ends and the user will be redirected to the login screen.

• If PCNS has been configured by this wizard or by a successful registration during a silent install, a visitor to the PCNS web user interface will be welcomed by the log in screen.

Page 25: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Since we use SSL and the browser does not know site a connection warning will appear.

You will need to accept the SSL certificate that is generated by PCNS.

Click I understand the

risk.

Page 26: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Click Add

Exception

Page 27: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Click Confirm

Security Exception

After accepting the security exception the customer will be directed to the PCNS

Configuration wizard .

Page 28: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Click next

This is the opening window for the configuration Wizard. The wizard can be accessed at anytime via the web interface and is

the same for all supported OS!

Page 29: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Enter the User Name and Password along with the Authentication PhraseThe User Name and Authentication Phrase must match the one entered on the NMCThe password can only include alpha numeric characters 0-9, a-z, A-Z

Click next

Page 30: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

If the server

has multiple

NICs you must

chose the IP

Address that

will be registered with

the NMC

Page 31: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

After choosing

the IP Address that will be

registered with

the NMC click

next

Page 32: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Select if the configuration is Single, Redundant, or Parallel UPS then

click next.

Page 33: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

In a Single-UPS configuration, each computer server or group of servers is

protected by a single UPS. That is, each server has one PCNS agent

communicating with a single NMC installed on a UPS.

Supported UPS devices: The entire Smart-UPS range of UPS devices,

including Smart-UPS VT and MGE Galaxy 3500 1- and 3-phase, Galaxy 7000,

Galaxy 300; the Symmetra 1-Phase and 3-Phase, the Symmetra PX, and the Silcon DP3500E and Silcon.

UPS

Server

Single-UPS Configuration

Page 34: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Two or more UPSs that support a load. Each UPS must be able to support the

load on its own. The additional UPSs act as reserve.

The first UPS provides all the power for the load, the others are in reserve. When the first UPS in unable to supply power, the server switches over to take

load from the next UPS

Supported UPS devices:

Smart-UPS range of UPS’s, including SUVT & G3500 (1&3-ph)

Symmetra 1-Ph & Symmetra 3-Ph.

See the updated Applications Note #98

Server

UPS

Redundant Configuration

Page 35: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Server

UPS in parallel

The combined output of several UPSs support the load. Depending on the

capacity of the load there may be reserve UPS(s) available.

Each UPS is in a Parallel-UPS configuration & must be of the same UPS

family.Supported UPS devices: SUVT,G3500(3-Ph), G7000, G300, Silcon

DP3500E&Silcon BC3.

SUVT & G3500(3-Ph) consists of 2–4 UPS’s.

Silcon, consists of 2–9 UPS’s.

See the updated Applications Note #98

Parallel Configurations

Page 36: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Enter protocol,

NMC

communication

port, and NMC ip

address then click next

Page 37: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Select whether to

check for updates,whether to

shutdown

the UPS then click

next

Page 38: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Click apply after

verifying the information is

correct.

Page 39: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

PCNS will register with the NMC

Page 40: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

If the UPS has the

proper firmware and supports outlet

groups you can

select the outlet group the server is

plugged into.

Page 41: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

For this example we selected outlet

group 1 then

clicked apply.

Page 42: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Once registered

Click next

Page 43: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Click Finish

Page 44: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

PowerChute Network Shutdown

web interface

Page 45: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

After the configuration is complete you will be logged into the PCNS clientThis is the opening page for PCNS client on all supported OS.

Page 46: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

This is the configure events page for all PCNS clients

To see a full list of configurable and non-configurable event view PCNS help

Page 47: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

If the UPS has the

proper firmware and supports outlet

groups you can

select the outlet group shutdown

behavior.

This is the configure shutdown page for all PCNS clients

Page 48: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

If the UPS has the proper firmware

and supports outlet

groups you can select the outlet

group the PCNS

client is attached

to.

This is the Set Up Communications page for all PCNS clients

Page 49: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

This is the check for Updates page for all PCNS clients

Page 50: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

How to verify communication

ports are open in the vMA and

how to add host servers to the

server list

Page 51: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

To verify the needed communications ports are open run this command

sudo /sbin/iptables –L

To open all ports – stop the firewall temporally run the command

sudo service iptables stop

To restart the firewall run the command sudo service iptables start

Page 52: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

If you would like to add additional host server to the server list (this will allow for the shutdown of multiple host by a single vMA) first check to be sure the server is not already in the list by running the command vifp listserversIf the server is not in the list add the server to the list by running the commandsudo vifp addserver 10.218.45.20 Verify the server has been addedvifp listservers

NOTE: The address of the host running the vMA should always be last in the list.

Page 53: ESXi-PCNS 3 installaton

All content in this presentation is protected – © 2011 American Power Conversion Corporation

Next you need to add the server to the fasspass list the command is vifptarget –s <server name or ipaddress> To verify there is communications between the cleint and the host run the command Vicfg-nics –l (lower case letter l) should display a list of the host NICs.