93
ES48/200-UHA01 IOM 2008.06. 09 ES48/200-UHA01 System IOM

ES48-200UHA01 IOM1014

Embed Size (px)

DESCRIPTION

ES48-200UHA01 IOM1014

Citation preview

  • ES48/200-UHA01 IOM 2008.06. 09

    ES48/200-UHA01 System IOM

  • ES48/200-UHA01 IOM

    Page: 2 of 93

    TABLE OF CONTENTS

    1 GENERAL ..............................................................................................................................................................................4 1.1 USING THIS MANUAL .......................................................................................................................................................4 1.2 SAFETY NOTICE ...............................................................................................................................................................4 1.3 ENVIRONMENTAL .............................................................................................................................................................5

    2 PRODUCT DESCRIPTION..................................................................................................................................................6 2.1 PRODUCT DESCRIPTION....................................................................................................................................................6 2.2 PRODUCT MAIN FEATURES...............................................................................................................................................6 2.3 CONFIGURATION ..............................................................................................................................................................6 2.4 SHELF OUTLOOK ..............................................................................................................................................................7 2.5 SYSTEM DIMENSIONS .......................................................................................................................................................8

    3 INSTALLATION ...................................................................................................................................................................9 3.1 TOOL REQUIRED...............................................................................................................................................................9 3.2 PRELIMINARY INSPECTION................................................................................................................................................9 3.3 SYSTEM MOUNTING .........................................................................................................................................................9 3.4 MODULE INSTALLATION...................................................................................................................................................9 3.5 SYSTEM WIRING.............................................................................................................................................................10 3.6 AC INPUT CONNECTIONS ...............................................................................................................................................11 3.7 FRAME GROUNDING .......................................................................................................................................................11 3.8 DC OUTPUT CONNECTIONS............................................................................................................................................11 3.9 SIGNAL/ALARM..............................................................................................................................................................11

    4 START - UP PROCEDURE ................................................................................................................................................13 4.1 INITIAL STARTUP PREPARATION .....................................................................................................................................13 4.2 NO LOAD START-UP .......................................................................................................................................................13 4.3 BASIC FUNCTIONAL VERIFICATION.................................................................................................................................13 4.4 PARAMETER SETTINGS ...................................................................................................................................................13 4.5 DC LOAD CONNECTIONS................................................................................................................................................14 4.6 FUNCTIONALITY CHECK .................................................................................................................................................14

    5 CONTROL & PARAMETER ADJUSTMENT.................................................................................................................15 5.1 DESCRIPTION............................................................................................................................................................15 5.2 PARAMETER SETTING .....................................................................................................................................................15 5.3 HARDWARE PARTS .........................................................................................................................................................20 5.4 FOR SOFTWARE FUNCTION ..............................................................................................................................................22 5.5 OUTPUT VOLTAGE OF SYSTEM (DC VOLTAGE) ................................................................................................................23 5.6 TEMPERATURE AND AC DE-RATING................................................................................................................................29 5.7 COMPENSATION .............................................................................................................................................................30 5.8 BATTERY TEST...............................................................................................................................................................33 5.9 BREAKER/ FUSE DETECTION ...........................................................................................................................................36 5.10 LVDS FUNCTION ...........................................................................................................................................................37 5.11 CONTROLLER POWER OFF ...............................................................................................................................................38 5.12 MODULE CONTROL TYPE.................................................................................................................................................38 5.13 EFFICIENCY MANAGEMENT (ENERGY SAVING) ...............................................................................................................38 5.14 LOCAL / INTERNET REMOTE FUNCTION............................................................................................................................39

    6 SWITCH MODE RECTIFIERS .........................................................................................................................................40 6.1 DESCRIPTION..................................................................................................................................................................40 6.2 SPECIFICATIONS .............................................................................................................................................................41 6.3 OUTLINE & DIMENSIONS................................................................................................................................................45 6.4 MECHANICAL ENDURANCE .................................................................................................................................46 6.5 ELECTROMAGNETIC COMPATIBILITY...............................................................................................................47 6.6 SAFETY STANDARD................................................................................................................................................47 6.7 SETTINGS AND CONTROLS ..............................................................................................................................................48 6.8 LIST OF REFERRED STANDARDS.......................................................................................................................48

  • ES48/200-UHA01 IOM

    Page: 3 of 93

    6.9 LIST OF USED SYMBOLS AND ABBREVIATIONS..........................................................................................49 6.10 SMR OPERATING PRINCIPLE ..........................................................................................................................................49

    7 SYSTEM ALARM DEFINITIONS.....................................................................................................................................51 7.1 INPUT VOLTAGE OF SYSTEM (AC MAIN VOLTAGE)...........................................................................................................51 7.2 DC VOLTAGE RELATIVE ALARM......................................................................................................................................51 7.3 TEMPERATURE DETECTION .............................................................................................................................................54 7.4 RECTIFIER RELATIVE ALARM ..........................................................................................................................................57 7.5 RELAY SIGNAL (DRY CONTACT)......................................................................................................................................57 7.6 OPERATION INTERFACE ..................................................................................................................................................58

    8 MAINTENANCE..................................................................................................................................................................65 8.1 CLEANING AND MAINTENANCE ......................................................................................................................................65 8.2 REMOVING AND REPLACING A RECTIFIER MODULE ........................................................................................................65

    9 REMOTE MORNITORING SYSTEM (NRMS)...............................................................................................................67 9.1 INTRODUCTION ........................................................................................................................................................67 9.2 CSU & NRMS DISPLAY SETTING..................................................................................................................................67 9.3 INSTALL AND UNINSTALL RMS SOFTWARE .....................................................................................................69 9.4 GET START NRMS SOFTWARE...............................................................................................................................70 9.5 HOW TO SETUP CONNECTION PROFILE INFORMATION .................................................................................71 9.6 SOFTWARE FUNCTION .....................................................................................................................................................74 9.7 SYSTEM INFORMATION MONITORING ...............................................................................................................................77 9.8 SYSTEM PARAMETER CONFIGURATION ...........................................................................................................................82 9.9 OTHER FUNCTION ...........................................................................................................................................................91

  • ES48/200-UHA01 IOM

    Page: 4 of 93

    1 GENERAL

    1.1 Using This Manual This manual contains specifications and instructions to properly install and maintain the DPR-2000 power system. Component specifications and drawings are contained in this manual.

    Included in this manual is the operation and maintenance of the Control Supervisory Unit (CSU), DPR-2000 Switch Mode Rectifier (SMR), system status and alarms, troubleshooting and system maintenance.

    Step by step procedures required for installation and turn-up are detailed. All equipment parameter settings, adjustments and confirmation as well as system monitoring, operations and maintenance procedures are included.

    Warnings are printed in bold lettering and alert the installation or maintenance craftsperson of a potential hazard to either or the craftsperson if the warning advisement is not followed.

    1.2 Safety Notice Products are not liable for any hazards incurred by not following proper safety procedures. Installation, Operation and maintenance personnel should always follow these safety rules:

    1. Caution - Do not install or remove any SMR with the AC Breaker On. The AC Breakers must be switched to the off position prior to inserting a module into a shelf.

    2. Before the shelf is operational, the AC input frequency and voltage must be verified, AC break rating and type is adequate, and other environmental conditions as noted in the specifications are met.

    3. The shelf has passed stringent system testing prior to shipment. To avoid electrical shock, the DPR-2000 shelf requires a single ground point permanently connected to earth ground.

    4. An AC Breaker must provide adequate isolation between the shelf input and Commercial AC Main.

    5. The environment should be dust free and controlled by an air condition system. The area must be free of any flammable vapors or fluids.

    6. To avoid electrical hazard, the covers must not be removed on any component including the CSU and Rectifier.

    7. Circuit breakers must be replaced with approved replacement circuit breakers meeting the original design specification.

    8. All AC connections must be made per the latest issue of the National Electrical Code and must also conform to all local codes.

    9. The short-circuit backup protection is rely on building installation. Please choose appropriate protective devices according to the rated input voltage and current.

  • ES48/200-UHA01 IOM

    Page: 5 of 93

    10. In a supply using more than one line conductor to a load, if a protective device interrupts the neutral conductor, it shall also interrupt all other supply conductors. Single pole protective devices, therefore, shall not be used in such cases.

    11. Protective systems or devices in PRIMARY CIRCUITS shall be in such a number and located so as to detect and to interrupt the over current flowing in any possible fault current path (for example, line-to-line, line-to-neutral, line to protective earth conductor or line to PROTECTIVE BONDING CONDUCTOR). When installed into IT power distribution system, suitable disconnect device according to item 18 shall be provided as part of the building installation.

    1.3 Environmental 1. Input Voltage: 200-240Vac, Single phase 2. Input Frequency: 50-60Hz 3. Operating Temperature: -20C~+55C (-4F~+131F) 4. Humidity: 10 ~ 95% RH (non-Condensing) 5. Floor Load Density: 600 Kg/M2 6. Space Recommended for Service:

    Front Clearance--- 12 inches minimum Rear Clearance--- 12 inches minimum

  • ES48/200-UHA01 IOM

    Page: 6 of 93

    2 PRODUCT DESCRIPTION

    2.1 Product Description The DPR-2000 Power shelf consists of modular DPR-2000 rectifiers, a Control and Supervisory Unit (CSU). Up to 3 rectifiers can be equipped in a shelf, max. 2 shelves (5 rectifiers + 1 CSU) can equip in a system. The shelf requires a nominal input of 220 Vac (single phase) and provide an output of -48 VDC to power the load and also maintain fully charged batteries.

    2.2 Product Main Features 53.5 VDC/37.4A 187A shelf (rectifiers 1-5,19 shelf * 2, 187A system).

    Hot Swappable 2000 Watts rectifiers, wide range PFC input (90~275Vac good for unstable utility environment)

    Light Weight Plug-in Modules for Simple Installation and Maintenance

    High Power Density Saves Valuable Floor space

    All rectifier modules are front accessible

    Active Power Factor Correction (> .99 PF)

    High Efficiency

    Temperature Compensation Float Voltage Control for VRLA Batteries

    Front Access for Simplified Operation and Maintenance

    Intelligent Remote Monitoring and Control (Remote Monitoring System) for Centralized

    Network Maintenance

    Battery temperature compensation voltage control

    Equalize charge timer

    2.3 Configuration AC Input: 200-240Vac, Single phase

    Shelf Capacity: 53.5VDC/110A Max.

    System Capacity: 2 Shelves, 53.5VDC/187A Max.

    Rectifier: 53.5VDC/2000W * 5 Max.

    CSU : Delta New Smart CSU

  • ES48/200-UHA01 IOM

    Page: 7 of 93

    2.4 Shelf Outlook

  • ES48/200-UHA01 IOM

    Page: 8 of 93

    2.5 System Dimensions

    19" 3U Power Supply System Configuration List

    POWER SYSTEM SHELF

    AC Terminal BlockDC OUTPUT BUS (-48V)

    CONTROLLER1

    45

    32

    Item1 5 SMR Shelf 19" 3U

    11

    11

    NCSU9 Poles

    Q'tyDescription Remark Remark

    For pitch 1" (2 hole lug terminal)DC OUTPUT BUS (0V)

    Item Description Q'ty

    For pitch 1" (2 hole lug terminal)

    Access for signal/alarm cable 1 D-SUB CABLE, 25P, Female6

    Note! 1. The shelf is fit for 19 rack. Recommended screw: M6 * 16 (L) * 8 Pcs

    Note! 2. Be sure to remain enough space both in front and rear for airflow.

  • ES48/200-UHA01 IOM

    Page: 9 of 93

    3 INSTALLATION

    3.1 Tool Required The following tools are recommended for the system installation:

    Phillips No. 3 screw driver

    Insulated slotted screw driver - blade size

    Insulated side cutters

    Metric Socket Wrenches with Extensions

    Warning! The power system intended to be installed by a service person and for installation in a service access area only.

    3.2 Preliminary Inspection Prior to removing the system from the crate, note any damage to the crate. Remove the shelf from the crate and inspect the shelf for any dents or damage. If any damage is noted, contact the carrier immediately.

    3.3 System Mounting The rectifiers mounted in a 19 shelf. The AC connections from the AC terminal to the rectifier are made at the factory. All CSU communication and signal leads are connected via the modular plugs and communicate with the rectifiers.

    Mount the shelf with a distance no less than 12 inches from the rear of the rectifier shelf to a wall. This will provide adequate ventilation for the rectifiers and for service space. The front of the shelf should be clear of all obstruction and allow room for proper ventilation, installation and maintenance. The shelf should be mounted to the superstructure and floor per customer provided equipment engineering drawings.

    3.4 Module Installation In order to minimize the weight of system, all rectifier modules can be removed from the shelf and re-installed.

    3.4.1 Rectifier Installation 1) Install rectifier modules into the shelf

    Warning! Do not force the module into the slot. If it does not slide in and connect easily, remove and re-seat the unit.

    2) Push both locker to lock position to lock the rectifier.

  • ES48/200-UHA01 IOM

    Page: 10 of 93

    3.5 System Wiring The shelf comes fully assembled and all the connections are made at the factory. There is no internal, shelf or module wiring required.

    3.5.1 Schematics

    3.5.2 I/O Connection Terminal

    D-Sub 25P female for signal/alarm access

    9P AC terminal block -48V Bus

    0V Bus

  • ES48/200-UHA01 IOM

    Page: 11 of 93

    3.6 AC Input Connections All the AC cables can be connected to shelf main terminals on the rear of the shelf.

    Input terminal block: 9 poles terminal block

    Warning! The maximum rating of overcurrent protective device shall be provided external to the system.

    Warning! A readily accessible disconnect device shall be incorporated external to the equipment. A short-circuit protective device with adequate breaking(rupturing) capacity (40A) to interrupt the maximum fault current shall be incorporated external to the system in the fixed wiring. The suitable wire cable size is 8AWG.

    Warning! Risk of electric shock. This unit has more than one power supply connection. To reduce the risk of electrical shock and disconnect all the power supply connection before servicing.

    Warning! The shelf operates at AC voltages that can produce fatal electrical shock. Installation and maintenance personnel must observe all safety precautions.

    Warning! Confirm the operating voltage before proceeding. Warning! The input feeder circuit breaker at the AC panel must be in the Off

    position before attempting to wire the shelf.

    3.7 Frame Grounding The frame ground must be connected to a permanent earth ground connection.

    Warning! Do not connect this terminal to AC power system neutral.

    3.8 DC Output Connections Both -48V and 0V terminals are Two-hole lug (M8, Pitch: 1 in)

    Recommended wire for 200A is AWG#3/0

    3.9 Signal/Alarm A 25P D-sub female connector is for signal/alarm access.

    Pin assignment:

    No. Pin Assignment No. Pin Assignment

    1 MBR-C 14 MBR-AB

    2 BBR-C 15 BBR-AB

    3 BCHF-C 16 BCHF-AB

    4 48OTB-C 17 48OTB-AB

    5 CSU Fail-C 18 CSU Fail-AB

    6 Emergency-C 19 Emergency-AB

    7 Coil+ 20 Coil-

  • ES48/200-UHA01 IOM

    Page: 12 of 93

    8 Coil+ 21 Coil-

    9 BUSBAT 22 BREAKER (Battery Breaker)

    10 IB+ 23 IB-

    11 TA-IN1 24 TA-D

    12 TBATT-IN1 25 TBATT-D

    13 Load-BK (Load Breaker)

  • ES48/200-UHA01 IOM

    Page: 13 of 93

    4 START - UP PROCEDURE

    4.1 Initial Startup Preparation Verify all connections prior to starting this section.

    Warning! Ensure the input AC circuit breaker located at the AC service panel is switched to the Off position.

    Warning! Confirm the operating voltage before proceeding.

    Warning! Ensure the frame ground is properly connected to a permanent earth ground connection.

    Failure to follow this sequence may damage the rectifier.

    4.2 No Load Start-up The shelf can be turned up without a load. The start-up procedure is as follows:

    1. Switch all DC circuit breakers (load) to the Off position.

    2. Make sure battery is not connected to the system Battery Bus.

    3. Check the CSU for alarm status.

    Example:

    Battery reversed connections:

    The PIN-9 of alarm outlet (D-Sub 25PIN) shall be connected to the battery side. (Refer the system wiring)

    a. CSU generates an alarm (Battery reversed alarm) and LED- BAT_F will be lighted on.

    b. To re-check the battery connections and re-connect them.

    Warning! Risk of explosion if battery is replaced by an incorrect type or connections dispose of used batteries according t the instructions.

    4.3 Basic Functional Verification After shelf start-up, check the monitor of CSU display.

    4.4 Parameter Settings Most parameters are pre-set at the factory and are listed on the shelf Test Report included with each shelf. This section provides a general explanation for some parameter may need changing.

  • ES48/200-UHA01 IOM

    Page: 14 of 93

    4.4.1 Float/Equalize Voltage Both Float and Equalize voltages are preset at factory and listed on the shelf Test Report. The CSU controls the system settings and overrides the settings made on each rectifier. If a different value is required, both SMR and CSU settings must be identical.

    4.4.2 Current Limit The CSU controls the system current limit threshold by monitoring the total load, the number of rectifiers in-service and the battery current. A parameter sets current limit in the event of a DC overload condition for the system and overrides the current limit set at each rectifier.

    If the CSU fails, the system will change current limit at the rectifier setting.

    4.4.3 Total Number of SMRs The CSU uses this parameter to scan for rectifier status and alarms.

    4.4.4 SMR Slot Assignment This parameter is used with the parameter Total Number of SMRs and directs the CSU to scan the assigned slots for rectifier status and alarms.

    4.4.5 Maximum Battery Capacity Battery capacity must reflect the rating of the installed battery. Refer the battery manufacture specification for the rated capacity.

    4.5 DC Load Connections

    Warning! Basic Functional Testing should be completed prior to the load being applied.

    Warning! Switch all DC circuit breakers to the OFF position.

    A. Connect the positive load cable to the Ground Bus.

    B. Connect the negative load cable to the DC breaker lug.

    C. Switch the DC circuit breakers or Load Fuse to the ON position.

    4.6 Functionality Check Control and supervisory functional testing can be performed at the CSU after the Basic Functional Testing is completed and the DC Load is connected.

    Check the status of the equipment by viewing the Main Page and by pressing button. Verify voltages, current and temperature for normal operation.

    Verify the Alarm display at the CSU to ensure that all alarm conditions are resolved.

  • ES48/200-UHA01 IOM

    Page: 15 of 93

    5 CONTROL & PARAMETER ADJUSTMENT

    5.1 Description

    5.2 Parameter Setting

    5.2.1 System Parameter Setting

    Parameter Function State Setting Setting Range Recovery Remark

    DCV Relation

    DCH DC high alarm threshold 58.0 V 56.0~58.0 V -1V 0.2V

    DCL DC low alarm threshold 46.0V 44.0~50.0 V +1V 0.2V

    HVSD DC high voltage shut down rectifiers 59.0 V 58.0~60.0 V Reset 0.5V

    LVDS1

    The value is just displayed only based on battery discharged current and battery capacity.

    40.0V Non-used

    40~48V

    LVDS2

    The value is just displayed only based on battery discharged current and battery capacity.

    40.0V Non-used 40~48V

    LVDS3

    The value is just displayed only based on battery discharged current and battery capacity.

    40.0V Non-used 40~48V

    FL Voltage To set the floating charge voltage value 53.5 V 50.0~56 V 0.1V

    EQU Voltage To set the equalizing charge voltage value 57 V 50~57 V 0.1V

    Ambient temperature Relation

    TAH TA high alarm 67 35 ~ 75 -5 3

  • ES48/200-UHA01 IOM

    Page: 16 of 93

    TAL TA low alarm -5 -40 ~ 10 +5 3 ACV Relation

    ACH AC input voltage high alarm 264V 230~330V -5Vac 5Vac

    ACL AC input voltage low alarm 180 V 90~229 V +5Vac 5Vac

    Energy Saving

    Enable/Disable To enable/disable this function Enable Enable/Disable Set Date and Time To set RMS date/time YY:MM:DD hh:mm:ss Current date/time

    LVDS Manual Trip

    LVDS1 Trip To trip LVDS1 manually Default

    LVDS2 Trip To trip LVDS1 manually Option

    Rectifier Relation Over percentage of capacity

    The load is over the backup power of rectifiers output. 80% 50%~90%

    5.2.2 System-1 Parameter Setting

    Parameter Function State Setting Setting Range Recovery Remark

    BBR Battery Breakdown 44.0V 40~50V +1V 0.2V

    Cut-off CSU Delay time

    The delay time to cut off controller after battery LVD trip.

    30sec 30~60sec

    AC restores and one rectifier power on

    1 sec

    The conditions which LVDS be opened

    HTSD TA high temperature to shut down all rectifiers and disconnect battery.

    70 65~70 3

    HTSD Hysteresis HTSD recovery hysteresis setting 13 3~45 3

    LTSD TA low temperature to shut down all rectifiers and disconnect battery

    -20 -40~-10 3

    LTSD Hysteresis LTSD recovery hysteresis setting 15 3~45 3

    LVDS open by TBH Battery disconnect by TBH condition 54 36 ~ 55 3 3

    LVDS open by TBL Battery disconnect by TBL -8 -10 ~ 5 3 3

    Emergency

    DCV Under

    Condition-1: DC voltage is under this condition to generate emergency alarm

    47V 40~50V N-1 or N rectifiers power on

    Continue Discharge Condition-2: Battery discharge current is over 3A continue 5 minutes

    5min 1~10min N-1 or N rectifiers power on

  • ES48/200-UHA01 IOM

    Page: 17 of 93

    5.2.3 Battery Parameter Setting

    Parameter Descriptions Function State Setting Setting Range Specification

    Battery

    Capacity Based on real battery capacity in system

    150 AH 0~6000 AH

    TBH

    Battery temperature high alarm to stop EQU/boost charge function

    35 30~50 Recovery: -5

    Middle test voltage Battery middle voltage alarm threshold

    1V 0.5V ~ 4V No used in this system

    Battery Charge Current

    SMR Max Current Limit

    Controller maximum command for each rectifier

    41.6A 1A~42A 2A

    Battery charge management EQU/Boost charge for battery current limitation

    Enable Enable/Disable

    Stage1 charge Limit Battery current limitation in stage-1 0.20C 0.05C~0.5C

    Stage2 charge Limit Battery current limitation in stage-2 0.15C 0.05C~0.5C

    Stage3 charge Limit Battery current limitation in stage-3 0.10C 0.05C~0.5C

    5.2.4 Battery Test

    Parameter Descriptions Function State Setting Setting Range Specification

    Battery Rough Test

    Test Volt End of test voltage 44.0V 44~50V 0.5V

    Test Time Test period 20min 0~255min 5min

    Test Result Display testing result after system is satisfied test conditions.

    Good, Fail, Inconclusive

    Battery Capacity Test

    Terminal Volt(50% Cap) End of test voltage 44.0V 44~50V 0.5V

    Test Curr Testing battery discharge current 0.22C 0.05~1C 2%

    Expectable Capacity(%) Expectable battery reserved capacity 5% 1~100% 1%

    Test Result Display testing result after system is satisfied test conditions. Good, Fail, Inconclusive

    Estimative Capacity Show real reserve/calculated battery capacity after the battery capacity test is passing. Periodic Battery Test

    Battery Periodic Enable this function or not Disable Enable/Disable

    Test Period Cycling period - Month 1 Month 1~12 Month

  • ES48/200-UHA01 IOM

    Page: 18 of 93

    Test Date Testing date in one month 1day 1~31day

    Test Oclock Testing time in one day 2 Oclock 0~23 Oclock 20 min

    Last Battery test time 2008/04/10 19:40:00

    Next Battery test time 2008/05/01 02:00:00

    5.2.5 Temperature Compensation

    Parameter Descriptions Function State Setting Setting Range Specification

    Temp compensation To enable this function Enable Enable/Disable

    Compensation mode To select the compensation mode

    1 0(Linear)/1(Curve)

    Linear

    Temp Comp Coefficient Compensation coefficient 4 mV/ 0.1~4mV/

    Temp Comp Range Compensation voltage limitation 1.3V 1.3V 0.2V

    Temp Comp Center Central temperature value

    25 18~27

    Curve

    Battery Type Selected

    To select default battery compensation type

    Hoppecke Hawker Powersafe/Hoppecke Enter/Cancel

    T0 Customer definable -5 -20~+60

    V0 Customer definable 57.6V 50.0~58.0V

    T1 Customer definable -5 -20~+60

    V1 Customer definable 57.6V 50.0~58.0V

    T2 Customer definable -5 -20~+60

    V2 Customer definable 57.6V 50.0~58.0V

    T3 Customer definable 40 -20~+60

    V3 Customer definable 51.6V 50.0~58.0V

  • ES48/200-UHA01 IOM

    Page: 19 of 93

    5.2.6 EQU

    Parameter Descriptions Function State Setting Setting Range Specification

    EQU To enable this function Disable Enable/Disable

    Inhibit EQU by TBH Battery temp is over this setting to stop EQU/boost charge mode

    35 30~40 3

    EQU max time Maximum EQU/boost charge period 10 hour 1 ~ 24 hour

    Additional EQU Time Additional charge time 1 hr 0~12 hr

    EQU Terminal curr

    The charged current is lower than this setting to stop EQU/boost charge mode

    0.05C 0.01C ~ 0.05C

    Periodic EQU

    EQU periodic To enable this function Disable Enable/Disable

    EQU period Cycling period - Month 1 Month 1~12 Month

    EQU Date EQU date in one month 2 1 ~ 31

    EQU 0clock EQU time in one day 0 0 ~ 23

    Last Battery test time 2008/04/10 19:40:00

    Next Battery test time 2008/05/01 02:00:00

    Boost Charge Condition

    Capacity Remain To enable this condition Disable Enable/Disable

    Deep voltage To enable this condition Disable Enable/Disable

    AC off time To enable this condition Disable Enable/Disable

    Charge Current To enable this condition Disable Enable/Disable

    Capacity Remaining

    System will change to boost charge mode, if Battery discharge capacity is lower than the setting.

    80

    Deep voltage

    System will change to boost charge mode, if DC output voltage is lower than the setting.

    46V 42V~48V

    AC off Time System will change to boost charge mode, if AC off time is over the setting.

    1Hr

    Charge Current

    System will change to boost charge mode, if Battery charge current is over the setting.

    0.08C 0.03C ~ 0.15C

    5.2.7 Alarm Mask

    Parameter Descriptions Function State Setting Setting Range Specification

    Current limit Mask/un-mask Un-mask

    1 rectifier fail Mask/un-mask Un-mask

    More rectifiers fail Mask/un-mask Un-mask

    Major Mask/un-mask Un-mask

    Minor Mask/un-mask Un-mask

  • ES48/200-UHA01 IOM

    Page: 20 of 93

    Load Breaker Mask/un-mask Un-mask

    Load priority Hi Mask/un-mask Un-mask

    Load priority Lo Mask/un-mask Un-mask

    Load fuse Mask/un-mask Un-mask

    Rail Mask/un-mask Un-mask

    GMT fuse Mask/un-mask Un-mask

    DCH Mask/un-mask Un-mask

    DCL Mask/un-mask Un-mask

    LVDS Trip Mask/un-mask Un-mask

    TAH Mask/un-mask Un-mask

    TAL Mask/un-mask Un-mask

    TA Sensor fail Mask/un-mask Un-mask

    ACH Mask/un-mask Un-mask

    ACL Mask/un-mask Un-mask

    AC Breaker Mask/un-mask Un-mask

    AC phase lost Mask/un-mask Un-mask

    TB sensor fail Mask/un-mask Un-mask

    TBH Mask/un-mask Un-mask

    Battery fuse Mask/un-mask Un-mask

    Battery discharge Mask/un-mask Un-mask

    Battery Breaker Mask/un-mask Un-mask

    Middle test fail Mask/un-mask Un-mask

    Battery test fail Mask/un-mask Un-mask

    Rect. Over Percent of Capacity Mask/un-mask Un-mask

    5.2.8 WEB (Optional)

    Parameter Descriptions Function State Setting Setting Range Specification

    IP Address 0.0.0.0

    Subnet Mask 0.0.0.0

    Gateway 0.0.0.0

    Web IP Follow ClassA,B,C/ Ignore ClassA,B,C Follow ClassA,B,C

    5.3 Hardware parts

    5.3.1 From AC side AC input1 is supported for rectifier-1 and rectifier-3;

    AC input2 is supported for rectifier-2 and rectifier-4;

    AC input3 is supported for rectifier-5.

    AC protection and surge arrestors for each AC terminal;

  • ES48/200-UHA01 IOM

    Page: 21 of 93

    Three AC transformers detections for three AC input terminals.

    5.3.2 From DC side DC surge arrestors for system BUSBAR to avoid the 0.5kV@8/20us (surge testing criteria) and 5*Un @

  • ES48/200-UHA01 IOM

    Page: 22 of 93

    Special Criteria: The CSU-fail alarm relay is combined into this function. In case the controller is failed, and then the alarm relay will be activated and turn off the controller.

    Note! 1. The product contains 3V/195mAH Lithium battery that must be processed according to applicable local regulation concerning batteries.

    Note! 2. The battery shall be disposed and recycled in compliance with local disposal regulations.

    Warning! Danger of explosion if battery is incorrectly connected or replaced. Use only approved replacement batteries.

    5.4 For software function

    Detection Output voltage of system (DCV). To set the output voltage:

    Float voltage

    Equalize voltage

    Boost mode

    Periodic mode

    Manual mode

    Detection AC power input voltage of system (ACV). Signal phase

    Three phases (Option)

    Three single-phases inputs for NSN (ISARIII)

    Current limitation Battery charge

    Over temperature

    AC low de-rating

    Compensation. DC output voltage compensation

    Battery temperature compensation

  • ES48/200-UHA01 IOM

    Page: 23 of 93

    Based on two typical battery graphs for battery compensations and one more

    additional battery compensation graph set by customers.

    Detection system ambient and battery temperature

    Circuit Breaker Trip-Off Detection.

    One breaker detection. (Individual breaker trip detection)

    Relay Output:

    Dry Contactor with two pins (NO, Com), 6 maximum and definable.

    LVDS (Low Voltage disconnect): One LVDSs controllable.

    Security protection (Technical Level password for parameter settings)

    NRMS: There are three levels to access NRMS, which FACTORY / ADMINISTRATION /

    USER.

    History record 100 events after power-off.

    User friendly interface 7 segments LED indicators

    1 push button to select DCV/DCI display;

    1 LED indicates the DCV or DCI;

    10 Alarm LED indicators

    5.5 Output voltage of system (DC voltage) Charge mode: Float and Equalize charge mode.

    5.5.1 Float voltage Regulated voltage used to maintain a battery in a fully charged state. Its systems normal operating voltage.

    Function Default Range Tolerance Adjustment Step

    Float voltage 53.5V 50.0 ~ 57.0V 0.5% 0.1V

    5.5.2 Equalize voltage:

    Regulated voltage used to charge batteries and to equalize the voltage of its individual cells.

  • ES48/200-UHA01 IOM

    Page: 24 of 93

    5.5.2.1 Boost mode:

    Whenever batteries are deeply discharged (AC fail or battery test), system start EQU charge process if system was able to charge the batteries. Function: Enable / Disable

    Active criterion:

    When battery state is transferred from discharging to charging. System is monitoring battery status if it satisfied below active condition. System will start boost charge function.

    Start Mode Selection: Capacity / Voltage / Time Capacity Mode

    Function Default Range Tolerance Adjustment Step

    Remain Battery Capacity percentage

    (RC)

    80% 30~90% 2% 1%

    Remain capacity of Batteries = Battery capacity (C) x Remain capacity percentage

    Voltage Mode:

    Function Default Range Tolerance Adjustment Step

    Deeply Discharge

    Voltage (DDV)

    46.0V 44.0 ~48.0V 0.5% 0.1V

    Time Mode:

    Function Default Range Tolerance Adjustment Step

    Deeply Discharge Time (DDT)

    1Hr 0Hr ~24Hr 5min 1Hr

    System count deeply discharge time during AC down (main fail).

    Charging Process: The percentage factor of battery boost charge current:

    Function Stage Current Factor (range)

    End Condition

    Window Current Tolerance

    1 0.20C (*1)

    (0.10C~1.00C)DDV+1 1.0V 2%

    2 0.15 C

    (0.05C~0.50C)Float

    Voltage 1.0V 2%

    Boost Charge

    3 Follow manual & Periodic charge method

    *1. C: Battery Capacity

  • ES48/200-UHA01 IOM

    Page: 25 of 93

    Controller follows float and equalize voltage to separate stage 2 and stage 3 current limitations. Initial maximum recharge current follows stage-1 current limit

    Charg

    e Volt

    age

    and C

    harge

    Cur

    rent

    Time

    Stage - 1 Current Limit

    Stage - 2 Current Limit Stage - 3

    Current Limit

    Float VoltageDeeply Discharge Voltage EqulizeVoltage

    Figure Charging characteristics of the boost charge

    The percentage factor of battery manual / periodic charge current:

    Function Default

    (Percentage Factor)

    Range

    (Stage 3 Percentage Factor)

    Tolerance Adjustment Step

    Manual/Periodic charge

    0.10C 0.05C ~ 1.00C 2% 0.01C

    Battery charge current(Limited current) = Battery capacity x percentage factor

    - System recovery criterion:

    Function Default Range Tolerance Adjustment Step

    Min. Charge current

    percentage

    0.10C 0.01C ~ 1.00C 2% 0.01C

    Extended Time 1Hr 0 ~ 10Hr 5 Min. 1Hr

    Max. Charge Time

    10Hr 10 ~ 20Hr 5 Min. 1Hr

  • ES48/200-UHA01 IOM

    Page: 26 of 93

    - Minimum charge current = battery charge x Min. charge current percentage

    - Battery Capacity and percentage factor are adjustable.

    - Charge Current and Interruption condition follow below Charge Interrupted condition.

    - PS: System has two ways to stop battery charge function in normal condition.

    1. Maximum charge time is one that system stops battery charge function. Battery charging time and Extended time are not over maximum charge time.

    2. Battery charge current is lower than minimum charge current and charge time is over extended time then system will stop charge function.

    Charge current = Recovery criterion

    Charge current > Recovery criterion Charge current < Recovery criterion

    Equalize Charge Voltage

    Float Charge Voltage

    Voltage

    Time

    Extend Time

    5.5.2.2 Periodic mode The battery was periodic recharge for compensating self-discharge of battery.

    Function: Enable / Disable

    Function Default Range Tolerance Adjustment Step

    Charge Voltage 57V 55.0~ 57.0V 0.5% 0.1V

    Recharge Cycle 1M(*1) 0 ~12M 10 Min. 1M

    *1. M = Month

    System Next Charge Tolerance

    Periodic Charge Time

    MM : DD : HH : mm : ss

    MM : DD : HH : mm : ss

    10 Min.

    PS: Next Charge Time = Periodic Charge Time (Function start Time) + Cycle Time.

    Figure Illustration of battery charge recovery method

  • ES48/200-UHA01 IOM

    Page: 27 of 93

    The battery charge condition and system recovery criterion are the same with the stage - 3 of boost charge. The percentage factor of battery periodic charge current:

    Function Default

    (Percentage Factor)

    Range

    (Stage 3 Percentage Factor)

    Tolerance Adjustment Step

    Manual/Periodic charge 0.10C 0.05C ~ 1.00C 2% 0.01C

    Battery charge current(Limited current) = Battery capacity x percentage factor

    System recovery criterion:

    Function Default Range Tolerance Adjustment Step

    Min. Charge current percentage 0.10C

    0.01C ~ 1.00C 2% 0.01C

    Extended Time 1Hr 0 ~ 10Hr 5 Min. 1Hr

    Max. Charge Time 10Hr 10 ~ 20Hr 5 Min. 1Hr

    - Minimum charge current = battery charge x Min. charge current percentage

    - Battery Capacity and percentage factor are adjustable.

    - Charge Current and Interruption condition follow below Charge Interrupted condition.

    - PS: System has two ways to stop battery charge function in normal condition.

    1. Maximum charge time is one that system stops battery charge function. Battery charging time and Extended time are not over maximum charge time.

    2. Battery charge current is lower than minimum charge current and charge time is over extended time then system will stop charge function.

    5.5.2.3 Manual mode Technician through RMS or push button controls system to switch float to equalize voltage mode.

    Below parameter settings are the same with periodic model.

    Function Default Range Tolerance Adjustment Step

    Charge Voltage 57V 50.0~ 57.0V 0.5% 0.1V

    The battery charge condition and system recovery criterion are the same with the stage - 3 of boost charge. The percentage factor of battery periodic charge current:

    Function Default

    (Percentage Factor)

    Range

    (Stage 3 Percentage Factor)

    Tolerance Adjustment Step

  • ES48/200-UHA01 IOM

    Page: 28 of 93

    Manual/Periodic charge

    0.10C 0.05C ~ 1.00C 2% 0.01C

    Battery charge current(Limited current) = Battery capacity x percentage factor

    System recovery criterion:

    Function Default Range Tolerance Adjustment Step

    Min. Charge current

    percentage

    0.10C 0.01C ~ 1.00C 2% 0.01C

    Extended Time 1Hr 0 ~ 10Hr 5 Min. 1Hr

    Max. Charge Time

    10Hr 10 ~ 20Hr 5 Min. 1Hr

    - Minimum charge current = battery charge x Min. charge current percentage

    - Battery Capacity and percentage factor are adjustable.

    - Charge Current and Interruption condition follow below Charge Interrupted condition.

    - PS: System has two ways to stop battery charge function in normal condition.

    1. Maximum charge time is one that system stops battery charge function. Battery charging time and Extended time are not over maximum charge time.

    Battery charge current is lower than minimum charge current and charge time is over extended time then system will stop charge function.

    Battery Capacity:

    Function Default Range Tolerance Adjustment Step

    Battery Capacity 150AH 70~ 6000 AH 2% 10AH

    5.5.2.4 Charge and Interrupted condition: Charge Current:

    Charge current depends on parameter setting of system. If CL (Current Limit) factor is boost / periodic mode, system will follow battery capacity and battery factor (percentage factor) to calculate battery charge current. If CL (Current Limit) factor is manual mode, system will follow customer setting to work battery charge function.

    - Interruption:

    If system happened

    Any one of Battery Temperature is High alarm except stage 1and stage 2 of boost charge mode.

    The Sum of load and battery charge current is over 95% of system capacity.

    System is working in battery test (periodic & manual)

  • ES48/200-UHA01 IOM

    Page: 29 of 93

    Note: CSU will cancel periodic battery test function during system in equalize charge function. And Start time of periodic battery test will be removed to next schedule.

    All Battery Temperature sensors all fail

    Manual switch to float charge mode by RMS, LCD and Button on CSU

    Battery charge time is over maximum charge time.

    Battery charge current is lower than minimum charge current and charge time is over extended time

    AC fail alarm or ACL (70 ~ 90Vac)

    SMR work no (DCOK, No alarm)=0

    In case the battery temperature is above than +35(3), the function will be disabled automatically. It also will be enabled again automatically as soon as the battery temperature drops below +33(1).

    System will stop EQU charge.

    System doesnt execute periodic charge function during battery testing, but manual EQU charge will stop testing procedure and start manual EQU process.

    5.5.2.5 Current Limit Control Mode: Auto/Manual

    Auto: Current limit value follows EQU limit charge criteria.

    Manual: Current limit control by user parameter setting.

    When in Manual Mode, Battery charge current limit function is disabled.

    Function Default

    (Percentage Factor)

    Range

    (Stage 3 Percentage Factor)

    Tolerance Adjustment Step

    Manual 0.10C 0.05C ~ 1.00C 2% 0.01C

    Note: The minimum controlled current of rectifier is 1 A.

    5.6 Temperature and AC de-rating

    5.6.1 Over temperature This part is limited by SMR. Not controlled by CSU

    High temperature will damage rectifiers, when rectifiers are fully output and high temperature. Rectifiers control temperature de-rating by itself. Control rule depend on rectifier type.

    5.6.2 AC low de-rating Rectifier is fully output during AC voltage low, some components will be getting and damaged. This function is controlled by each rectifier itself automatically.

  • ES48/200-UHA01 IOM

    Page: 30 of 93

    Function AC input voltage under setting of rectifier

    AC input voltage above setting of rectifier

    Window Tolerance

    Low AC input

    De-rating

    Linear de-rating 100% 5V 2%

    This part is controlled by SMR.

    5.7 Compensation

    5.7.1 DC output voltage compensation Sometimes system output voltage happened tolerance or heavy load. Output voltage doesnt meet requirement. Controller uses this function to correct error.

    Function Default Range Tolerance

    Compensation 0 1 ~ +1V 2%

    - Interruption:

    If system happened When system is current limit Battery under test. Zero Rectifier work (DCOK, no alarm) AC fail

    System will stop voltage compensation.

    5.7.2 Battery temperature compensation Temperature compensation of charge voltage is to prevent the thermal runaway of battery when it is used in high temperature conditions and to secure sufficient charge of the battery when it is used in low temperature condition. Controller provides two methods for temperature compensation, one is linear compensation, and another is characteristics curve of battery. Technicians can choice one of two methods to improvement compensation.

    Temperature Compensation Mode: Linear/Curve/Graphs(Based on different battery types) Method I: Linear

    Range:

    Default Range Tolerance Adjustment Step

    Normal 0 -1.3V~+1.3V 2% 0.1V

    Coefficient:

    Range Default Range Adjustment Step

    Normal 2mV 0~5 mV/ cell 0.1V

    Function Default Range Adjustment Step

    Temperature reference 25 18 ~ 27 1

  • ES48/200-UHA01 IOM

    Page: 31 of 93

    Method II : Curve Battery temperature compensation follows battery specific curve. There are 3 coefficients to draw battery curve. Technician uses NRMS software to fill in coefficients and define curve line.

    Offer 4 points (Temp,Volt) to describe the curve .

    Battery Temperature ()

    Coefficient 2

    Temperature

    Coefficient 3

    Output Voltage (V)

    Temperature Reference (Default: 25)

    Float Voltage

    Coefficient 1

    Output voltage

    -15 10 30 50

    Figure Illustration of battery characteristics method

    Slope: Temperature coefficient (mV/)

    Coefficient 4

  • ES48/200-UHA01 IOM

    Page: 32 of 93

    Method III: Battery graphs Hawker Powersafe

    Method IV: Battery graphs - Hoppecke

  • ES48/200-UHA01 IOM

    Page: 33 of 93

    5.8 Battery Test The purpose of battery test is battery function confirmation. Controller bases on discharge current (Constant current) and discharge time to calculate battery lost capacity. Measurement of discharge current is according to load discharge current.

    5.8.1 Battery Rough Test: This battery test mode is only manual mode, and the technician can enable/disable this function through NRMS, and push button of front panel.

    Test Criteria

    In case the battery rough test is started, the output voltage of rectifiers will be decreased to lower than 2Vdc of the threshold setting Rough test voltage.

    Example:

    When discharging time > 20min, and battery discharging voltage >44V, the test result is OK.

    When discharging time > 20min, and battery discharging voltage

  • ES48/200-UHA01 IOM

    Page: 34 of 93

    Rough test OK, Rough test Fault

    Note: Refer to the section 5.6.5 for the interruption conditions.

    5.8.2 Battery Capacity mode The battery capacity test can be set in periodic or manual modes, and technician can set relative parameters via NRMS.

    Periodic Mode:

    Next Test Tolerance

    Capacity Test Time

    MM : DD : HH : mm : ss 20 Min.

    PS: Next Test Time = Periodic Test Time + Cycle Time.

    Function Cycle Time Range Tolerance Adjustment step

    Capacity Test Cycle

    0 M 0 ~12M 20 Min. 1M

    Note: Battery Capacity test discharging current = 0.22C = 0.22 x battery capacity setting (AH)

    Manual mode:

    The technician could enable/disable this battery capacity test via NRMS or push button of controller front panel.

    Test criteria:

    1. The battery capacity test will be completed when the battery voltage reaches the threshold value. (Capacity test voltage)

    2. In case the battery calculated capacity is higher than threshold (Expectable capacity), the testing result is considered Good. Otherwise, the result is fail.

    3. In case the interrupted conditions occur, the testing result is inconclusive.

    Function Default Range Tolerance Adjustment Step

    Capacity Test Voltage

    44.0 V 44V~50V 2 % 0.1V

    Capacity Test Discharge

    Current

    0.22C 0.05C ~ 1.00C 2% 0.01C

    Expectable Capacity

    5% 0~100% 1% 1%

    Capacity Test Switch

    OFF ON/OFF

  • ES48/200-UHA01 IOM

    Page: 35 of 93

    4. The above testing result will be indicated on Event Logs screen of NRMS.

    5. If the testing result is passing, the estimated values of actual battery capacity will be indicated on NRMS screen. The estimated value is twice the value of the totally cumulated Ampere hours.

    5.8.2.1 Battery test result Battery Rough Test:

    The testing result has Rough test OK, and Rough Test Fault showed on the Event Logs of NRMS.

    In case the result is fault, this alarm message is also displayed on Alarm screen of NRMS.

    Battery Capacity Test:

    The testing result has Good, Fail, and Inconclusive, which can be showed on Event Logs of NRMS.

    In case the result is fail, this alarm message is also displayed on Alarm screen of NRMS.

    5.8.2.2 TEST Fail Recover Press Alarm clear button via NRMS or push button of controller front panel to reset the alarm.

    5.8.2.3 System mode after battery testing - If system status has satisfied boost charge active condition. System will start

    boost charge function, when test was finished.

    - Boost charge after testing:

    - If CL (Current Limit) factor is Auto Mode and boost function is enabled, system will follow boost charge process to charge the battery.

    5.8.3 Interruption conditions for battery rough test / capacity test - Interruption:

    If the following system situations are happened:

    Technician terminates the test function via push button of controller or LCD/NRMS manually.

    AC is out of specified range alarms. (AC fail, ACHV or ACLV alarms)

    All rectifiers are fault

    Any one of Battery temperature is out of range. (10 ~ 35) All Battery temperature sensors fail.

    Ambient/cabinet temperature protection alarms (HTSD, LTSD)

  • ES48/200-UHA01 IOM

    Page: 36 of 93

    Battery LVD contactor is opened.

    Battery capacity setting is zero.

    Real battery discharging current shall be over setting threshold Capacity discharge current for battery capacity test.

    Battery fail alarm

    System will stop battery test, if the above conditions occur.

    5.8.4 Battery management Process Priority BOOST > Capacity Test > Rough Test > EQU

    Means: system may get in TEST mode (by schedule or manual) when in EQU mode. But when system is in TEST mode, periodic EQU function cannot interrupt it.

    5.9 Breaker/ Fuse detection Breakers detection

    Use the Aux-switch of battery breaker or Load breaker as below system wiring.

  • ES48/200-UHA01 IOM

    Page: 37 of 93

    5.10 LVDS function When system is in Battery Deep discharge protection mode, the LVDS function follows the below conditions.

    Criteria: Battery Deep discharge protection In order to guarantee optima operation during the entire lift time and protect from damage battery must not be discharged below special minimum voltage. This minimum voltage depends on battery capacity and load of battery.

    In case the function is enabled via NRMS, the LVD voltage threshold will follow the below criteria.

    Open criteria:

    1. Battery duty = battery capacity (AH) divided by battery current (A)

    2. Battery load = the average values of last 10 seconds measured data.

    3. LVD Trip voltage is based on the battery duty and below table to define the actual trip-voltage.

    LVD Trip voltage threshold: 43.2Vdc @ Battery duty >9 hrs;

    LVD Trip voltage threshold: 42.0Vdc @ 6hrs < Battery duty 9hrs; LVD Trip voltage threshold: 40.8Vdc @ 2hrs < Battery duty 6hrs; LVD Trip voltage threshold: 40.0Vdc @ 0hr < Battery duty 2hrs;

    Connect criteria:

    1. DCV > LVDSV+2V

    2. Any one of SMR is working (No alarm, DC OK)

    3. AC restores

  • ES48/200-UHA01 IOM

    Page: 38 of 93

    When system is in TEST mode, LVDS function is disabled.

    Note: LVD control hardware

    During normal operation: -DC voltage(-48Vdc nominal)

    Otherwse the output control: Open or 0Vdc.

    5.11 Controller power off The purpose is to avoid battery discharge deeply. The function will be based on battery LVD trip situation and the delay time to cut-off controller power.

    Default voltage Range (Trip Time)

    Tolerance Window & Recovery condition

    Time Cut-off CSU

    30 sec 30 sec ~ 60 sec 1 sec AC restores and 1

    rectifier power on

    Special conditions:

    1. In case HTSD/LTSD or HTBSD function is activated, the controller shall cut-off by itself within 30 sec as soon as the dc-voltage drops below 40.5V 0.5Vdc.

    2. In case system output voltage is below 40.5 V 0.5Vdc, controller shall disconnect the battery LVDS and then cut-off itself after 30 seconds.

    Recovery condition: AC restores and either one of rectifier is powered on.

    5.12 Module control type DPR2000 serial module (Digital type communication)

    5.13 Efficiency Management (Energy Saving) Definition

    In order to system works to more efficiency and extend rectifiers life. So CSU control rectifiers on or off to improve system efficiency

    Enable/Disable

    Operation process:

    Rectifier operating cycling: 12hrs to switch on and off a rectifier if no any alarm during the energy saving mode. And rectifiers switch on and off sequence follow rectifiers ID in system. Rectifiers on and off process follow turn rectifiers on first then turn off rectifiers. Energy saving mode function keep rectifier output with 50% ~ 85 % rectifier capacity.

  • ES48/200-UHA01 IOM

    Page: 39 of 93

    Energy saving mode to be stopped when following situations.

    9 Any alarm trigger. 9 Conflict with battery test mode. 9 Periodic, Manual or Boost charge. 9 Battery discharge.

    5.14 Local / internet remote function

    5.14.1 Local remote NRMS (New Remote Monitoring Supervisor), Delta provides convenient and friendly PC software to remote control and monitor system. It is in a Windows based PC via dial-up RS-232 interface port. If the CSU is connected to a modem, it can remote control and monitoring by communicating remotely over a telephone line with PC loaded with the RMS software package. The detail description refers to Delta NRMS Quite User Guide.

  • ES48/200-UHA01 IOM

    Page: 40 of 93

    6 SWITCH MODE RECTIFIERS

    6.1 Description Deltas DPR2000 series is a compact and very reliable family of front-end rectifier offering 2000W constant power output (From 48Vdc to 59.5Vdc, under 48Vdc is constant current output). The modular design provides the flexibility to configure and expand the system as the load demand increases. Each rectifier is hot swappable with front access for ease of maintenance without system shutdown providing uninterrupted service.

    DPR2000 series is active power factor corrected to great than 0.99 PF (THD

  • ES48/200-UHA01 IOM

    Page: 41 of 93

    6.2 Specifications

    6.2.1 Input Item Specifications Remark Nominal 230Vac / Single Phase Vinrmsnom Input characteristics Voutdcnom: 53.5Vdc; Tamb: 55C

    No PFC

    31080 90 176 300

    2000

    Max. Pout/ W

    230 Vin / Vrms276

    1000

    Rectifier is not working but safe when voltage below 90Vac 310V to 400V is allowed for 2hr rectifier is not working but safe.

    Input current Max: 14 Arms Vinrms 176 & 2000W Vinrms 90V & 1000W

    Inrush current 0.99 Vinrmsnom , Voutdcnom,

    and Poutdcmax Harmonic content EN 61000-3-2 class A ( 5%)

    100Hz 2KHz Vinrmsnom , Voutdcnom, and Poutdcmax

    Input connector FCI 51939-211 Input protection 2 x 16A time lag T, type Littelfuse

    314 series L,N

    Mains on/off switch None Drop out The rectifier remains operation

    when subject to repeated application of AC half cycle drop out.

    AC is on 50/60Hz and Vinrmsnom Full load There shall be 3.5cycles of normal AC power between each dropout

    No damage to rectifier when following condition occurs: Either 50 or 60Hz and Vinrmsnom Full load The off time > 70ms AC

    T

    off time

  • ES48/200-UHA01 IOM

    Page: 42 of 93

    6.2.2 Output Item Specifications Remark Nominal voltage 53.5V (Factory default), adjustable Voutdcnom Nominal current 37.40A @ 53.5V Output characteristics

    Constantvoltage

    37.40

    Constantcurrent

    Factory setting

    41.70

    59.5

    Vout / Vdc

    33.64Iout / Idc

    53.5

    48

    Adj

    ustm

    entr

    ange

    40

    Constant power

    Output power vs temperature . 2000W @ 55 Degree C . 1800W @ 65 degree C

    Poutdcmax: 2000W Ioutdcnom: 37.40A

    Current limit Max. 41.7A, adjustable Efficiency 91.0% (50%~100% load)

    Vinrmsnom, Voutdcnom, Tambnom

    Current sharing 5% of nominal output current 50% to 100% load Line regulation 50mV Vinrmsnom Vinrmsmin

    respectively Vinrmsnom Vinrmsmax

    Load regulation 250mV Voutdcnom, Vinrmsnom and Tambnom with Ioutdc varied from 0.5Ioutdcnom to 0 or Ioutdcnom

    Temperature regulation

    100mV Tamb variations Tambnom .. Tambmax respectively Tambnom ..Tambmin

    Start up delay Output start-up time (Time1):310s Remark: Measured from mains turn-on to Vout within 1% of Voutdcnom, Ioutdc=0, Vinrms=Vinrmsnom and Tambnom.

    AC ON

    AC OFF

    DC Nominal

    DC 0V

    TimeTime 1

    DC42 V

    Output connector FCI 51939-211 Output protection 3 x 20A fuse in parallel Output short circuit No damage to rectifier once short

    circuit condition occurs. The rectifier restarts automatically once fault release. The rectifier automatically detects short circuit for 10 seconds, if the short circuit condition persists, the rectifier will latch for 1 minute then detect short circuit again.

  • ES48/200-UHA01 IOM

    Page: 43 of 93

    Noise Audio band

    24 dBrnc 40 dBrnc

    CCITT, connect battery No battery connection

    Wide band 15 mVrms 10KHz~100MHz Peak to peak ripple voltage

    100mV

    BW = 0...20MHz

    Narrow band 5 mV 3 mV 2 mV 1 mV

    3.4KHZ~150KHz 150KHZ~200KHz 200KHZ~500KHz 500KHZ~30MHz

    Acoustic noise < 50 dB(A) at the distance of 1m in front of rectifier with 1.5m height

    Vin=230Vac,25 degree C ambient,

    Dynamic response Overshoot Recovery time

    5% of Voutdcnom

  • ES48/200-UHA01 IOM

    Page: 44 of 93

    6.2.4 Environmental Specification Item Specifications Remark Operating temperature

    -40C ... 75C

    2000

    Ambient

    OTPshuts down

    Power limit

    Rectifierrestart

    65C55C 75C

    1800

    Vinrms: 176

    1500

    70C 77C

    With power derating Tambnom: 25C To warn up the components inside, the SMR will start up without any DC output for the first ten minutes at the temperature between -15C and -40C. And it can operate with full load immediately after that.

    Storage temperature

    - 40C .. + 75C

    Humidity 095% RH, non-condensing Altitude < 4000m above mean sea level

    2000 m - 3000 m: 3000 m 4000 m:

    1% power derating per 100m. At 3000m altitude, the output power can be 90% of the nominal power rating at maximum temperature 2% power derating per 100m. At 4000m altitude, the output power can be 70% of the nominal power rating at maximum temperature

    RoHS Full RoHS Dust level Air cleaning recommended

    Air filter on front of fans is not allowed

    Max. power dissipation

    < 235W Vout=53.5V, Iout=37.4A, and Vinrms=176V

    Fan life Life time: 50K hours MTTF: 350K hours

    Tamb = 40C with 15~65% RH

    Fan speed control

    Fan speed may be reduced at low temperatures to reduce noise generation and to decrease dust accumulation inside the rectifier

    Fan fail alarm Fan will issue a failure signal in case there is failure of the fan, fan not connected or the rotor is locked. If a fan failure is detected, an alarm is issued, the rectifier shuts down.

    6.2.5 Physical Item Specifications Remark Dimension (W x H x D)

    125.5 x 41.0 x 269.9 / mm 4.94 x 1.61 x 10.63 / inch

    Overall

    Weight < 2.0 kg / 4.4 lb Marking language English Front panel color Pantone cool gray 5C

  • ES48/200-UHA01 IOM

    Page: 45 of 93

    6.3 Outline & Dimensions

    6.3.1 Connector on Rectifier

    Pin Number Signal Description P1 AC_L AC mains, L terminal P2 AC_N AC mains, N terminal P3 FG AC mains, frame ground P4 VOP Precharge P5 VO- DC output P6 VO- DC output P7 VO- DC output P8 VO+ DC output P9 VO+ DC output P10 VO+ DC output A1 SGNDO Signal ground A2 RS485+ RS 485 connection B1 CGND Communication signal ground B2 RS485- RS 485 connection C1 INH Short pin for well connection

  • ES48/200-UHA01 IOM

    Page: 46 of 93

    C2 IDA ID analog D1 IDD ID digital D2 IBUS Load sharing bus

    6.4 MECHANICAL ENDURANCE

    6.4.1 Vibration according to Delta Telecom Power Standard (TPQE-037-00)

    - in 3 axes (x, y, z) - rectifier non-operation - sinusoidal - frequency & acceleration

    Frequency Acceleration (G peak)

    5 Hz 0.5 g

    10 500 Hz 2.0 g

    - total test time: 30 minutes per axis

    Visual, soldering check and power-on parameter test are conducted after test.

    6.4.2 Shock according to Delta Telecom Power Standard (TPQE-013-00)

    - in 3 axes / 6 shocks per axes - rectifier non-operation - half sinusoidal - acceleration 50 g - pulse duration 10 ms

    Visual, soldering check and power-on parameter test are conducted after test.

    6.4.3 Penetration of foreign bodies and water According to EN 60529

    enclosure: IP 20

    6.4.4 Drop test according to Delta Telecom Power Standard (TPQE-012-00) and MIL-810E

    516.4

    one Corner, three Edge, six Surface; rectifier packed

    Visual, soldering check and power-on parameter test are conducted after test.

    Packing Weight (Kg)@ Drop height (cm):

    45.4~90.8 Kg @ 76cm 21~45.4 Kg @ 91 cm 0 ~21 Kg @ 122cm

  • ES48/200-UHA01 IOM

    Page: 47 of 93

    6.5 ELECTROMAGNETIC COMPATIBILITY

    Item Specifications Remark Emission Radiation FCC class B

    CISPR 22 class B FCC Part 15 subpart J

    Conduction (AC input)

    FCC class B CISPR 22 class B

    FCC Part 15 subpart J

    Conduction (DC output)

    EN 55022, class A (150Khz~30Mhz)

    Harmonic content EN 61000-3-2; class A Flicker EN 61000-3-3 Immunity Enclosure electromagnetic field: EN 61000-4-3

    electrostatic discharge (ESD): EN 61000-4-2

    10V/m 15KV air discharge 8KV contact discharge

    AC input radio frequency common mode: EN 61000-4-6

    10V

    Voltage dips and interruptions: EN 61000-4-11

    Voltage transients - burst: EN 61000-4-4

    4KV

    Voltage transients - surge: EN 61000-4-5

    6kV

    6.6 SAFETY STANDARD

    6.6.1 Test voltages rectifier primary-enclosure 2800Vdc (60s for approval)

    rectifier secondary-enclosure 1000Vdc (60s for approval)

    components primary - secondary 4242Vdc (60s for approval)

    special creepage distance secondary enclosure: 1 mm

    Tested on every production unit:

    rectifier primary-enclosure 2500Vdc (1s)

    rectifier secondary-enclosure 1000Vdc (1s)

    components primary - secondary 2800Vdc (1s)

    6.6.2 Approvals (Pending) CB certificate, CB scheme IEC 60950-1 TUV Approval EN 60950 CE mark UL/cUL 60950-1

  • ES48/200-UHA01 IOM

    Page: 48 of 93

    6.7 Settings and Controls Setting from CSU

    Item Specifications Remark Floating Voltage - Function - Setting Window - Default

    Default setting of rectifier output voltage 40VDC 59VDC 53.5VDC

    EEPROM keeps the default setting value

    Current Limit - Function - Setting Window - Default

    Setting for rectifier maximum output current1 110%, 1% per step 110%

    EEPROM keeps the default setting value. Rectifier accepts dynamic current limit command from controller

    DC High Voltage Shutdown - Function - Setting Window - Default

    Threshold voltage setting for rectifier shutdown 57VDC 59.5VDC 59.5VDC

    EEPROM keeps the default setting value

    Remote SMR On/Off

    - Function

    Command for turn on or turn off rectifier

    SMR O/P Voltage - Function - Setting Window - Default

    Dynamic rectifier output voltage command from controller 40VDC 60VDC 53.5VDC

    6.8 LIST OF REFERRED STANDARDS CAN/CSA-C22.2 No. 60950-00 UL 60950 Rev 3 (DEC 1, 2000)

    Safety standard (USA, Canadian)

    EN 60950 (2000-06) Safety standard (European) EN 300386-2 V1.3.1 (2000-09) Telecom equipment EMC requirements ETSI EN 300386 V1.3.1 (2001-09) Telecom equipment EMC requirements EN 55022 (1998-09) Limits to and measurement of radio interference IEC 61000-3-2 (2000-10) Limits for harmonic current emissions (

  • ES48/200-UHA01 IOM

    Page: 49 of 93

    ETSI EN 300132-2 V2.0.0 (2001-12) Power supply interface at the input to telecom equipment. Part2: operated by direct current DC

    IEC 60651 Edition 1.2 (2001-10) Sound level meters ISO 7779 Acoustic noise test EN 60529 Degree of protection by enclosures (IP code)

    6.9 LIST OF USED SYMBOLS AND ABBREVIATIONS Item Definition Default Value Vinrms rms value of ac mains voltage Vinrmsnom nominal rms value of ac mains voltage 230Vac Vinrmsmin minimum rms value of ac mains voltage (rectifier maintains

    operation) 176Vac

    Vinrmsmax maximum rms value of ac mains voltage (rectifier maintains operation)

    276Vac

    Voutpsorms rms value of psophometric noise on ac mains voltage Voutacrms rms value of ripple voltage on ac mains voltage Iinrmsmax maximum rms value of ac mains current Iinp peak value of inrush current Finnom nominal value of ac main frequency Dfin tolerance range of ac mains frequency Vout output voltage Voutdcnom nominal value of dc output voltage (factory set value) 53.5Vdc Voutdcmin minimum adjustable value of dc output voltage Voutdcmax maximum adjustable value of dc output voltage dVout output voltage deviation for static output current variation ddVout output voltage excursion for dynamic responses Voutacpp peak-to-peak value of ac output voltage (ripple & spikes) in steady-

    state

    Iout output current Ioutdcnom nominal value of dc output current (=Poutdcnom/Uoutdcnom) 37.4A Ioutlimnom nominal value of output current limit (factory set value) Pout output power Poutdcmax maximum value of dc output power Poutdcnom nominal value of dc output power (=Uoutdcnom Ioutdcnom) Tamb ambient temperature Tambnom nominal value of ambient temperature 25C Tambmin minimum value of ambient temperature rang -40C Tambmax maximum value of ambient temperature range 75C Efficiency

    6.10 SMR Operating Principle After applying single phase 220 VAC to the SMR, current is applied to the EMI filter and circulates through protection components such as the AC circuit breaker and the fuse. The major functions of the protection devices are to prevent the SMR from being damaged by surge current and to efficiently reduce the interruption signal of differential mode and common mode, to eliminate the high frequency interruption signal from input current and to prevent the feedback of interruption signal reverse current to the circuit. After the single phase AC current been converted to DC current through bridge rectifier, PFC boost converter, and reaches the requirement of True Power Factor (PF>0.99) (THD

  • ES48/200-UHA01 IOM

    Page: 50 of 93

    Through a DC/DC converter, the 400 VDC voltage produces a stable output voltage. The circuitry uses the Full Bridge series resonant converter technique. Using a switching frequency higher than 100 KHz, the 400 VDC is converted to an AC pulse, then through the high frequency transformer, step down, the voltage becomes an appropriate AC pulse width. The stable DC current is yielded by the Secondary AC pulse after flowing through a diode and output filter and is fed back through a DC/DC controller. Before the stable voltage and DC current is delivered by the output of the rectifier, it has been converted by a DC/DC converter, the common mode EMI noise is eliminated by a filter circuit, through an output circuit fuse, to the system in parallel.

  • ES48/200-UHA01 IOM

    Page: 51 of 93

    7 SYSTEM ALARM DEFINITIONS

    7.1 Input voltage of system (AC main voltage)

    7.1.1 AC main voltage Alarm

    Function Default Range Tolerance Window (Recover)

    High Voltage 264V 230 ~ 330V 5V 5V

    Function Default Range Tolerance Window (Recover)

    Low Voltage 180V 90~229V 5V 5 V

    - AC main voltage alarm recovery criterion:

    AC input voltage is higher or lower than parameter setting (AC low voltage alarm or high voltage alarm) 5 voltage then controller will disable alarm information.

    - AC fail (Main fail) alarm: When AC input voltage is lower than 75 Vac, CSU will launch AC fail alarm.

    - AC fail alarm recovery criterion:

    AC input voltage is higher than 80Vac and keeping 5 sec by this status, when AC fail alarm will be disable.

    If system happened AC fail alarm then system will stop below events,

    Battery test

    Equalize charge

    Voltage and temperature compensation

    SMR information launch (SMR fail, SMR off, SMR output low, SMR comm. error)

    7.2 DC voltage relative alarm

    7.2.1 Battery breakdown (BBR) alarm

    Function Default Range Tolerance Window (Recover)

    Voltage 44.0V 40.0V~50.0V 0.1V 1V

    BBR detection is disabled in Battery TEST.

  • ES48/200-UHA01 IOM

    Page: 52 of 93

    7.2.2 Low voltage alarm Function Default Range Tolerance Window (Recover)

    Voltage 46.0V 44.0V~50.0V 0.1V 1V

    LV detection is disabled in Battery TEST

    7.2.3 High voltage alarm Function Default Range Tolerance Window (Recover)

    Voltage 58.0V 56.0V ~ 58.0V 0.1V 1V

    7.2.4 High voltage Shut-dowm (HVSD) Technician through LCD or NRMS set parameters for HVSD function. Controller provides HVSD parameter to rectifier for HVSD function reference. When system happened output high voltage, then rectifier will shut down by itself if output voltage higher than HVSD criterion. System isnt affect by the fail rectifier.

    Function: Enable / Disable

    Function Default Range Tolerance Adjustment Step

    Voltage 59.0V 56.0V ~ 60.0V 0.1V 1V

    Function default setting: Disable

    Notice: * If HVSD function of controller is disabled or system doesnt have controller, HVDS function follows default setting of rectifier (59.5V). HVSD recovery method is pull-out rectifier then push-in.

    * HVSD setting should be higher than HV alarm 1V at the least.

    7.2.5 DC voltage out of range (48OTB) alarm Description: DCV out of range or DCV out of control Parameter: Parameter setting - DCH & DCL settings Criteria: (1). DCV out of range

    DCH: DCV >= Parameter DCH DCL: DCV

  • ES48/200-UHA01 IOM

    Page: 53 of 93

    48OTB = DCV out of range | DCV out of control

    7.2.6 Emergency Alarm (Original alarm is MAJ in ISARII) Description: System can not provide enough power for load or battery starts to discharge.

    Parameter:

    Para. Emergency DCL (xx.x V) default: 47.0V

    Function Default Range Tolerance Adjustment Step

    Voltage 47.0V 40.0V ~ 50.0V 0.1V 1V

    Para. Emergency Discharge Time (xx Min.) default: 5 Min.

    Function Default Range Tolerance Adjustment Step

    Voltage 5 Min 5Min ~ 10Min 1Min 1Min

    Criteria:

    System Target Voltage

    DCV Out Of Control: Recover point (Target voltage +- 1.8)

    DCV: Out Of Control - Alarm point (Target voltage +- 2.2)

    1.8V

    1.8V

    2.2V

    2.2V

    Criteria for DCV out of control

  • ES48/200-UHA01 IOM

    Page: 54 of 93

    Emergency DCL => DCV Para .Emergency DCL Emergency Discharge = Battery discharge continue Para. Emergency Discharge Time Alarm shall be activated in case battery is discharged by more than 3A (+/- 1A) within a time period of 5 minutes (+/- 10 s), or DC voltage is below 47V (+/- 0,5V) and system is not in battery re-charge operation. Alarm shall be re-set as soon as N-1 or N rectifiers are ON again (N is number of rectifiers plugged). If Rectifier working NO. >= 1 & Rectifier Fail NO.

  • ES48/200-UHA01 IOM

    Page: 55 of 93

    Action: Controller will turn off all rectifiers and disconnect LVDS in case the TA temperature is higher than the HTSD threshold and10 sec later.

    Operation mode: Enable/Disable

    -System recovery criterion:

    The ambit temperature of system is under shutdown factor level 13 and then controller will automatically recover all rectifiers. And reconnect LVDS.

    Notice: * If temperature is higher than 80 on LCD display or NRMS, temperature sensor should be damage and controller will ignore this error message. And LCD and NRMS have to alarm message (temperature fail) for cable failure and substitute wrong value for dash mark.

    7.3.3 Low ambit temperature shutdown (LTSD)

    Rectifiers shutdown is to prevent communication equipments damage during low temperature condition. The temperature reaches LTSD threshold and keeps 3 sec by this status. The system will shut down all rectifiers. And may open the LVDS (if enabled)

    Function: Enable / Disable

    Function Default Range Tolerance Delay Time

    Adjustment Step

    Shutdown Level

    -15 -40 ~ -10 2% 10 sec 1

    Recover

    Level

    (Hysteresis)

    3 3 ~ 45 2% 1

    Action: Controller will turn off all rectifiers and disconnect LVDS in case the TA temperature is lower than the LTSD threshold and10 sec later.

    Operation mode: Enable/Disable

    -System recovery criterion:

    In case the ambit temperature of system is higher than shutdown factor level 3, controller will automatically recover all rectifiers and connect all LVDS.

    Notice: If temperature is lower than 50 on LCD display or NRMS, temperature

    sensor should be damage and controller will ignore this error message.

  • ES48/200-UHA01 IOM

    Page: 56 of 93

    And LCD and RMS have to alarm message (temperature fail) for cable failure and substitute wrong value for dash mark.

    7.3.4 Controller internal temperature detection One additional temperature sensor is embedded in controller. If the user didnt insert the external TA temperature sensor into power system or TA sensor fails, this embedded temperature sensing values will be displayed in NRMS, and handle relative function.

    Operation mode: Enable/Disable

    Enable: In case TA sensors werent inserted into system, controller will depend on the internal temperature to do HTSD, LTSD, HT, LT.

    7.3.5 Battery temperature alarm criterion Function Default Range Recovery

    Window

    Tolerance Adjustment Step

    Low Level Alarm (TBH)

    35 30 ~ 40 5 2% 1

    Controller will stop the EQU/boost charge function, if the battery temperature is higher the above setting threshold.

    Function Default Range Recover

    Window

    Tolerance Adjustment Step

    HTB Alarm 54 36 ~ 55 3 2% 1 LTB alarm -8 -10 ~ 5 3 2% 1

    Action: Controller will disconnect the battery LVDS contactor in case the battery temperature is higher than the value of HTB alarm threshold. The alarm shall be restored and reconnect the battery LVD automatically when the battery temperature is falling to -3.

    7.3.6 Battery reversed alarm CSU will generate the reversed alarm via NRMS and LED (BAT_F) on front panel is lighted on, when the battery is connected to inverted polarity.

    Procedure to solve this problem:

    1. To re-check the wiring of PIN-9(BUSBAT) from D-sub 25P connector (Alarm outlet), which shall be connected between battery minus bus and battery breaker.

    2. To refer the instruction start-up with no-load, before turn on battery breaker.

    3. To re-check the battery connections and re-move them, if CSU generates Battery reversed alarm or LED-BAT_F lighted on.

  • ES48/200-UHA01 IOM

    Page: 57 of 93

    7.4 Rectifier relative alarm

    7.4.1 BCHF alarm Definition: One or more than one rectifier fail

    7.4.2 Communication Error The controller will generate the communication error alarm when any rectifier is pulled out from system.

    Continue to press the FL/EQU button on the front of controller panel more than 3 seconds to clear this kind of alarm.

    Note: The system will be changed from FL charged mode to EQU mode when pressing the FL/EQU button less than 3 seconds.

    7.5 Relay signal (Dry contact)

    7.5.1 Relay Position Relay output contact criteria:

    Open contact = Alarm;

    Contact rating: +30Vdc/120Vac= 0.5A;

    Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6

    Definition

    (Default)

    MBR.

    BBR.

    CSU Fail

    BCHF

    48OTB

    Emergency.

    Remark NSN request

    NSN request

    Fixed NSN request

    NSN request

    NSN request

    Note:

    1. Five dry contact relays are definable (min, DCF, LVDS2-F, Battery test fail) Function of Relay-3 is fixed for CSU fail.

    2. Relay output terminal is twice output (normal close, common.)

    A 25P D-sub female connector is for signal/alarm access.

    Pin assignment:

    No. Pin Assignment No. Pin Assignment

    1 MBR-C 14 MBR-AB

    2 BBR-C 15 BBR-AB

    3 BCHF-C 16 BCHF-AB

    4 48OTB-C 17 48OTB-AB

    5 CSU Fail-C 18 CSU Fail-AB

  • ES48/200-UHA01 IOM

    Page: 58 of 93

    6 Emergency-C 19 Emergency-AB

    7 Coil+ 20 Coil-

    8 Coil+ 21 Coil-

    9 BUSBAT 22 BREAKER (Battery Breaker)

    10 IB+ 23 IB-

    11 TA-IN1 24 TA-D

    12 TBATT-IN1 25 TBATT-D

    13 Load-BK (Load Breaker)

    7.6 Operation Interface 7 segment LED display / LCD display (Optional)

    LED indicators (Function Definable)

    V: DCV of system output voltage (Green color)

    A: DCI of system output current (Green color)

    The above two LEDs are selectable by push button.

    Push buttons functions

    First DCV/DCI selectable button;

    Cap Test Battery Capacity test button;

    Rough Test Battery Rough test button;

    FL/EQU Floating / Equalizing charging mode selectable button;

    LED alarms indicate the default definition

    9 AC (AC OK) 9 DC (DC OK)

    DCV/DCI selectable Button DCV (V) / DCI (A) LED indicators

    Eme

    B

  • ES48/200-UHA01 IOM

    Page: 59 of 93

    9 BAT_F (Battery temperature high or fails) 9 Temp (Ambient temperature high/low or fails) 9 Reset (MCU of CSU is working, not goes to normal condition) 9 EQU. (System in EQU charge mode) 9 BCHF+ Mixed Rect. (One or more than one rectifier fail or wrong rectifier

    plugged) Note: In case Mixed Rect. Alarm occurs, this LED will be blinking continue till user replace correct rectifier mode.

    9 Maj. (Battery in discharge conditions) 9 LVDS. (LVD trip alarm) 9 Breaker (Battery/load breaker trip)

    7.6.1 LED definition

    NAME COLOR MEANING Remark

    1. Present of the primary power source and the LED is on if the alarm MBB is not activated

    AC Green

    2. The AC voltage out of specified range.

    Threshold >264V

  • ES48/200-UHA01 IOM

    Page: 60 of 93

    NAME COLOR MEANING Remark

    BAT FAIL Red

    1. Temperature sensor on battery is off.

    Test Items

    1. Without battery sensor

    2. The LED is on if the alarms Battery test fail.

    Test Items

    1. Battery Rough Test

    2. Battery Capacity Test

    3. Battery Connected to inverted polarity

    3. TB sensor fail is activated.

    Test Items Test Value 1. Temperature over high limit (80) 81 2 Temperature under low limit (-48) -50

    4. Battery Temperature is out of setting threshold.

    Test Items Test Value 1. Temperature over high limit (54) Battery LVDS is disconnected.

    54

    2 Temperature under low limit recover condition(51)

    51

    3.Temperature under low limit (-5) Battery LVDS is disconnected.

    -5

    4.Temperature over high limit recover condition(-2)

    -2

  • ES48/200-UHA01 IOM

    Page: 61 of 93

    NAME COLOR MEANING Remark

    TEMP Red

    Over-/Under-temperature protection 1. The LED is on if the over temperature protection

    is triggered

    Threshold > 67 < -1 LED OFF OFF

    Recovery < 57 5 LED ON ON

    The minimum time between triggering one of the over or under temperature alarms and switching off the DC power has to be 5 s, also when the temperature falls or rises faster.

    RESET Red

    1. During RESET this LED is active. After Power On of the AC/DC Controller this LED shall be on. In case the Controller has come into normal operation, the LED shall be switched off.

    EQU Red

    1. The LED is on if the AC/DC change to equalize voltage.

    NRMS Setting Range -50.0 ~ -57.0V

    Equalize voltage -56.4V

    EQU LED ON

    BCHF Red

    The LED is on if either one rectifier is faulty.

    Item MIN LED

    No Rectifier Faulty OFF

    One or more than one Rectifier Faulty

    ON

    Emergency Red

    Alarm shall be activated in case battery is discharged by more than 3A (+/- 1A) within a time period of 5 minutes (+/- 10 s), or DC voltage is below 47V (+/- 0,5V) and system is not in battery re-charge operation. Alarm shall be re-set as soon as. N-1 or N rectifiers are ON again (N is number of rectifiers plugged).

    Item MAJ LED Result Battery discharge current over 3A and continue 5 minutes. Or DC voltage is below 47V and battery charge current below 3A (indicate battery not in battery recharge operation)

    ON OK

  • ES48/200-UHA01 IOM

    Page: 62 of 93

    NAME COLOR MEANING Remark

    MAJ-Alarm shall reset: As soon as N-1 or N rectifiers are ON again (N is number of rectifiers plugged).

    OFF OK

    AC ON Over Load Condition: SMR amount N or N-1

    >N-1 Capacity

    Test Item MAJ LED MAJ LED Over Current:100%Load O