Aeroflex® USA Aerocel® EPDM Insulation

Installation Guide

EPDM Closed Cell Elastomeric Foam Insulation

HVAC | VRF | Chilled Water | Refrigeration Duct Wrap | Duct Liner | Plumbing

Page 2: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

1For more information, visit www.aeroflexusa.com

INTENTThe intent of the Aeroflex USA Installation Guide is to provide building/facility owners, mechanical engineers, design-build mechanical and insulation contractors with illustrated step-by-step instructions and best practices for correctly installing the Aerocel® brand of EPDM closed cell flexible elastomeric foam insulation.

Although specific application methods are referenced in this guide, such as fabricating a variety of fitting covers, there can be alternative installation methods to achieve a successful outcome with many applications. This guide does not address every method.

For additional industry references related to the installation of flexible closed cell elastomeric insulation, Aeroflex USA recommends considering the guidance of the following industry standards and installation specifications:

ASTM International

C1710 “Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form”

https://www.astm.org/Standards/C1710.htm

National Insulation Association (NIA)

https://insulation.org

National Institute of Building Sciences | National Insulation Association

“Mechanical Insulation Design Guide” (MIDG)

https://www.wbdg.org/guides-specifications/mechanical-insulation-design-guide

Midwest Insulation Contractors Association (MICA)

“National Commercial & Industrial Insulation Standards”

https://www.micainsulation.org/standards-manual.html

Sheet Metal & Air Conditioning Contractor’s National Association (SMACNA)

“HVAC Duct Construction Standards - Metal & Flexible”

https://www.smacna.org

Page 3: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

2 For more information, visit www.aeroflexusa.com

INTRODUCTIONAerocel is available in the following formulas:

• AC (HVAC/Plumbing)• REF™ (Refrigeration)• ULP® (Ultra-Low Perm)• WG (White/Gray)

Aerocel is available in the following formats:

• Tubes (unslit – AC, REF, ULP, WG)• Tubes (pre-slit, Stay Seal® with Protape® | SSPT™ - AC, REF, ULP, WG)• Tubes (unslit or SSPT - Aerocel with SaniGuard™)• Tubes (AC Continuous Tube)• Sheets (AC & ULP Sheet, AC & ULP Sheet with PSA)• Rolls (AC & ULP Roll, AC & ULP Roll with PSA)• AeroFit™ factory fabricated fitting covers (standard and mechanical-

grooved available in all Aerocel formulas)

Aeroflex USA, Inc. manufactures the Aerocel® brand of EPDM closed cell elastomeric foam insulation in Sweetwater, TN.

Aerocel complies with Buy American requirements.

PREVIOUS PAGE

Page 4: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

3For more information, visit www.aeroflexusa.com

Aerocel installation system accessories include:

• Adhesives- Aeroflex Cel-Link II® glueless seam seals- Aeroseal (all applications)- Aeroseal LVOC™ Black (low-VOC, LEED® compliant)- REF 1520™ (all applications)

• Protape® EPDM high-performance zero-perm rubber tape• Aerotape™ EPDM foam tape• Aerofix® insulated pipe hanger supports• Aerocoat™ premium UV-protective coating• Aerocoat LVOC™ low-VOC UV-protective coating (LEED® compliant)

Key Compliances:

ASTM C534 Grade 1, Type I & II ANSI/ASHRAE/IES 90.1

ASTM C692 International Energy Conservation Code® (IECC®)

ASTM D1056, 2C1 California Title 24

ASTM D1171 California Department of Public Health CDPH 01350

ASTM E84 USGBC LEED®

ASTM G7 RoHS 3

ASTM G21 REACH

NFPA 90A/90B MIL-P-15280

International Mechanical Code® (IMC®) Free of CFC’s, HFC’s, HCFC’s, PBDE’s & Nitrosamine

International Residential Code® (IRC®) Asbestos, formaldehyde & fiber-free

Buy American Act

PREVIOUS PAGE

Page 5: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

4 For more information, visit www.aeroflexusa.com

TABLE OF CONTENTSGENERAL INFORMATIONDefinitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Best Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Substrate Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Aerocel EPDM Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Cel-Link II Glueless Seam Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Aerocel Adhesives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

AeroFit Fitting Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Aerofix Insulated Pipe Hanger Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Aerocel with SaniGuard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Protape | Aerotape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Aerocoat | Aerocoat LVOC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Sleeving | Multi-Layering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Aerocel Sheet & Roll | Pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Stainless Steel Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Exterior Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Cladding | Jacketing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Direct Burial | Underground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Heat Trace Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Maintenance | Repair | Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

SMALL DIAMETER PIPESUnslit Aerocel tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Pre-slit Aerocel SSPT tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

AeroFit Factory Fabricated Fitting Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Using the Aerocel Template | Field-Fabricated Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Pipe Bends | 45° angle | Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Pipe Bends | 90° angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Elbows (welded). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Elbows (oversized) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Curved Pipe Bends [< 90°] | Elbows (segmented) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Curved Pipe Bends [> 90°] | Elbows (oversized) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Pipe Intersections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

T’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Angle-T’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Y-Tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Pipe Reducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

PREVIOUS PAGE

Page 6: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

5For more information, visit www.aeroflexusa.com

LARGE DIAMETER PIPES | ROUND DUCTSAerocel Sheet & Roll . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Pipe Bends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Pipe Intersections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Collars | Reducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Angled Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

PIPE HANGERSInsulate with Aerofix EPDM pipe supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Insulate with other pipe supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Insulate over pipe hanger brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

TANKS & VESSELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

DUCT WRAP | RECTANGULAR | ROUND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

DUCT LINER | RECTANGULAR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 TECHNICAL RESOURCESSleeving | Multi-Layering schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

Yield Table | Aerocel Sheet & Roll . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Cladding | Jacketing schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Aeroflex USA Technical Bulletins. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Insulation Thickness calculator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Aeroflex USA Express Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

PREVIOUS PAGE

Page 7: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

6 For more information, visit www.aeroflexusa.com

TOOLSDEFINITIONSReference: ASTM C1710 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form (license agreement)

• Seams – longitudinal or horizontal cross-

sections where insulation meets and must be

adhered to itself or other system components.

• Butt Joints – cross-sections where two pieces

of tubular or sheet insulation must be adhered

to itself or other system components.

• Vapor (Water) Stops – locations/methods to

prevent water or water vapor from traveling

from one pipe insulation section to an adjacent

insulation and prevent water traveling down

annular space between the pipe insulation and

the tubular pipe.

• Sleeving/Multi-Layering – applying another

layer of insulation over the first layer. This

process is used when the insulation thickness

required is greater than that which is

commercially available. This technique is also

employed when proper installation practice

requires multiple layers and or staggered joint

application, even if a single layer thickness is

available.

SYMBOLS

Direction/Application

Measurement

Measurement/Dimension

Section to be glued

Template (printed on every Aerocel tube carton)

Tape measures (rigid & flexible)

Straight edge

Chalk (to mark measurements and cuts)

Ink marking pen (silver or light color)

Caliper (to measure outside diameters)

Divider (to draw reference lines)

Scissors

Denatured alcohol (to clean insulation and substrates)

Acetone (to clean tools)

Short knives (3”, 7.6 cm)

Long knives (10”, 25.4 cm)

Knife sharpener or stone

Sharp pipe ends (to make holes for common pipe sizes)

Aerocel squeegee (one included in every SSPT carton)

Brushes (short firm bristles to apply adhesives, standard for coatings)

Roller(s) to apply adhesives and coatings on flat surfaces

Gluemaster

Weighted roller

PREVIOUS PAGE

Page 8: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

7For more information, visit www.aeroflexusa.com

adhesive from thickening. Stir frequently to

prevent activators from settling to bottom.

Note: Do not use adhesives when relative

humidity is 100% due to the formation of

condensation on substrates.

Aerocel EPDM Insulation 1. Storage: store Aerocel insulation at 40°F - 100°F

[4°C - 38°C] prior to installation. Cold closed

cell elastomeric foam insulation will lose its

flexibility. Keep dry.

2. Pressure-Sensitive Adhesive (PSA): SSPT

tubes, Cel-Link II, Sheet & Roll with PSA,

Protape and Aerotape should be installed when

substrate and ambient temperatures are above

50°F [10°C]. At temperatures between 0°F - 50°F

[4°C - 10°C], significant pressure must be applied

to achieve an adequate bond. Installation of PSA

products below 40°F [4°C] is not recommended.

Pinch corner and pull release liner back 6" - 10"

[15 cm - 25 cm] at a time during installation.

For sheets/rolls, use weighted roller to achieve

complete contact.

BEST PRACTICESSubstrate Preparation - Never insulate a system in operation. Turn off

system 24 hours prior to installation to avoid

moisture development under insulation, potential

corrosion under insulation (CUI) and adhesive

failure. Follow Aerocel adhesive complete dry

times prior to system start-up.

- Clean substrates with denatured alcohol.

Remove dirt, dust, grease, moisture, oil and

other contaminants that can serve as corrosion

accelerators beneath the insulation and bond-

breaking agents on direct-adhered adhesive

applications.

- Untreated steel surfaces must be treated with a

rust inhibitor for HVAC/R applications. Follow the

rust inhibitor manufacturer’s full cure time prior

to installing Aerocel.

- Corrosion Protection Primers: test Aerocel

adhesive for compatibility with epoxy resin

and polyurethane primers. Adhesives are not

compatible with asphalt, bitumen, linseed oil or

red lead primers.

- Recommended application temperature range

(substrates and ambient) is 40°F - 100°F [4°C -

38°C].

- Cold weather installation: cold substrates will

prolong flash time of adhesives. When conditions

are below 40°F [4°C], adhesive bonded to very

cold substrates may not flash off at all due to

formation of condensation from latent heat of

adhesive. Adhesive container can be warmed in a

bucket of hot water. Adhesive container opening

should be covered with a Aerocel sheet insulation

or cardboard cut-out with brush hole to prevent

adhesive from thickening. Stir frequently to

prevent activators from settling to bottom.

- Hot weather installation: heated substrates

will cause adhesive to flash off very quickly. If

adhesive is left open beyond flash time, adhesion

will not occur. Adjust by applying adhesive to

smaller areas. Adhesive container opening should

be covered with a Aerocel sheet insulation or

cardboard cut-out with brush hole to prevent

2

PREVIOUS PAGE

Page 9: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

8 For more information, visit www.aeroflexusa.com

5. Push, Never Pull (Stretch) Insulation

6. Spacing: allow a minimum of 4” [10 cm]

between insulated chilled water and

refrigeration pipes to allow for air movement to

prevent condensation.

7. Seams, Butt Joints & Termination Points:

completely seal with Aerocel adhesive to create

vapor seal in order to prevent air and moisture

from penetrating under the insulation and

causing corrosion under insulation (CUI). Seal all

cut-outs and termination points, such as flanges,

3. Sizing: properly sized pipe insulation tubes

should slide easily over the pipe and fittings.

Aerocel ID’s are designed to properly fit copper

and iron piping. A tube that fits loosely over

a pipe is better than a smaller size that is too

snug. Never stretch Aerocel insulation. An air

gap between the pipe and insulation (annular

space) is acceptable provided that all seams are

completely sealed with an Aerocel adhesive.

When measuring sheet material, mark where the

adjoining edges overlap.

Note: Although Aerocel SSPT tubes are

available up to 16” IPS, Sheet & Roll can be

used on pipe sizes ≥4” [10 cm] OD.

4. Cutting: use sharp non-serrated knives. Knife

should be maintained at low angle to prevent tip

from cutting/slitting inside wall. Cut flattest side

of tube. Measure and cut all lengths (tube and

sheet) long +1/8” [.32 cm] on each side (1/4”, .64

cm) to install under compression. Use sharpened

pipe cut-offs for holes. Glued seams should

never be stretched and under stress.

4”

5

4

6

7

3

PREVIOUS PAGE

Page 10: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

9For more information, visit www.aeroflexusa.com

was dry to the touch prior to contact. For

exterior applications, taping all glued seams

with Protape is required; turn taped longitudinal

seams away from direct sun exposure when

possible.

• Note: Protape should never be installed over

a seam that is not sealed with an Aerocel

adhesive or Cel-Link II.

Cel-Link II Glueless Seam Seals - Cel-Link II glueless seam seals, Aeroflex squeegee

and instructions are included with every carton of

Aerocel SSPT pipe insulation.

- Install Cel-Link II over pipe and between adjoining

tubes.

- Peel seam seal from release liner.

- Apply exposed adhesive side of Cel-Link II to

one tube and thoroughly compress to maximize

adhesion.

- Peel gold release liner to other side of seam seal

facing adjoining tube and align longitudinal seams.

- Press adjoining tubes together under

compression.

- Apply 2” Protape evenly over all butt joints

(required).

supports and valves, with Aerocel adhesive.

Note: Never use zip ties as substitute for

adhesive; zip ties do not seal and they

compress the insulation.

8. Vapor Stops: for below-ambient (cold)

applications, adhere the tube or sheet insulation

directly to the pipe a maximum of every 18

linear feet [5.5 m]. The adhesive width should be

at a minimum equal to the insulation thickness.

Protape wrapped around the pipe can be used

as vapor stop in place of adhesive. Seal butt

joints with Aerocel adhesive or Cel-Link II for

SSPT installations.

9. Taping Seams: applying zero-perm Protape

over sealed seams for interior applications

is recommended as an additional level of

protection to prevent CUI. For pipe sizes over

6" IPS [15 cm] and sheets/rolls over 1" thick [2.5

cm], apply 2" [5 cm] Protape evenly over seams

followed by 2" on either side of taped seam

(4" [10 cm] total taped seam width). Protape

may be applied immediately over glued seams

if Aeroseal or Aeroseal LVOC Black adhesive

8

9

PREVIOUS PAGE

Page 11: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

10 For more information, visit www.aeroflexusa.com

TIP - Use the “fingernail test” to determine when

tack time has been achieved; touch the glued

surface with fingernail; if fingernail sticks and

glue transfers, the adhesive is not ready; if the

fingernail does not stick, there is no glue transfer

and adhesive is either dry to the touch (Aeroseal

and Aeroseal LVOC Black) or tacky (REF 1520),

the two glued surfaces are ready for contact.

- Apply thin even coat to both surfaces to be sealed

with a short stiff-bristle brush from the inside out

(tubes) or with an adhesive/short-nap roller for

sheets and rolls.

- Brush adhesive on approximately 7” [18 cm] on

one surface, then 7” [18 cm] on the other surface,

alternating back and forth until longitudinal seam

is glued; once adhesive is ready for contact, press

both surfaces together under compression to

ensure full adhesion.

- Avoid stretching and tension at glued seams.

- When applying to surfaces other than insulation

(i.e. metal termination points), apply adhesive to

Aerocel insulation first, then the other surface.

- For applications over concrete substrates, consult

with Aeroflex USA.

- For exterior applications, turn glued seams away

from sun when possible.

- Use acetone to clean tools.

AeroFit Fitting Covers

- AeroFit fitting covers ship unslit.

- When fittings and straight runs are same size,

install fittings first followed by straight sections.

- When fittings are larger than straight runs

(oversized), install straight runs first.

- Slit inside radius of fitting (throat) with sharp

knife.

Aerocel Adhesives

- Read label and follow warnings; work area should

be well-ventilated; do not smoke.

- Do not thin adhesives.

- Substrates, ambient temperatures and adhesive

should be 40°F - 100°F [4°C - 38°C].

- Do not use below 40°F [4°C].

- Store at 60°F - 80°F [16°C - 27°C].

- Do not allow to freeze.

- Cold adhesive containers can be warmed in

bucket of hot water.

- Stir thoroughly before use and frequently during

use.

- For non-brush top containers, use a Gluemaster

or cover opening with Aerocel sheet insulation

or cardboard cut-out with brush hole to prevent

adhesive from thickening.

- Follow tack time on label and adjust based on

jobsite conditions – ambient temperature, relative

humidity and wind.

- Aeroseal and Aeroseal LVOC Black adhesives

must be dry to the touch (no transfer) prior to

contact to ensure immediate adhesion and a

permanent bond.

- REF 1520 adhesive must be tacky (no transfer)

prior to contact to ensure a permanent bond.

- Aeroseal LVOC Black adhesive requires a

longer tack time than Aeroseal or REF 1520;

allow 3-5 minutes depending on ambient

conditions during installation. LVOC adhesive

must be dry to the touch (no transfer) prior to

contact to ensure immediate adhesion and a

permanent bond.

PREVIOUS PAGE

Page 12: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

11For more information, visit www.aeroflexusa.com

Aerocel with SaniGuard

- Outer surface temperature of Aerocel

insulation must be continuously maintained

below 150°F [65°C].

- Follow best practices to install Aerocel unslit

tube, SSPT tube and AeroFit fitting covers.

- SaniGuard PVC jacket sections are included in

carton with 3-foot [.91 m] Aerocel unslit tube or

SSPT pipe insulation. AeroFit 90° long-radius

elbows, SaniGuard White 2” [5 cm] PVC Tape and

welding adhesive are sold separately.

- SaniGuard sections are intentionally 2” [5 cm]

longer than the insulation tubes to ensure an

overlap at SaniGuard seams. When cutting

SaniGuard, add 2” [5 cm] to all measurements.

- When applicable, install AeroFit fittings first

followed by straight pipe runs.

- Ensure that all longitudinal seams, butt joints and

termination points of insulation are sealed with an

Aerocel adhesive or Cel-Link II and covered with

Protape prior to installing the SaniGuard jacket.

- Carefully install SaniGuard jacket over sealed

Aerocel insulation to prevent surface damage.

- Position longitudinal overlap of SaniGuard jacket

downward to allow watershed and position out of

sight line.

- Prior to sealing seams, fit SaniGuard jacket tightly

to outer surface of Aerocel insulation leaving no

gaps.

- Seal the SaniGuard overlaps with pressure-

sensitive adhesive release liner located on inside

of jacket; peel, seal and apply firm pressure to

ensure complete adhesion.

- Once a sufficient amount of jacketing has been

- Install over pipe fitting to ensure proper fit - snug

or slightly loose (not stretched).

- Apply adhesive to both sides of radius seam; allow

to tack up and press together under compression

to ensure full adhesion and vapor seal.

- When bonding fitting covers to straight runs of

pipe insulation, allow adhesive to tack up and

press together under compression to ensure

complete adhesion and vapor seal.

- Optional: for interior applications, apply Protape

over glued seams.

- Required: for exterior applications, apply Protape

over glued seams; turn taped longitudinal seams

away from direct sun exposure when possible.

Aerofix Pipe Hanger Fittings

- Open Aerofix fitting, remove two inside release

liners, wrap around pipe, center at hanger

location and firmly press two halves together.

- Remove release liner from Protape outer jacket

and apply with firm pressure to achieve a strong

bond.

- Position Aerofix so seam between the two halves

is horizontal to the legs of pipe support system.

- Do not allow any gaps in the closure of the

insulation envelope.

- Seal Aerofix to adjoining Aerocel insulation tubes

with Aerocel adhesive and press together under

compression to ensure vapor seal.

- Optional: for systems operating above -20 F̊

[-29̊ C], apply Protape over glued seams.

- Required: for systems operating below -20 F̊

[-29̊ C], apply Protape over glued seams.

PREVIOUS PAGE

Page 13: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

12 For more information, visit www.aeroflexusa.com

- Required: For pipe sizes over 6" IPS and sheets/

rolls over 1" thick, apply 2" Protape evenly over

seams followed by 2" on either side of taped seam

(4" [10 cm] total taped seam width).

Aerocoat | Aerocoat LVOC Coatings - Select Aerocoat LVOC for

LEED® registered projects.

- Recommended application

temperature is 50°F - 100°F

[10°C - 38°C]

- Ensure insulation surface

is free from dust, grease,

oil or moisture prior to

application. Use denatured

alcohol if necessary.

- Do not dilute or tint.

- No primer is required.

- If Aeroseal or Aeroseal

LVOC Black adhesives were

installed and dry to the touch

prior to contact, coating may

be applied immediately after insulation installation

(seams and full coverage adhesion).

- If REF 1520 adhesive was installed and tacky to the

touch prior to contact, coating may be applied over

seams (24-36 hours) and full adhesive coverage (7

days) after insulation installation.

- Stir thoroughly and apply with new brush or short-

nap roller.

- Two coats are required to achieve 100% coverage;

allow a minimum of 4 hours between coats.

- Apply Aerocoat or Aerocoat LVOC within 2 weeks

of installation for optimum UV protection.

- Clean-up: clean water.

Sleeving | Multi-Layering

applied over pipe insulation, seal all outside

edge of all longitudinal seams, butt joints and

termination points with SaniGuard Tape.

- Do not stretch SaniGuard Tape; it will shrink and

recover.

- Ensure that 2” [5 cm] SaniGuard Tape is applied

continuously and evenly over all seams.

- To meet FDA and USDA washdown requirements,

SaniGuard jacket seams must be welded with

PIC Welding Adhesive for warranty purposes;

SaniGuard Tape should not be installed for this

application.

Protape

- Clean surfaces to receive Protape with denatured

alcohol.

- Recommended substrate and ambient

temperature should be above 50°F [10°C]. At

temperatures between 40°F - 50°F [4°C - 10°C],

significant pressure must be applied to achieve an

adequate bond. Installation is not recommended

below 40°F [4°C].

- If Aeroseal or Aeroseal LVOC Black adhesives

were dry to the touch prior to contact, Protape

may be applied over sealed seams immediately

after insulation installation (seams and full

coverage adhesion).

- If REF 1520 adhesive was tacky to the touch

prior to contact, tape may be applied over sealed

seams (24-36 hours) and full adhesive coverage

(7 days) after insulation installation.

- Optional: for interior installations, apply Protape

over glued seams.

PREVIOUS PAGE

Page 14: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

13For more information, visit www.aeroflexusa.com

• Adhere second layer to first layer with full

coverage using Aerocel adhesive.

• Apply Protape over sealed seams for additional

protection (required for exterior applications).

Aerocel Sheet & Roll on Pipes

- To minimize waste of Aerocel Sheet & Roll, refer

to Aerocel Yield Table – Sheet & Roll.

Stainless Steel Piping

- Aerocel EPDM is safe for austenitic stainless-steel

piping; Aerocel will not cause external stress

crack corrosion (ESCC).

• Reference: aeroflexusa.com/technical

resources/technical bulletins/february 2021.

- Piping:

• Stagger and seal all longitudinal and transverse

seams with Aerocel adhesive.

• Sheet or Roll should be used as second layer

when tube size is not available.

• Edges of second layer (tubes or sheets) should

be adhered to first layer with Aerocel adhesive.

• 16" - 24" [41 cm - 61 cm] pipes: adhere bottom

3rd of first layer to pipe, or second layer to first

layer, with Aerocel adhesive to prevent sagging.

• 24”+ [61 cm] pipes: full adhesion with Aerocel

adhesive is required for all layers.

• Apply Protape over sealed seams for additional

protection (required for exterior applications).

• Reference: aeroflexusa.com/technical

resources/technical bulletins/december 2020.

- Flat Surfaces

• Stagger all seams of first and second layers.

• First layer of Aerocel sheets to be installed with

full Aerocel adhesive coverage or Aerocel with

PSA (pressure-sensitive adhesive back).

PREVIOUS PAGE

Page 15: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

14 For more information, visit www.aeroflexusa.com

does not compress the insulation. See “Cladding |

Jacketing” schedule under Technical Resources for

Aerocel pipe insulation OD’s.

• Reference: aeroflexusa.com/technical

resources/technical bulletins/september 2020.

Direct Burial | Underground

- Aerocel should be sleeved within a protective

conduit, such as a fully-supported and sealed

waste-water drainage pipe, to ensure long-term

performance once backfilled.

- Direct contact with soil acids, ground water

chemicals, contaminants, plus insulation

compression from the weight of the backfilled

soil, can reduce the thermal efficiency and life of

the insulation.

• Reference: aeroflexusa.com/technical

resources/technical bulletins/april 2020.

Heat Trace Systems

Exterior Applications - Although Aerocel EPDM has greater UV-

resistance than traditional NBR/PVC closed cell

flexible elastomeric insulation, UV protection

is recommended to

prolong the life of

Aerocel. Options include

Aerocoat, Aerocoat

LVOC or an insulation

jacketing system. When

mechanical damage,

such as impacts from

maintenance, extreme

weather, birds, etc.

are expected, Aerocel

should be protected with a jacketing system.

- For pipe sizes over 6" IPS and sheets/rolls over

1" thick, apply 2" Protape evenly over seams

followed by 2" on either side of taped seam (4"

[10 cm] total taped seam width).

• Note: Aerocoat and Aerocoat LVOC satisfy

national and state energy code requirements,

such as ASHRAE 90.1, IECC® and California Title

24, for outdoor service protection from solar

radiation (adhesive tape is not permitted).

• Reference: aeroflexusa.com/technical

resources/technical bulletins/july 2020.

Cladding | Jacketing

- Aeroflex USA does not recommend specific

protective jacketing systems. However, the specified

and installed system should be sized correctly so it

PREVIOUS PAGE

Page 16: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

15For more information, visit www.aeroflexusa.com

adhesion and a vapor seal.

- Apply Protape over sealed seams (optional

for interior applications, required for exterior

applications).

• Cuts/nicks to surface (skin)

- Seal with Aerocel adhesive and apply

Protape over sealed repair (optional for

interior applications, required for exterior

applications).

- Replacement

• Carefully cut out damaged section on pipe, duct

or equipment with sharp non-serrated knife.

• For multi-layer applications, take care not to cut

into 1st or 2nd layers; avoid cutting directly over

sealed seams below to maintain staggered seam

layout.

• Cut replacement piece of same Aerocel tube,

sheet or roll insulation to fit under compression.

• Apply Aerocel adhesive to existing edges and

replacement piece; allow adhesive to tack up.

• When ready for contact, carefully install

replacement piece under compression without

gaps.

• Ensure complete adhesion to create vapor seal.

• Apply Protape over sealed seams (optional

for interior applications, required for exterior

applications).

- Aerocel is compatible with self-regulating heat

trace systems which ensure that the continuous

line temperature does not exceed 257°F [125°C].

- For proper fit, the next tube ID size up should be

installed.

- An air gap between the pipe and insulation

(annular space) is acceptable provided that all

seams are completely sealed with an Aerocel

adhesive to create a vapor seal.

• Reference: aeroflexusa.com/technical

resources/technical bulletins/august 2020.

Maintenance | Repair | Replacement

- Maintenance

• For light-duty cleaning, use non-acidic neutral

cleaner.

• For heavy-duty cleaning, use denatured alcohol.

- Repair

• Openings at longitudinal seams and butt joints

- Apply Aerocel adhesive to existing edges and

allow adhesive to tack up.

- When ready for contact, apply firm pressure

to both sides of seams to ensure complete

PREVIOUS PAGE

Page 17: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

16 For more information, visit www.aeroflexusa.com

- Adhere insulation directly to the pipe with

Aerocel adhesive a maximum of every 18’ [5.5

m] to create a vapor stop on below-ambient

(cold) systems. BEST PRACTICES/AEROCEL

EPDM INSULATION/VAPOR STOPS.

- Glue adjoining tubes and fittings with Aerocel

adhesive following BEST PRACTICES/

AEROCEL ADHESIVES.

- Once adhesive is ready for contact, press both

sides of glued butt joints together with firm

pressure under compression to ensure

complete adhesion.

• Optional: for interior installations, apply

Protape over glued butt joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Snap-On Method (installed piping)

SMALL DIAMETER PIPES

- Unslit Aerocel Tubes

• Slide-On Method (new uninstalled piping)

- Push (never pull) tube over pipe.

• Note: Aerocel unslit tube sizes up to 3-1/8”

[7.9 cm] ID ship with an asbestos-free talc

for ease of installation.

- Do not push tube over pipe bends when

insulation thickness is 1/2” [1.3 cm] or greater.

- Install AeroFit or field-fabricated mitered fittings

at pipe bends to prevent insulation compression

(reduced thickness) and condensation.

PREVIOUS PAGE

Page 18: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

17For more information, visit www.aeroflexusa.com

- Turn longitudinal seam down or out of sight

line before adhering to butt joints and fittings

with Aerocel adhesive.

- Once adhesive is ready for contact, press both

sides of glued longitudinal seams and butt

joints together under compression with firm

pressure to ensure complete adhesion.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

- Slit flattest side of tube along 6’ [1.8 m]

longitudinal seam with sharp non-serrated

knife; maintain knife at low angle to prevent

tip from cutting inside wall of tube.

- Install mitered fittings at pipe bends to

prevent insulation compression (reduced

thickness) and condensation.

• Notes:

- Welded pipes (pipe & fittings same size) -

insulate fittings first.

- Pipes with large fittings - insulate straight

runs first.

- Snap slit tube over clean pipe.

- Adhere insulation directly to the pipe with

Aerocel adhesive a minimum of every 18’ [5.5

m] to create a vapor stop on below-ambient

(cold) systems. BEST PRACTICES/AEROCEL

EPDM INSULATION/VAPOR STOPS.

- Glue longitudinal seams, butt joints and

fittings with Aerocel adhesive. BEST

PRACTICES/AEROCEL ADHESIVES

PREVIOUS PAGE

Page 19: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

18 For more information, visit www.aeroflexusa.com

wall and slowly pull away from tube

approximately every 12” [30 cm].

• Carefully line up and press approximately 12”

[30 cm] PSA seam together with firm pressure

to ensure complete adhesion.

• Repeat until inside wall of SSPT tube is

completely sealed.

• If necessary, clean outside skin of tube where

Protape will adhere to with denatured alcohol.

• Locate release liner to Protape double closure

seal and slowly pull away.

12”

- Pre-slit Aerocel SSPT Tubes

• CAUTION: BEST PRACTICES/AEROCEL

EPDM INSULATION/PRESSURE-SENSITIVE

ADHESIVE (PSA)

• Install mitered fittings at pipe bends to prevent

insulation compression (reduced thickness) and

condensation.

- Notes:

• Welded pipes (pipe & fittings same size) -

insulate fittings first.

• Pipes with large fittings - insulate straight

runs first.

• Open SSPT tube and snap on pipe.

• Gently press Protape double closure seal away

from inside seam before adhering inside walls

together.

• Locate the end of gold release liner on inside

PREVIOUS PAGE

Page 20: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

19For more information, visit www.aeroflexusa.com

• Turn longitudinal seam down or out of line of

sight before adhering to butt joints and fittings.

• Once adhesive is ready for contact, press glued

butt joints together under compression with

firm pressure to ensure complete adhesion of

Aerocel adhesive.

- Optional: for interior installations, apply

Protape over glued butt joints and fittings.

- Required: for exterior installations, apply

Protape over glued butt joints and fittings;

turn taped longitudinal seams away from

direct sun exposure when possible.

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Carefully press Protape double closure seal

onto clean outside wall of tube with firm

pressure, avoiding any kinks or gaps, until the

SSPT tube is fully sealed.

• Apply Aeroflex SSPT squeegee (included in

every carton of SSPT) to Protape seam seal to

remove any air bubbles, kinks or gaps.

• Adhere insulation directly to the pipe with

Aerocel adhesive a minimum of every 18’ [5.5

m] to create a vapor stop on below-ambient

(cold) systems. BEST PRACTICES/AEROCEL

EPDM INSULATION/VAPOR STOPS

• Glue adjoining tubes and fittings with Aerocel

adhesive following BEST PRACTICES/

AEROCEL ADHESIVES.

PREVIOUS PAGE

Page 21: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

20 For more information, visit www.aeroflexusa.com

- Straight pipe runs are typically insulated up to

45° bend.

- Cut Aerocel unslit tube at 22.5° angle using

Aeroflex Template and long sharp knife.

- Cut horizontal and vertical lengths long to

install with compression to adjoining tubes.

- Glue two 22.5° pieces under compression to

form 45° angle with Aerocel adhesive.

A

Br

r

- AeroFit Factory Fabricated Fitting Covers

BEST PRACTICES/AEROFIT FITTING COVERS

- Using the Aeroflex Template | Field-Fabricated

Fittings

• The Aeroflex Template is printed on every

carton of Aerocel pipe insulation as a convenient

alternative to a miter box to fabricate quality

fittings in the shop or field for the most common

pipe fittings.

• Break down an empty carton or cut out

template and place on flat work surface.

• Use a sharp non-serrated knife with a knife

sharpener on hand.

• Place tube along bold horizonal base line.

• Mark cuts with light-colored marker or chalk.

• Align knife with desired angle reference and

cut smoothly through tube; ensure clean cuts

without rough edges. Sharpen knife if necessary.

- Pipe Bends | 45° | 2-piece

• Elbows - Welded (fitting & piping same

diameter)

22.5

PREVIOUS PAGE

Page 22: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

21For more information, visit www.aeroflexusa.com

- Pipe Bends | 90° | 2-piece

• Elbows - Welded (fitting & piping same

diameter)

- Install fitting cover before insulating straight

runs.

• Note: If straight runs are installed prior to

90° fitting cover, measure and cut fitting

cover to fit with compression.

- Once 45° seam is bonded, cut inside radius of

cover (throat).

- Install over pipe fitting and glue throat under

compression with Aerocel adhesive.

- Glue fitting cover to adjoining tubes under

compression with Aerocel adhesive.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

PREVIOUS PAGE

Page 23: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

22 For more information, visit www.aeroflexusa.com

- Install over pipe fitting and glue throat under

compression with Aerocel adhesive.

- Glue fitting cover to adjoining tubes under

compression with Aerocel adhesive.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

- Cut Aerocel unslit tube at 45° angle using

Aeroflex Template and long sharp knife.

- Cut horizontal and vertical lengths long to

install with compression to adjoining tubes.

- Glue two 45° pieces under compression to

form 90° angle with Aerocel adhesive.

- Once 45° seam is bonded, cut inside radius of

cover (throat).

OD

OD

45˚

PREVIOUS PAGE

Page 24: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

23For more information, visit www.aeroflexusa.com

- Cut two (2) segmented pieces to form 90°

angle.

- Glue two (2) sections to form elbow with

Aerocel adhesive.

OD

OD

45˚

• Elbows – Oversized (fitting larger than piping)

- Insulate straight runs before fitting covers.

- Select Aerocel unslit tube ID that snugly fits

over insulated straight run pipe.

- Cut horizontal and vertical lengths long to

install with compression to adjoining tubes.

≥ 1"

PREVIOUS PAGE

Page 25: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

24 For more information, visit www.aeroflexusa.com

- Curved Pipe Bends | 90° | Segmented

• 3-Piece Elbows - Welded (fitting & piping same

diameter)

• 3-Piece Elbows - Oversized (fitting larger than

piping)

3/8"

22.5˚ 22.5˚

OD

OD

- Once 45° seam is bonded, cut inside radius of

cover (throat).

- Install over pipe fitting and glue throat under

compression with Aerocel adhesive.

- Glue fitting cover to outside surface of

insulated straight runs under compression

with Aerocel adhesive.

- Ensure complete vapor seal with no gaps present.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

22.5°

PREVIOUS PAGE

Page 26: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

25For more information, visit www.aeroflexusa.com

• 5-Piece Elbows - Welded (fitting & piping same

diameter)

- Pipe Intersections

• Tee’s

- Hole Punch method

• Punch hole in tube to insulate main

(horizontal) pipe with sharpened pipe end

of right diameter; use divider to cut hole for

larger pipes.

OD

3/8”

3/8”

OD3/8”

11.25˚ 11.25˚11.25˚ 11.25˚

11.25°

OD

OD

• 4-Piece Elbows - Welded (fitting & piping same

diameter)

• 4-Piece Elbows - Oversized (fitting larger than

piping)

15°

OD

OD

3/8”

3/8”

15˚ 15˚

PREVIOUS PAGE

Page 27: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

26 For more information, visit www.aeroflexusa.com

• Using Aeroflex Template, cut two 45° angles

to center at end of tube for branch (vertical)

pipe.

• Cut two 45° angles in bottom center of

main (horizontal pipe) at intersection; notch

should fit OD of branch pipe.

• Join and glue two fabricated pieces

together with Aerocel adhesive.

• Slit Tee on sides, snap over pipe intersection

and glue seams and butt joints to adjoining

straight runs under compression with

Aerocel adhesive.

• Ensure complete vapor seal with no gaps

present.

- Optional: for interior installations, apply

Protape over glued longitudinal seams,

butt joints and fittings.

- Required: for exterior installations,

apply Protape over glued longitudinal

seams, butt joints and fittings; turn taped

longitudinal seams away from direct sun

exposure when possible.

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Slit tube and snap over main pipe at

intersection with hole positioned over

branch (vertical) pipe.

• At end of tube used for branch (vertical)

pipe, cut radiused recess which will contact

bottom of main pipe inside horizontal tube.

• Slit tube and snap over branch pipe and join

with horizontal tube.

• Glue horizontal and vertical pieces together

with Aerocel adhesive and to adjoining

straight runs.

• Ensure complete vapor seal with no gaps

present.

- Optional: for interior installations, apply

Protape over glued longitudinal seams,

butt joints and fittings.

- Required: for exterior installations,

apply Protape over glued longitudinal

seams, butt joints and fittings; turn taped

longitudinal seams away from direct

sun exposure when possible; turn taped

longitudinal seams away from direct sun

exposure when possible.

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or

jacketing system for UV protection. For

mechanical protection, install jacketing

system specifically designed for pipe

insulation.

- Miter Box / 90° method

1/2 OD

1/2 OD1/2 OD

1/2 OD

45˚45˚

45˚45˚

PREVIOUS PAGE

Page 28: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

27For more information, visit www.aeroflexusa.com

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or

jacketing system for UV protection. For

mechanical protection, install jacketing

system specifically designed for pipe

insulation.

• Cross Joints

• Angle-T’s / Y-Branches

- Cut piece of Aerocel unslit tube to correct

length for main vertical pipe.

OD

OD

OD

- 3-Piece Segmented method

• Using Aeroflex Template, place tube on

baseline.

• Make one 45° cut.

• Make 2nd 45° cut in opposite direction of 1st

cut while holding both pieces together.

• Make 3rd 45° cut.

• Lengths of cuts must be equal.

• Join and glue three fabricated pieces

together with Aerocel adhesive.

• Slit Tee on sides, snap over pipe intersection

and glue seams and adjoining straight runs

under compression with Aerocel adhesive.

• Ensure complete vapor seal with no gaps

present.

- Optional: for interior installations, apply

Protape over glued longitudinal seams,

butt joints and fittings.

- Required: for exterior installations,

apply Protape over glued longitudinal

seams, butt joints and fittings; turn taped

longitudinal seams away from direct sun

exposure when possible.

1/2 OD

OD

1/2 OD

45˚45˚

45˚45˚

PREVIOUS PAGE

Page 29: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

28 For more information, visit www.aeroflexusa.com

- Cut U-shape at end of 45° cut that meets up

with main vertical pipe insulation so there are

no gaps.

- Cut mitered piece along one side, fit over pipe

and glue seam.

- Glue mitered branch to main pipe under

compression with Aerocel adhesive.

- Ensure complete vapor seal with no gaps present.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Y-Tubes

45˚ Bend 45˚ Bend

90˚ Bend

- Punch hole in tube at correct location and

angle with hole punch or sharpened copper

pipe with the correct OD of branch pipe.

- Cut main vertical tube lengthwise where it

intersects with branch pipe and glue seam

with Aerocel adhesive.

- Using Aeroflex Template, cut another tube to

fit branch pipe with 45° angle cut at one end.

PREVIOUS PAGE

Page 30: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

29For more information, visit www.aeroflexusa.com

• Glue notched edges together with Aerocel

adhesive

• Cut end of notched size so diameter lines up

with OD of smaller tube.

• Cut end of larger ID side so length of reducer is

1/2” longer than opening to allow for 1/4”

compression on each side.

- Collars / Pipe Reducers

• With piece of Aerocel tube the same ID as larger

pipe, cut a section larger than opening between

straight run tubes installed on either side of

pipe transition.

• At one end, cut two equal notches out of

opposite sides to fit smaller tube.

PREVIOUS PAGE

Page 31: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

30 For more information, visit www.aeroflexusa.com

- Valves

• Valve stem (small diameter)

- From edge of straight run tube to center of

valve stem, cut and punch hole same

diameter as stem.

- Install tube on pipe and fit under compression

around valve and with adjoining tube.

- Glue valve stem, seam between valve stem,

end of tube and butt joint under compression

with Aerocel adhesive.

• Cut reducer along entire length and snap on

pipe collar.

• Glue reducer seam and butt joints under

compression with Aerocel adhesive.

• Ensure complete vapor seal with no gaps

present.

- Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

- Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

PREVIOUS PAGE

Page 32: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

31For more information, visit www.aeroflexusa.com

- Slit sleeve along entire length and flatten out.

- Measure and cut seam longitudinally from

edge of sleeve to center of valve stem.

- Punch hole to wrap around valve stem at end

of seam.

- Install sleeve over valve and adjoining tubes.

- Glue sleeve to both adjoining tubes and

seams within sleeve under compression with

Aerocel adhesive.

- If space allows between sleeve and valve

handle, insulate by fabricating, gluing and

installing a donut to insulate the stem.

- Seal all terminations with Aerocel adhesive.

- Ensure complete vapor seal with no gaps present.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation

• Valve stem (large diameter)

- Install straight runs of Aerocel pipe insulation

up to valve stem.

- Wrap Protape securely around the base of valve.

- Cut length of Aerocel tube with the same ID as

OD of installed tubes; this will be the sleeve.

PREVIOUS PAGE

Page 33: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

32 For more information, visit www.aeroflexusa.com

LARGE DIAMETER PIPES | ROUND DUCTS

- Aerocel Sheet & Roll

• Sheet:

- Standard Back (no PSA) - available in 3’x4’

[.91 m x 1.2 m], thicknesses 1/4” to 3” [.63 cm -

7.6 cm] (ASTM E84 25/50 through 2”)

- PSA Back - available in 3’x4’ [.91 m x 1.2 m],

thicknesses 1/4” to 2-1/2” [.64 cm - 6.4 cm]

(ASTM E84 25/50 through 2”)

• Roll:

- Standard Back (no PSA) - available in 48” [122

cm] width, thicknesses 1/8” to 2-1/2” [.32 cm -

6.4 cm] (ASTM E84 25/50 through 2”)

- PSA Back - available in 48” width [122 cm],

thicknesses 1/4” to 2-1/2” [.64 cm - 6.4 cm]

(ASTM E84 25/50 through 2”)

- Seal all terminations with Aerocel adhesive.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

- Block at Pipe End (no termination point)

• Using proper sized sharpened pipe end, cut

plug out of same thickness of Aerocel sheet/roll

insulation.

• Glue end of tube ID and fabricated plug with

Aerocel adhesive.

• Once glue is ready for contact, insert plug in

end of tube.

• Ensure complete vapor seal with no gaps

present.

PREVIOUS PAGE

Page 34: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

33For more information, visit www.aeroflexusa.com

• Apply Aerocel

adhesive to cut

edges of longitudinal seam, allow to tack up

until ready for contact.

• Place insulation over pipe and adhere glued

longitudinal seam by pressing from the outside

edges towards the middle to ensure straight

edges at butt joints, full adhesion and vapor

seal.

• Glue butt joints under compression with Aerocel

adhesive.

- Sheet & Roll | Pipe Size Applications

- Pipes (straight runs)

• Determine pipe circumference by wrapping strip

of Aerocel Sheet or Roll, the same thickness to

be installed, around pipe; add 1/4” [.64 cm] to

measurement.

• Do not stretch strip; insulation should fit slightly

loose over pipe without stress on seams.

• Mark and cut length of sheet or roll with

straight edge.

Sheet/RollThickness

Outside Pipe Diameter (inches)

≥ 4” [10 cm]

≥ 5” [13 cm]

≥ 6” [15 cm]

≥ 8” [20 cm]

3/8” [.95 cm] • • • •

1/2” [1.3 cm] • • • •

3/4” [1.9 cm] • • • •

1” [2.5 cm] • • • •

1-1/2” [3.8 cm] • • •

2” [5 cm] •

PREVIOUS PAGE

Page 35: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

34 For more information, visit www.aeroflexusa.com

• Mark and cut length of Aerocel Sheet & Roll

with straight edge; add 1/4" [.64 cm] to

measurement.

• Apply Aerocel adhesive to cut edges of

longitudinal seam, allow to tack up until ready

for contact.

• Place insulation over pipe and adhere glued

longitudinal seam by pressing from the outside

edges towards the middle to ensure straight

edges at butt joints, full adhesion and vapor seal.

• Ensure complete vapor seal with no gaps

present.

- Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

- Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings; turn taped longitudinal

seams away from direct sun exposure when

possible.

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Notes:

- Full coverage adhesion of sheets/rolls

to pipes is not recommended due to

variation of expansion/contraction by

layer on an operational system.

- Prior to sealing butt joints on chilled water

or refrigerant piping, install vapor stop at

all butt joints by applying at least 1/2” [1.3

cm] strip of adhesive to pipe and insulation

bonding insulation directly to the pipe.

- To minimize sagging on vertical piping,

apply wide (approx. 4” [10 cm]) adhesive

strips to pipe and insulation at all butt joints

and directly adhere insulation to the pipe.

- For pipe sizes ≥12” [30 cm] OD, sheets/

rolls should be directly adhered to bottom

1/3 of the pipe to prevent sagging.

- Multi-Layering

• Ensure that outer skin of first layer is dry

and dust-free; clean with denatured alcohol if

necessary.

- Note: If Aeroseal or Aeroseal LVOC Black

were installed with 1st layer and dry to the

touch prior to contact, the 2nd layer may be

applied immediately. For REF 1520, allow 24-

36 hours cure time for 1st layer.

• Measure outside diameter of 1st insulated layer

by applying the same principles when

measuring pipe OD for 1st layer.

PREVIOUS PAGE

Page 36: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

35For more information, visit www.aeroflexusa.com

• Mark and cut length of Aerocel Sheet & Roll

with straight edge; add 1/4" [.64 cm] to

measurement.

• Apply Aerocel adhesive to cut edges of

longitudinal seam, allow to tack up until ready

for contact.

• Place insulation over pipe and adhere glued

longitudinal seam by pressing from the outside

edges towards the middle to ensure straight

edges at butt joints, full adhesion and vapor seal.

- Required: for exterior and extreme

installations, apply Protape over glued

longitudinal seams, butt joints and fittings;

turn taped longitudinal seams away from

direct sun exposure when possible.

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Notes:

- Full coverage adhesion of multiple

layers is not recommended due to varied

expansion/contraction by layer on an

operational system.

- For extreme refrigeration or cryogenic

applications, apply Protape over all sealed

longitudinal seams and butt joints of 1st

layer.

- Pipe Bends

• 90° Angles | Elbows

- Calculate inside (throat) radius (r) by

determining intersection of horizontal and

vertical lines outside of pipe welds.

r

• Ensure that all longitudinal seams and butt

joints are staggered; do not overlap the

previous layer.

• Glue butt joints under compression with Aerocel

adhesive.

• Ensure complete vapor seal with no gaps

present.

- Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

PREVIOUS PAGE

Page 37: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

36 For more information, visit www.aeroflexusa.com

- Divide the circumference (c) by 2 and mark

sheet with outer radius from inner radius

using divider.

- Cut first half of fitting cover and use as

template to cut out 2nd half.

- Position both sides together with smooth skin

facing out and apply Aerocel adhesive to

outer edges.

- On Aerocel Sheet or Roll, mark line

representing insulation thickness along edge

of length and width (X & Y axis).

- From the intersection of X & Y axis, mark

outline of inside radius with divider.

- Measure the circumference of pipe using strip

of Aerocel Sheet or Roll (same thickness, do

not stretch); add 1/4" [.64 cm] to measurement.

1/4 Øt'

1/4 Ø

t'r 1/2 c

PREVIOUS PAGE

Page 38: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

37For more information, visit www.aeroflexusa.com

- Divide the circumference (c) by 2 and mark

sheet with outer radius from inner radius

using divider.

- Cut first half of fitting cover and use as

template to cut out 2nd half.

- Position both sides together with smooth skin

facing out and apply Aerocel adhesive to

outer edges.

- Once glued inside seam is ready for contact,

wrap the fitting cover around pipe bend and

apply firm pressure to ensure complete

adhesion.

- Glue fitting cover to butt joints of

adjoining tubes under compression with

Aerocel adhesive.

- Once glued edges are ready for contact,

adhere outside edges together from the outer

edges inwards.

- Turn fitting cover over, lay flat and apply firm

pressure to seam from inside to ensure

complete adhesion.

- Apply Aerocel adhesive to inside edges and

allow to tack.

PREVIOUS PAGE

Page 39: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

38 For more information, visit www.aeroflexusa.com

- Using strip used to measure circumference of

pipe (Z), mark circumference and center line

on bottom edge of Aerocel sheet.

- Mark inner (X) and outer (Y) measurements

to perpendicular edge of sheet.

- Using divider, mark arcs measuring 1/2 of the

circumference.

- Draw continuous line to join arcs and cut

along line.

Y

Z

X X

XY Y

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over glued butt joints and fitting

seams.

• Required: for exterior and extreme

installations, apply Protape over glued butt

joints and fitting seams; turn taped seams away

from direct sun exposure whenever possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Miter Angles | Bevel Joints

- Measure the circumference of pipe using strip

of Aerocel Sheet or Roll (same thickness, do

not stretch); add 1/4" [.64 cm] to measurement.

- Measure the inner height (X) and out height

(Y) of miter joint.

X

Y

PREVIOUS PAGE

Page 40: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

39For more information, visit www.aeroflexusa.com

- Pipe Intersections | One-Piece T

• Measure length of main pipe (X) and branch

pipe (Y).

• With strip of Aerocel Sheet the same thickness

as insulation to be installed, measure the

circumference of main and branch pipes (do not

stretch); add 1/4" [.64 cm] to measurement.

• Mark horizontal and vertical measurements on

Aerocel sheet.

Y

X

Z

X1/2 a

1/2 d Y

- Flip both cut pieces 180° to create upper and

lower sections of miter joint.

- Apply Aerocel adhesive to longitudinal and

miter seam; allow to tack.

- When ready for contact, join longitudinal

seam first followed by miter seam with firm

pressure under compression.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over glued butt joints and fitting

seams.

• Required: for exterior and extreme

installations, apply Protape over glued butt

joints and fitting seams.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

PREVIOUS PAGE

Page 41: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

40 For more information, visit www.aeroflexusa.com

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

- Collars | Pipe Reducers

• Concentric

- Measure length and diameters of large and

small pipes.

• L = length of reducer including weld on both

sides

• D1 = diameter of larger pipe + 2x insulation

thickness

• D2 = diameter of smaller pipe + 2x

insulation thickness

- Transfer L, D1 and D2 measurements to

Aerocel Sheet; draw lines from ends of both

measurements to point.

L

D1D2

D1

D2

L

• For branch pipe, mark the center and to both

sides of vertical line.

• Mark 1/2 diameter of branch pipe with straight

lines and cut out sections.

• Apply Aerocel adhesive to edges of fabricated T

fitting cover and allow to tack.

• Once glued edges are ready for contact, wrap T

fitting cover around pipe intersection and apply

firm pressure under compression to glued seams

to ensure complete adhesion and vapor seal.

• Once straight run pipe insulation and flange

covers are installed, glue T fitting cover to

flange covers under compression with Aerocel

adhesive.

• Ensure complete vapor seal with no gaps present.

- Optional: for interior installations, apply Protape

over glued butt joints and T fitting cover seams.

- Required: for exterior and extreme

installations, apply Protape over glued butt

joints and T fitting cover seams.

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

PREVIOUS PAGE

Page 42: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

41For more information, visit www.aeroflexusa.com

- Apply Aerocel adhesive to both edges of

reducer seam and allow to tack.

- Once ready for contact, wrap fitting cover

over reducer and firmly adhere from the

outer edges to center to ensure flush edges

at seam.

- Glue butt joints of reducer fitting to insulation

on large and small pipes under compression

with Aerocel adhesive.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over glued butt joints and reducer

fitting cover seams.

• Required: for exterior and extreme

installations, apply Protape over glued butt

joints and reducer fitting cover seams; turn

taped longitudinal seams away from direct

sun exposure when possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

- With divider, draw two arcs.

- Measure circumference of larger pipe with

strip of Aerocel Sheet of same thickness as

insulation on larger pipe (do not stretch); add

1/4" [.64 cm] to measurement.

- Mark center of circumference strip and place

on larger arc; draw lines from both ends of

strip to center.

- Carefully cut out reducer from sheet.

D1

PREVIOUS PAGE

Page 43: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

42 For more information, visit www.aeroflexusa.com

- Carefully cut out reducer from sheet.

- Apply Aerocel adhesive to both edges of

reducer seam and allow to tack.

- Once ready for contact, wrap fitting cover over

reducer and firmly adhere from the outer

edges to center to ensure flush edges at seam.

- Glue butt joints of reducer fitting to insulation

on large and small pipes under compression

with Aerocel adhesive.

- Ensure complete vapor seal with no gaps present.

- Optional: for interior installations, apply

Protape over glued butt joints and

reducer fitting cover seams.

- Required: for exterior and extreme

installations, apply Protape over glued butt

joints and reducer fitting cover seams; turn

taped longitudinal seams away from direct

sun exposure when possible.

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

• Eccentric

- Measure length and diameters of large and

small pipes.

• L = length of reducer including weld on both

sides

• A = angled length of reducer

• D1 = diameter of larger pipe + 2x insulation

thickness

• D2 = diameter of smaller pipe + 2x

insulation thickness

- Transfer L, A, D1 and D2 measurements to

Aerocel Sheet.

L

A

D1D2 d2

d1

D1

L

D2

S

AerocelStrip

L

S

A

1/4 D2

AerocelStrip

PREVIOUS PAGE

Page 44: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

43For more information, visit www.aeroflexusa.com

• Using divider, draw inner and outer

circumferences on two separate pieces of

Aerocel Sheet.

• Carefully cut out both rings and slit one side to

wrap around flange.

• Wrap rings around pipes on both sides of flange

and fully adhere to insulation inserts and bolts

with Aerocel adhesive; do not glue rings to

installed pipe insulation yet.

protection, install jacketing system

specifically designed for pipe insulation.

- Flanges

• Insulate adjoining pipes up to flange.

- Note: for chilled water or refrigeration

systems, insert and glue strips of Aerocel

insulation between flange bolts.

• Using caliper, measure circumference of

insulated pipe.

• Using caliper, measure circumference of flange.

W = width + 2x insulation thickness

D= diameter + 3/8”

PREVIOUS PAGE

Page 45: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

44 For more information, visit www.aeroflexusa.com

• Wrap jacket around rings to confirm proper fit

(not stretched).

• Apply Aerocel adhesive to inside of long edges

and horizontal seam of jacket and outside edges

of rings and allow to tack.

• When ready for contact, carefully adhere jacket

to rings with flush edges under compression;

glue inside radius of rings to pipe insulation

with Aerocel adhesive under compression.

• Ensure complete vapor seal with no gaps present.

• Optional: for interior installations, apply

Protape over glued butt joints and flange

fitting cover seams.

• Required: for exterior and extreme

installations, apply Protape over glued butt

joints and flange fitting cover seams; turn

taped longitudinal seams away from direct

sun exposure when possible.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Measure circumference of rings with strip of

Aerocel Sheet that is the same thickness (do

not stretch); add 1/4" [.64 cm] to measurement.

• Measure width of insulated flange.

• Draw with straight edge and cut flange jacket

from Aerocel Sheet.

PREVIOUS PAGE

Page 46: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

45For more information, visit www.aeroflexusa.com

- Carefully cut out both rings and slit one side

to wrap around flange.

- Wrap rings around pipes on both sides of

flange and fully adhere to insulation inserts

and bolts at flange and insulated pipes.

- Measure circumference of rings (C) with strip

of Aerocel Sheet that is the same thickness

(do not stretch); add 1/4" [.64 cm] to

measurement.

C

- Valves

• Body

- Insulate adjoining pipes up to flange; valve

body should always be insulated after piping.

• Note: for chilled water or refrigeration

systems, insert and glue strips of Aerocel

insulation between flange bolts in valve body.

- Using caliper, measure circumference of

insulated pipe and flange.

- Using divider, draw inner and outer

circumferences on two separate pieces of

Aerocel Sheet.

PREVIOUS PAGE

Page 47: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

46 For more information, visit www.aeroflexusa.com

- When ready for contact, carefully adhere

jacket to rings with flush edges under

compression.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Spindles

- Measure height (H) and width (W) and shape

of spindle housing.

H

W

- Measure width of insulated valve including

rings (W) and spindle housing (S).

- On Aerocel Sheet, mark and cut width (W),

ring circumference (C) and diameter of

spindle (S); mark spindle cut-out 1/8”-1/4”

[.32 cm -.64 cm] short for compression fit.

- Cut jacket and wrap around valve to ensure

proper fit (not stretched).

- Apply Aerocel adhesive to jacket seam, flange

rings, spindle housing and allow to tack.

W S

C

W S

PREVIOUS PAGE

Page 48: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

47For more information, visit www.aeroflexusa.com

- On Aerocel Sheet (same thickness), lay

circumferential strip on sheet and mark into 4

equal segments.

- Measure depth from outside edge of cover to

nearest and farthest distance to valve body.

- Transfer both depth measurements to marked

sheet.

- Mark and cut cover for face plate of spindle

flange from Aerocel Sheet.

- Cut one side of cover, glue edges with Aerocel

adhesive and allow to tack.

- Once ready for contact, wrap cover over

spindle and press glued edges firmly together;

be sure to glue inside seam of cover to

spindle face plate for vapor seal.

- Measure circumference (C) of cover with strip

of Aerocel Sheet the same thickness (do not

stretch); add 1/4" [.64 cm] to measurement.

W

H

PREVIOUS PAGE

Page 49: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

48 For more information, visit www.aeroflexusa.com

- Apply Aerocel adhesive to longitudinal seam,

allow to tack and seal around spindle housing.

- Glue edges of spindle housing jacket to valve

cover body with Aerocel adhesive under

compression.

- Glue edges of spindle housing jacket to face

plate cover with Aerocel adhesive under

compression.

- Using divider with radius equaling difference

between long and short measurements, draw

intersecting arcs to create continuous line

across 4 segments on sheet.

- Carefully cut along continuous line.

- Miter inside edge that will join valve body.

PREVIOUS PAGE

Page 50: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

49For more information, visit www.aeroflexusa.com

- Using divider, draw inner and outer

circumferences on two separate pieces of

Aerocel Sheet.

- Carefully cut out both rings and slit one side

to wrap around flange.

- Wrap rings around pipes on both sides of

flange and fully adhere to insulation inserts

and bolts at flange and insulated pipes with

Aerocel adhesive.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over all glued spindle cover seams.

• Required: for exterior and extreme

installations, apply Protape over all spindle

cover seams.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

- Angled | Inclined Seat | Strainer Valves

• Body

- Insulate adjoining pipes up to flange; valve

body should always be insulated after piping.

• Note: For chilled water or refrigeration

systems, insert and glue strips of Aerocel

insulation between flange bolts in valve body.

- Using caliper, measure circumference of

insulated pipe (P) and flange (F).

F P

PREVIOUS PAGE

Page 51: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

50 For more information, visit www.aeroflexusa.com

- Transfer above measurements to Aerocel

sheet and mark sheet accordingly.

- Cut sheet along marked lines and wrap

fabricated cover around valve body to ensure

an accurate fit (do not stretch).

- Glue valve body cover to rings, longitudinal

seam and around strainer body with Aerocel

adhesive under compression.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over glued longitudinal seams, butt

joints and strainer valve body seams.

• Required: for exterior installations, apply

Protape over glued longitudinal seams, butt

joints and fittings.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

S2 S3

S1

C

1/2 F

1/2 F

- Measure circumference of rings with strip of

Aerocel Sheet that is the same thickness (do

not stretch); add 1/4" [.64 cm] to measurement.

- Measure length between outer edges of each

ring (S1, S2+S3) and strainer body.

- Using caliper, measure diameter of strainer

body (S).

S1

S3

S2S4

S1

PREVIOUS PAGE

Page 52: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

51For more information, visit www.aeroflexusa.com

- Transfer measurement of 1/2 ring

circumference (1/2 c) and inner/outer strainer

dimensions to Aerocel Sheet of the same

thickness.

- Cut strainer cover along marked lines and

miter inside edge to be adhered to strainer

body to ensure flush fit (do not stretch).

- Glue strainer body cover to rings, longitudinal

seam and around strainer wheel with Aerocel

adhesive under compression.

1/4 pipe

L L

1/2 c1/2 cS

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

• Strainer

- Using caliper & divider, measure diameter at

end of strainer body, transfer measurements

to Aerocel sheet of the same thickness, draw

and cut ring to install at end of strainer. Glue

ring to strainer with Aerocel adhesive.

- Measure long (L) and short (S) sides of

strainer body (including thickness of ring).

S

L

PREVIOUS PAGE

Page 53: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

52 For more information, visit www.aeroflexusa.com

• Pipe (P) = outside diameter

• Length (L) = end-to-end

• Height (H) = height of screws plus 2x

insulation thickness

• Diameter (D) = outside diameter

• Radius (R) = D x 1/2 + 2x insulation thickness

- Using divider, mark circular arc (P) and (D),

length (L), height (H) and center line to Aerocel

Sheet of the same thickness.

- Create oval shape by connecting circular arc

and four points (coupling ring).

- Cut out this ring to use as template to

duplicate a second coupling ring.

- Glue rings to both sides of coupling and pipe

insulation with Aerocel adhesive.

- Measure width (X) and circumference of outer

edges of rings with strip of Aerocel Sheet of

the same thickness (do not stretch); add 1/4"

[.64 cm] to measurement.

L

H

D

P

X

- Ensure complete vapor seal with no gaps present.

• Optional: for interior installations, apply

Protape over all glued strainer cover seams.

• Required: for exterior and extreme

installations, apply Protape over all strainer

cover seams.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

- Pumps

- Note: Due to the wide variety of pump

configurations, apply general fabrication

principals with other fitting cover types,

primarily no gaps, proper adhesion and

complete vapor seals at all insulation seams

and terminations with Aerocel adhesive.

- Couplings

- Insulate adjoining pipes up to coupling.

- Measure dimensions of coupling.

L

HD

P

PREVIOUS PAGE

Page 54: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

53For more information, visit www.aeroflexusa.com

• Pipe (P) = outside diameter

• Length (L) = end-to-end

• Height (H) = height of screws plus 2x

insulation thickness

• Diameter (D) = outside diameter

• Radius (R) = D x 1/2 + 2x insulation thickness

- Using divider, mark circular arc (P) and (D),

length (L), height (H) and center line to Aerocel

Sheet of the same thickness.

- Create oval shape by connecting circular arc

and four points (coupling ring).

- Cut out this ring to use as template to

duplicate a second coupling ring.

- Glue rings to both sides of coupling and pipe

insulation with Aerocel adhesive.

- Measure width (X) and circumference of outer

edges of rings with strip of Aerocel Sheet of

the same thickness (do not stretch); add 1/4"

[.64 cm] to measurement.

L

H

D

P

X

PIPE HANGERS

- Aerofix insulated pipe supports

• Open Aerofix fitting, remove two inside release

liners, wrap around pipe, center at hanger

location and press two halves together.

- Transfer these measurements to Aerocel

Sheet of same thickness and cut out the

coupling cover.

- Glue coupling cover to rings and cover seam

with Aerocel adhesive under compression.

- Ensure complete vapor seal with no gaps

present.

• Optional: for interior installations, apply

Protape over all glued coupling cover seams.

• Required: for exterior and extreme

installations, apply Protape over all coupling

cover seams.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

PREVIOUS PAGE

Page 55: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

54 For more information, visit www.aeroflexusa.com

• Ensure complete vapor seal with no gaps

present.

• Optional: for systems operating above -20°F

[-29°C], apply Protape over glued seams.

• Required: for systems operating below -20°F

[-29°C], apply Protape over glued seams.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for pipe insulation.

- Insulate other pipe support systems

- Note: not an ideal system since two different

insulation materials are installed through pipe

hanger.

• Clean all pipe support surfaces with denatured

alcohol.

• Apply thin coat of Aerocel adhesive to pipe

support and allow to dry.

• Apply 2nd coat of Aerocel adhesive to pipe

support and adjoining Aerocel insulation tubes;

allow to tack up until ready for contact.

• Bond insulation to both sides of pipe support

under compression.

• Ensure that entire pipe support is insulated and

glued to provide vapor seal and prevent thermal

bridging (condensation).

• Cover all glued seams and terminations with

zero-perm Protape.

- Insulate over pipe hanger

- Note: not recommended for below-ambient

systems.

• Remove release liner from Protape outer jacket

and apply with pressure to achieve a vapor seal.

• Position Aerofix so seam between the two

halves is horizontal to the legs of pipe support

system.

• Do not allow any gaps in the closure of the

insulation envelope.

• Seal Aerofix to adjoining Aerocel insulation

tubes with Aerocel adhesive and apply firm

pressure under compression.

PREVIOUS PAGE

Page 56: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

55For more information, visit www.aeroflexusa.com

TANKS & VESSELS

- Surface Preparation

• Clean and dry tank/vessel surface to remove

bond-breaking agents (grease, oil & water) and

contaminants that could cause bond failure and/

or corrosion under insulation.

- Note: When using an aerosolized spray

contact adhesive, confirm with manufacturer

that adhesive is recommended for bonding

closed cell flexible elastomeric foam

insulation to tanks/vessels and follow

application instructions.

- Aerocel Sheet & Roll with AEROSEAL adhesive

• Install straight runs of Aerocel tube up to

hanger.

• Glue ends of both tubes to pipe with Aerocel

adhesive to form vapor stops at hanger.

• Cut square piece of Aerocel unslit tube greater

than the circumference of the insulated pipe and

punch hole for vertical hanger riser and slit from

hole to edge. Cut length parallel to pipe.

• Wrap fitting cover over hanger and check for

proper fit (do not stretch).

• Seal all fitting cover seams and to outer surface

of adjoining tubes with Aerocel adhesive to

provide complete vapor seal.

PREVIOUS PAGE

Page 57: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

56 For more information, visit www.aeroflexusa.com

• Use weighted roller to activate and ensure full

contact of PSA adhesive on insulation sheet/roll

to tank/vessel.

• Glue all adjoining seams and termination points

with Aeroseal or Aeroseal LVOC Black adhesive

under compression to create vapor seal.

- Optional: for interior installations, apply

Protape over glued seams.

- Required: for exterior installations, apply 2"

Protape evenly over seams followed by 2" on

either side of taped seam (4" [10 cm] total

taped seam width).

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system specifically

designed for tank/vessel insulation.

- Small (< 5’ diameter)

• Measure the circumference of the tank using a

strip of Aerocel Sheet insulation of same

thickness. Adhere strips together if necessary

(do not stretch); add 1/4" [.64 cm] to

measurement.

• Transfer this measurement to Aerocel Sheet,

mark and cut length with straight edge.

• Starting from the top where the dome meets

the body, install insulation approximately 2” [5

cm] above tank body for compression fit with

dome insulation.

• Follow adhesive/PSA installation guidance above.

Tangent Line

• Follow adhesive best practices and adjust

depending on jobsite conditions (ambient

temperature, direct sun and relative humidity).

• Apply Aeroseal adhesive to insulation and tank/

vessel with adhesive roller and allow to tack dry

to the touch without transfer.

• Ensure full contact of glued insulation to glued

tank/vessel surface with weighted roller.

• Glue all adjoining seams and termination points

with Aeroseal adhesive under compression to

create vapor seal.

• To meet low-VOC requirements, select

Aerocel Sheet & Roll with PSA and Aeroseal

LVOC Black adhesive to seal all seams and

termination points.

- Optional: for interior installations, apply

Protape over glued seams.

- Required: for exterior installations, apply 2"

Protape evenly over seams followed by 2" on

either side of taped seam (4" [10 cm] total

taped seam width).

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system specifically

designed for tank/vessel insulation.

- Aerocel Sheet/Roll with PSA

• Peel PSA release liner and adhere Aerocel

insulation directly to clean tank/vessel surface.

PREVIOUS PAGE

Page 58: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

57For more information, visit www.aeroflexusa.com

• Cut out dome cover. If necessary, glue multiple

sheets together for dome cover.

• Apply Aeroseal adhesive to both surfaces and

allow to tack.

• When adhesive is ready for contact, apply to

dome pressing down firmly from the center to

outer edges.

• Continue to install insulation horizontal

courses to bottom of tank/vessel ensuring that

insulation is installed under compression.

• Glue vertical seam under compression with

Aerocel adhesive.

• Measure the diameter of the dome using a strip

of Aerocel Sheet insulation of same thickness.

Adhere strips together if necessary (do not

stretch); add 1/4" [.64 cm] to measurement.

• Transfer diameter measurement to Aerocel

Sheet, draw radius and then circumference.

PREVIOUS PAGE

Page 59: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

58 For more information, visit www.aeroflexusa.com

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system specifically

designed for tank/vessel insulation.

- Large (> 5’ diameter)

• Starting from the top of the tank/vessel where

the dome meets the body, install insulation

approximately 2” [5 cm] above tank body for

compression fit with dome insulation.

• Glue vertical and horizontal seams under

compression with Aerocel adhesive.

• Follow adhesive/PSA installation guidance above.

• Continue to install insulation horizontal courses

under compression to bottom of tank/vessel.

Tangent Line Insulate body

from top down

• For both full-coverage adhesive and PSA

applications, seal all seams and terminations on

dome and body with Aeroseal or Aeroseal LVOC

Black adhesive under compression to provide

vapor seal.

- Optional: for interior installations, apply

Protape over all glued dome cover and body

seams.

- Required: for exterior and extreme

installations, apply 2" Protape evenly over

seams followed by 2" on either side of taped

seam (4" [10 cm] total taped seam width).

PREVIOUS PAGE

Page 60: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

59For more information, visit www.aeroflexusa.com

• Once all sections of the dome are insulated,

glue perimeter seam with Aeroseal adhesive

under compression to create vapor seal.

• For both full-coverage adhesive and PSA

applications, seal all seams and termination

points on dome and body with Aeroseal

or Aeroseal LVOC Black adhesive under

compression to provide vapor seal.

• Optional: for interior installations, apply

Protape over all glued dome cover and body

seams.

• Required: for exterior and extreme

installations, apply 2" Protape evenly over

seams followed by 2" on either side of taped

seam (4" [10 cm] total taped seam width).

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or

jacketing system for UV protection. For

mechanical protection, install jacketing

system specifically designed for tank/vessel

insulation.

• To fabricate dome cover, first mark top

insulation edges of tank/vessel body that

intersect dome with chalk.

• Apply Aerocel Sheet over section to be

insulated with 2” [5 cm] overlap and press into

chalked edge to make impression on underside

of insulation.

• Cut sheet with chalked outline.

• Apply Aeroseal adhesive to cut sheets and

dome, allow to tack and apply with firm

pressure, working from the center to outer

edges of each sheet; do not adhere to perimeter

of body insulation yet.

1

2

34

5

6 7

8

91/4”

PREVIOUS PAGE

Page 61: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

60 For more information, visit www.aeroflexusa.com

- Thoroughly clean sheet metal surfaces to

receive insulation with denatured alcohol to

remove dust, oil or moisture.

• Notes:

- When using an aerosolized spray contact

adhesive, confirm with manufacturer that

adhesive is recommended for bonding

closed cell flexible elastomeric foam

insulation to sheet metal ductwork and

follow application instructions.

- For exterior applications, horizontal

rectangular ductwork must have a pitch

on top side, as determined by HVAC

designer, to allow for watershed to

prevent ponding of water and ice.

- When jacketing Aerocel for exterior

applications, confirm with jacket

manufacturer recommended jacket and tape

overlap (when applicable) at sealed seams.

- For multi-layer applications, ensure that

all 2nd-layer seams are staggered over 1st

layer.

- Measure duct dimensions and cut Aerocel

Sheet & Roll with straight edge.

B

T

R

SB= width of duct + 1/4”S= height of duct + 1/4“ + thickness of insulationT= width of duct + 1/4” + 2x thickness of insulation

DUCT WRAP Interior | Exterior

- Rectangular

• Aerocel Sheet & Roll | Wet-Applied Adhesive

PREVIOUS PAGE

Page 62: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

61For more information, visit www.aeroflexusa.com

- Apply Aeroseal adhesive to flush edge seams

and allow to tack.

- Once adhesive is ready for contact, carefully

install glued edge seams flush and with firm

pressure under compression to ensure

complete contact and vapor seal.

- To meet low-VOC requirements, select

Aerocel Sheet & Roll with PSA and Aeroseal

LVOC Black adhesive to seal seams.

• Optional: for interior installations, apply

Protape over all glued seams.

• Required: for exterior installations, apply

2" Protape evenly over seams followed by

2" on either side of taped seam (4" [10 cm]

total taped seam width).

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for duct insulation.

• Note: add 1/4” [.64 cm] to all measurements

for compression-fitting seams (not

stretched).

- Duct must be insulated in same sequence as

measurements:

• Bottom (B) – flush with side edges of duct.

• Sides (S) – flush with bottom section of

insulation.

• Top (T) – flush with outside edges of side

sections (to shed water if necessary).

- Using Aerocel adhesive best practices,

apply thin coat of Aeroseal adhesive to clean

duct surface and cut sheet/roll with brush

or roller and allow to tack. Do not glue edge

seams yet.

- Once adhesive is ready for contact, carefully

apply sheet/roll to duct with weighted roller

to ensure complete contact.

- Ensure that edge seams are flush.

1/4”

PREVIOUS PAGE

Page 63: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

62 For more information, visit www.aeroflexusa.com

• Note: add 1/4” [.64 cm] to all measurements

for compression-fitting seams (not

stretched).

- Duct must be insulated in same sequence as

measurements:

• Bottom (B) – flush with side edges of duct.

• Sides (S) – flush with bottom section of

insulation.

• Top (T) – flush with outside edges of side

sections (to shed water if necessary).

- To remove PSA release liner, pinch corner of

sheet/roll and peel back 1”-2” [2.5 cm - 5 cm].

1/4”

• Aerocel Sheet/Roll with PSA

- Thoroughly clean sheet metal surfaces to

receive insulation with denatured alcohol to

remove dust, oil or moisture.

• Notes:

- For exterior applications, horizontal

rectangular ductwork must have a pitch

on top side, as determined by HVAC

designer, to allow for watershed to

prevent ponding of water and ice.

- When jacketing Aerocel for exterior

applications, confirm with jacket

manufacturer recommended jacket and

tape overlap (when applicable) at sealed

seams.

- For multi-layer applications, ensure that

all 2nd-layer seams are staggered over 1st

layer.

- Measure duct dimensions and cut Aerocel

Sheet & Roll with straight edge.

B

T

R

SB= width of duct + 1/4”S= height of duct + 1/4“ + thickness of insulationT= width of duct + 1/4” + 2x thickness of insulation

PREVIOUS PAGE

Page 64: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

63For more information, visit www.aeroflexusa.com

- Once adhesive is ready for contact, carefully

install glued edge seams flush and with firm

pressure under compression to ensure

complete contact and vapor seal.

• Optional: for interior installations, apply

Protape over all glued seams.

• Required: for exterior installations, apply

2" Protape evenly over seams followed by

2" on either side of taped seam (4" [10 cm]

total taped seam width).

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for duct insulation.

• Duct Flanges

- Position and align exposed edge at

termination or adjoining insulation.

- Peel back approximately 6" - 10" [15 cm - 25 cm]

of release liner and press sheet/roll firmly into

place to activate PSA using weighted roller to

ensure complete adhesion.

- Continue to end of cut sheet/roll.

- Ensure that edge seams are flush.

- Apply Aeroseal or Aeroseal LVOC Black to

flush edge seams and allow to tack.

PREVIOUS PAGE

Page 65: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

64 For more information, visit www.aeroflexusa.com

• Glue three (3) of the four (4) 45° seams with

Aeroseal or Aeroseal LVOC Black to create

flange cover.

• Wrap flange cover around duct flange and

glue final 45° seam.

• Glue four (4) flange cover edges to duct

wrap with Aeroseal or Aeroseal LVOC Black

under compression to create vapor seal.

- Optional: for interior installations, apply

Protape over all flange cover seams.

- Aerocel Tubes

• Using Aerocel 6’ [1.9 m] unslit tube of same

thickness as duct wrap, slit longitudinally

along entire length.

• Measure length of four duct flanges.

• Using Aeroflex Template, cut end of slit tube

at 45° angle.

• Mark duct flange length on cut tube at 45°

angle.

• Continue until all four (4) duct flange cover

components are cut.

PREVIOUS PAGE

Page 66: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

65For more information, visit www.aeroflexusa.com

DUCT LINER | RECTANGULAR DUCTS

- Aerocel Sheet & Roll | Wet-Applied Adhesive

• Notes:

- Metal nosing must be installed where Aerocel

duct liner edges meet unlined metal and when

upstream edges are exposed to air velocities

> 4,000 fpm [1,219 mpm].

- Mechanical fasteners (weld pins), installed

per SMACNA duct construction standards,

should have beveled or cupped heads and not

compress the insulation more than 1/8” [.32 cm].

- CAUTION: Allow Aeroseal and Aeroseal LVOC

Black adhesives to flash off until dry to the

touch prior to installing weld pins.

- When using an aerosolized spray contact

adhesive, confirm with manufacturer that

adhesive is recommended for bonding closed

cell flexible elastomeric foam insulation as a

- Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for duct insulation.

• Aerocel Sheet/Roll

- Using Aerocel Sheet & Roll insulation of same

height as duct flange, fabricate strips using

various methods to fully insulate flange.

- Glue all four (4) edges of flange cover to duct

wrap insulation with Aeroseal or Aeroseal

LVOC Black adhesive under compression to

create vapor seal.

• Optional (recommended): to maximize

Aerocel life cycle for exterior applications,

apply Aerocoat, Aerocoat LVOC or jacketing

system for UV protection. For mechanical

protection, install jacketing system

specifically designed for duct insulation.

PREVIOUS PAGE

Page 67: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

66 For more information, visit www.aeroflexusa.com

- Note: Add 1/4” [.64 cm] to all measurements

for compression-fitting seams (not stretched,

no gaps).

• Duct liner must be installed in the following

sequence:

- Top – flush with side edges of duct.

- Sides – abuts top section of insulation and

bottom side of sheet metal.

1/4”

duct liner to sheet metal ductwork and follow

application instructions.

- If UV lights are installed inside the ductwork,

Aerocel insulation should be protected

with Aerocoat or Aerocoat LVOC insulation

coating.

• Thoroughly clean sheet metal surfaces to

receive insulation with denatured alcohol to

remove dust, oil or moisture.

• Measure duct dimensions and cut Aerocel Sheet

& Roll with straight edge.

PREVIOUS PAGE

Page 68: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

67For more information, visit www.aeroflexusa.com

• Seal all transverse edges under compression

with Aeroseal or Aeroseal LVOC Black adhesive.

- Aerocel Sheet/Roll with PSA

• Notes:

- Metal nosing must be installed where Aerocel

duct liner edges meet unlined metal and when

upstream edges are exposed to air velocities

> 4,000 fpm [1,219 mpm].

- Mechanical fasteners (weld pins), installed

per SMACNA duct construction standards,

should have beveled or cupped heads and not

compress the insulation more than 1/8” [.32

cm].

- If UV lights are installed inside the ductwork,

Aerocel insulation should be protected with

Aerocoat or Aerocoat LVOC insulation coating.

- Bottom – abuts inside edges of side sections.

• Using adhesive best practices, apply thin coat

of Aeroseal or Aeroseal LVOC Black adhesive

to clean duct surface and Aerocel insulation

achieving a minimum of 90% coverage and

allow to tack.

• Once adhesive is ready for contact, carefully

install cut sheet/roll to duct using weighted

roller to ensure complete contact.

• Ensure that all four (4) inside corner edge seams

fit under compression with no gaps present since

it is impractical to seal them with adhesive.

PREVIOUS PAGE

Page 69: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

68 For more information, visit www.aeroflexusa.com

• Duct liner must be installed in the following

sequence:

- Top – flush with side edges of duct.

- Sides – flush with top section of insulation and

bottom side of sheet metal.

- Bottom – flush with inside edges of side

sections.

• Thoroughly clean sheet metal surfaces to

receive insulation with denatured alcohol to

remove dust, oil or moisture.

• Measure duct dimensions and cut Aerocel Sheet

& Roll with PSA with straight edge.

- Note: Add 1/4” [.64 cm] to all measurements

for compression-fitting seams (not stretched).

1/4”

PREVIOUS PAGE

Page 70: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

69For more information, visit www.aeroflexusa.com

• To remove PSA release liner, pinch corner of

sheet/roll and peel back 1”-2” [2.5 cm - 5 cm].

• Position and align exposed edge at termination

or transverse edge.

• Peel back approximately 6" - 10" [15 cm - 25 cm]

of release liner and press sheet/roll firmly into

place to activate PSA with weighted roller to

ensure complete adhesion.

• Continue to end of cut sheet/roll.

• Ensure that all four (4) inside corner edge

seams fit under compression with no gaps

present since it is impractical to seal them with

adhesive.

• Seal all transverse edges under compression

with Aeroseal or Aeroseal LVOC Black adhesive.

PREVIOUS PAGE

Page 71: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

70 For more information, visit www.aeroflexusa.com

TECHNICAL RESOURCESNesting (Layering) Chart for Aerocel® Pipe Insulation

WALL THICKNESS

1/4" 3/8" 1/2" 3/4" 1" 1-1/2" 2"

Label ID Sleeve with Pipe Insulation ID

1/4" 3/4" 1-1/8" 1-3/8" 1-7/8" 2-3/8" 3-1/2" N/A

3/8" 7/8" 1-1/8" 1-3/8" 1-7/8" 2-3/8" 3-1/2" 4-1/2"

1/2" 1-1/8" 1-3/8" 1-5/8" 2-1/8" 2-5/8" 3-5/8" 4-1/2"

5/8" 1-1/8" 1-3/8" 1-5/8" 2-1/8" 2-5/8" 4-1/8" 5-1/8"

3/4" 1-3/8" 1-5/8" 1-7/8" 2-3/8" 2-7/8" 4-1/8" 5-1/8"

7/8" 1-3/8" 1-5/8" 1-7/8" 2-3/8" 2-7/8" 4-1/8" 5-1/8"

1-1/8" 1-5/8" 1-7/8" 2-1/8" 2-5/8" 3-1/8" 4-1/8" 5-1/8"

1-3/8" N/A 2-1/8" 2-3/8" 3-1/8" 3-1/2" 4-1/2" 5-1/2"

1-5/8" N/A 2-3/8" 2-5/8" 3-1/8" 3-5/8" 5-1/8" 6-1/8"

1-7/8" N/A 2-5/8" 3-1/8" 3-1/2" 4-1/8" 5-1/8" 6-1/8"

2-1/8" N/A 2-7/8" 3-1/2" 3-5/8" 4-1/8" 5-1/8" 6-1/8"

2-3/8" N/A 3-1/8" 3-1/2" 4-1/8" 4-1/2" 5-1/2" 6-5/8"

2-5/8" N/A 3-1/2" 3-5/8" 4-1/8" 5-1/8" 6-1/8" 6-5/8"

2-7/8" N/A 3-5/8" 4-1/8" 4-1/2" 5-1/8" 6-1/8" SHEET

3-1/8" N/A 4-1/8" 4-1/2" 5-1/8" 5-1/8" 6-1/8" SHEET

3-1/2" N/A 4-1/2" 5-1/8" 5-1/8" 5-1/2" 6-5/8" SHEET

3-5/8" N/A 4-1/2" 5-1/8" 5-1/2" 6-1/8" 6-5/8" SHEET

4-1/8" N/A 5-1/8" 5-1/2" 6-1/8" 6-1/8" SHEET 8-5/8"

4-1/2" N/A 5-1/2" 6-1/8" 6-1/8" 6-5/8" SHEET 8-5/8"

5-1/8" N/A N/A 6-5/8" SHEET SHEET 8-5/8" SHEET

5-1/2" N/A N/A 6-5/8" SHEET 8-1/8" 8-5/8" SHEET

6-1/8" N/A N/A 8-1/8" 8-1/8" 8-1/8" SHEET 10-3/4"

6-5/8" N/A N/A SHEET 8-5/8" 8-5/8" SHEET 10-3/4"

8-5/8" N/A N/A SHEET 10-3/4" 10-3/4" SHEET 12-3/4"

10-3/4" N/A N/A 12-3/4" 12-3/4" 12-3/4" 14" SHEET

12-3/4" N/A N/A N/A N/A SHEET 16" SHEET

14" N/A N/A N/A N/A 16" SHEET SHEET

16" N/A N/A N/A N/A SHEET SHEET SHEET

The ID sizes are calculated using maximum ID and wall tolerances for first inner layer.These size combinations represent the best possible fit for the nesting thickness on standard copper and and iron pipe sizes.

PREVIOUS PAGE

Page 72: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

71For more information, visit www.aeroflexusa.com

TECHNICAL RESOURCESYield of Aerocel® Sheet & Roll Insulation on Piping

Pipe SizeInsulation Thickness(inches)

Insulation Width Pipe

Circumference (inches)

Sheet Length (linear feet)

Coverageper Sheet

(linear feet)

Roll Length(linear feet)

Yield per Roll(4’ lengths)

Coverage per Roll (square feet)

5” IPS

1/2” 18-3/4” 3 6 70 44 1763/4” 19-3/4” 3 6 50 30 120

1” 20-1/4” 3 6 35 20 801-1/2” 22-1/8” 3 6 25 13 52

6” IPS

1/2” 22-3/4” 3 6 70 36 1443/4” 23-3/4” 3 6 50 25 100

1” 25-1/8” 4 4 35 16 641-1/2” 25-3/4” 4 4 25 11 44

8” IPS

1/2” 28-7/8” 4 4 70 29 1163/4” 30” 4 4 50 20 80

1” 31” 4 4 35 13 521-1/2” 33-1/8” 4 4 25 9 36

2” 34-1/2” 4 4 18 6 24

10” IPS

1/2” 35-1/8” 4 4 70 23 923/4” 37-1/4” 3 3 50 16 64

1” 37-1/2” 3 3 35 11 441-1/2” 39-1/2” 3 3 25 7 28

2” 41-5/8” 3 3 18 5 20

12” IPS

1/2” 41-3/4” 3 3 70 20 803/4” 42-5/8” 3 3 50 14 56

1” 43-1/2” 3 3 35 9 361-1/2” 46” 3 3 25 6 24

2” 47-7/8” 3 3 18 4 16

14” IPS

1/2” 45-5/8” 3 3 70 18 723/4” 46-3/8” 3 3 50 12 48

1” 48” 3 3 35 8 321-1/2” 48-7/8” ROLL ROLL 25 6 24

2” 50-1/2” ROLL ROLL 18 4 16

16” IPS

1/2” 51-7/8” ROLL ROLL 70 16 643/4” 52-5/8” ROLL ROLL 50 11 44

1” 53-3/8” ROLL ROLL 35 7 281-1/2” 55-1/8” ROLL ROLL 25 5 20

2” 55-7/8” ROLL ROLL 18 3 12

18” IPS

1/2” 58-3/4” ROLL ROLL 70 14 563/4” 59-1/4” ROLL ROLL 50 10 40

1” 59-7/8” ROLL ROLL 35 7 281-1/2” 61-1/2” ROLL ROLL 25 4 16

2” 62-1/4” ROLL ROLL 18 3 12

20” IPS

1/2” 64-7/8” ROLL ROLL 70 12 483/4” 65-5/8” ROLL ROLL 50 9 36

1” 66-1/2” ROLL ROLL 35 6 241-1/2” 68” ROLL ROLL 25 4 16

2” 69-5/8” ROLL ROLL 18 3 12

24” IPS

1/2” 77-1/2” ROLL ROLL 70 10 403/4” 78” ROLL ROLL 50 7 28

1” 78-5/8” ROLL ROLL 35 5 201-1/2” 80-3/8” ROLL ROLL 25 3 12

2” 82” ROLL ROLL 18 2 8

PREVIOUS PAGE

Page 73: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

72 For more information, visit www.aeroflexusa.com

Outside Diameters for Jacketing of Aerocel® EPDM Pipe Insulation

TECHNICAL BULLETINNo: TB06

September 1, 2020

Outside Diameters for Jacketing of Aerocel® EPDM Pipe Insulation

WARNING:

• Maximum outside diameters are calculated using dimensional properties of Aerocel maximum wall and ID manufacturing tolerances. Actual OD may be smaller than referenced OD’s.

• This table is provided as a convenience for sizing jacketing materials. It is the responsibility of the installer to determine the correct fit of jacketing materials over Aerocel pipe insulation.

Aeroflex USA | 282 Industrial Park Road | Sweetwater, TN 37874 | Toll Free: 866.AEROCEL | www.aeroflexusa.com

AerocelTHICKNESS

1/4" 3/8" 1/2" 3/4" 1" 2"

Label IDTotal OD

(in)Total OD

(in)Total OD

(in)Total OD

(in)Total OD

(in)Total OD

(in)Total OD

(in)

1/4"

3/8"

1/2"

5/8"

3/4"

7/8"

1 -1/8"

1 -3/8"

1 -5/8"

1 -7/8"

2-1/8"

2-3/8"

2-5/8"

2-7/8"

3-1/8"

3-1/2"

3-5/8"

4-1/8"

4-1/2"

5-1/8"

5-1/2"

6-1/8"

6-5/8"

8-5/8"

10 -3/4"

12 -3/4"

14"

16"

0.95 1.15 1.35 1.85 2.40 3.55 N/A

1.10 1.28 1.48 1.98 2.53 3.68 N/A

1.23 1.43 1.63 2.13 2.68 3.83 N/A

1.36 1.56 1.76 2.26 2.86 3.96 5.01

1.48 1.68 1.88 2.38 2.98 4.08 5.13

1.59 1.79 2.05 2.61 3.09 4.29 5.34

1.84 2.04 2.30 2.86 3.34 4.54 5.59

N/A 2.34 2.66 3.24 3.64 4.84 5.89

N/A 2.70 2.92 3.50 3.90 5.15 6.25

N/A 3.00 3.22 3.80 4.20 5.45 6.55

N/A 3.20 3.48 4.00 4.40 5.65 6.75

N/A 3.45 3.73 4.25 4.65 5.90 7.00

N/A 3.71 3.99 4.51 4.91 6.16 7.26

N/A 4.04 4.32 4.84 5.24 6.49 7.59

N/A 4.23 4.51 5.03 5.43 6.68 7.78

N/A 4.69 5.03 5.49 5.89 7.14 8.24

N/A 4.75 5.09 5.55 5.95 7.20 8.30

N/A 5.26 5.6 6.06 6.46 7.71 8.81

N/A N/A 6.01 6.47 6.87 8.12 9.22

N/A N/A 6.62 7.08 7.48 8.73 9.83

N/A N/A 7.10 7.56 7.96 9.21 10.31

N/A N/A 7.73 8.19 8.59 9.84 10.94

N/A N/A 8.27 8.73 9.13 10.38 11.48

N/A N/A 10.27 10.73 11.13 12.38 13.48

N/A N/A 12.39 12.85 13.25 14.50 15.60

N/A N/A N/A N/A 15.25 16.50 17.60

N/A N/A N/A N/A 16.53 17.78 18.88

N/A N/A N/A N/A 18.53 19.78 20.88

1 - 1/2"

TECHNICAL RESOURCES

PREVIOUS PAGE

Page 74: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

73For more information, visit www.aeroflexusa.com

TECHNICAL RESOURCESAeroflex USA Technical Bulletins https://www.aeroflexusa.com/technical-bulletins

Insulation Thickness calculator • Mechanical Insulation Design Guide (MIDG)

• The condensation control calculator gives you the ability to easily and efficiently calculate the correct

insulation thickness for your project.

• Once the link below is clicked, scroll towards bottom of page and click on link for “Condensation Control

Calculator for Horizontal Pipe.”

• https://insulation.org/training-tools/systemdesign/

- Disclaimer - The reference to this mechanical insulation industry resource is provided as a service and

convenience for our customers. Aeroflex USA, Inc. has no control over the content or accuracy of the

information provided, nor do we guarantee the results of the thickness calculations generated by the

MIDG.

PREVIOUS PAGE

Page 75: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

74 For more information, visit www.aeroflexusa.com

Aeroflex USA Express Limited Warranty

Please read the following terms and conditions (herein, the “Express Limited Warranty Information”) carefully, as

such terms and conditions are affected by the installation conditions for products to be warranted. Products not

specifically listed herein are not warranted. Aeroflex USA, Inc. (“Seller”) does not assume nor does it authorize any

person to assume or extend on its behalf any warranty obligation or liability other than that set out in the Express

Limited Warranty appearing below; such Express Limited Warranty constitutes the entire warranty obligation of

Seller with respect to the following described products, which are divided into two categories: (a) Insulation Products;

and (b) Tape, Adhesive, and Coating Products (the Insulation Products and the Tape, Adhesive, and Coating Products

are collectively referred to herein as the “Aerocel®

Products”).

Warranted Products (each a “Warranted Product”):

Insulation Products

Aerocel® AC EPDM Elastomeric Flexible Tubing Insulation

Aerocel® AC EPDM Elastomeric Flexible Sheet and Roll Insulation

Aerocel® AC EPDM Elastomeric Flexible Sheet and Roll Insulation with PSA

Aerocel® Stay-Seal® with Protape® (SSPT™, Aerocel-SSPT™) EPDM Elastomeric Flexible Tubing Insulation

Aerocel® WG White-Gray EPDM Elastomeric Flexible Tubing Insulation

Aerocel® WG White-Gray SSPT™ EPDM Elastomeric Flexible Tubing Insulation

Aerocel® REF™ EPDM Elastomeric Flexible Tubing Insulation

Aerocel® REF™ EPDM Elastomeric Flexible Sheet and Roll Insulation

Aerocel® REF™ WG White-Gray EPDM Elastomeric Flexible Tubing Insulation

Aerocel® REF™ SSPT™ EPDM Elastomeric Flexible Tubing Insulation

Aerocel® REF™ WG White-Gray SSPT™ EPDM Elastomeric Flexible Tubing Insulation

Aerocel® ULP® EPDM Elastomeric Flexible Tubing Insulation

Aerocel® ULP® EPDM Elastomeric Flexible Sheet and Roll Insulation

Aerocel® ULP® EPDM Elastomeric Flexible Sheet and Roll Insulation with PSA

Aerocel® ULP® SSPT™ EPDM Elastomeric Flexible Tubing Insulation

Aerocel® with Saniguard™ (SG) EPDM Elastomeric Flexible Tubing Insulation with PVC Jacketing

Aerocel® CG EPDM Elastomeric Flexible Tubing Insulation

Aerocel® COIL PACK EPDM Elastomeric Flexible Tubing Insulation

Aerocel® CONTINUOUS EPDM Elastomeric Flexible Tubing Insulation

REV. 04.13.21

PREVIOUS PAGE

Page 76: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

75For more information, visit www.aeroflexusa.com

Aerocel® AEROFIT™ AC EPDM Elastomeric Flexible Fittings (Elbows, 45s, P-Traps, Tees, Mechanical Grooved)

Aerocel® AEROFIT™ WG White-Gray EPDM Elastomeric Flexible Fittings (Elbows, 45s, P-Traps, Tees, Mechanical

Grooved)

Aerocel® AEROFIT™ REF™ EPDM Elastomeric Flexible Fittings (Elbows, 45s, P-Traps, Tees, Mechanical Grooved)

Aerocel® AEROFIT™ SG EPDM Elastomeric Flexible Fittings with SaniGuard™ (Elbows, Tees)

Aerocel® AEROFIT™ ULP® EPDM Elastomeric Flexible Fittings (Elbows, 45s, P-Traps, Tees, Mechanical Grooved)

Aerocel® AEROFIX® Insulated Pipe Supports

Tape, Adhesive and Coating Products

Aerocel® EPDM Elastomeric Flexible Insulation Adhesive - trade name is AEROSEAL

Aerocel® EPDM Elastomeric Flexible Insulation Low-VOC Adhesive - trade name is AEROSEAL LVOC™ BLACK

Aerocel® EPDM Elastomeric Flexible Insulation Adhesive - trade name is REF 1520™

Aerocel® EPDM Elastomeric Flexible Insulation Coating - trade name is AEROCOAT™

Aerocel® EPDM Elastomeric Flexible Insulation Coating - trade name is AEROCOAT LVOC™

Aerocel® EPDM Elastomeric Flexible Insulation Tape - trade name is AEROTAPE™

Aerocel® EPDM Rubber Seam Sealing Tape - trade name is PROTAPE®

Aerocel® ULP® EPDM Rubber Seam Seaming Tape - trade name is PROTAPE®

Aerocel® Insulation Cork Tape - trade name is EVERSEAL™

Express Limited Warranty

The Aerocel® Products (listed above) are warranted to the original purchaser (“Buyer”), provided that the

Aerocel® Products are installed and used in accordance with the Seller’s written installation instructions,

to be free from original defects in materials or factory workmanship, or excessive degradation as a result

thereof, for: (a) one (1) year from the date of installation for Insulation Products (except for obvious defects in

materials or factory workmanship appearing at the time of installation, of which Buyer must notify Seller in

writing within 30 days of the date of installation in order to make a warranty claim hereunder – See Procedure

to Submit a Warranty Claim, below); and (b) one (1) year from the date of purchase for Tape, Adhesive and Coating

Products (except for obvious defects in materials or factory workmanship appearing at the time of purchase, of

which Buyer must notify Seller in writing within 30 days of the date of purchase in order to make a warranty

claim hereunder – See Procedure to Submit a Warranty Claim, below). This Express Limited Warranty is limited

as stated in this section captioned Express Limited Warranty, is subject to further conditions (the “Warranty

Conditions”) and limitations (the “Warranty Limitations”) appearing below in this Express Limited Warranty

Information and provides solely the remedy (the “Exclusive Remedy for Valid Warranty Claim”) to the Buyer as

listed below.

THIS EXPRESS LIMITED WARRANTY CONSTITUTES THE ENTIRE OBLIGATION OF SELLER AND THERE ARE

NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY,

WARRANTY OF FITNESS FOR ANY PURPOSE WHATSOEVER OR WARRANTY OF FITNESS FOR A PARTICULAR

PURPOSE; SELLER HEREBY DISCLAIMS ALL IMPLIED WARRANTIES OF ANY TYPE OR SORT, INCLUDING

WITHOUT LIMITATION: (1) THE IMPLIED WARRANTY OF MERCHANTABILITY, (2) THE IMPLIED WARRANTY

OF FITNESS FOR ANY PURPOSE WHATSOEVER AND (3) THE IMPLIED WARRANTY OF FITNESS FOR A

PARTICULAR PURPOSE. LIABILITY IS LIMITED TO THAT SET FORTH BELOW AND SELLER SHALL IN NO EVENT BE

LIABLE TO BUYER OR TO ANY THIRD PARTY CLAIMING THROUGH BUYER, FOR ANY INSTALLATION OR REMOVAL

COST OR FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES (INCLUDING WITHOUT LIMITATION, LOSS

REV. 04.13.21

PREVIOUS PAGE

Page 77: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

76 For more information, visit www.aeroflexusa.com

OF PROPERTY, PERSONAL INJURY, LOSS OF BUSINESS, LOSS OF PROFITS, OR ECONOMIC LOSSES) NOR FOR

PUNITIVE, STATUTORY, OR EXEMPLARY DAMAGES, WHETHER IN NEGLIGENCE, WARRANTY, STRICT LIABILITY OR

OTHERWISE.

This Express Limited Warranty shall not be modified, enlarged, expanded upon or affected in any way by verbal

commentary or non-written installation instructions or other advice by any person or entity, regardless of the

existence of a relationship of any type or sort between such person or entity and Seller; site specific and/or installation

conditions are not the responsibility of Seller or its representatives to address or provide advice and no verbal advice

by Seller or its representative concerning such matters shall constitute a warranty by Seller or alter the terms and

conditions of the Express Limited Warranty as set out in this Express Limited Warranty Information. Seller makes

no warranty, expressed or implied, with regard to the end-product manufactured by Buyer. Buyer, by purchasing the

Aerocel® Products, agrees that Buyer will not alter, amend or add to Seller’s Express Limited Warranty. If Buyer

desires to offer additional warranties or make any representation on its own, such warranties and/or representations

will clearly state that they are Buyer’s additional warranties and not those of Seller.

Warranty Limitations

The Aerocel® Products are manufactured and warranted for their thermal insulation performance hereunder solely

for use under normal conditions. Abnormal Conditions include exposure to certain chemical vapors, petroleum-based

substances, other substances and compounds not compatible with EPDM rubber products, INCLUDING WITHOUT

LIMITATION, petroleum oil and petroleum solvents such as Benzene, Gasoline, Kerosene, Octane, Toluene and Butyl

Acetate and the vapors of the same. Damage to the Aerocel® Products which may occur from fire, accident or any

form of abuse, or exposure to Abnormal Conditions is not covered by this warranty. While exposure to ultraviolet

light due to outdoor use is not considered Abnormal Conditions for purposes of this Express Limited Warranty,

cosmetic damage caused by outdoor use without additional weather protective coatings or coverings is not covered

by this Express Limited Warranty. Cosmetic damage due to uncovered or uncoated Aerocel® product exposed to

ultraviolet light for purposes of this warranty is considered any damage which does not affect the thermal insulative

properties of Aerocel® Products. All Aerocel® Products, including AeroFit™ fitting covers, used outdoors must

have Aerocel® Protape® EPDM rubber seam sealing tape applied to and covering all product seams, butt joints and

termination points to provide a vapor seal. If exposed or installed subject to Abnormal Conditions, the product

should be removed immediately and replaced once the conditions of installation are normal or with products more

suitable to general ambient conditions of the installation or installation site. The growth of mold is not covered by

this warranty nor is damage arising from the growth of mold the responsibility of Seller. All Aerocel® Products

should be maintained to avoid excessive dirt or dust buildup, or the presence of excessive moisture, that would

provide a medium for microbial growth on the Aerocel® Products.

Warranty Conditions

The above described Aerocel® Products each must be installed in accordance with Seller’s written installation

instructions for that product in effect at the time of installation and in accordance with best industry practice. Prior to

installation, the insulation product must be kept clean and dry and not subject to Abnormal Conditions. Installation of

the Aerocel® Products shall be installed when the ambient temperature is between 40°F (4°C) and 100°F (38°C) to

allow Aerocel® PSA insulation products and adhesives to properly tack and bond. The Express Limited Warranty is

void if improper installation practices or unapproved installation products are used. This Express Limited Warranty

does not extend to any component of the insulation system other than the specific Aerocel® Products identified

herein above, such as, but not limited to, adhesives other than Aerocel® adhesives, pinning devices, tapes other than

Protape® or Aerotape™, or any other accessory used in the installation of the Aerocel® Products.

REV. 04.13.21

PREVIOUS PAGE

Page 78: EPDM Closed Cell Elastomeric Foam Insulation Duct Wrap

Aerocel® EPDM Insulation | Installation Guide

77For more information, visit www.aeroflexusa.com

Exclusive Remedy for Valid Warranty Claim

Subject to confirmation by Seller of the failure of any one or more of the Aerocel® Products to which the above

Express Limited Warranty is to be applied, Seller will deliver, at Seller’s expense, F.O.B. to the place of installation,

new product, of the same or similar type and grade, in an amount equal to that which is determined to be defective.

The foregoing is the EXCLUSIVE remedy against Seller upon a valid warranty claim hereunder. No other remedy

(including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or

property, or any other incidental or consequential loss) shall be available to the Buyer or to any other person, firm

or entity.

Procedure to Submit a Warranty Claim

The Buyer must notify Aeroflex USA, Inc. of any product failure covered by this Express Limited Warranty within 30

days of first observation of failure by writing to the following address: Aeroflex USA, Inc., 282 Industrial Park Road,

Sweetwater, TN 37874, or call us at 1 866 AEROCEL. Reference to Aeroflex USA, Inc. in this section shall mean, for

the United States, Aeroflex USA, Inc. 282 Industrial Park Road, Sweetwater, TN 37874.

State Law

The Express Limited Warranty provided above gives you specific legal rights and you may also have other rights,

which vary from state to state. Some jurisdictions do not allow exclusion or limitation of incidental or consequential

damages or limitations on how long an implied warranty lasts, so the limitation or exclusion herein may not apply to

you.

Warranty Information Complete. This Express Limited Warranty Information and the Express Limited Warranty

contained herein is the complete and final expression of the Seller’s warranty obligations with respect to the Aerocel®

Products listed herein. All other prior or contemporaneous communications with regard to warranty obligations of

Seller for the Aerocel® Products, regardless of whether in writing or otherwise, are merged into this Express Limited

Warranty Information and this Express Limited Warranty Information shall not be modified except in a writing signed

by Seller.

REV. 04.13.21