48
EPCOT BUILDING CODES 2015 Edition Code Change Submittals Effective 10/01/2015 BUILDING Preface Notation: PREFACE The EPCOT Building Code© is intended to promote the development of sound building construction and a safe environment for the public through accomplishing the following objectives: • To accomplish coordinated, balanced and harmonious development in accordance with present and future needs. • To provide the flexibility that will encourage American industry, through free enterprise, to introduce, test and demonstrate new ideas, materials and systems emerging now and in the future from the creative centers of industry. • To provide an environment that will stimulate the best thinking of industry and the professions in the creative development of new technologies to meet the needs of people, expressed by the experience of those who live, work and visit here. • To assure the safety, health and general welfare of the District’s inhabitants, visitors and premises. • To establish a sound, safe and forward-looking basis for developing and maintaining the District and its properties. To provide safety and good practice during construction, alteration, removal or demolition of buildings and structures within the district by establishing uniform, modern and progressive standards, rules and regulations. • To regulate the quality of materials and systems for all buildings and structures within the District, including their design, construction, occupancy, location and maintenance. * This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney, and shortly before Walt’s untimely death. The meeting included an indepth discussion about Walt’s vision for EPCOT. Errata 106.8 Decisions. (b) If a decision of the Board reverses or modifies a refusal, order or disallowance of the Building Official, or varies the application of any provision of this Code, the Building Official shall take action immediately in accordance with such decision. B12-0001 202 Definitions BUILDING OFFICIAL. The officer or other designated authority charged with the administration and enforcement of this Code, or his duly authorized deputy or representative by the Building Official. CART. A mobile unit that is easily moveable by no more than two persons and may require some disassembly prior to transport or storage. HEIGHT OF BUILDING. Vertical distance from the grade (q.v.) to the highest point of the coping of a flat room roof or to the deck line of a mansard roof or to the average height of the highest gable of a pitch or hip roof (See STORY). KIOSK. A kiosk is defined as a small structure, no larger than 200 square feet, which may be portable through more extensive disassembly, but is primarily intended as permanent. It may be constructed on- or off-site, then anchored and connected to utilities as permanent. MOBILE FOOD DISPENSING VEHICLE. A vehicle mounted public food service establishment, self- propelled or otherwise moveable from place to place. Such vehicles must be self-sufficient for utilities. Each mobile food dispensing vehicle is required to have a State approved commissary that it reports to at least once a week. NONCOMBUSTIBLE MATERIAL. As applied to materials used in building construction, material that, in the form in which it is used, falls into one of the following groups in Paragraph (a), (b) or (c). Material shall not be classed as noncombustible when it is subject to increase in combustibility or flame spread rating beyond the limits established herein, through effects of age, moisture or other atmospheric condition. (a) Materials no part of which will ignite and burn when subject to fire. (b) Materials having a structural base of noncombustible material as defined in Paragraph (a), with a surfacing not more than 1/8 inch thick and having a flame spread rating of not more than 50.

EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

EPCOT BUILDING CODES 2015 Edition

Code Change Submittals Effective 10/01/2015

BUILDING Preface Notation: PREFACE The EPCOT Building Code© is intended to promote the development of sound building construction and a safe environment for the public through accomplishing the following objectives: • To accomplish coordinated, balanced and harmonious development in accordance with present and future needs. • To provide the flexibility that will encourage American industry, through free enterprise, to introduce, test and demonstrate new ideas, materials and systems emerging now and in the future from the creative centers of industry. • To provide an environment that will stimulate the best thinking of industry and the professions in the creative development of new technologies to meet the needs of people, expressed by the experience of those who live, work and visit here. • To assure the safety, health and general welfare of the District’s inhabitants, visitors and premises. • To establish a sound, safe and forward-looking basis for developing and maintaining the District and its properties. • To provide safety and good practice during construction, alteration, removal or demolition of buildings and structures within the district by establishing uniform, modern and progressive standards, rules and regulations. • To regulate the quality of materials and systems for all buildings and structures within the District, including their design, construction, occupancy, location and maintenance. * This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney, and shortly before Walt’s untimely death. The meeting included an indepth discussion about Walt’s vision for EPCOT. Errata 106.8 Decisions. (b) If a decision of the Board reverses or modifies a refusal, order or disallowance of the Building Official, or varies the application of any provision of this Code, the

Building Official shall take action immediately in accordance with such decision. B12-0001 202 Definitions BUILDING OFFICIAL. The officer or other designated authority charged with the administration and enforcement of this Code, or his duly authorized deputy or representative by the Building Official. CART. A mobile unit that is easily moveable by no more than two persons and may require some disassembly prior to transport or storage. HEIGHT OF BUILDING. Vertical distance from the grade (q.v.) to the highest point of the coping of a flat room roof or to the deck line of a mansard roof or to the average height of the highest gable of a pitch or hip roof (See STORY). KIOSK. A kiosk is defined as a small structure, no larger than 200 square feet, which may be portable through more extensive disassembly, but is primarily intended as permanent. It may be constructed on- or off-site, then anchored and connected to utilities as permanent. MOBILE FOOD DISPENSING VEHICLE. A vehicle mounted public food service establishment, self-propelled or otherwise moveable from place to place. Such vehicles must be self-sufficient for utilities. Each mobile food dispensing vehicle is required to have a State approved commissary that it reports to at least once a week. NONCOMBUSTIBLE MATERIAL. As applied to materials used in building construction, material that, in the form in which it is used, falls into one of the following groups in Paragraph (a), (b) or (c). Material shall not be classed as noncombustible when it is subject to increase in combustibility or flame spread rating beyond the limits established herein, through effects of age, moisture or other atmospheric condition. (a) Materials no part of which will ignite and burn when subject to fire. (b) Materials having a structural base of noncombustible material as defined in Paragraph (a), with a surfacing not more than 1/8 inch thick and having a flame spread rating of not more than 50.

Page 2: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 2 of 48

(c) Materials, other than those described in Paragraphs (a) and (b), having a flame spread rating of not more than 25 without evidence of continued progressive combustion, and of such composition that surfaces that would be exposed by cutting through the material in any way would not have a flame spread rating more than 25 without evidence of continued progressive combustion. As used in Paragraphs (a), (b) and (c), flame spread rating refers to the rating obtained when the material is tested in accordance with EPCOT Standard 6-3. A material that complies with any one of the following shall be considered a noncombustible material: (a) The material, in the form in which it is used, and under the conditions anticipated, will not ignite, burn, support combustion, or release flammable vapors when subjected to fire or heat; (b) The material is reported as passing ASTM E 136; (c) The material is reported as complying with the pass/fail criteria of ASTM E 136 when tested in accordance with the test method and procedure in ASTM E 2652.

Exception: Inherently nonncombustible materials such as steel, concrete, masonry, glass, etc., are not required to be tested in order to be classified as noncombustible materials.

PORTABLE BUILDING. A structure built for support, shelter or enclosure for persons, animals, chattels, or property of any kind and capable of being carried or moved about. SHED. A manufactured or site-built building which does not exceed 200 square feet in size and is used for storage only. SMOKE BARRIER. A continuous membrane, either vertical or horizontal, such as a wall, floor or ceiling assembly, that is designed and constructed to restrict the movement of smoke. 715.4 Where Automatic Sprinkler Systems are Required. (c) Sprinkler protection shall be required on every floor of any enclosed exit stairway and in closets and bathrooms of Group R-1, R-2 and R-3 occupancies.

Exceptions: 6. Any building in Group S occupancies greater than 800 square feet shall have smoke detectors installed in accordance with Subsection 503.12(b).

503.12 Fire Protection and Special Systems. (b) Every building greater than 400 square feet not provided with automatic sprinkler protection throughout shall be provided with approved smoke product of combustion detectors located in accordance with EPCOT Standard 7-20. Each detector shall be connected to an AC power source and shall be connected to a central monitored station, if available. If a central monitored station is not available, an outside

audible alarm shall be installed subject to approval by the Building Official. Every building in which sleeping areas are provided shall have smoke product of combustion detectors located in accordance with Subsection 513.4 and EPCOT Standard 7-20. B12-0002 SHADE STRUCTURE. A free-standing structure open on four all sides that is primarily intended for use by occupants for protection from the elements and not used for merchandising, retail, storage or other non-approved uses, less than 400 square feet, with a minimum separation of 15 feet to the nearest building or structure. B12-0003 301.1 Permits Required. New Exception 82.

Exceptions: 82. Walking or driving surfaces that are not structural elements, not over any basement or story below, not more than 30 inches above adjacent grade and/or not part of an accessible route shall be exempt from permitting and inspection.

(Note: In order to be grammatically correct, the Exceptions will have to be numbered as Exceptions: 1 and 2. Under Exception 1, the seven exceptions listed will be indicated by using 1.1, 1.2, 1.3, etc.) B12-0004 302.1 Permit Application Requirements. (j) Fire Alarm submissions over $5,000 must be signed and sealed by a design professional. B12-0005 New Section 302.6 (i) 302.6 (i) Time limitation of application. An application for a permit for any proposed work shall be deemed to have been abandoned 180 days after the date of filing, unless such application has been pursued in good faith or a permit has been issued; except that the Building Official is authorized to grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested in writing and justifiable cause demonstrated.

Page 3: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 3 of 48

BD12-0006 503.5 Correction to Reference 503.5 Protection of Vertical Openings. (a) Exits. Where enclosures of exits and vertical openings are required, the enclosure shall be constructed in accordance with the requirements of Section 703 and Table 7.2. (b) Elevator and Escalator. For protection of elevator and escalator openings, see EPCOT Standard 5-1. (c) Waste and Linen Chutes. In other than Group R-3 occupancies (dwellings), waste and linen chutes shall terminate in rooms separated from the remainder of the building by an occupancy separation having the same fire resistance as required for the shaft enclosure, but not less than 1 hour. Openings into chutes shall not be located in required exit corridors or in stairways. Construction of waste and linen chutes shall comply with Chapter 3-2.2 of EPCOT Standard 5-14. BD12-0007 Formatting to move Table 5.3

4. All floor and roof areas providing for the parking or movement of automobiles shall be provided with pedestrian guardrails in accordance with Subsection 503.11 at all exterior and interior vertical openings when the vertical distance to the ground or surface directly below exceeds 3 feet. Such parking areas shall also be provided with exterior or interior walls or impact guardrails, except at pedestrian or vehicular accesses, capable of withstanding an impact of not less than 150 pounds per lineal foot applied at 18 inches above the floor. Each floor of such structure shall have wheel guards not less than 4 inches in height above the floor with a clear passage of 3 feet between the wheel guard and edge of structure.

(c) Enclosed and basement public parking decks shall be provided with a mechanical ventilation system capable of providing six air changes per hour for each level.

TABLE 5.3 OPEN AUTOMOBILE PARKING STRUCTURES

ALLOWABLE HEIGHTS AND AREAS CONSTRUCTION

TYPE ALLOWABLE AREA

(square feet per floor) ALLOWABLE

HEIGHT Type I No Limit No Limit Type II No Limit No Limit Type III 30,000 4 stories or 40 feet Type IV 160,000 8 stories or 75 feet

(c) Enclosed and basement public parking decks shall be provided with a mechanical ventilation system

capable of providing six air changes per hour for each level. B12-0008 New Section 503.13 503.13 CARBON MONOXIDE PROTECTION 503.13 Carbon monoxide protection. Every separate building or an addition to an existing building for which a permit for new construction is issued and having a fossil-fuel-burning heater or appliance, a fireplace, an attached garage, or other feature, fixture, or element that emits carbon monoxide as a byproduct of combustion shall have an operational carbon monoxide alarm installed in accordance with NFPA 720 within 10 feet of each room used for sleeping purposes in the new building or addition, or at such other locations as required by this Code. 503.13.1 Carbon Monoxide Alarm. The requirements of this Section shall be satisfied by providing for one of the following alarm installations:

1. A hard-wired carbon monoxide alarm. 2. A battery-powered carbon monoxide alarm. 3. A hard-wired combination carbon monoxide and

smoke alarm. 4. A battery-powered combination carbon

monoxide and smoke alarm. 503.13.2 Combination Alarms. Combination smoke/carbon monoxide alarms shall be listed and labeled by a Nationally Recognized Testing Laboratory.

Exceptions: 1. An approved operational carbon monoxide

detector shall be installed inside or directly outside of each room or area within a hospital, inpatient hospice facility or nursing home facility licensed by the Agency for Health Care Administration, or a new state correctional institution where a fossil-fuel burning heater, engine, or appliance is located. The carbon monoxide detector shall be connected to the fire-alarm system of the hospital, inpatient hospice facility, or nursing home facility as a supervisory signal.

2. This Section shall not apply to existing buildings that are undergoing alterations or repair unless the alteration is an addition. For the purpose of this Section only, an addition is defined as an extension or increase in floor area, number of stories or height of a building or structure.

(Note: Remaining sections to be renumber.)

Page 4: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 4 of 48

BD12-0009 503.13 14 Tents and Air-Supported Structures. Structures used in connection with an occupancy for temporary shelter of persons, material or equipment, shall comply with the application applicable provisions of the EPCOT Fire Prevention Code©, EPCOT Standard 5-8 and Appendix N. Air-supported structures shall be designed and erected in accordance with Appendix N. B12-0010 Table 6.2 Remove footnote: Exterior nonbearing walls – Type IV Protected / Unprotected Remove foot (c) from all Opening Permitted % Wall numbers. (Note: See ** at end of document.) Table 6.2 Formatting: Trusses, girders, beams – Supporting masonry or bearing walls, columns, girders and beams Supporting roofs Supporting floors Table 7.2 Formatting: Tenant separations (remove extra space here)

Walls within tenant spaces

B12-0011 Section 704.5 (d) 704.5 Approved Types of Fire Windows, Doors and Shutters. (d) In corridor walls and partitions having a 1-hour fire-resistance rating smoke barriers,, unless otherwise specified all door openings shall be protected with a tight-fitting smoke and draft assembly (including door frame and hardware), having a fire protection rating of 20 minutes when tested in accordance with ASTM E 152 without the hose streamUL 1784. Said These doors shall be equipped with approved self-closing or automatic-closing devices. When approved by the Building Official, any door required to have a level of fire resistance and which that is permitted to be automatic closing by smoke detection or which that is self-closing, may not have a delay in closing or reclosing of more than 10 seconds. Door assemblies shall be identified in accordance with their listing. Said These doors shall not have louvers. Add New Reference standard to Appendix A

UL 1784 - Standard for Air Leakage Tests of Door Assemblies - 2001 B12-0012 SECTION 701 LOCATION ON PROPERTYGENERAL REQUIREMENTS 701.1 General Requirements. (a) Buildings shall adjoin or have access to a public space, yard or street on at least one side. (b) Required yards shall be maintained permanently. (c) The centerline of an adjoining street or alley shall be considered an adjacent property line for purposes of this Subsection. (d) Eaves over windows shall be not less than 30 inches from the side and rear property lines. For fire protection of eaves, see Subsection 707.6. 701.5 Definitions: F RATING. The time period that the through-penetration fire-stop system limits the spread of fire through the penetration when tested in accordance with ASTM E 814 or UL 1479. L RATING. The amount of air leakage (cubic feet per minute) through a penetration. T RATING. The time period that the penetration fire-stop system, including the penetrating item, limits the maximum temperature rise to 325F above its initial temperature through the penetration on the non-fire side when tested in accordance with ASTM E 814 or UL 1479. SECTION 707.10 PENETRATIONS 707.10 Penetration and Fire-Resistant Joint Systems. Penetration of fire-resistance-rated walls, floors or floor/ceiling assemblies for electrical, telephone, plumbing, ducts, intercommunication systems or similar facilities shall be protected with an approved firestop system or assembly and meet the criteria of Paragraphs (a) through (c), and EPCOT Standards 6-1 and 7-24. (a) Penetration Firestop System. Penetrations shall be protected by an approved penetration firestop system installed as tested in accordance with ASTM E 814, with a minimum positive pressure differential of 0.01 inch of water and shall have an F rating of not less than the required rating of the wall penetrated. (b) Membrane Penetrations. Membrane penetrations shall be protected by an approved penetration firestop system installed as tested in accordance with EPCOT Standard 7-24.

Page 5: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 5 of 48

Exception: Steel electrical boxes that do not exceed 16 square inches in area provided that the area of such openings does not exceed 100 square inches for any 100 square feet of wall area. Outlet boxes on opposite sides of the wall shall be separated by a horizontal distance of not less than 24 inches. Membrane penetrations for electrical outlet boxes of any other material are permitted provided that such boxes are tested for use in fire-rated assemblies and installed in accordance with the tested assembly.

(c) Fire-Resistant Joint Systems. Joints installed in or between fire-resistant walls, fire-resistant floor or floor/ ceiling assemblies and fire-resistant roof or roof/ceiling assemblies shall be protected by an approved fire-resistant joint system designed to resist the passage of fire for a time period not less than the required fire-resistance rating of the wall, floor or roof in or between which it is installed. Fire-resistant joint systems shall be installed and tested in accordance with EPCOT Standard 6-1.

Exception: Fire-resistant joint systems shall not be required for joints in the following locations: 1. Floors within a single dwelling unit. 2. Floors where the joint is protected by a shaft enclosure in accordance with Section 703. 3. Floors within atriums where the space adjacent to the atrium is included in the volume of the atrium for smoke-control purposes. 4. Floors within malls. 5. Floors within open parking structures. 6. Mezzanine floors. 7. Walls which are permitted to have unprotected openings.

707.10 Scope. The provisions of this Section shall govern the materials and methods of construction used to protect through penetrations and membrane penetrations of horizontal assemblies and fire-resistance-rated wall assemblies. 707.10.1 Ducts and air transfer openings. Penetrations of fire-resistance-rated walls by ducts that are not protected with dampers shall comply with Sections 707.10.2 through 707.10.3.3. Penetrations of horizontal assemblies not protected with a shaft as permitted by Section 703.1, and not required to be protected with fire dampers by other sections of this Code, shall comply with Sections 707.10.4 through 707.10.4.2.2. Ducts and air transfer openings that are protected with dampers shall comply with the requirements of UL 555. 707.10.2 Installation details. Where sleeves are used, they shall be securely fastened to the assembly penetrated. The space between the item contained in the sleeve and the sleeve itself and any space between the sleeve and the assembly penetrated shall be protected in accordance with this Section. Insulation

and coverings on or in the penetrating item shall not penetrate the assembly unless the specific material used has been tested as part of the assembly in accordance with this Section. 707.10.3 Fire-resistance-rated walls. Penetrations into or through fire walls, fire barriers, smoke barrier walls and fire partitions shall comply with Sections 707.10.3.1 through 707.10.3.3. Penetrations in smoke barrier walls shall also comply with Section 707.10.5. 707.10.3.1 Through penetrations. Through penetrations of fire-resistance-rated walls shall comply with Section 707.10.3.1.1 or 707.10.3.1.2.

Exception: Where the penetrating items are steel, ferrous or copper pipes, tubes or conduits, the annular space between the penetrating item and the fire-resistance-rated wall is permitted to be protected as follows: 1. In concrete or masonry walls where the penetrating item is a maximum 6-inch nominal diameter and the area of the opening through the wall does not exceed 144 square inches, concrete, grout or mortar is permitted where it is installed the full thickness of the wall or the thickness required to maintain the fire-resistance rating; or 2. The material used to fill the annular space shall prevent the passage of flame and hot gases sufficient to ignite cotton waste when subjected to ASTM E 119 (EPCOT Standard 6-1) or UL 263 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.

707.10.3.1.1 Fire-resistance-rated assemblies. Penetrations shall be installed as tested in an approved fire-resistance-rated assembly. 707.10.3.1.2 Through-penetration firestop system. Through penetrations shall be protected by an approved penetration firestop system installed as tested in accordance with ASTM E 814 (EPCOT Standard 7-24) or UL 1479, with a minimum positive pressure differential of 0.01 inch of water and shall have an F rating of not less than the required fire-resistance rating of the wall penetrated. 707.10.3.2 Membrane penetrations. Membrane penetrations shall comply with Section 707.10.3.1. Where walls or partitions are required to have a fire-resistance rating, recessed fixtures shall be installed such that the required fire-resistance will not be reduced.

Exceptions: 1. Membrane penetrations of maximum 2-hour fire-resistance-rated walls and partitions by steel

Page 6: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 6 of 48

electrical boxes that do not exceed 16 square inches in area, provided the aggregate area of the openings through the membrane does not exceed 100 square inches in any 100 square feet of wall area. The annular space between the wall membrane and the box shall not exceed 1/8 inch. Such boxes on opposite sides of the wall or partition shall be separated by one of the following:

1.1. By a horizontal distance of not less than 24 inches where the wall or partition is constructed with individual non-communicating stud cavities; 1.2. By a horizontal distance of not less than the depth of the wall cavity where the wall cavity is filled with cellulose loose-fill, rockwool or slag mineral wool insulation; 1.3. By solid firestopping in accordance with Section 707.9; 1.4. By protecting both outlet boxes with listed putty pads; or 1.5. By other listed materials and methods.

2. Membrane penetrations by listed electrical boxes of any material, provided such boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. The annular space between the wall membrane and the box shall not exceed 1/8 inch unless listed otherwise. Such boxes on opposite sides of the wall or partition shall be separated by one of the following:

2.1. By the horizontal distance specified in the listing of the electrical boxes; 2.2. By solid firestopping in accordance with Section 707.9; 2.3. By protecting both boxes with listed putty pads; or 2.4. By other listed materials and methods.

3. Membrane penetrations by electrical boxes of any size or type, which have been listed as part of a wall opening protective material system for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. 4. Membrane penetrations by boxes other than electrical boxes, provided such penetrating items and the annular space between the wall membrane and the box, are protected by an approved membrane penetration firestop system installed as tested in accordance with ASTM E 814 (EPCOT Standard 7-24) or UL 1479, with a minimum positive pressure differential of 0.01 inch of water, and shall have an F and T rating of not less than the required fire-resistance rating of the wall penetrated and be installed in accordance with their listing. 5. The annular space created by the penetration of an automatic sprinkler, provided it is covered by a metal escutcheon plate.

707.10.3.3 Dissimilar materials. Noncombustible penetrating items shall not connect to combustible items beyond the point of firestopping unless it can be demonstrated that the fire-resistance integrity of the wall is maintained. 707.10.4 Horizontal assemblies. Penetrations of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly not required to be enclosed in a shaft by Section 703.1 shall be protected in accordance with Sections 707.10.4.1 through 707.10.4.2.2. 707.10.4.1 Fire-resistance-rated assemblies. Penetrations of the fire-resistance-rated floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall comply with Sections 707.10.4.1.1 through 707.10.4.1.3. Penetrations in horizontal smoke barriers shall also comply with 707.10.5. 707.10.4.1.1 Through penetrations. Through penetrations of fire-resistance-rated horizontal assemblies shall comply with Section 707.10.4.1.1.1 or 707.10.4.1.1.2.

Exceptions: 1. Penetrations by steel, ferrous or copper conduits, pipes, tubes or vents or concrete or masonry items through a single fire-resistance-rated floor assembly where the annular space is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste when subjected to ASTM E 119 (EPCOT Standard 6-1) or UL 263 time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch of water at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated. Penetrating items with a maximum 6-inch nominal diameter shall not be limited to the penetration of a single fire-resistance-rated floor assembly, provided the aggregate area of the openings through the assembly does not exceed 144 square inches in any 100 square feet of floor area. 2. Penetrations in a single concrete floor by steel, ferrous or copper conduits, pipes, tubes or vents with a maximum 6-inch nominal diameter, provided the concrete, grout or mortar is installed the full thickness of the floor or the thickness required to maintain the fire-resistance rating. The penetrating items shall not be limited to the penetration of a single concrete floor, provided the area of the opening through each floor does not exceed 144 square inches. 3. Penetrations by listed electrical boxes of any material, provided such boxes have been tested for use in fire-resistance-rated assemblies and installed in accordance with the instructions included in the listing.

Page 7: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 7 of 48

707.10.4.1.1.1 Installation. Through penetrations shall be installed as tested in the approved fire-resistance-rated assembly. 707.10.4.1.1.2 Through-penetration firestop system. Through penetrations shall be protected by an approved through-penetration firestop system installed and tested in accordance with ASTM E 814 (EPCOT Standard 7-24) or UL 1479, with a minimum positive pressure differential of 0.01 inch of water. The system shall have an F rating/T rating of not less than 1 hour but not less than the required rating of the floor penetrated.

Exceptions: 1. Floor penetrations contained and located within the cavity of a wall above the floor or below the floor do not require a T rating. 2. Floor penetrations by floor drains, tub drains or shower drains contained and located within the concealed space of a horizontal assembly do not require a T rating.

707.10.4.1.2 Membrane penetrations. Penetrations of membranes that are part of a horizontal assembly shall comply with Section 707.10.4.1.1.1 or 707.4.1.1.2. Where floor/ceiling assemblies are required to have a fire-resistance rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced.

Exceptions: 1. Membrane penetrations by steel, ferrous or copper conduits, pipes, tubes or vents, or concrete or masonry items where the annular space is protected either in accordance with Section 707.10.4.1.1 or to prevent the free passage of flame and the products of combustion. The aggregate area of the openings through the membrane shall not exceed 100 square inches in any 100 square feet of ceiling area in assemblies tested without penetrations. 2. Ceiling membrane penetrations of maximum 2-hour horizontal assemblies by steel electrical boxes that do not exceed 16 square inches in area, provided the aggregate area of such penetrations does not exceed 100 square inches in any 100 square feet of ceiling area, and the annular space between the ceiling membrane and the box does not exceed 1/8 inch. 3. Membrane penetrations by electrical boxes of any size or type, which have been listed as part of an opening protective material system for use in horizontal assemblies and are installed in accordance with the instructions included in the listing. 4. Membrane penetrations by listed electrical boxes of any material, provided such boxes have been tested for use in fire-resistance-rated

assemblies and are installed in accordance with the instructions included in the listing. The annular space between the ceiling membrane and the box shall not exceed 1/8 inch unless listed otherwise. 5. The annular space created by the penetration of a fire sprinkler, provided it is covered by a metal escutcheon plate. 6. Noncombustible items that are cast into concrete building elements and that do not penetrate both top and bottom surfaces of the element. 7. The ceiling membrane of 1- and 2-hour fire-resistance-rated horizontal assemblies is permitted to be interrupted with the double wood top plate of a fire-resistance-rated wall assembly, provided that all penetrating items through the double top plates are protected in accordance with Section 707.10.4.1.1.1 or 707.10.4.1.1.2. The fire-resistance rating of the wall shall not be less than the rating of the horizontal assembly.

707.10.4.1.3 Dissimilar materials. Noncombustible penetrating items shall not connect to combustible materials beyond the point of firestopping unless it can be demonstrated that the fire-resistance integrity of the horizontal assembly is maintained. 707.10.4.2 Nonfire-resistance-rated assemblies. Penetrations of nonfire-resistance-rated floor or floor/ceiling assemblies or the ceiling membrane of a nonfire-resistance-rated roof/ceiling assembly shall meet the requirements of Section 703.1(c) or shall comply with Section 707.10.4.2.1 or 707.10.4.2.2. 707.10.4.2.1 Noncombustible penetrating items. Noncombustible penetrating items that connect not more than five stories are permitted, provided that the annular space is filled to resist the free passage of flame and the products of combustion with an approved noncombustible material or with a fill, void or cavity material that is tested and classified for use in through-penetration firestop systems. 707.10.4.2.2 Penetrating items. Penetrating items that connect not more than two stories are permitted, provided that the annular space is filled with an approved material to resist the free passage of flame and the products of combustion. 707.10.5 Penetrations in smoke barriers. Penetrations in smoke barriers shall be protected by an approved through-penetration firestop system installed and tested in accordance with the requirements of UL 1479 for air leakage. The L rating of the system measured at 0.30 inch of water in both the ambient temperature and elevated temperature tests, shall not exceed:

1. 5.0 cfm per square foot of penetration opening for each through-penetration firestop system; or

Page 8: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 8 of 48

2. A total cumulative leakage of 50 cfm for any 100 square feet of wall area, or floor area.

SECTION 707.11 FIRE-RESISTANT JOINT SYSTEMS 707.11 General. Joints installed in or between fire-resistance-rated walls, floor or floor/ceiling assemblies and roofs or roof/ceiling assemblies shall be protected by an approved fire-resistant joint system designed to resist the passage of fire for a time period not less than the required fire-resistance rating of the wall, floor or roof in or between which it is installed. Fire-resistant joint systems shall be tested in accordance with Section 707.11.3.

Exception: Fire-resistant joint systems shall not be required for joints in all of the following locations: 1. Floors within a single dwelling unit. 2. Floors where the joint is protected by a shaft enclosure in accordance with Section 703.1(c). 3. Floors within atriums where the space adjacent to the atrium is included in the volume of the atrium for smoke control purposes. 4. Floors within malls. 5. Floors and ramps within open and enclosed parking garages or structures constructed in accordance with Sections 508.5. 6. Mezzanine floors. 7. Walls that are permitted to have unprotected openings. 8. Roofs where openings are permitted. 9. Control joints not exceeding a maximum width of 0.625 inch and tested in accordance with ASTM E 119 (EPCOT Standard 6-1) or UL 263.

707.11.1 Curtain wall assembly. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 707.11.4. 707.11.2 Installation. A fire-resistant joint system shall be securely installed in accordance with the listing criteria in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to accommodate expected building movements and to resist the passage of fire and hot gases. 707.11.3 Fire test criteria. Fire-resistant joint systems shall be tested in accordance with the requirements of either ASTM E 1966 or UL 2079. Nonsymmetrical wall joint systems shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests. When evidence is furnished to show that the wall was tested with the least fire-resistant side exposed to the furnace, subject to acceptance of the building official, the wall need not be subjected to tests from the opposite side.

Exception: For exterior walls with a horizontal fire separation distance greater than 5 feet, the joint system shall be required to be tested for interior fire exposure only.

707.11.4 Exterior curtain wall/floor intersection. Where fire resistance-rated floor or floor/ceiling assemblies are required, voids created at the intersection of the exterior curtain wall assemblies and such floor assemblies shall be sealed with an approved system to prevent the interior spread of fire. Such systems shall be securely installed and tested in accordance with ASTM E 2307 to provide an F rating for a time period at least equal to the fire-resistance rating of the floor assembly. Height and fire-resistance requirements for curtain wall spandrels shall comply with Section 707.3(b).

Exception: Voids created at the intersection of the exterior curtain wall assemblies and such floor assemblies where the vision glass extends to the finished floor level shall be permitted to be sealed with an approved material to prevent the interior spread of fire. Such material shall be securely installed and capable of preventing the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 (EPCOT Standard 6-1) time-temperature fire conditions under a minimum positive pressure differential of 0.01 inch of water column for the time period at least equal to the fire-resistance rating of the floor assembly.

707.11.4.1 Exterior curtain wall/nonfire-resistance-rated floor assembly intersections. Voids created at the intersection of exterior curtain wall assemblies and nonfire-resistance-rated floor or floor/ceiling assemblies shall be sealed with an approved material or system to retard the interior spread of fire and hot gases between stories. 707.11.5 Spandrel wall. Height and fire-resistance requirements for curtain wall spandrels shall comply with Section 707.3(b). Where Section 707.3(b) does not require a fire-resistance-rated spandrel wall, the requirements of Section 707.11.4 shall still apply to the intersection between the spandrel wall and the floor. 707.11.6 Fire-resistant joint systems in smoke barriers. Fire-resistant joint systems in smoke barriers, and joints at the intersection of a horizontal smoke barrier and an exterior curtain wall, shall be tested in accordance with the requirements of UL 2079 for air leakage. The L rating of the joint system shall not exceed 5 cfm per linear foot of joint at 0.30 inch of water for both the ambient temperature and elevated temperature tests.

Page 9: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 9 of 48

B12-0014 SECTION 711 INTERIOR WALL, CEILING AND FLOOR FINISHFINISHES 711.1 Scope. Provisions of this Section shall govern the use of materials used as interior finishes, trim and decorative materials. (Note: Renumber remaining sections.) 711.1 2 Conforming Materials. Materials used for wall and ceiling interior finishes shall conform to the requirements of this Section and EPCOT Standard 6-3 and 6-4. 711.3 Definitions: (a) Decorative Materials. All materials applied over the building interior finish for decorative, acoustical or other effect (such as curtains, draperies, fabrics, streamers and surface coverings), and all other materials utilized for decorative effect (such as batting, cloth, cotton, hay, stalks, straw, vines, leaves, trees, moss, and similar items), including foam plastics and materials containing foam plastics. Decorative materials do not include floor coverings, ordinary window shades, interior finish and materials 0.03625 inch or less in thickness applied directly to and adhered tightly to a substrate. (b) Interior Finish. Interior finish includes interior wall and ceiling finish and interior floor finish (c) Interior Floor Finish. The exposed floor surfaces of buildings including coverings over a finished floor or stair, including risers. (d) Interior Wall and Ceiling Finish. The exposed interior surfaces of buildings including, but not limited to, fixed or movable walls and partitions; toilet room privacy partitions; columns; ceilings; and interior wainscoting, paneling or other finish applied structurally or for decoration, acoustical surface insulation, structural fire resistance or similar purposes, but not including trim. (e) Smoke-Developed Index. A comparative measure, express as a dimensionless number, derived from measurements of smoke obscuration versus time for a material tested in accordance with EPCOT Standard 6-3 or 6-4. (f) Trim. Picture molds, chair rails, baseboards, handrails, door and window frames and similar decorative or protective materials used in fixed applications. 711.2 4 Classification of Finishes. Wall and ceiling interior finish shall mean interior wainscotting, paneling or other finish applied structurally, or for decoration or acoustical correction. Decorative Materials and Trim.

Decorative materials and trim shall be restricted by combustibility and flame propagation performance criteria of NFPA 701, in accordance with Section 711.5 Finish requirements for the fire protection shall not apply to trim, doors and windows or their frames; nor to plastics used for light transmission as provided in Subsections 705.9 and 706.4; nor to materials less than 0.036 inch thick cemented to wall or ceiling surfaces when such materials have flame spread characteristics no greater than the thickness of paper cemented to a noncombustible backing. Foam plastic shall not be used as interior finish or trim, except as provided in Section 717. 711.3 5 Material Testing. (a) Tests shall be made by an approved testing agency to establish flame spread characteristics and shall substantiate that materials, when cemented or otherwise fastened in place, will not become detached readily when subjected to room temperatures of 300°F for 25 minutes. (b) Flame spread characteristics of wall and ceiling finishes shall be determined by one of the following methods: 1. The tunnel test as specified in EPCOT Standard 6-3 or 6-4. 2. Any other nationally recognized test procedure for determining the flame spread characteristics of finish materials that will give comparable results to that specified in Paragraph (1). (c) Material classification based on the tunnel test shall meet the requirements of Table 7.4. All interior finish materials regulated by this Section shall be approved by the Building Official. In determining the acceptability of a material, the Building Official may consider the smoke development and toxicity of the materials according to such evidence as he considers appropriate to the approval. 711.4 6 Application of Interior Finish.

TABLE 7.3 FLAME SPREAD CLASSIFICATION

Material Qualified By: CLASS TUNNEL TESTa

I 0 – 25 II 26 – 75 III 76 – 200 IV 200 – 500

a. Smoke developed index: 0 – 450

TABLE 7.4 MINIMUM INTERIOR FINISH CLASSIFICATIONa

OCCUPANCY GROUP

ENCLOSED VERTICAL EXITWAYS

OTHER EXITWAYS

ROOMS OR AREAS

A-1 – A-6 I II III B I II III D I I I

Page 10: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 10 of 48

E I II III H I II III

R-1 – R-2 I II III R-3 III III III S No

Restrictions

*a. See Subsection 719.11. 711.5 7 Finishes Based on Occupancy. 711.6 8 Unprotected Materials. Trim, picture molds, chair rails, baseboards, handrails and show-window backing may be of any Class III material. Interior trim. Material, other than foam plastic used as interior trim, shall have a minimum Class III flame spread and smoke developed index when tested per Standard 6-3 or 6-4. Combustible trim, excluding handrails and guardrails, shall not exceed 10 percent of the specific wall or ceiling area in which it is attached. Unprotected wood doors and windows may be used, except where openings are required to be fire protected. 711.7 9 Carpet on Walls and Ceilings. 711.8 10 Floor Finish. 711.9 11 Floor Covering. 711.12 Combustible decorative materials. The permissible amount of decorative materials meeting the flame propagation performance criteria of NFPA 701 shall not exceed 10 percent% of the specified wall or ceiling area to which it is attached.

Exception: In auditoriums in Group A, the permissible amount of decorative material meeting the flame propagation performance requirements of NFPA 701 shall not exceed 75 percent of the aggregate wall area where the building is equipped throughout with an automatic sprinkler system.

B12-0015 New Section SECTION 714 (NOT USED)SMOKE BARRIERS 714.1 General. Smoke barriers shall comply with this Section. 714.2 Materials. Smoke barriers shall be of materials permitted by the building type of construction. 714.3 Fire-Resistance Rating. A 1-hour fire-resistance rating is required for smoke barriers. 714.4 Continuity. Smoke barriers shall form an effective membrane continuous from outside wall to outside wall and from the top of the foundation or

floor/ceiling assembly below to the underside of the floor or roof sheathing, deck or slab above, including continuity through concealed spaces, such as those found above suspended ceilings, and interstitial structural and mechanical spaces. The supporting construction shall be protected to afford the required fire-resistance rating of the wall or floor supported in buildings of other than Type IV, V or VI unprotected construction.

Exception: Smoke-barrier walls are not required in interstitial spaces where such spaces are designed and constructed with ceilings that provide resistance to the passage of fire and smoke equivalent to that provided by the smoke-barrier walls.

714.5 Openings. Openings in a smoke barrier shall be protected in accordance with Section 704.

Exception: In Group E-3, where doors are installed across corridors, a pair of opposite-swinging doors without a center mullion shall be installed having vision panels with fire-protection-rated glazing materials in fire-protection-rated frames, the area of which shall not exceed that tested. The doors shall be close fitting within operational tolerances, and shall not have undercuts in excess of 3/4-inch, louvers or grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges and shall be automatic-closing by smoke detection in accordance with the EPCOT Fire Prevention Code. Where permitted by the door manufacturer's listing, positive-latching devices are not required.

714.6 Penetrations and Joints. Penetrations of smoke barriers and joints made in or between smoke barriers, shall comply with Section 707.10. 714.7 Ducts and Air Transfer Openings. Penetrations in a smoke barrier by ducts and air transfer openings shall comply with the EPCOT Mechanical Code. B12-0017 715.2 Definitions. (b) Automatic Sprinkler Systems. A fire-extinguishing system having an approved two-source water supply with all control valves electronically supervised and in compliance with EPCOT Standard 7-10. All underground piping shall be rated a minimum 200 pounds per square inch (psi). 715.3 Detailed Requirements. (a) Water Supply. Automatic sprinkler systems shall be connected to an approved two source water supply of adequate pressure, capacity and reliability for the requirements of this system.

Page 11: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 11 of 48

B12-0019 719 ATRIUMS 719.1 General. Vertical openings through 2 3 or more floor levels may be unenclosed in all buildings other than Group H occupancies when meeting the requirements of this Section. Stair enclosures, utility chases, elevator hoistways and escalators shall not be classified as an atrium. 719.4 Smoke Control. A smoke control system, complying with Section 720, shall be designed to control the migration of products of combustion in the atrium space. Upon detection of a fire, the system shall shut down the air supply to the fire floor and the return air from all non-fire floors. Any other approved design, which will achieve the same level of smoke control as described in this Section, may be used in lieu of these requirements. Manual control capability shall be afforded. (a) Atriums shall have a smoke exhaust system located at the ceiling of the atrium. Such system shall exhaust 40,000 cfm or six air changes per hour, whichever is greater. When the volume of the atrium exceeds 600,000 cubic feet, the exhaust system shall be sized to provide a minimum of four air changes per hour. (b) Supply air inlets may be provided at the lowest level of the atrium. The inlets shall be sized to provide 75 percent of the exhaust air. (c) For purposes of this Section, the volume of the atrium shall include all spaces not separated from the atrium provided in Section 719. (d) When the heights of the atrium exceeds three stories, an exhaust system shall be provided as required in Paragraph (a); however, supply air shall be introduced mechanically from the floor of the atrium. The capacity of the supply shall be 75 percent of the exhaust.

Exception: Smoke control is not required for atriums that connect only two stories.

B12-0020 New Section 720 SMOKE CONTROL SYSTEMS 720.1 Scope and Purpose. This Section applies to mechanical or passive smoke control systems when they are required by other provisions of this Code. The purpose of this Section is to establish minimum requirements for the design, installation and acceptance testing of smoke control systems that are intended to provide a tenable environment for the evacuation or relocation of occupants. These provisions are not

intended for the preservation of contents, the timely restoration of operations or for assistance in fire suppression or overhaul activities. Smoke control systems regulated by this Section serve a different purpose than the smoke- and heat-venting provisions found in Section 716. Mechanical smoke control systems shall not be considered exhaust systems under the EPCOT Mechanical Code. 720.2 General Design Requirements. Buildings, structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accordance with the applicable requirements of Section 720 and the generally accepted and well-established principles of engineering relevant to the design. The construction documents shall include sufficient information and detail to adequately describe the elements of the design necessary for the proper implementation of the smoke control systems. These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions.

720.2.1 Smoke Control in Group B and R High Rise Buildings. The smoke control system shall prevent the migration of smoke from the floor or smoke zone of fire incidence to adjacent smoke zones and stories by pressure differential. The floor or zone of incident shall be exhausted to produce no less than a negative 0.05 inches water column with respect to the adjacent smoke zones and floors above and below. Exception: Smoke zones on lower floor levels not used for sleeping may be protected by passive or other approved smoke control methods.

720.3 Special Inspection and Test Requirements. In addition to the ordinary inspection and test requirements which buildings, structures and parts thereof are required to undergo, smoke control systems subject to the provisions of Section 720 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its final installed condition. The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests. Such commissioning shall be in accordance with generally accepted engineering practice and, where possible, based on published standards for the particular testing involved. The special inspections and tests required by this Section shall be conducted under the same terms in Subsection 306.5. 720.4 Analysis. A rational analysis supporting the types of smoke control systems to be employed, their methods of operation, the systems supporting them and the methods of construction to be utilized shall accompany the submitted construction documents and

Page 12: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 12 of 48

shall include, but not be limited to, the items indicated in Subsections 720.4.1 through 720.4.6.

720.4.1 Stack Effect. The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the system's capabilities. In determining the maximum probable stack effect, altitude, elevation, weather history and interior temperatures shall be used. 720.4.2 Temperature Effect of Fire. Buoyancy and expansion caused by the design fire in accordance with Subsection 720.9 shall be analyzed. The system shall be designed such that these effects do not adversely interfere with the system's capabilities. 720.4.3 Wind Effect. The design shall consider the adverse effects of wind. Such consideration shall be consistent with the wind-loading provisions of Chapter 9. 720.4.4 HVAC Systems. The design shall consider the effects of the heating, ventilating and air-conditioning (HVAC) systems on both smoke and fire transport. The analysis shall include all permutations of systems status. The design shall consider the effects of the fire on the HVAC systems. 720.4.5 Climate. The design shall consider the effects of low temperatures on systems, property and occupants. Air inlets and exhausts shall be located so as to prevent snow or ice blockage. 720.4.6 Duration of Operation. All portions of active or passive smoke control systems shall be capable of continued operation after detection of the fire event for a period of not less than either 20 minutes or 1.5 times the calculated egress time, whichever is greater.

720.5 Smoke Barrier Construction. Smoke barriers shall comply with Section 714 and shall be constructed and sealed to limit leakage areas exclusive of protected openings. The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios: 1. Walls: A/Aw = 0.00100 2. Exit enclosures: A/Aw = 0.00035 3. All other shafts: A/Aw = 0.00150 4. Floors and roofs: A/AF = 0.00050 where: A = Total leakage area, square feet.

AF = Unit floor or roof area of barrier, square feet. Aw = Unit wall area of barrier, square feet. The leakage area ratios shown do not include openings due to doors, operable windows or similar gaps. These shall be included in calculating the total leakage area.

720.5.1 Leakage Area. The total leakage area of the barrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio, plus the area of other openings such as gaps and operable windows. Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems. Passive smoke control systems tested using other approved means such as door fan testing shall be as approved by the Building Official. 720.5.2 Opening Protection. Openings in smoke barriers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system. Door openings shall be protected by fire door assemblies complying with Subsection 704.5. Exceptions: 1. Passive smoke control systems with automatic-closing devices actuated by spot-type smoke detectors listed for releasing service installed in accordance with Section 1418 of the EPCOT Fire Prevention Code. 2. Fixed openings between smoke zones that are protected utilizing the airflow method. 3. In Group E-3, where such doors are installed across corridors, a pair of opposite-swinging doors without a center mullion shall be installed having vision panels with fire protection-rated glazing materials in fire protection-rated frames, the area of which shall not exceed that tested. The doors shall be close-fitting within operational tolerances and shall not have undercuts, louvers or grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges and shall be automatic-closing by smoke detection in accordance with Subsection 704.3(d). Positive-latching devices are not required. 4. Group D-1. 5. Openings between smoke zones with clear ceiling heights of 14 feet or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size.

720.5.2.1 Ducts and Air Transfer Openings. Ducts and air transfer openings are required to be protected with a minimum Class II, 250°F smoke damper

Page 13: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 13 of 48

complying with Section 610 of the EPCOT Mechanical Code. 720.6 Pressurization Method. The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers. Maintenance of a tenable environment is not required in the smoke control zone of fire origin. 720.6.1 Minimum Pressure Difference. The minimum pressure difference across a smoke barrier shall be 0.05-inch water gage (in fully sprinklered buildings). 720.6.2 Maximum Pressure Difference. The maximum air pressure difference across a smoke barrier shall be determined by required door-opening or closing forces. The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Subsection 804.2(c). Opening and closing forces for other doors shall be determined by standard engineering methods for the resolution of forces and reactions. The calculated force to set a side-hinged, swinging door in motion shall be determined by:

F = Fdc + K(WA∆P)/2(W- d) (Equation 9-1) where: A = Door area, square feet. d = Distance from door handle to latch edge of door, feet. F = Total door opening force, pounds. Fdc = Force required to overcome closing device, pounds. K = Coefficient 5.2. W = Door width, feet. ∆P = Design pressure difference, inches of water. 720.7 Airflow Design Method. When approved by the Building Official, smoke migration through openings fixed in a permanently open position, which are located between smoke control zones by the use of the airflow method, shall be permitted. The design airflow shall be in accordance with this Section. Airflow shall be directed to limit smoke migration from the fire zone. The geometry of openings shall be considered to prevent flow reversal from turbulent effects. 720.7.1 Velocity. The minimum average velocity through a fixed opening shall not be less than: v = 217.2 [h (Tf - To)/(Tf + 460)]1/2 (Equation 9-2) For SI: v = 119.9 [h (Tf - To)/Tf]

1/2

where: h = Height of opening, feet. Tf = Temperature of smoke, °F. To = Temperature of ambient air, °F. v = Air velocity, feet per minute. 720.7.2 Prohibited Conditions. This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system, unduly intensify the fire, disrupt plume dynamics or interfere with exiting. In no case shall airflow toward the fire exceed 200 feet per minute. Where the formula in Subsection 720.7.1 requires airflow to exceed this limit, the airflow method shall not be used. 720.8 Exhaust Method. When approved by the Building Official, mechanical smoke control for large enclosed volumes, such as in atriums or malls, shall be permitted to utilize the exhaust method. Smoke control systems using the exhaust method shall be designed in accordance with NFPA 92B. 720.8.1 Smoke Layer. The height of the lowest horizontal surface of the smoke layer interface shall be maintained at least 6 feet above any walking surface that forms a portion of a required egress system within the smoke zone. 720.9 Design Fire. The design fire shall be based on a rational analysis performed by the registered design professional and approved by the Building Official. The design fire shall be based on the analysis in accordance with Subsection 720.4 and this Section. 720.9.1 Factors Considered. The engineering analysis shall include the characteristics of the fuel, fuel load, effects included by the fire and whether the fire is likely to be steady or unsteady. 720.9.2 Separation Distance. Determination of the design fire shall include consideration of the type of fuel, fuel spacing and configuration. 720.9.3 Heat-Release Assumptions. The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material. 720.9.4 Sprinkler Effectiveness Assumptions. A documented engineering analysis shall be provided for conditions that assume fire growth is halted at the time of sprinkler activation. 720.10 Equipment. Equipment including, but not limited to, fans, ducts, automatic dampers and balance

Page 14: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 14 of 48

dampers, shall be suitable for its intended use, suitable for the probable exposure temperatures that the rational analysis indicates and as approved by the Fire Official. 720.10.1 Exhaust fans. Components of exhaust fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. This temperature rise shall be computed by: Ts = (Qc/mc) + (Ta) (Equation 9-3) where: c = Specific heat of smoke at smoke layer temperature, Btu/lb °F. m = Exhaust rate, pounds per second. Qc = Convective heat output of fire, Btu/s. Ta = Ambient temperature, °F. Ts = Smoke temperature, °F.

Exception: Reduced Ts as calculated based on the assurance of adequate dilution air.

720.10.2 Ducts. Duct materials and joints shall be capable of withstanding the probable temperatures and pressures to which they are exposed as determined in accordance with Subsection 720.10.1. Ducts shall be constructed and supported in accordance with the EPCOT Mechanical Code. Ducts shall be leak tested to 1.5 times the maximum design pressure in accordance with nationally accepted practices. Measured leakage shall not exceed 5 percent of design flow. Results of such testing shall be a part of the documentation procedure. Ducts shall be supported directly from fire-resistance-rated structural elements of the building by substantial, noncombustible supports.

Exception: Flexible connections (for the purpose of vibration isolation) complying with the EPCOT Mechanical Code, that are constructed of approved fire-resistance-rated materials.

720.10.3 Equipment, Inlets and Outlets. Equipment shall be located so as to not expose uninvolved portions of the building to an additional fire hazard. Outside air inlets shall be located so as to minimize the potential for introducing smoke or flame into the building. Exhaust outlets shall be so located as to minimize reintroduction of smoke into the building and to limit exposure of the building or adjacent buildings to an additional fire hazard. 720.10.4 Automatic Dampers. Automatic dampers, regardless of the purpose for which they are installed within the smoke control system, shall be listed and

conform to the requirements of approved, recognized standards. 720.10.5 Fans. In addition to other requirements, belt-driven fans shall have 1.5 times the number of belts required for the design duty, with the minimum number of belts being two. Fans shall be selected for stable performance based on normal temperature and, where applicable, elevated temperature. Calculations and manufacturer's fan curves shall be part of the documentation procedures. Fans shall be supported and restrained by noncombustible devices in accordance with the requirements of Chapter 9. Motors driving fans shall not be operated beyond their nameplate horsepower (kilowatts), as determined from measurement of actual current draw, and shall have a minimum service factor of 1.15. 720.11 Power Systems. The smoke control system shall be supplied with two sources of power. Primary power shall be from the normal building power systems. Secondary power shall be from an approved standby source complying with the EPCOT Electrical Code. The standby power source and its transfer switches shall be separate from the normal power transformers and switch gears and when installed inside the building ventilated directly to and from the exterior. When installed inside a building the standby power source and transfer switched shall be installed in a room enclosed with not less than 1-hour rated constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 705, or both. The transfer to full standby power shall be automatic and within 10 seconds of failure of the primary power system. 720.11.1 Power Sources and Power Surges. Elements of the smoke management system relying on volatile memories or the like shall be supplied with uninterruptable power sources of sufficient duration to span a 15-minute primary power interruption. Elements of the smoke management system susceptible to power surges shall be suitably protected by conditioners, suppressors or other approved means. 720.11.2 Variable Frequency Drives (VFD). VFD or similar devices used in conjunction with any smoke management system shall automatically default to the original settings established at which time the system was originally accepted. If a VFD or similar devise is installed after a smoke management system has been tested and accepted, new system testing shall be required. 720.12 Detection and Control Systems. Fire detection systems providing control input or output signals to mechanical smoke control systems or elements thereof shall comply with the requirements of Section 1418 of the EPCOT Fire Prevention Code. Such systems shall be equipped with a control unit complying with UL 864 and listed as smoke control equipment.

Page 15: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 15 of 48

Control systems for mechanical smoke control systems shall include provisions for verification. Verification shall include positive confirmation of actuation, testing, manual override, the presence of power downstream of all disconnects and, through a preprogrammed weekly test sequence, report abnormal conditions audibly, visually and by printed report. 720.12.1 Verification. Control systems for mechanical smoke control systems shall include provisions for verification. Verification shall include positive confirmation of actuation, testing, manual override, and the presence of power downstream of all disconnects. A preprogrammed weekly test sequence shall report abnormal conditions audibly, visually and by printed report. The preprogrammed weekly test shall operate all devices, equipment, and components used for smoke control.

Exception: Where verification of individual components tested through the preprogrammed weekly testing sequence will interfere with normal building operation and produce unwanted effects to normal building operation, such individual components are permitted to be bypassed from the weekly preprogrammed weekly testing, where approved by the Building Official and in accordance with the following:

1. Where the operation of components that are bypassed from the preprogrammed weekly test, presence of power downstream of all disconnects shall be verified weekly by a listed control unit. 2. Where components of the smoke control system are bypassed by the preprogrammed weekly test required by Section 909.12.1 such components shall be tested semi-annually. The system shall also be tested under standby power conditions.

720.12.2 Wiring. In addition to meeting requirements of the EPCOT Electrical Code all wiring, regardless of voltage, shall be fully enclosed within continuous raceways. 720.12.3 Activation. Smoke control systems shall be activated in accordance with this Section. 720.12.3.1 Pressurization, Airflow or Exhaust Method. Mechanical smoke control systems using the pressurization, airflow or exhaust method shall have completely automatic control. 720.12.3.2 Passive Method. Passive smoke control systems actuated by approved spot-type detectors listed for releasing service shall be permitted. 720.12.4 Automatic Control. Where completely automatic control is required or used, the automatic-control sequences shall be initiated from an

appropriately zoned automatic sprinkler system complying with Section 715, manual controls that are readily accessible to the fire department and any smoke detectors required by engineering analysis. 720.13 Control Air Tubing. Control air tubing shall be of sufficient size to meet the required response times. Tubing shall be flushed clean and dry prior to final connections and shall be adequately supported and protected from damage. Tubing passing through concrete or masonry shall be sleeved and protected from abrasion and electrolytic action. 720.13.1 Materials. Control-air tubing shall be hard- drawn copper, Type L, ACR in accordance with ASTM B 42, ASTM B 43, ASTM B 68, ASTM B 88, ASTM B 251 and ASTM B 280. Fittings shall be wrought copper or brass, solder type in accordance with ASME B 16.18 or ASME B16.22. Changes in direction shall be made with appropriate tool bends. Brass compression-type fittings shall be used at final connection to devices; other joints shall be brazed using a BCuP5 brazing alloy with solidus above 1,100ºF and liquids below 1,500ºF. Brazing flux shall be used on copper-to-brass joints only.

Exception: Nonmetallic tubing used within control panels and at the final connection to devices provided all of the following conditions are met:

1. Tubing shall be listed by an approved agency for flame and smoke characteristics. 2. Tubing and connected devices shall be completely enclosed within a galvanized or paint-grade steel enclosure having a minimum thickness of 0.0296 inch (No. 22 gage). Entry to the enclosure shall be by copper tubing with a protective grommet of neoprene or Teflon or by suitable brass compression to male barbed adapter.

3. Tubing shall be identified by appropriately documented coding. 4. Tubing shall be neatly tied and supported within the enclosure. Tubing bridging cabinets and doors or moveable devices shall be of sufficient length to avoid tension and excessive stress. Tubing shall be protected against abrasion. Tubing serving devices on doors shall be fastened along hinges.

720.13.2 Isolation from Other Functions. Control tubing serving other than smoke control functions shall be isolated by automatic isolation valves or shall be an independent system. 720.13.3 Testing. Control air tubing shall be tested at three times the operating pressure for not less than 30 minutes without any noticeable loss in gauge pressure prior to final connection to devices.

Page 16: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 16 of 48

720.14 Marking and identification. The detection and control systems shall be clearly marked at all junctions, accesses and terminations. 720.15 Control diagrams. Identical control diagrams showing all devices in the system and identifying their location and function shall be maintained current and kept on file with the Building Official and the Fire Official, and at the fire alarm control panel or the fire command center, in a format and manner approved by the Fire Official. 720.16 Fire-fighter's Smoke Control Panel. A fire-fighter's smoke control panel for fire department emergency response purposes only shall be provided and shall include manual control or override of automatic control for mechanical smoke control systems. The panel shall be located in a fire command center complying with Section 718 in high- rise buildings or buildings with smoke-protected assembly seating. In all other buildings, the fire-fighter's smoke control panel shall be installed in an approved location adjacent to the fire alarm control panel. The fire-fighter's smoke control panel shall comply with Subsections 720.16.1 through 720.16.3. 720.16.1 Smoke Control Systems. Fans within the building shall be shown on the fire-fighter's control panel. A clear indication of the direction of airflow and the relationship of components shall be displayed. Status indicators shall be provided for all smoke control equipment, annunciated by fan and zone, and by pilot-lamp-type indicators as follows: 1. Fans, dampers and other operating equipment in their normal status-WHITE. 2. Fans, dampers and other operating equipment in their off or closed status-RED. 3. Fans, dampers and other operating equipment in their on or open status-GREEN. 4. Fans, dampers and other operating equipment in a fault status-YELLOW/AMBER. 720.16.2 Smoke Control Panel. The fire-fighter's control panel shall provide control capability over the complete smoke-control system equipment within the building as follows: 1. ON-AUTO-OFF control over each individual piece of operating smoke control equipment that can also be controlled from other sources within the building. This includes stairway pressurization fans; smoke exhaust fans; supply, return and exhaust fans; elevator shaft fans and other operating equipment used or intended for smoke control purposes. 2. OPEN-AUTO-CLOSE control over individual dampers relating to smoke control and that are also controlled from other sources within the building. 3. ON-OFF or OPEN-CLOSE control over smoke control and other critical equipment associated with a

fire or smoke emergency and that can only be controlled from the fire-fighter's control panel.

Exceptions: 1. Complex systems, where approved, where the controls and indicators are combined to control and indicate all elements of a single smoke zone as a unit. 2. Complex systems, where approved, where the control is accomplished by computer interface using approved, plain English commands.

720.16.3 Control Action and Priorities. The fire-fighter's control panel actions shall be as follows: 1. ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any control point within the building. Once issued from the fire-fighter's control panel, no automatic or manual control from any other control point within the building shall contradict the control action. Where automatic means are provided to interrupt normal, nonemergency equipment operation or produce a specific result to safeguard the building or equipment (i.e., duct freezestats, duct smoke detectors, high-temperature cutouts, temperature-actuated linkage and similar devices), such means shall be capable of being overridden by the fire-fighter's control panel. The last control action as indicated by each fire-fighter's control panel switch position shall prevail. In no case shall control actions require the smoke control system to assume more than one configuration at any one time.

Exception: Power disconnects required by the EPCOT Electrical Code.

2. Only the AUTO position of each three-position fire-fighter's control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO position shall be the NORMAL, nonemergency, building control position. Where a fire-fighter's control panel is in the AUTO position, the actual status of the device (on, off, open, closed) shall continue to be indicated by the status indicator described above. When directed by an automatic signal to assume an emergency condition, the NORMAL position shall become the emergency condition for that device or group of devices within the zone. In no case shall control actions require the smoke control system to assume more than one configuration at any one time. 720.17 System Response Time. Smoke-control system activation shall be initiated immediately after receipt of an appropriate automatic or manual activation command. Smoke control systems shall activate individual components (such as dampers and fans) in the sequence necessary to prevent physical damage to the fans, dampers, ducts and other equipment. For purposes of smoke control, the fire-fighter's control panel response time shall be the same for automatic or manual smoke control action initiated from any other building control point. The total response time, including

Page 17: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 17 of 48

that necessary for detection, shutdown of operating equipment and smoke control system startup, shall allow for full operational mode to be achieved before the conditions in the space exceed the design smoke condition. The system response time for each component and their sequential relationships shall be detailed in the required rational analysis and verification of their installed condition reported in the required final report. 720.18 Acceptance Testing. Devices, equipment, components and sequences shall be individually tested. These tests, in addition to those required by other provisions of this code, shall consist of determination of function, sequence and, where applicable, capacity of their installed condition. 720.18.1 Detection devices. Smoke or fire detectors that are a part of a smoke control system shall be tested in accordance with NFPA 72 in their installed condition. When applicable, this testing shall include verification of airflow in both minimum and maximum conditions. 720.18.2 Ducts. Ducts that are part of a smoke control system shall be traversed using generally accepted practices to determine actual air quantities. 720.18.3 Dampers. Dampers shall be tested for function in their installed condition. 720.18.4 Inlets and outlets. Inlets and outlets shall be read using generally accepted practices to determine air quantities. 720.18.5 Fans. Fans shall be examined for correct rotation. Measurements of voltage, amperage, revolutions per minute and belt tension shall be made. 720.18.6 Smoke barriers. Measurements using inclined manometers or other approved calibrated measuring devices shall be made of the pressure differences across smoke barriers. Such measurements shall be conducted for each possible smoke control condition. 720.18.7 Controls. Each smoke zone equipped with an automatic-initiation device shall be put into operation by the actuation of one such device. Each additional device within the zone shall be verified to cause the same sequence without requiring the operation of fan motors in order to prevent damage. Control sequences shall be verified throughout the system, including verification of override from the fire-fighter's control panel and simulation of standby power conditions. 720.18.8 Special Inspections for Smoke Control. Smoke control systems shall be tested by a special inspector.

720.18.8.1 Scope of testing. Special inspections shall be conducted in accordance with the following: 1. During erection of ductwork and prior to concealment for the purposes of leakage testing and recording of device location. 2. Prior to occupancy and after sufficient completion for the purposes of pressure-difference testing, flow measurements, and detection and control verification. 720.18.8.2 Qualifications. Special inspection agencies for smoke control shall have expertise in fire protection engineering, mechanical engineering and certification as air balancers. 720.18.8.3 Reports. A complete report of testing shall be prepared by the special inspector or special inspection agency. The report shall include identification of all devices by manufacturer, nameplate data, design values, measured values and identification tag or mark. The report shall be reviewed by the responsible registered design professional and, when satisfied that the design intent has been achieved, the responsible registered design professional shall seal, sign and date the report. 720.18.8.3.1 Report Filing. A copy of the final report shall be filed with the Building Official and an identical copy shall be maintained in an approved location at the building. 720.18.9 Identification and Documentation. Charts, drawings and other documents identifying and locating each component of the smoke control system, and describing its proper function and maintenance requirements, shall be maintained on file at the building as an attachment to the report required by Subsection 720.18.8.3. Devices shall have an approved identifying tag or mark on them consistent with the other required documentation and shall be dated indicating the last time they were successfully tested and by whom. 720.19 System Acceptance. Buildings, or portions thereof, required by this Code to comply with this Section shall not be issued a certificate of occupancy until such time that the Building Official determines that the provisions of this Section have been fully complied with and that the fire department has received satisfactory instruction on the operation, both automatic and manual, of the system.

Exception: In buildings of phased construction, a temporary certificate of occupancy, as approved by the Fire Official, shall be allowed provided that those portions of the building to be occupied meet the requirements of this Section and that the remainder does not pose a significant hazard to the safety of the proposed occupants or adjacent buildings.

Page 18: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 18 of 48

720.20 Smokeproof Enclosures. Where required by Section 810, a smokeproof enclosure shall be constructed in accordance with this Section. A smokeproof enclosure shall consist of an enclosed interior exit stairway that conforms to Section 809 and an open exterior balcony or ventilated vestibule meeting the requirements of this Section. Where access to the roof is required by the Subsection 806.13 walls, such access shall be from the smokeproof enclosure where a smokeproof enclosure is required. 720.20.1 Access. Access to the stair shall be by way of a vestibule or an open exterior balcony. The minimum dimension of the vestibule shall not be less than the required width of the corridor leading to the vestibule but shall not have a width of less than 44 inches and shall not have a length of less than 72 inches in the direction of egress travel. 720.20.2 Construction. The smokeproof enclosure shall be separated from the remainder of the building by not less than 2-hour fire walls constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 705, or both. Openings are not permitted other than the required means of egress doors. The vestibule shall be separated from the stairway by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 705, or both. The open exterior balcony shall be constructed in accordance with the fire-resistance rating requirements for floor assemblies. 720.20.2.1 Door Closers. Doors in a smokeproof enclosure shall be self- or automatic closing by actuation of a smoke detector in accordance with Section 704 and shall be installed at the floor-side entrance to the smokeproof enclosure. The actuation of the smoke detector on any door shall activate the closing devices on all doors in the smokeproof enclosure at all levels. Smoke detectors shall be installed in accordance with the EPCOT Fire Prevention Code. 720.20.3 Natural Ventilation Alternative. The provisions of Subsections 720.20.3.1 through 720.20.3.3 shall apply to ventilation of smokeproof enclosures by natural means. 720.20.3.1 Balcony Doors. Where access to the stairway is by way of an open exterior balcony, the door assembly into the enclosure shall be a fire door assembly in accordance with Section 704. 720.20.3.2 Vestibule Doors. Where access to the stairway is by way of a vestibule, the door assembly into the vestibule shall be a fire door assembly complying with Section 704. The door assembly from the vestibule to the stairway shall have not less than a 20-minute fire protection rating complying with Section 704.

720.20.3.3 Vestibule Ventilation. Each vestibule shall have a minimum net area of 16 square feet of opening in a wall facing an outer court, yard or public way that is at least 20 feet in width. 720.20.4 Mechanical Ventilation Alternative. The provisions of Subsections 720.20.4.1 through 720.20.4.4 shall apply to ventilation of smokeproof enclosures by mechanical means. 720.20.4.1 Vestibule Doors. The door assembly from the building into the vestibule shall be a fire door assembly complying with Subsection 805.8. The door assembly from the vestibule to the stairway shall not have less than a 20-minute fire protection rating and meet the requirements for a smoke door assembly in accordance with Subsection 805.8. The door shall be installed in accordance with NFPA 105. 720.20.4.2 Vestibule Ventilation. The vestibule shall be supplied with not less than one air change per minute and the exhaust shall not be less than 150 percent of supply. Supply air shall enter and exhaust air shall discharge from the vestibule through separate, tightly constructed ducts used only for that purpose. Supply air shall enter the vestibule within 6 inches of the floor level. The top of the exhaust register shall be located at the top of the smoke trap but not more than 6 inches down from the top of the trap, and shall be entirely within the smoke trap area. Doors in the open position shall not obstruct duct openings. Duct openings with controlling dampers are permitted where necessary to meet the design requirements, but dampers are not otherwise required. 720.20.4.2.1 Engineered Ventilation System. Where a specially engineered system is used, the system shall exhaust a quantity of air equal to not less than 90 air changes per hour from any vestibule in the emergency operation mode and shall be sized to handle three vestibules simultaneously. Smoke detectors shall be located at the floor-side entrance to each vestibule and shall activate the system for the affected vestibule. Smoke detectors shall be installed in accordance with the EPCOT Fire Prevention Code. 720.20.4.3 Smoke Trap. The vestibule ceiling shall be at least 20 inches higher than the door opening into the vestibule to serve as a smoke and heat trap and to provide an upward-moving air column. The height shall not be decreased unless approved and justified by design and test. 720.20.4.4 Stair Shaft Air Movement System. The stair shaft shall be provided with a dampered relief opening and supplied with sufficient air to maintain a minimum positive pressure of 0.10 inch of water in the shaft relative to the vestibule with all doors closed.

Page 19: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 19 of 48

720.20.5 Stair Pressurization Alternative. Where the building is equipped throughout with an automatic sprinkler system in accordance with Subection 715.4, the vestibule is not required, provided that interior exit stairways are pressurized to a minimum of 0.05 inch of water and a maximum of 0.35 inch of water in the shaft relative to the building measured with all stairway doors closed under maximum anticipated stack effect and wind effect. 720.20.6 Ventilating Equipment. The activation of ventilating equipment required by the alternatives in Subsections 720.20.4 and 720.20.5 shall be by smoke detectors installed at each floor level at an approved location at the entrance to the smokeproof enclosure. When the closing device for the stair shaft and vestibule doors is activated by smoke detection or power failure, the mechanical equipment shall activate and operate at the required performance levels. Smoke detectors shall be installed in accordance with the EPCOT Fire Prevention Code. 720.20.6.1 Ventilation Systems. Smokeproof enclosure ventilation systems shall be independent of other building ventilation systems. The equipment, control wiring, power wiring and ductwork shall comply with one of the following: 1. Equipment, control wiring, power wiring and ductwork shall be located exterior to the building and directly connected to the smokeproof enclosure or connected to the smokeproof enclosure by ductwork enclosed by not less than 2-hour fire walls constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 705, or both. 2. Equipment, control wiring, power wiring and ductwork shall be located within the smokeproof enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed by not less than 2-hour fire walls constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 705, or both. 3. Equipment, control wiring, power wiring and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by not less than 2-hour fire walls constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 705, or both.

Exceptions: 1. Control wiring and power wiring utilizing a 2-hour rated cable or cable system. 2. Where encased with not less than 2 inches of concrete.

720.20.6.2 Standby Power. Mechanical vestibule and stair shaft ventilation systems and automatic fire

detection systems shall be powered by an approved standby power system conforming to the EPCOT Electrical Code. 720.20.6.3 Acceptance and Testing. Before the mechanical equipment is approved, the system shall be tested in the presence of the Building Official to confirm that the system is operating in compliance with these requirements. Corrections to Table 8.1 – Need to put in alpha order. TABLE 8.1 NUMBER OF EXITS AND SQUARE FEET PER OCCUPANT

USE MINIMUM OF 2 MEANS OF

EGRESS REQUIRED WHERE

NUMBER OF OCCUPANTS IS

OVER

AREA PER OCCUPANTb (square feet)

Aircraft hangars (no repair)

10 500 gross

Auction rooms 30 7 net Assembly areas Auditoriums Bowling lanes (assembly areas only) Churches and chapels Dance floors Lodge rooms

50 7 net

Reviewing stands Stadiums Queue lines

4.5 net (See 817.4(c))

Queue 4.5 net

B12-0021 804.8 Change in Floor Level at Doors. New Exception:

4. A maximum ¾ inch threshold is permitted for sliding glass doors serving any guest room. The height is measured from the top of the interior finished floor. Typical allowances for carpeted finishes are ¼ inch for padding and ¼ inch for carpet. The interior floor must be ramped to the threshold with a slope that does not exceed 1:20 in order to provide the ¾ inch maximum height described above. The Building Official, where space limitations prohibit the use of a 1:20 slope or less, may approve greater slopes. (see EPCOT Accessibility Code Subsection 4.1.6(3) & 4.8.5.) A slope between 1:10 and 1:12 will be considered for a maximum rise of 6 inches. A slope between 1:8 and 1:10 will be considered for a maximum rise of 3 inches. A slope steeper than 1:8 is not allowed. The maximum height difference between the top of the interior finished floor (interior of the door to the exterior) cannot exceed 2 inch as required in Section 804.8 of the EPCOT Building Code. The Building Official may permit a greater step-down

Page 20: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 20 of 48

where it is necessary to protect the integrity of the unit from wind/water damage. Accessible door thresholds and changes in level shall comply with EPCOT Accessibility Code Subsections 4.3.8, 4.13.8, 9.2.2, 4.1.6(3) and 4.8.5.

B12-0022 806.3 Treads and Risers. (c) The slope of the walking surface of treads in any direction shall not exceed 1/4 inch per foot (a slope of 1 in 48), except that the radius of curvature at the leading edge of the tread shall not be greater than 1/2 inch. Beveling or rounding of nosings shall not exceed 1/2 inch in a horizontal dimension. Risers shall be solid and vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 degrees from the vertical. The leading edge (nosings) of treads shall project not more than 11/4 inches beyond the tread below. All projections of the leading edges shall be of uniform size, including the leading edge of the floor at the top of a flight of stairs.

Exceptions: 1. Stairways required to be accessible shall comply with the EPCOT Accessibility Code for Building Construction. 2. Solid risers are not required for stairways that are not required to be in an enclosure by Subsection 809.1, provided the opening between treads does not permit the passage of a sphere with a diameter of 4 inches. 3. Where access to a performance platform is strictly limited to performers and technicians, an 8-inch stair riser shall be permitted.

B12-0023 806.3 Treads and Risers. (a) Stairway risers shall be not less than 4 inches or more than 7 inches high and treads shall be not less than 11 inches wide. (b) Treads shall be of uniform depth and risers of uniform height in any flight of stairs. There shall be no variation exceeding 3/8 inch in the depth of adjacent treads or in the height of adjacent risers. Tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads. Stair treads and risers shall be of uniform size and shape. The tolerance between the largest and smallest riser or between the largest and smallest tread shall not exceed 3/8 inch in any flight of stairs.

Exceptions: 1. Where the bottom or top riser adjoins a sloping public way, walk or driveway having an established

grade and serving as a landing, a variation in the height of the riser of not more than 3 inches for every 3 feet of stairway width is permitted. 2. Aisle stairs in accordance with 816.6.

B12-0024 New Section 806.4(e) Industrial Stairways. Fixed industrial interior and exterior stairs around machinery, tanks and other equipment, and stairs leading to or from floors, platforms or pits and where the requirements of Subsection 806.3(a) are technically infeasible shall comply with this Section. This Section does not apply to stairs used for fire exit purposes. The minimum width requirement for fixed industrial stairs shall be 22 inches. Fixed industrial stairs shall be installed at angles to the horizontal of between 30 degrees and 50 degrees. Any uniform combination of rise/tread dimensions may be used that will result in a stairway angle to the horizontal within the permissible range. Riser height and tread width shall be uniform with no variation between adjacent treads or risers exceeding 3/8 inch.

Angle To Horizontal

Rise (Inches)

Tread (Inches)

30 degrees 35’ 6½ 11

32 degrees 08’ 6¾ 10¾

33 degrees 41’ 7 10½

35 degrees 16’ 7¼ 10¼

36 degrees 52 7½ 10

38 degrees 29’ 7¾ 9¾

40 degrees 08’ 8 9½

41 degrees 44’ 8¼ 9¼

43 degrees 22’ 8½ 9

45 degrees 00’ 8¾ 8 ¾

46 degrees 38’ 9 8 ½

48 degrees 16’ 9¼ 8 ¼

49 degrees 54’ 9½ 8 (f) Ship ladders. Ship ladders are permitted to be used as a component of a means of egress from catwalks, control rooms or elevated facility observation stations not more than 250 square feet with not more than three occupants and for access to equipment and unoccupied roofs. Ship ladders shall have a minimum tread depth of 5 inches. The ladder shall be sloped such that the total depth of each consecutive two treads, measured horizontally from the nose of the lower tread to the back of the next tread above, is not less than 8½ inches. The maximum riser height between treads shall be 9½ inches.

Page 21: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 21 of 48

Handrails shall be provided on both sides of ship ladders. The minimum clear width at and below the handrails shall be 20 inches. B12-0025 810 SMOKE-PROTECTED ENCLOSURES 810.1 Smoke-Protected Enclosures Defined. A smoke-protected enclosure shall consist of a vestibule and continuous stairway enclosed from the highest point to the lowest point by walls of 2-hour fire-resistive construction. Smokeproof enclosures and pressurized stairways. In buildings required to comply with Section 718 or 719, each of the exit enclosures serving a story with a floor surface located more than 75 feet above the lowest level of fire department vehicle access shall be a smokeproof enclosure or pressurized stairway in accordance with Subsection 720.20. The supporting frame shall be protected as set forth in Table 6.2. 810.1.1 Termination and Extension. A smokeproof enclosure or pressurized stairway shall terminate at an exit discharge or a public way. The smokeproof enclosure or pressurized stairway shall be permitted to be extended by an exit passageway in accordance with Section 811. The exit passageway shall be without openings other than the fire door assembly required by Subsection 809.3 and those necessary for egress from the exit passageway. The exit passageway shall be separated from the remainder of the building by 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 705, or both.

Exceptions: 1. Openings in the exit passageway serving a smokeproof enclosure are permitted where the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure, and openings are protected as required for access from other floors. 2. Openings in the exit passageway serving a pressurized stairway are permitted where the exit passageway is protected and pressurized in the same manner as the pressurized stairway. 3. The fire barrier separating the smokeproof enclosure or pressurized stairway from the exit passageway is not required, provided the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure or pressurized stairway.

810.1.2 Enclosure Access. Access to the stairway within a smokeproof enclosure shall be by way of a vestibule or an open exterior balcony.

Exception: Access is not required by way of a vestibule or exterior balcony for stairways using the

pressurization alternative complying with Section 720.20.5.

810.2 Where Required. Where the floor of a story is located more than 60 feet above grade, at least one of the required exits shall be a smoke-protected enclosure. When a smokeprotected enclosure is required, it shall be used to meet the requirements of Subsection 806.13. 810.3 Construction. Stairs in smoke-protected enclosures shall be of noncombustible construction. 810.4 Outlet. A smoke-protected enclosure shall exit into a public way, or into an exit passageway leading to a public way. The exit passageway shall be without other openings and shall have wall, floor and ceiling assemblies of 2-hour fire-resistive construction. 810.5 Barrier at Grade Level Exit. A stairway in a smoke-protected enclosure shall not continue below the grade level unless an approved barrier is provided at the ground level to prevent persons from unintentionally continuing to the lower level. 810.6 Access. Access to the stairway shall be by way of a vestibule or by way of an open exterior balcony constructed of noncombustible materials. 810.7 Ventilation. Ventilation shall be provided in smoke-protected enclosures as required in this Subsection. (a) Natural ventilation. When natural ventilation is used, the following requirements shall apply: 1. Doors. Doors to both the vestibule and to the stairway shall have a 1-hour fire-resistive rating and shall have closing devices as specified in paragraph (b) 6. 2. Open-air vestibules. The vestibule shall have a minimum of 16 square feet of opening in a wall facing an exterior court, yard or public way that is at least 20 feet wide. (b) Mechanical ventilation. When mechanical ventilation is used, the following requirements shall apply: 1. Doors. The door from the building into the vestibule shall have a 11/2-hour fire-resistive rating and shall have closing devices as specified in Subsection 704.3. The door from the vestibule to the stairway shall be a tight-fitting door equal to not less than an exterior type solid wood door without voids, assembled with exterior type glue, not less than 13/4 inch thick, and shall glazing be not more than 100 square inches in area set in steel frame. The door shall have a drop sill or other provision to minimize air leakage. 2. Vestibule size. The vestibule shall be not less than 44 inches wide and not less than 72 inches in the direction of exit travel. 3. The vestibule ventilation shall be provided with not less than one air change per minute and the exhaust shall be 150 percent of the supply. Supply air shall enter and the exhaust air shall leave the vestibule through separate tightly constructed ducts used only for that purpose. Supply air shall enter the vestibule within 6 inches of the floor level. The top of the exhaust register shall be located at the top of the smoke trap but not more than 6 inches down from the top of the trap

Page 22: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 22 of 48

and shall be entirely within the smoke trap area. Doors, when in the open position, shall not obstruct duct openings. Duct openings may be provided with controlling dampers if needed to meet the design requirements.

EXCEPTION: For buildings where such air changes would result in excessively large duct and blower requirements, a specially engineered system may be used. Such an engineered system shall provide 2,500 cfm exhaust from a vestibule when in emergency operation and shall be sized to handle three vestibules when in emergency operation and shall be sized to handle three vestibules simultaneously. The smoke detector located outside each vestibule shall release to open the supply and exhaust duct dampers in the vestibule.

4. Smoke trap. The vestibule ceiling shall be at least 20 inches higher than the door opening into the vestibule to serve as a smoke and heat trap and to provide an upward moving air column. 5. Stairshaft air movement system. The stairshaft shall be provided with mechanical supply and exhaust air. There shall be a minimum of 2,500 cfm discharge at the top of the shaft. The supply shall be sufficient to provide a minimum of 0.05 inch water column with respect to atmospheric pressure with all doors closed and a minimum of 0.10 inch water column difference between the stairshaft and the vestibule. 6. Detector. The exit doors into the vestibule and into the stairshaft shall close automatically when released by activation of a detector meeting the requirements of Subsection 704.3(c) 2. The door-holding device shall be of an approved type that will release the doors to close in the event of a power failure. 7. Operation of ventilating equipment. Vestibule and stairshaft mechanical ventilation may be inactive or may operate at reduced levels for normal operations, as approved by the Building Official, but when the detectors referred to in Paragraph 6 either fail or are activated, the mechanical equipment shall operate at the levels specified in Paragraphs 3 and 5. 8. Standby power. Mechanical ventilation equipment shall be provided with an approved self-contained generator set to operate whenever there is a loss of power in the normal house current. The generator shall be located in a separate room having a minimum 1-hour fire-resistive occupancy separation and shall have a minimum fuel supply sufficient to operate the equipment for two hours. 9. Acceptance and testing. Before the mechanical equipment is accepted by the Building Official, it shall be tested in his presence to confirm that the equipment is operating in compliance with the requirements of this Subsection. 810.1.310.Emergency Lighting. The stairshaft and the vestibule shall be provided with emergency lighting. The standby generator, which is installed to operate the mechanical ventilation equipment, may be used for standby emergency lighting power supply.

810.1.411.Air Conditioned Buildings. In buildings with air conditioning systems or pressure air supply, a detector conforming to the requirements of Subsection 704.3(c) shall be placed in the main circulating air supply duct in the downstream side of any filters and so located as to operate and shut off the building system when smoke enters the air stream, or such device may be installed in each room or space served by a return-air duct. 810.1.512. Periodic Tests of Mechanical Equipment. The building engineer shall test the mechanical ventilating equipment every 7 days and shall maintain a record of the results. The record shall be available for inspection by the Building Official or his deputyrepresentative. B12-0026 SECTION 817 817.1 Scope. In addition to the applicable requirements of Sections 801 to 816, Group A-6 and A-7 occupancies, including stadiums, reviewing stands, grandstands, and bleachers and tents constructed or erected in the District prior to and subsequent to the enactment of this Code, shall conform to the provisions of this Section and the EPCOT Fire Prevention Code. 817.2 Definitions. (d) Tent. As defined in the EPCOT Fire Prevention Code. [See Subsection 506.4(f).] B12-0027 SECTION 904 WIND LOADS 904.1 Design for Wind Loads Required. (a) Buildings and structures, and every part thereof, shall be designed to withstand the forces of wind pressure assumed in any direction. No allowance shall be made for the effect of shielding by other structures. Wind pressures shall be assumed to act normal to the surface considered.

Exception: Fences six feet or less in height associated with R-3 occupancies are not required to withstand the forces of wind.

B12-0028 904.1 Design for Wind Loads Required. (c) Roofing assemblies (material) shall be U.L. Class I-90 for Type I, II, III, IV,V and VI buildingscomply with the requirements of Standard 9-7 and FM 4450, FM4470, UL 580, UL 1897 or ASTM E 1592.

Page 23: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 23 of 48

Exception: Satellite buildings may be U.L. Class I-60 if determined by the Building Official. (See EPCOT Standard 7-7.)

B12-0029 904.2 Determination of Wind Loads. (a) Wind loads on buildings and other structures shall be determined in accordance with EPCOT Standard 9-7 (Section 6.0), 9-8 or 9-9 in Appendix A. The Ultimate Design Wind Speed shall be 129 mph (Risk Category 1), 139 mph (Risk Category II) and 149 mph (Risk Category III and IV). The Building Official may accept a design based on lower pressures, the validity of which is based on nationally recognized data. The Building Official may require evidence to support design pressures used in the design of structures not included in this Section. For buildings or structures with unusual geometry, or subjected to unusual wind responses, the Building Official may require wind tunnel tests or additional nationally recognized data. (e) Basic wind speed used for determining wind loads on temporary structures shall be obtained from the Basic Wind Speed Map in EPCOT Standard 9-7. The basic wind speed from Section 6 of that Standard should be multiplied by the conversion factor for other Mean Recurrence Intervals (MRI), Table C6-3 of EPCOT Standard 9-7, Section C6.0 representing an MRI of 5 years. Ultimate design wind speed used for determining wind loads on temporary structures shall be 94 mph. (Note: The referenced standards deleted in Section 904.2(a) should also be removed from Appendix A.) Appendix A 9-8 Guide Specifications for Design ANSI/NAAMM of Metal Flagpoles FP 1001-1997 9-9 Structural Standards for Steel Antenna Towers and Antenna Supporting Structures ANSI/TIA-(Revised 2003) 222F-1996 B12-0031 New Section 1003.5 1003.5 Anchorage to Concrete-Strength Design. The strength design procedure of anchors installed in concrete, including headed bolts, headed studs, hooked bolts (J-bolts or L-bolts), expansion anchors and undercut anchors shall be in accordance with Appendix D of ACI 318. The strength design procedure of anchors not within the scope of Appendix D of ACI 318 shall be approved by the Building Official.

Appendix C Formatting Table C-101.5.2 should be split. B12-0032 Appendix D D-301.5 Roof Signs. (c) Roof signs shall be constructed to leave a clear space of not less than 6 feet1 foot clearance between the roof level and the lowest part of the signs. and shall have at least 5 feet clearance between the vertical supports. B12-0033 J-101.1 Scope. The provisions of this Appendix shall apply to: (a) Group S-4 occupancies including mobile homes, campers, trailers and manufactured buildings not intended for human occupancy; and (b) Manufactured buildings used for occupancies other than Group S-4. B12-0034 New Kiosk & Shed, Modification to Portable Building Definition in J-101.2 (c) Kiosk. A kiosk is defined as a small structure, no larger than 200 square feet, which may be portable through more extensive disassembly, but is primarily intended as permanent. It may be constructed on- or off-site, then anchored and connected to utilities as permanent. (Note: Renumber existing definitions.) (e) Portable Building. A structure built for support, shelter or enclosure for persons, animals, chattels, or property of any kind and capable of being carried or moved about. (g) Shed. A shed is defined as a manufactured or site built building, which does not exceed 200 square feet in size, and is used for storage only. Appendix J Formatting: J-101.2 Definitions. (c) Manufactured Building. A structure, transported on a separate vehicle in one or more sections, designed to

Page 24: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 24 of 48

be used as dwelling, commercial, institutional, storage, industrial structures with permanent foundation, which may include plumbing, heating and air conditioning, and electrical manufactured in accordance with the Florida Manufactured Building Act of 1979, in Section 553, Part IV, of the Florida Statutes, and administered and promulgated by the Rules and Regulations of the Florida Department of Community Affairs.Business and Professional Regulation (DBPR). (d) Mobile Home. Any residential unit constructed to standards promulgated by the U.S. Department of Housing and Urban Development, and administered by the Florida Department of Transportation and the Florida Department of Community Affairs (DCA).DBPR. (g) Temporary Construction Trailers. A temporary building used for construction purposes has been defined as any building or shed that is temporary, does not exceed 8 feet in width and 32 feet in length, is used for the storage of materials and equipment, and may include a small office for a construction superintendent to use for functions that are exclusively for construction purposes. Temporary manufactured buildings, which meet this definition, are exempt from the requirements of the following: accessibility, DCA DBPR approval, sealed engineering, energy calculations and emergency egress illumination. B12-0035 Appendix J J-301.1 Piers, Tie Downs and Anchors. (c) 3. Ground Anchors. 3.4. Other types of ground anchors may be approved by the Building Official if he deems them the equivalent of the foregoing specifications. When the manufacturer’s installation instructions are not available, piers, blocking, tie downs and ground anchors shall be installed per the Division of Motor Vehicles Bureau of MH/RV Construction Installer Licensing Program. B12-0036 SECTION J-501 GROUP S-4 OCCUPANCIES J-501.1 Scope. This Section shall apply to Group S-4 occupancies, including mobile homes, manufactured buildings, recreational vehicles, and trailers and portable buildings. J-501.2.1 Access. Access to mobile homes, manufactured buildings, recreational vehicles, and trailers and portable buildings shall be in accordance

with Subsection 1407.1 of the EPCOT Fire Prevention Code. J-501.2.3 Separation between mobile homes, manufactured buildings, recreational vehicles, and trailers, portable buildings and a permanent structure shall be a minimum horizontal clear and unobstructed distance of 25 feet. J-501.2.5 Fire Protection. Non-residential mobile homes, manufactured buildings, trailers, or portable buildings that are 800 square feet or more of floor space, shall be provided with an approved product of combustion detector. Each detector shall be connected to a central monitored station, if available. If a central monitored station is not available, an outside audible alarm shall be installed. (Note: Changes to the EPCOT Fire Prevention Code to match changes made to J-501.2.5) 3603.11 Fire Protection. Non-residential mobile homes, manufactured buildings, trailers, or portable buildings that are 800 400 square feet or more of floor space, shall be provided with an approved product of combustion detector. Each detector shall be connected to a central monitoring station, if available. If a central monitoring station is not available, an outside audible alarm shall be installed. J-501.3 Cluster or Grouping. J-501.3.1 Mobile homes, recreational vehicles, trailers, portable buildings and manufactured buildings may be arranged in clusters and/or groups when a minimum fire water flow of 1,000 gallons per minute is accessible. J-501.3.6 Portable buildings of less than 800 square feet each, used for other than residential purposes, may be set up to a maximum group of four. Separation between portable buildings and permanent structures shall be a minimum horizontal (clear and unobstructed) distance of 25 feet. Appendix J Formatting: J-501.2.2 Separation. Separation between mobile homes, manufactured buildings, recreational vehicles, trailers and other similar units shall be a minimum horizontal, clear and unobstructed distance of 15 feet. J-501.2.3 Separation between mobile homes, manufactured buildings, recreational vehicles, trailers, portable buildings and a permanent structure shall be a minimum horizontal, clear and unobstructed distance of 25 feet.

Page 25: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 25 of 48

B12-0037 Appendix N Add New Section N-301.10 Air-Inflated Structures. Air-inflated, air-supported (inflatable) structures shall comply with the provisions of ASTM F2374. Add New Section 5-12.501.5 501.5 Air-Inflated and Air-Supported Structures. See Appendix N-301.10. Appendix Q Errata Q-301.2 Exit Signs and Emergency Lighting. Buildings and structures housing Group S-8 occupancies shall be equipped with approved exit signs and emergency illumination for spaces occupied by human keepers and handlers as required by Section 812 813 and the EPCOT Electrical Code. Appendix R Add definition for Private Pool SWIMMING POOL, PRIVATE. Any structure, intented for and restricted to the use of a single dwelling unit, located in a residential area, that is intended for swimming or recreational bathing and contains water over 24 inches deep including but not limited to inground, aboveground, and onground swimming pools, hot tubs, and nonportable spas Appendix R Errata R-104.1 Electrical Equipment and Wiring. Electrical equipment wiring and installation, including the grounding of pool components, shall conform with the National Electrical Code® (NEC), 2008 Edition. Appendix R Errata R-109.8.7.2 Showers shall be provided at or near the entrance (queue line) to a water recreation attraction. B12-0038

STANDARD 5-1 SECTION 5-1.101 5-1.101.2 Criteria. (d) Where applicable, the following Standards shall be considered as part of this Standard. 1. Safety Code for Elevators, Dumbwaiters and Moving Walks and Escalators, ANSI/ASME A17.1-20084, addendum A17.1a-20085 supplement A17.1S 2005, and the current addition of A17.2. with A17.1a/CSA B44a Addenda, and the Guide for Inspection of Elevators, Escalators, and Moving Walks, ASME A17.2. 2. Safety Standard for Belt Manlifts, ANSI/ASME A90.1-2003. 3. Safety Code for Conveyors, Cableways and Related Equipment, ANSI/ASME B20.1-2003. 4. Safety Code for Existing Elevators and Escalators, ANSI/ASME A17.3-1996. 5. Safety Standard for Platform Lifts and Stairways Chairlifts, ANSI/ASME A18.1-20083. Specifically Excluded: (Note: All ASME corrections (removal of ANSI/) need to be made in the remaining sections of Standard 5-1.) 5-1.101.4 Definitions. Terms and words used in this Standard have the meaning set forth in Chapter 2 and the Standards listed in Subsection 5-1.101.2(d), modified as follows: (a) Alteration. Any change to equipment, including its parts, components, and/or subsystems, other than maintenance, repair, or replacement. (ba) Automatic. Self-activating, self-acting and self-regulating mechanism performing a required act at a predetermined point in an operation. (cb) Automobile Parking Elevator. Elevator located either in a stationary or horizontal moving hoistway that is (1a) used solely for parking automobiles where attendants are normally stationed only on the receiving level; (2b) where each automobile is moved on or off the elevator directly into parking spaces or cubicles in line with the elevator; and (3c) where an automobile is moved either under its own power or by a powerdriven transfer device. (dc) Conveyance. Elevator, escalator, dumbwaiter, manlift, automobile parking elevator, moving walk, aerial tramway, stairway chairlift, conveyor and the cableways, derricks, hoists, jacks, slings, cranes and other equipment and devices used in connection therewith. (Note: Renumber remaining sections.)

Page 26: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 26 of 48

(ed) Conveyor. (fe) Door Closer. (gf) Dual Control. (hg) Elevator. (ih) Escalator. (ji) Hoistway (Shaft). (kj) Manlift. (lk) Manufacturer’s Agent. (ml) Moving Walk. Passenger-carrying device on which passengers stand or walk in which the passenger-carrying surface remains parallel to its direction of motion and is uninterupted. (For special types, see ANSIASME A17.1.) (nm)Owner. (on) Shaft. (po) Transporting Assembly. SECTION 5-1.401 CONVEYING SYSTEMS ELEVATORS, ESCALATORS AND HOISTWAYS 5-1.401.1 Fire-Protected Enclosures. (a) Enclosure of Eelevators and escalator openings through a floor/ceiling assembly shall be protected by a shaft enclosure for fire protection shall complingy with the provisions of this StandardSection. Exceptions: 1. Wheren the area of the floor opening between stories does not exceed twice the horizontal projected area of the escalators moving stairways, large monumental staircases or similar the floor openings may be are unenclosed, if the floor openings involved is areshall be protected by a draft stops curtain in combination with closely spaced sprinklers. The draft stops curtain shall be located immediately adjacent to the opening, shall be 18 inches deep and shall be of substantially noncombustible material. Sprinklers spaced not more than 6 feet apart, shall be placed 6 inches to 12 inches from the draft stop curtain on the side away from the opening to form a water curtain. Sprinklers in this water curtain shall be hydraulically designed to provide a discharge of 3 gallons per minute (gpm) per lineal foot of water curtain, measured horizontally around the opening with no sprinkler discharging less than 15 gpm. Nominal 1/2- inch orifice closed-head systems using sprinklers of Ordinary Temperature Classification are adequate for this purpose. When sprinklers are closer than 6 feet, cross baffles shall be provided. When

sprinklers in the normal ceiling pattern are closer than 6 feet from the water curtain, it may be preferable to locate the water curtain sprinklers in recessed baffle pockets. 2. A shaft enclosure is not required for elevator hoistways in open or enclosed parking garages that serve only the parking garage. 5-1.401.2 Venting of Hoistways. (b) Locations of Vents. Vents shall be located at the top the hoistway and shall open either directly to the outer air or through noncombustible ducts to the outer air. Noncombustible ducts shall be permitted to pass through the elevator machine room, provided that portions of the ducts located outside the hoistway or machine room are enclosed by construction having not less than the fire-resistance rating required for the hoistway. Holes in the machine room floors for the passage of ropes, cables or other moving elevator equipment shall be limited as not to provide greater than 2 inches of clearance on all sides. Vents shall be located: 1. In the side of the hoistway enclosure directly below the floor or floors at the top of the hoistway, and shall open either directly to the outer air or through noncombustible ducts to the outer air; or 2. In the wall or roof of the penthouse or overhead machinery space above the roof, provided that openings have a total area not less than the minimum specified in Paragraph (c). (c) Area of Vents. The area of the vents shall be not less than 31/2 percent of the area of the hoistway, nor less than 3 square feet, for each elevator car, whichever is greater. Of the total required vent area, not less than one-third shall be permanently open or automatically opened by a damper. Note: A hinged damper, which will open under a small amount of pressure, is considered a permanently open vent.

Exceptions: 1. Where mechanical ventilation providing equivalent venting of the hoistway is provided, the required vent area may be reduced subject to the following: 1.1. The building is not a hotel, apartment house, hospital or similar building with overnight sleeping quarters. 1.2. The hoistway or machine room is so located that it has no outside exposure. 1.3. The hoistway does not extend to the top of the building. 1.4. The hoistway or machine room exhaust fan is automatically reactivated by thermostatic means. 2. The total required vent area shall not be required to be permanently open where all the vent openings automatically open upon detection of smoke in the elevator lobbies or hoistway, upon power failure and upon activation of a manual override control. The manual override control shall be capable of opening

Page 27: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 27 of 48

and closing the vents and shall be located in an approved location.

5-1.401.3 Prohibited uses, plumbing and mechanical systems. Plumbing and mechanical systems shall not be located in an elevator shaft.

Exception: Floor drains, sumps and sump pumps shall be permitted at the base of the shaft provided they are indirectly connected to the plumbing system. Elevators as Exits. Elevators and escalators shall not be included in the calculations for required exits and exitways as specified in Section 803.

5-1.401.6 An approved pictorial permanent sign shall be installed immediately above each hall push button station on each floor reading: “In Fire Emergency, Do Not Use Elevator. Use Exit Stairs.”

Exception: 1. The emergency sign shall not be required for elevators that are part of an accessible means of egress complying with Section 407 of the EPCOT Accessibilty Code for Building Construction.

5-1.401.9 Electrolysis Protection for Underground Hydraulic Elevator Cylinders.Environmental Protection. Underground hydraulic cylinders shall be installed in accordance with the following:All newly installed underground hydraulic pressure cylinders shall be encased in outer plastic containment to minimize electrolytic corrosion between the metal cylinder and ground cathode. (a) PVC The plastic casing shall be capped at the bottom and all joints must be solvent or heat welded to ensure water tightness sealed and dry around hydraulic cylinders to contain any leakage into the ground and to prevent electrolysis to the hydraulic cylinders. (b) The plastic casing shall be constructed of polyethylene or polyvinyl chloride (PVC). The plastic pipe wall thickness must not be less than 0.125 inch. (bc) A 1/2-inch pipe nipple with removable cap located between support channels, 6 inches above pit floor and 6 inches below pit floor, between PVC casing and cylinder for monitoring purposes. (dc) Monitoring shall be on a monthly basis. Note: A minimum amount of dry sand may be used to stabilize hydraulic cylinders from movement between casings and cylinders. (See Figure 5-1.) (e) Replacements of existing hydraulic cylinders shall be protected by the aforementioned method where existing physical dimensions permit. 5-1.401.10 Headroom in Machine Rooms and Overhead Machinery Spaces.

(a) Elevator machine rooms and machinery spaces not located over the hoistway shall have a clear headroom of not less than 7 feet. (b) Spaces containing other elevator equipment shall have a clear headroom of not less than 54 inches. (c) Floors shall be provided for overhead equipment when the distance between the car top, with car at top landing and at floor level, and the bottom of the secondary or deflecting sheaves is greater than 66 inches. Floors shall conform to ANSI A17.1, Rule 2.1.3. (cd) Access to machine rooms and machinery spaces shall conform to ANSIASME A17.1., Rule 2.7.3. (d) Venting - Elevator machine rooms that contain solid-state equipment for elevator operation shall be provided with an independent ventilation or air-conditioning system to protect against the overheating of the electrical equipment. The system shall be capable of maintaining temperatures within the range established for the elevator equipment. (e) Pressurization - The elevator machine room serving a pressurized elevator hoistway shall be pressurized upon activation of a heat or smoke detector located in the elevator machine room. (f) Prohibited uses - Plumbing systems shall not be located in elevator equipment rooms. 5-1.401.12 Sump Pump in Elevator Pits. A Ssump pump or drain shall be provided in elevators with Firefighters Emergency Operations,,where provided, shall be installed per ASME A17.1as a portable unit. An Electrical outlet for damp locations in accordance with the National Electrical Code (NEC) shall be located within 4 feet of pump and 18 inches high from pit floor. Drains and sumps shall be installed per the EPCOT Plumbing Code. Discharge pipe shall be metal pipe with uniform installed close to pump for removal. A sump pump cover shall be provided at floor level. In hydraulic units only, An an oil separator shall be installed and water discharged indirectly into a sanitary system. (Note: Add new Section 501.401.16 and renumber remaining sections.) 5-1.401.16 Elevator car to accommodate ambulance stretcher. Any building that is more than one story must be constructed to contain at least one passenger elevator that is operational for building occupants and fire department emergency access to all floors. The elevator car shall be of such a size and arrangement to accommodate an ambulance stretcher 24 inches by 81 inches with not less than 5-inch radius corners, in the horizontal, open position and shall be identified by the international symbol for emergency medical services (star of life). The symbol shall not be less than 3 inches

Page 28: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 28 of 48

high and shall be placed inside on both sides of the hoistway door frame. 5-1.401.176 Material Lifts and Conveyers. 5-1.401.187 Battery Emergency Return Unit. 5-1.401.198 Wheelchair Lifts. 5-1.401.2019 Hydraulic Elevator Brake Annual Test. 5-1.401.210 Hydraulic Elevator Brake Five-Year Test. 5-1.401.221 Hydraulic Elevator Brake Run-By. Minimum bottom car run-by shall not be less than 1 inch for operating speed in down direction not exceeding 100 feet per minute and 3 inches for operating speed in the down direction exceeding 100 feet per minute per ASME A17.1 Rule 8.11.3.4.4. 5-1.401.23 Personnel and Material Hoists. Personnel and material hoists shall be designed utilizing an approved method that accounts for the conditions imposed during the intended operation of the hoist device. The design shall include, but is not limited to, anticipated loads, structural stability, impact, vibration, and stresses. The design shall account for the construction, installation, operation and inspection of the hoist tower, car, machinery and control equipment, guide members and hoisting mechanism. Additionally, the design of personnel hoists shall include provisions for field testing and maintenance which will demonstrate that the hoist device functions in accordance with the design. Field tests shall be conducted upon the completion of an installation or following alteration of a personnel hoist. SECTION 5-1.402 FIRE SERVICE ELEVATORS HIGH RISE BUILDINGS OVER 120 FEET 5-1.402 Fire Service Access Elevator. Elevators installed and operating in high rise buildings with an occupied floor more than 120 feet above the lowest fire department vehicle access, shall have at a minimum one fire service access provided per this Section. Every floor of the building shall be served by a fire service access elevator. Except as modified in this Section, the fire service access elevator shall be installed in accordance with this chapter and ASME A17.1/CSA B44. 5-1.402.1 Hoistway Enclosures Protection. The fire service access elevator shall be located in a shaft enclosure complying with this code. 5-1.402.2 Hoistway Lighting. When firefighters' emergency operation is active, the entire height of the hoistway shall be illuminated to not less than 1

footcandle as measured from the top of the car of each fire service access elevator. 5-1.402.3 Fire Service Access Elevator Lobby. The fire service access elevator shall open into a fire service access elevator lobby in accordance with Subsections 5-1.402.4.1 through 5-1.402.4.4.

Exception: Where a fire service access elevator has two entrances onto a floor, the second entrance shall be permitted to open into an elevator lobby in accordance with Subsection 708.14.1.

5-1.402.3.1 Access. The fire service access elevator lobby shall have direct access to an exit enclosure. 5-1.402.3.1 Lobby Enclosure. The fire service access elevator lobby shall be enclosed with a smoke barrier having a minimum 1-hour fire-resistance rating, except that lobby doorways shall comply with Subsection 5-1.402.3.2.

Exception: Enclosed fire service access elevator lobbies are not required at the street floor.

5-1.402.3.2 Lobby Doorways. Each fire service access elevator lobby shall be provided with a doorway that is protected with a 3/4-hour fire door assembly complying with Subsection 704.3. The fire door assembly shall also comply with the smoke and draft control door assembly requirements of Subsection 704(d) with the UL 1784 test conducted without the artificial bottom seal. 5-1.402.3.3 Lobby Size. Each enclosed fire service access elevator lobby shall be a minimum of 150 square feet in an area with a minimum dimension of 8 feet. 5-1.402.4 Standpipe Hose Connection. A Class I standpipe hose connection in accordance with Subsection 715.2 and EPCOT Standard 7-14 shall be provided in the exit enclosure having direct access from the fire service access elevator lobby. 5-1.402.5 Elevator System Monitoring. The fire service access elevator shall be continuously monitored at the fire command center by a standard emergency service interface system meeting the requirements of NFPA 72. 5-1.402.6 Electrical Power. The following features serving each fire service access elevator shall be supplied by both normal power and Type 60/Class 2/Level 1 standby power: 1. Elevator equipment. 2. Elevator hoistway lighting. 3. Elevator machine room ventilation and cooling equipment. 4. Elevator controller cooling equipment.

Page 29: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 29 of 48

5-1.402.6.1 Protection Of Wiring Or Cables. Wires or cables that provide normal and standby power, control signals, communication with the car, lighting, heating, air conditioning, ventilation and fire-detecting systems to fire service access elevators shall be protected by construction having a minimum 1-hour fire-resistance rating or shall be circuit integrity cable having a minimum 1-hour fire-resistance rating. SECTION 5-1.403 SERIAL NUMBERS 5-1.403 Serial Numbers. Each elevator shall have a serial number assigned by the authority having jurisdiction painted on or attached to the elevator car in plain view and also to the driving mechanism. This serial number shall be shown on all required certificates and permits. 5-1.403.1 Certificates of operation must be posted in a conspicuous location in the elevator and shall contain the text of Subsection 823.12, Florida Statutes relating to the prohibition against smoking in elevators. The certificate must be framed with a transparent cover. 5-1.403.2 The designation "NO SMOKING" along with the international symbol for no smoking shall be conspicuously displayed within the interior of the elevator in the plain view of the public. 5-1.403.3 The following ASME A17.1, rule is hereby amended to read as follows: (a) Rule 2.29.1 amend to add the following to the rule: "Each car in a multicar group shall be sequentially identified from left to right, as viewed from the elevator lobby." (b) Rule 2.7.3.1 of the ASME A17.1, which is amended to read as follows: "Rule 2.7.3.1 General Requirements. A permanent, safe and convenient means of access to elevator machine rooms and overhead machinery spaces shall be provided for authorized persons. The key to the machine rooms and overhead machinery spaces shall be kept on the premises at all times and readily available for use by State of Florida certified Elevator Inspectors." (c) Rule 3.11.3 of ASME A17.3 is amended to read as follows: NOTE: Updates to the Safety Code for Existing Elevators and Escalators ASME A17.1 and ASME A17.3 which require Phase II Firefighters' Service shall apply except where Subsection 399.02(9) Florida Statute states Phase II Firefighters' Service on elevators may not be enforced until July 1, 2015, or until the elevator is replaced or requires major modification, whichever occurs first, on elevators in condominiums or multifamily residential buildings, including those that are part of a continuing care facility licensed under Chapter

651, or similar retirement community with apartments, having a certificate of occupancy by the local building authority that was issued before July 1, 2008. This exception does not prevent an elevator owner from requesting a variance from the applicable codes before or after July 1, 2015. This Subsection does not prohibit the Building Official from granting variances pursuant to Subsection 120.542, Florida Statute or other applicable rules and regulations. SECTION 5-1.404 ALTERATIONS TO ELECTRIC AND HYDRAULIC ELEVATORS AND ESCALATORS 5-1.404.1 Alterations To Electric And Hydraulic Elevators And Escalators. Alterations set forth in Part 8, ASME A17.1 to include any change to equipment, including its parts, components, and/or subsystems, other than maintenance, repair, or replacement; require an elevator construction permit, along with documented performance of inspections and tests to determine conformance with ASME A17.1. A repair or replacement of equipment, parts, components or subsystems that requires inspection, tests and independent witnessing in other sections of ASME A17.1, A17.3 and A18.1 shall require an elevator construction permit. Standard 5-13 Formatting: SECTION 5-13.201 DESIGN AND MANUFACTURE 5-13.201.2 Referenced Documents. Boiler and Pressure Vessel Code, (italic) Section VIII, Division 1 Pneumatic Storage Tanks Automotive and Off-Highway Air Brake Reservoir Performance and Identification Requirements - Truck and Bus SAE J-10 B12-0039 Standard 1010-9 1010-9.301.3 Fasteners in Preservative-Treated and Fire-Retardant-Treated Wood. Fasteners in preservative-treated or fire-retardant-treated wood shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicone bronze or copper. 1010-9.301.3 Fasteners in preservative-treated and fire-retardant-treated wood. Fasteners for preservative-treated and fire-retardant-treated wood shall be in accordance with ASTM A 153.

1010-9.301.3.1 Fasteners for preservative-treated wood. Fasteners for preservative-treated

Page 30: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 30 of 48

wood shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper. The coating weights for zinc-coated fasteners shall be in accordance with ASTM A 153. Exception: Fasteners other than nails and timber rivets shall be permitted to be of mechanically deposited zinc-coated steel with coating weights in accordance with ASTM B 695, Class 55 minimum.

1010-9.301.3.2 Fastenings for wood foundations. Fastenings for wood foundations shall be as required in AF&PA Technical Report No. 7. 1010-9.301.3.3 Fasteners for fire-retardant-treated wood used in exterior applications or wet or damp locations. Fasteners for fire-retardant-treated wood used in exterior applications or wet or damp locations shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper. Fasteners other than nails, timber rivets, wood screws and lag screws shall be permitted to be of mechanically deposited zinc-coated steel with coating weights in accordance with ASTM B 695, Class 55 minimum. 1010-9.301.3.4 Fasteners for fire-retardant-treated wood used in interior applications. Fasteners for fire-retardant-treated wood used in interior locations shall be in accordance with the manufacturer's recommendations. In the absence of manufacturer's recommendations Section 1010-9.301.3.3 shall apply.

B12-0040 SECTION 1010-9.901 FIRE-RETARDANT-TREATED WOOD 1010-9.901.1 Treatment. Fire-retardant-treated wood, when impregnated with chemicals by pressure process or other means during manufacture, shall have, when tested in accordance with EPCOT Standard 6-3, a smoke-developed rating and flame spread index of 25 or less and show no evidence of significant progressive combustion when the test is continued for an additional 20-minute period. In addition, the flame front shall not progress more than 101/2 feet beyond the centerline of the burners at any time during the test. Reference EPCOT Standards 1010-21(c) and 1010-21(d). 1010-9.901.2 Identification. All fire-retardant-treated wood shall bear an identification mark showing the flame spread index thereof issued by an approved agency having a reexamination service. Fire-retardant-treated wood shall bear the quality mark of an approved inspection agency that maintains continued supervision and inspection over the method of drying. The drying

shall be done according to the EPCOT Standard 1010-21(c) for lumber and EPCOT Standard 1010-21(d) for plywood. Where fire-retardant-treated wood is exposed to weather, it shall be further identified to indicate that there is no increase in the listed flame spread index as defined above when subjected to EPCOT Standard 1010-21(a). Where experience has demonstrated a specific need for use of material of low hygroscopicity, fire-retardant-treated wood to be subjected to high humidity conditions shall be identified to indicate the treated wood has a moisture content of not more than 28 percent when tested in accordance with EPCOT Standard 1010-21(b) procedures at 92 percent relative humidity. 1010-9.901.3 Moisture Content. Fire-retardant-treated wood shall be dried to a moisture content of 19 percent or less for lumber and 15 percent or less for plywood before use. 1010-9.901.1 Fire-retardant-treated wood. Fire-retardant-treated wood is any wood product which, when impregnated with chemicals by a pressure process or other means during manufacture, shall have, when tested in accordance with ASTM E 84 or UL 723, a listed flame spread index of 25 or less and show no evidence of significant progressive combustion when the test is continued for an additional 20-minute period. Additionally, the flame front shall not progress more than 10½ feet beyond the centerline of the burners at any time during the test. 1010-9.901.1.2 Pressure process. For wood products impregnated with chemicals by a pressure process, the process shall be performed in closed vessels under pressures not less than 50 pounds per square inch gauge (psig). 1010-9.901.1.3 Other means during manufacture. For wood products produced by other means during manufacture, the treatment shall be an integral part of the manufacturing process of the wood product. The treatment shall provide permanent protection to all surfaces of the wood product. 1010-9.901.1.4 Testing. For wood products produced by other means during manufacture, other than a pressure process, all sides of the wood product shall be tested in accordance with and produce the results required in Subsection 1010-9.901.1. Wood structural panels shall be permitted to test only the front and back faces. 1010-9.901.1.5 Labeling. Fire-retardant-treated lumber and wood structural panels shall be labeled. The label shall contain the following items:

Page 31: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 31 of 48

1. The identification mark of an approved agency in accordance with Subsection 1010.3(f). 2. Identification of the treating manufacturer. 3. The name of the fire-retardant treatment. 4. The species of wood treated. 5. Flame spread and smoke-developed index. 6. Method of drying after treatment. 7. Conformance to appropriate standards in accordance with Subsections 1010-9.901.1.6 through 1010-9.901.1.9. 8. For fire-retardant-treated wood exposed to weather, damp or wet locations, include the words "No increase in the listed classification when subjected to the Standard Rain Test" (ASTM D 2898). 1010-9.901.1.6 Strength adjustments. Design values for untreated lumber and wood structural panels, as specified in Subsection 1010-9.201.1(d), shall be adjusted for fire-retardant-treated wood. Adjustments to design values shall be based on an approved method of investigation that takes into consideration the effects of the anticipated temperature and humidity to which the fire-retardant-treated wood will be subjected, the type of treatment and redrying procedures. 1010-9.901.1.6.1 Wood structural panels. The effect of treatment and the method of redrying after treatment, and exposure to high temperatures and high humidities on the flexure properties of fire-retardant-treated softwood plywood shall be determined in accordance with ASTM D 5516. The test data developed by ASTM D 5516 shall be used to develop adjustment factors, maximum loads and spans, or both, for untreated plywood design values in accordance with ASTM D 6305. Each manufacturer shall publish the allowable maximum loads and spans for service as floor and roof sheathing for its treatment. 1010-9.901.1.6.2 Lumber. For each species of wood that is treated, the effects of the treatment, the method of redrying after treatment and exposure to high temperatures and high humidities on the allowable design properties of fire-retardant-treated lumber shall be determined in accordance with ASTM D 5664. The test data developed by ASTM D 5664 shall be used to develop modification factors for use at or near room temperature and at elevated temperatures and humidity in accordance with ASTM D 6841. Each manufacturer shall publish the modification factors for service at temperatures of not less than 80°F and for roof framing. The roof framing modification factors shall take into consideration the climatological location. 1010-9.901.1.7 Exposure to weather, damp or wet locations. Where fire-retardant-treated wood is exposed to weather, or damp or wet locations, it shall be identified as "Exterior" to indicate there is no increase in the listed flame spread index as defined in Subsection 1010-9.901.1 when subjected to ASTM D 2898.

1010-9.901.1.8 Interior applications. Interior fire-retardant-treated wood shall have moisture content of not over 28 percent when tested in accordance with ASTM D 3201 procedures at 92-percent relative humidity. Interior fire-retardant-treated wood shall be tested in accordance with Subsection 1010-9.901.1.6.1 or 1010-9.901.1.6.2. Interior fire-retardant-treated wood designated as Type A shall be tested in accordance with the provisions of this Section. 1010-9.901.1.9 Moisture content. Fire-retardant-treated wood shall be dried to a moisture content of 19 percent or less for lumber and 15 percent or less for wood structural panels before use. For wood kiln dried after treatment (KDAT), the kiln temperatures shall not exceed those used in kiln drying the lumber and plywood submitted for the tests described in Subsection 1010-9.901.1.6.1 for plywood and 1010-9.901.1.6.2 for lumber. 1010-9.901.1.10 Type I and II construction applications. See Section 602 for limitations on the use of fire-retardant-treated wood in buildings of Type I or II construction. Additional Revisions, based on revisions to 1010-9.901 602.2 Roofs. In buildings of Types I and II construction, housing a Group A and (or) E occupancy, approved fire-retardant-treated wood or structural members of heavy timber sizes construction and fire protection of structural members may shall be omitted permitted in such buildings where structural members support a roof only and there is 20 feet or more clear height above the upper floor or balcony to the roofand where an automatic sprinkler system is installed throughout. In such buildings, structural members of heavy timber sizes may be used as alternatives to unprotected roof members. 602.4 Walls. (a) In buildings of Types I and II construction, nonbearing walls required to be 1- or 2-hour fire-resistance construction shall be noncombustible permitted to be or fire-retardant-treated wood enclosed within noncombustible materials. (b) Fire-retardant-treated wood shall be permitted in nonbearing exterior walls where no fire rating is required. 604.2 Walls. In buildings of Type IV construction, nonbearing walls required to be 1- or 2-hour fire-resistance construction shall be noncombustible or fire-retardant-treated wood enclosed within noncombustible materials. B12-0041 Index Referenced Standards Appendix A

Page 32: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 32 of 48

Standards, Referenced Appendix A Index Doors Overhead….704.10, 804.6

ACCESSIBILITY Update by substituting Florida Building Code 5th Edition (2014) Accessibility A12 – 0001 SECTION 207 ACCESSIBLE MEANS OF EGRESS 207.1 General. Accessible means of egress shall comply with this CodeSection. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by the EPCOT Building Code from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress. See Subsection 803.1 of the EPCOT Building Code.

Exceptions: 1. Where means of egress are permitted by local building or life safety codes to share a common path of egress travel, accessible means of egress shall be permitted to share a common path of egress travel. 2. Areas of refuge shall not be required in detention and correctional facilities. 3. Accessible means of egress are not required in alterations to existing buildings. 4. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 207.3 or 207.4. 5. In assembly spaces with sloped floors, one accessible means of egress is required from a space where the common path of travel of the accessible route for access to the wheelchair spaces is not more than 30 feet from a location where there is a choice of two accessible means of egress available.

207.1.1 Barriers at common or emergency entrances and exits of business establishments conducting business with the general public that are existing, under construction, or under contract for construction which would prevent a person from using such entrances or exits shall be removed.

207.2 Platform Lifts. Standby power shall be provided for platform lifts approved to serve as a part of an accessible means of egress. 207.2 Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: 1. Accessible routes complying with Chapter 4. 2. Stairways within exit enclosures complying with Sections 207.3 and the EPCOT Building Code. 3. Elevators complying with Section 207.4. 4. Platform lifts complying with Section 207.5. 5. Horizontal exits complying with the EPCOT Building Code. 6. Smoke barriers complying with the EPCOT Building Code.

Exceptions: 1. Where the exit discharge is not accessible, an exterior area for assisted rescue must be provided in accordance with Section 207.8. 2. Where the exit stairway is open to the exterior, the accessible means of egress shall include either an area of refuge in accordance with Section 207.6 or an exterior area for assisted rescue in accordance with Section 207.8.

207.2.1 Buildings with four or more stories. In buildings where a required accessible floor is four or more stories above or below a level of exit discharge, at least one required accessible means of egress shall be an elevator complying with Section 207.4.

Exceptions: 1. In buildings equipped throughout with an automatic sprinkler system installed in accordance with the EPCOT Building Code, the elevator shall not be required on floors provided with a horizontal exit and located at or above the level of exit discharge.

2. In buildings equipped throughout with an automatic sprinkler system installed in accordance with the EPCOT Building Code, the elevator shall not be required on floors provided with a ramp conforming to the provisions of Section 405.

207.3 Enclosed exit stairways. An enclosed exit stairway, to be considered part of an accessible means of egress, shall have a clear width of 48 inches minimum between handrails and shall either incorporate an area of refuge within an enlarged floor-level landing

Page 33: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 33 of 48

or shall be accessed from either an area of refuge complying with Section 207.6 or a horizontal exit.

Exceptions: 1. Open exit stairways as permitted by the EPCOT Building Code are permitted to be considered part of an accessible means of egress. 2. The area of refuge is not required at open stairways that are permitted by the EPCOT Building Code in buildings or facilities that are equipped throughout with an automatic sprinkler system installed in accordance with the EPCOT Building Code. 2. The clear width of 48 inches between handrails and the area of refuge is not required at exit stairways in buildings or facilities equipped throughout with an automatic sprinkler system installed in accordance with the EPCOT Building Code. 3. The clear width of 48 inches between handrails is not required for enclosed exit stairways accessed from a horizontal exit. 4. Areas of refuge are not required at exit stairways serving open parking garages.

207.4 Elevators. An elevator to be considered part of an accessible means of egress shall comply with the emergency operation and signaling device requirements of Section 2.27 of ASME A17.1. Standby power shall be provided in accordance with the EPCOT Electrical Code. The elevator shall be accessed from either an area of refuge complying with Section 207.6 or a horizontal exit.

Exceptions: 1. Elevators are not required to be accessed from an area of refuge or horizontal exit in open parking garages. 2. Elevators are not required to be accessed from an area of refuge or horizontal exit in buildings and facilities equipped throughout with an automatic sprinkler system installed in accordance with the EPCOT Building Code.

207.5 Platform lifts. Platform (wheelchair) lifts shall not serve as part of an accessible means of egress, except where allowed as part of a required accessible route in accordance with Section 206.7 and installed in accordance with Section 410. Standby power shall be provided for platform lifts permitted to serve as part of a means of egress. 207.6 Areas of refuge. Every required area of refuge shall be accessible from the space it serves by an accessible means of egress. The maximum travel distance from any accessible space to an area of refuge shall not exceed the travel distance permitted for the

occupancy in accordance with the EPCOT Building Code. Every required area of refuge shall have direct access to an enclosed stairway complying with Sections 207.3 and the EPCOT Building Code or an elevator complying with Section 207.4. Where an elevator lobby is used as an area of refuge, the shaft and lobby shall comply with the EPCOT Building Code for smokeproof enclosures except where the elevators are in an area of refuge formed by a horizontal exit or smoke barrier. 207.6.1 Size. Each area of refuge shall be sized to accommodate one wheelchair space of 30 inches by 48 inches for each 200 occupants or portion thereof, based on the occupant load of the area of refuge and areas served by the area of refuge. Such wheelchair spaces shall not reduce the required means of egress width. Access to any of the required wheelchair spaces in an area of refuge shall not be obstructed by more than one adjoining wheelchair space. 207.6.2 Separation. Each area of refuge shall be separated from the remainder of the story by a smoke barrier complying with the EPCOT Building Code. Each area of refuge shall be designed to minimize the intrusion of smoke.

Exceptions: 1. Areas of refuge located within a stairway enclosure. 2. Areas of refuge where the area of refuge and areas served by the area of refuge are equipped throughout with an automatic sprinkler system installed in accordance with the EPCOT Building Code.

207.6.3 Two-way communication. Areas of refuge shall be provided with a two-way communication system between the area of refuge and a central control point. If the central control point is not constantly attended, the area of refuge shall also have controlled access to a public telephone system. Location of the central control point shall be approved by the fire department. The two-way communication system shall include both audible and visible signals. 207.6.4 Instructions. In areas of refuge that have a two-way emergency communications system, instructions on the use of the area under emergency conditions shall be posted adjoining the communications system. The instructions shall include all of the following: 1. Directions to find other means of egress. 2. Persons able to use the exit stairway do so as soon as possible, unless they are assisting others. 3. Information on planned availability of assistance in the use of stairs or supervised operation of elevators and how to summon such assistance.

Page 34: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 34 of 48

4. Directions for use of the emergency communications system. 207.6.5 Identification. Each door providing access to an area of refuge from an adjacent floor area shall be identified by a sign complying with ICC A117.1, stating: AREA OF REFUGE, and including the International Symbol of Accessibility. Where exit sign illumination is required by the EPCOT Building Code, the area of refuge sign shall be illuminated. Additionally, tactile signage complying with ICC A117.1 shall be located at each door to an area of refuge. 207.7 Signage. At exits and elevators serving a required accessible space but not providing an approved accessible means of egress, signage shall be installed indicating the location of accessible means of egress. 207.8 Exterior area for assisted rescue. The exterior area for assisted rescue must be open to the outside air and meet the requirements of Section 207.6.1. Separation walls shall comply with the requirements of the EPCOT Building Code for exterior walls. Where walls or openings are between the area for assisted rescue and the interior of the building, the building exterior walls within 10 feet horizontally of a nonrated wall or unprotected opening shall be constructed as required for a minimum 1-hour fire-resistance rating with 3/4-hour opening protectives. This construction shall extend vertically from the ground to a point 10 feet above the floor level of the area for assisted rescue or to the roof line, whichever is lower. 207.8.1 Openness. The exterior area for assisted rescue shall be at least 50 percent open, and the open area above the guards shall be so distributed as to minimize the accumulation of smoke or toxic gases. 207.8.2 Exterior exit stairway. Exterior exit stairways that are part of the means of egress for the exterior area for assisted rescue shall provide a clear width of 48 inches between handrails. 207.8.3 Identification. Exterior areas for assisted rescue shall have identification as required for area of refuge that complies with Section 207.6.5. A12-0002 604.7 Dispensers. Toilet paper dispensers shall comply with Subsection 309.4 and shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. When combination dispensers are used, the minimum / maximum dimensions above shall apply to the dispenser furthest from the water closet. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Other dispenser outlets and

dispenser controls located at the water closet shall comply with the above dimensions. All dispensers shall be located such that a minimum of 1½-inch clearance is provided below grab bars and a minimum of 12-inch clearance is provided above grab bars, except that flush mounted dispensers need not comply with the 12 inches minimum clearance above grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

ELECTRICAL E12-0001 80.2 Definitions. (d) National Electrical Code. The National Electrical Code, 2008 2011 Edition, as published by the National Fire Protection Association (NFPA) and further identified as ANSI/NFPA 70-2008 2011 by the American National Standards Institute (ANSI). E12-0002 230.6 Main Disconnects. (d) Interior Disconnects. On commercial all buildings, except one and two family dwellings, if the main switch is not readily apparent on the exterior of the building, a shunt trip switch shall be installed on the exterior of the building mounted at 7 feet above finished floor or grade. This requirement shall also apply to buildings served by feeders. The shunt trip switch it shall be properly indicated identified by a reasonable sign constructed of permanent materials with not less than 2-inch-high letters. designating is exact location. The sign shall be located on the exterior of the building at the service doorway, if the main switch is located other than on the main floor, there shall be a shunt trip switch installed adjacent to the sign and as previously noted. The sign and the shunt trip switch shall be mounted at 7 feet above finished floor or grade. E12-0003 Section 310.1 310.1 Aluminum Conductors. Aluminum conductors in sizes No. 1/0 AWG and larger may be used when installed in accordance with all applicable Sections of the NEC. All devices used for terminations and connections shall be approved for the purpose and shall be installed with suitable tools. An approved oxide prohibitive compound shall be applied to all aluminum conductor terminations and connections. 310.2 Aluminum Conductors. Aluminum conductors in sizes No. 1/0 AWG and larger may be used when

Page 35: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 35 of 48

installed in accordance with all applicable sections of the National Electrical Code. All devices used for terminations and connections shall be approved for the purpose and shall be installed with suitable tools. An approved oxide prohibitive compound shall be applied to all aluminum conductor terminations and connections. (Note: Section to be renumbered.) 310.2 1 Color Code. The ungrounded conductors of the different voltage systems in the following list shall be identified by using colored wire insulation with the following colors: 120 volts, single phase, 2 wire: black 240/120 volts; single phase, 3 wire: black and red 480/240 volts; single phase, 2 wire: brown and yellow 240 volts; 3 phase, 3-wire delta: black, red and blue 240/120 volts; 3 phase, 4 wire, high-leg delta: black, red and orange (high-leg) 208Y/120 volts; 3 phase, 4 wire: black, red and blue 480Y/277 volts; 3 phase, 4 wire: brown, orange and yellow 480 volts; 3 phase, 3-wire delta: brown, orange and yellow. The grounded conductor for the 120-, 208-, 240-volt system shall be white, and for the 480-, 277-volt systems shall be gray. Switch legs may be any other color, except those specified for other voltage classifications, and grounded and grounding conductors. AWG sizes four and larger may be identified by means of colored tape or other permanent and substantial means of color coding. E12-0004 New Section 310.2 310.2 Identification. Prior to installation of conductors, means shall be provided to ensure that conductor ends are identified at each end as phase, grounded or gounding conductors. Prior to energizing conductors, verification that each conductor is identified identically at each end shall be required. E12-0005 Two New Articles 700.2 Dimmers. Egress illumination (emergency lighting) required by Subsection 813.2 of the EPCOT Building Code may be controlled by switches and/or dimmers when approved by the Building Official in accordance with this Article. When approved, in addition to the requirements of this Article, all of the following shall apply: (a) Dimmers and/or switches shall be automatically

overridden with loss of normal power and / or with any fire alarm activation,

(b) Dimmers system shall not automatically reset after activation. A manual reset feature shall be provided,

(c) An engineering analysis is required for the devices

used to ensure proper operation and compatibility.

Exception: Switches permitted in NEC Article 700.21.

700.3 Dimmer System. A dimmer system containing more than one dimmer and listed for use in emergency systems may be permitted in accordance with Article 700.2 to be used as a control device for energizing emergency lighting circuits. Upon failure of normal power and activation of any fire alarm initiating device, the dimmer system shall be permitted to energize those circuits required to provide emergency lighting levels established by the EPCOT Building Code. All branch circuits supplied by the dimmer system cabinet shall comply with the wiring methods of Article NEC 700.

ENERGY EFFICIENCY EE12-0001 Update by substituting Florida Building Code 5th Edition (2014) Energy Conservation

FIRE PREVENTION FP12-0001 1416.1 Water Supply. Automatic sprinkler systems shall be connected to an approved two-source water supply of adequate pressure, capacity and reliability for the requirements of the system.

GAS EPCOT FUEL GAS CODE (Note: References in all codes will need to be changed.) G12-0001 New Section 101.4 101.4 Abandonment of piping and/or fittings. Abandoned piping and/or fittings shall be removed.

Page 36: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 36 of 48

Exception: If it is technically in-feasible to remove the pipe/fittings the pipe/fittings may be abandoned in place, at the discretion of the Chief Gas Inspector. Abandon in place; requires the pipe/fittings to be filled and sealed with grout equal to Class "C" concrete. The grout shall form a solid waterproof plug completely bonded to the pipe, and the pipe shall be permanently labeled as abandoned.

G12-0002 SECTION 302 PIPING PLAN 302.1 Plan Requirements. Before proceeding with the installation of a gas piping system, a piping sketch or plan shall may be required to show the proposed location of the piping, the developed length of the piping, the location of valves, regulators, devices, and appliances, as well as the size of different branches, and the demand for each of the existing and/or new appliances. Adequate consideration shall be given to future demands and provisions shall be made for added gas services. When an additional appliance is to be served, the existing piping shall be checked to determine if it has adequate capacity (see Section 305). If inadequate, the existing system shall be enlarged, as required, or separate gas piping of adequate capacity shall be provided. G12-0003 SECTION 306 PIPING MATERIALS AND WORKMANSHIP 306.1 Metallic Pipe. Metallic gas piping shall be of steel pipe complying with ASME B 36.10, ASTM A 53 or ASTM A 106. Where approved by the Chief Gas Inspector, copper or brass pipe in steel pipe sizes assembled with threaded fittings of the same materials may be used when the gas does not contain more than an average of 0.3 grains of hydrogen sulfide per 100 standard cubic feet of gas (a trace as determined by ASTM D 2385 or ASTM D 2420). Exposed gas manifolds piping in kitchen applications shall be of 316 Grade stainless steel, minimum Schedule 10. Headers and drops shall be full size to the last appliance, with outlets facing down at a minimum height of 40 inches above the finish floor. Gas manifolds shall have a drop for each appliance supplied. G12-0004 SECTION 310 GAS SHUTOFF VALVES 310.1 Accessibility of Gas Valves. Shutoff valves controlling separate piping systems shall be placed an

adequate distance from each other so they will be readily accessible for operation, and shall be installed so as to be protected from damage. They shall be plainly marked with an identification tag attached by the installer so that the piping systems supplied through them can be readily identified. The shutoff valve, regulator, and/or gas shut-off solenoid, for any grease hood shall not be located under the hood. G12-0005 New Sections 402.16 & 402.17 402.16 Engineered installations. Engineered combustion air installations shall provide an adequate supply of combustion, ventilation and dilution air and shall be approved. 402.17 Mechanical combustion air supply. Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from the outdoors at a rate not less than 0.35 cubic feet per minute per 1,000 Btu/h of total input rating of all appliances located within the space. 402.17.1 Makeup air. Where exhaust fans are installed, makeup air shall be provided to replace the exhausted air. 402.17.2 Appliance interlock. Each of the appliances served shall be interlocked with the mechanical air supply system to prevent main burner operation when the mechanical air supply system is not in operation. 402.17.3 Combined combustion air and ventilation air system. Where combustion air is provided by the building’s mechanical ventilation system, the system shall provide the specified combustion air rate in addition to the required ventilation air. G12-0006 New Section 709 Carbon Monoxide Protection 709 Carbon monoxide protection. See Subsection 503.13 in the EPCOT Building Code.

MECHANICAL M12-0001 New Section 101.5 101.5 Abandonment of equipment, duct work, vents, piping/fittings.

Page 37: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 37 of 48

101.5.1 Abandonment of equipment. All abandoned equipment shall be removed. 101.5.2 Abandonment of ductwork. All abandoned ductwork shall be removed. 101.5.3 Abandonment of vents. Abandoned inlet openings in chimneys and vents shall be closed by an approved method, sealed and permanently labeled as abandoned. 101.5.4 Abandonment of piping and/or fittings. Abandoned piping and/or fittings shall be removed.

Exception: If it is technically infeasible to remove the pipe/fittings, the pipe/fittings may be abandoned in place, at the discretion of the Chief Mechanical Inspector. Abandon in place requires the pipe/fittings to be filled and sealed with grout equal to Class "C" concrete. The grout shall form a solid waterproof plug completely bonded to the pipe, and the pipe shall be permanently labeled as abandoned.

101.6.1 Abandonment of Smoke/Fire Damper. Abandoned Smoke/Fire dampers require the damper to be removed and the wall/ceiling assembly shall be filled in to meet the fire resistive rating of the existing wall/ceiling.

Exception: If it is technically infeasible to remove the fire/smoke damper, the damper may be allowed to be abandoned in place, at the discretion of the Chief Mechanical Inspector. Abandon in place will the damper to be closed and secured in the closed position and permanently labled as abandoned.

M12-0002 New Section 404.1 404.1 Intake opening location. Air intake openings shall comply with all of the following: 1. Intake openings shall be located a minimum of 10 feet from lot lines or buildings on the same lot. 2. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet horizontally from any hazardous or noxious contaminant source, such as vents, streets, alleys, parking lots and loading docks that accommodate vehicular traffic, except as specified in Item 3. Outdoor air intake openings shall be permitted to be located less than 10 feet horizontally from streets, alleys, parking lots and loading docks provided that the openings are located not less than 25 feet vertically above such locations. Where openings front on a street or public way, the distance shall be measured from the closest edge of the street or public way. 3. Intake openings shall be located not less than 3 feet below contaminant sources where such sources are located within 10 feet of the opening.

404.2 Air Intake Protection. Outdoor air intakes shall be protected against fire exposure by means of approved fire doors, dampers or other suitable protection in accordance with the degree of exposure hazard, and shall be screened with a corrosion-resistant material not greater than 1/2-inch mesh. Fresh air intakes shall not be located closer than 10 feet from any chimney or vent outlet, or sanitary sewer vent outlet, unless such vent outlet is not less than 24 inches above the fresh air inlet. M12-0003 New Section 504.16 504.16 Grease duct test. Prior to the use or concealment of any portion of a grease duct system, a leakage test shall be performed. Ducts shall be considered to be concealed where installed in shafts or covered by coatings or wraps that prevent the ductwork from being visually inspected on all sides. The permit holder shall be responsible to provide the necessary equipment and perform the grease duct leakage test. A smoke or air pressure test shall be performed to determine that all welded and brazed joints are liquid tight. The test shall be performed for the entire duct system, including the hood-to-duct connection. The duct work shall be permitted to be tested in sections, provided that every joint is tested.

Exception: For listed factory-built grease ducts, this test shall be limited to duct joints assembled in the field and shall exclude factory welds.

M12-0004 New Section 506 SECTION 506 FIRE-EXTINGUISHING EQUIPMENT SECTION 506 COMMERCIAL KITCHEN MAKEUP AIR 506.1 Makeup air. Makeup air shall be supplied during the operation of commercial kitchen exhaust systems that are provided for commercial cooking appliances. The amount of makeup air supplied to the building from all sources shall be approximately equal to the amount of exhaust air for all exhaust systems for the building. The makeup air shall not reduce the effectiveness of the exhaust system. Makeup air shall be provided by gravity or mechanical means or both. Mechanical makeup air systems shall be automatically controlled to start and operate simultaneously with the exhaust system. Makeup air intake opening locations shall comply with Section 404. 506.1.1 Makeup air temperature. The temperature differential between makeup air and the air in the

Page 38: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 38 of 48

conditioned space shall not exceed 10°F except where the added heating and cooling loads of the makeup air do not exceed the capacity of the HVAC system. 506.2 Compensating hoods. Manufacturers of compensating hoods shall provide a label indicating minimum exhaust flow and/or maximum makeup airflow that provides capture and containment of the exhaust effluent. Exception: Compensating hoods with makeup air supplied only from the front face discharge and side face discharge openings shall not be required to be labeled with the maximum makeup airflow. 507 FIRE-EXTINGUISHING EQUIPMENT (Note: The remainder of Chapter 5 will need to be renumbered.

PLUMBING Formatting Preface Marginal Markings Solid vertical lines in the margins within the body of this Code indicate a change from the requirements of the 2002 2009 edition, except where a change was minor. Deletion indicators ( ) are provided in the margin where a an entire section, paragraph, exception or table or item listing has been deleted if the deletion resulted in a change of requirements. P12-0001 New Section 101.6 101.6 Abandonment of piping and/or fittings. Abandoned piping and/or fittings shall be removed.

Exception: If it is technically infeasible to remove the pipe/fittings the pipe/fittings may be abandoned in place, at the discretion of the Chief Plumbing Inspector. Abandon in place requires the pipe/fittings to be filled and sealed with grout equal to Class "C" concrete. The grout shall form a solid waterproof plug completely bonded to the pipe, and the pipe shall be permanently labeled as abandoned.

P12-0002 New Definitions THIRD-PARTY CERTIFICATION AGENCY. An approved agency operating a product or material

certification system that incorporates initial product testing, assessment and surveillance of a manufacturer’s quality control system. THIRD-PARTY CERTIFIED. Certification obtained by the manufacturer indicating that the function and performance characteristics of a product or material have been determined by testing and ongoing surveillance by an approved third-party certification agency. Assertion of certification is in the form of identification in accordance with the requirements of the third-party certification agency. THIRD-PARTY TESTED. Procedure by which an approved testing laboratory provides documentation that a product, material or system conforms to specified requirements. P12-0003 SECTION 303 MATERIALS 303.1 Identification. The manufacturer’s mark or name and the quality of the product or identification shall be cast, embossed, stamped or indelibly marked on eEach length of pipe and each pipe fitting, trap, fixture, material and device utilized in a plumbing system in accordance with shall bear the identification of the manufacturer and any markings required by the applicable approved standard. 303.3 Plastic Pipe, Fittings and Components. All plastic pipe, fittings and components shall be identified with the mark of an approved agency third-party certified as conforming to NSF 14. 303.4 Labeled. All plumbing appliances, plastic pipe, plastic fittings, plastic components, potable water pipe, potable water fittings, potable water components, faucets, fixture fittings and backflow preventers shall be labeled by an approved agency. Labeling shall be in accordance with the procedures set forth in Subsections 303.4.1 through 303.4.2.3. 303.4 Third-party certification. All plumbing products and materials shall be listed by a third-party certification agency as complying with the referenced standards. Products and materials shall be identified in accordance with Subsection 303.1. 303.4.1 Testing. An approved agency shall test a representative sample of the material or piping being labeled to the relevant standard or standards. The approved agency shall maintain a record of all of the tests performed. The record shall provide sufficient detail to verify compliance with the test standard. 303.4.2 Inspection and Identification. The approved agency shall periodically perform an inspection, which shall be in-plant if necessary, of the material or piping

Page 39: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 39 of 48

that is to be labeled. The inspection shall verify that the labeled material or piping is representative of the material or piping tested. 303.4.2.1 Independent. The agency to be approved shall be objective and competent. The agency shall also disclose all possible conflicts of interest so that objectivity can be confirmed. 303.4.2.2 Equipment. An approved agency shall have adequate equipment to perform all required tests. The equipment shall be periodically calibrated. 303.4.2.3 Personnel. An approved agency shall employ experienced personnel educated in conducting, supervising and evaluating tests. P12-0004 Section 305 305.1 Corrosion. Pipes passing through concrete or cinder walls and floors, or other corrosive material, shall be protected against external corrosion by a protective sheathing or wrapping, or other means, that will withstand any reaction from lime and acid of concrete, cinder or other corrosive material. Sheathing or wrapping shall allow for expansion and contraction of piping to prevent any rubbing action. Minimum wall thickness of material shall be 0.025 inch.

Exception: Sleeving is not required for installation of CPVC into concrete or similar material.

305.2 Breakage. Pipes passing through or under walls shall be protected from breakage. 305.23 Stress and Strain. 305.4 Sleeves. Annular spaces between sleeves and pipes shall be filled or tightly caulked in an approved manner. Annular spaces between sleeves and pipes in fire-resistance-rated assemblies shall be filled or tightly caulked in accordance with the EPCOT Building Code. (Note: Renumber remaining sections…) 305.53 Pipes Through or Under Footings or Foundation Walls. 305.64 Freezing. 305.64.1 Sewer Depth. 305.64.2 Exterior Utilities. 305.75 Waterproofing of Openings. 305.86 Protection Against Physical Damage.

305.9 7 Protection of Components of Plumbing System. P12-0005 New Subsection 312.1.1 312.1 Required Tests. The permit holder shall perform the applicable tests prescribed in Subsections 312.2 through 312.9 to determine compliance with the provisions of this Code. The permit holder shall give reasonable advance notice to the Building Official when the plumbing work is ready for tests. The equipment, material, power and labor necessary for the inspection and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. All plumbing system piping shall be tested with either water or air. After the plumbing fixtures have been set and their traps filled with water, the entire drainage system shall be submitted to final tests. The Building Official shall require the removal of any cleanouts, if necessary, to ascertain if the pressure has reached all parts of the system.

312.1.1 Test gauges. Gauges used for testing shall be as follows:

1. Tests requiring a pressure of 10 pounds per square inch (psi) or less shall utilize a testing gauge having increments of 0.10 psi or less.

2. Tests requiring a pressure of greater than 10 psi but less than or equal to 100 psi shall utilize a testing gauge having increments of 1 psi or less.

3. Tests requiring a pressure of greater than 100 psi shall utilize a testing gauge having increments of 2 psi or less.

P12-0006 Insert New Section 312.9 312.9 Shower liner test. Where shower floors and receptors are made water-tight by the application of materials required by Section 417.5.2, the completed liner installation shall be tested. The pipe from the shower drain shall be plugged water tight for the test. The floor and receptor area shall be filled with potable water to a depth of not less than 2 inches measured at the threshold. Where a threshold of at least 2 inches

Page 40: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 40 of 48

high does not exist, a temporary threshold shall be constructed to retain the test water in the lined floor or receptor area to a level not less than 2 inches deep measured at the threshold. The water shall be retained for a test period of not less than 15 minutes, and there shall not be evidence of leakage. (Note: Renumber section 312.9 to 312.10.) 312.910 Inspection and Testing of Backflow Prevention Assemblies. Inspection and testing shall comply with Subsections 312.9 10.1 and 312.9 10.2. 312.910.1 Inspections. 312.910.2 Testing. P12-0007 New Section SECTION 315 PENETRATIONS 315.1 Sealing of annular spaces. The annular space between the outside of a pipe and the inside of a pipe sleeve or between the outside of a pipe and an opening in a building envelope wall, floor, or ceiling assembly penetrated by a pipe shall be sealed in an approved manner with caulking material, foam sealant or closed with a gasketing system. The caulking material, foam sealant or gasketing system shall be designed for the conditions at the penetration location and shall be compatible with the pipe, sleeve and building materials in contact with the sealing materials. Annular spaces created by pipes penetrating fire-resistance-rated assemblies or membranes of such assemblies shall be sealed or closed in accordance with the EPCOT Building Code. P12-0008 New Line Item for Table 403.1 (note this should be added to “Assembly” in the table.) TABLE 403.1 MINIMUM NUMBER OF PLUMBING FACILITIESa (see Sections 403.2 and 403.3)

Occupancy

WATER CLOSETS

Lavatories Bathtubs/ Showers

Drinking fountains Others Male Female

Ass

embl

y Area Development occupant load is 40% of the total occupant load of all buildings within 500’

1 per 120

1 per 60

1 per 150 — 1 per 1,000

1 service

sink

Note: Unless an IE study is accepted by the Building Official.

P12-0009 SECTION 404 ACCESSIBLE PLUMBING FACILITIES 404.1 Where Required. Toilet rooms and bathing facilities containing fixtures for occupants of a structure that is required to be accessible by the EPCOT Building Code shall have at least one fixture or element of each type accessible Accessible plumbing facilities and fixtures shall be provided in accordance with the EPCOT Accessibility Code for Building Construction. P12-0010 New Section 405.9 405.9 Design and installation of plumbing fixtures. Integral fixture fitting mounting surfaces on manufactured plumbing fixtures or plumbing fixtures constructed on site, shall meet the design requirements of ASME A112.19.2/CSA B45.1 or ASME A112.19.3/CSA B45.4. New Section 407.4 407.4 Bathtub enclosure. Doors within a bathtub enclosure shall conform to ASME A112.19.15. New Section 408.3 408.3 Bidet water temperature. The discharge water temperature from a bidet fitting shall be limited to a maximum temperature of 110°F by a water temperature limiting device conforming to ASSE 1070 or CSA B125.3. P12-0011 Section 410 410.1 Approval. Drinking fountains shall conform to ASME A112.19.1/CSA B45.2, or A112.19.2/CSA B45.1 or A112.19.9, and water coolers shall conform to AHRI 1010. Drinking fountains and water coolers shall conform to NSF 61 Section 9. Where water is served in restaurants or where bottled water coolers are provided in other occupancies, drinking fountains shall not be required. 410.2 Minimum number. Where drinking fountains are required, not fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons.

Page 41: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 41 of 48

Exception: A single drinking fountain that complies with the requirements for people who use a wheelchair and standing persons shall be permitted to be substituted for two separate drinking fountains.

410.3 Substitution. Where restaurants provide drinking water in a container free of charge, drinking fountains shall not be required in those restaurants. In other occupancies, where drinking fountains are required, water coolers or bottled water dispensers shall be permitted to be substituted for not more than 50 percent of the required number of drinking fountains. 410.2 Prohibited Location. Drinking fountains, water coolers and bottle water dispensers shall not be installed in public restrooms. P12-0012 SECTION 412 FLOOR AND TRENCH DRAINS 412.1 Approval. Floor drains shall conform to ASME A112.3.1, ASME A112.21.1 or CSA B79. Trench drains shall comply with ASME A112.6.3. 412.2 Floor Drains Trap and Strainer. Floor drains traps shall have removable strainers. The strainer shall have a waterway area of not less than the area of the tailpiece. The floor drain shall be constructed so that the drain is capable of being cleaned. Access shall be provided to the drain inlet. Ready access shall be provided to floor drains.

Exception: Floor drains serving refrigerated display cases shall be provided with access.

412.4.15 Public Toilet Rooms and Mechanical Equipment Rooms. Floor drains shall be installed in all public toilet rooms, mechanical equipment rooms (not used as a plenum) and accessible plumbing chases. The floor drains shall be not less than 3 inches and the trap shall be equipped with a trap primer connected to the fixture waste outlet in order to maintain the water seal in the floor drain trap. If no waste outlet is available, the trap primer may be connected to the cold water supply. 412.5 6 Prohibited Location. No floor drain or other plumbing fixture, except electric water heaters, shall be installed in a room containing air-handling equipment when such room is used as a plenum. When rooms are used as a plenum, equipment drains shall be conveyed through an indirect waste receptor located outside such rooms or other approved points of disposal. 412.56.1 Elevator Pits. Floor drains directly connected to the plumbing system shall not be located in elevator pits.

P12-0013 Section 413.4 413.4 Water Supply Required. All food waste grinders shall be provided with a supply of cold water. The water supply shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608. P12-0014 Section 417.5 417.5.2 Shower Lining. Floors under shower compartments, except where prefabricated receptors have been provided, shall be lined and made water tight utilizing material complying with Subsections 417.5.3 through 417.5.68. Such liners shall turn up on all sides at least 2 inches above the finished threshold level. Liners shall be recessed and fastened to an approved backing so as not to occupy the space required for wall covering, and shall not be nailed or perforated at any point less than 1 inch above the finished threshold. Liners shall be pitched one-fourth unit vertical in 12 units horizontal (2-percent slope), sloped toward the fixture drains and securely fastened to the waste outlet at the seepage entrance, making a watertight joint between the liner and the outlet. The completed liner shall be tested in accordance with Section 312.9.

Exceptions: 1. Floor surfaces under shower heads provided for rinsing, laid directly on the ground, are not required to comply with this Subsection. 2. Where a sheet-applied, load-bearing, bonded, waterproof membrane is installed as the shower lining, the membrane shall not be required to be recessed.

417.5.5 Sheet Lead. Sheet lead shall not weigh less than 4 pounds per square foot and shall be coated with an asphalt paint or other approved coating. The lead sheet shall be insulated from conducting substances other than the connecting drain by 15-pound asphalt felt or its equivalent. Sheet lead shall be joined by burning. 417.5.7 Sheet-applied, load-bearing, bonded, waterproof membranes. Sheet-applied, load-bearing, bonded, waterproof membranes shall meet requirements of ANSI A118.10 and shall be applied in accordance with the manufacturer’s installation instructions. 417.5.8 Liquid-type, trowel-applied, load-bearing, bonded waterproof materials. Liquid-type, trowel applied, load-bearing, bonded waterproof materials shall meet the requirements of ANSI A118.10 and shall

Page 42: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 42 of 48

be applied in accordance with the manufacturer’s instructions. P12-0015 New Section 418.3 418.3 Moveable sink systems. Moveable sink systems shall comply with ASME A112.19.12. P12-0016 Section 420.1 420.1 Approval. Water closets shall conform to the water consumption requirements of Subsection 604.4, and shall conform to ANSI Z124.4, ASME A112.19.2, /CSA B45.1, ASME A112.19.3/CSA B45.4 or CSA B45.5. Water closets shall conform to the hydraulic performance requirements of ASME A112.19.62/CSA B45.1. Water closet tanks shall conform to ANSI Z124.4, ASME A112.19.2/CSA B45.1, ASME A112.19.93, CSA B45.1, /CSA B45.4 or CSA B45.5. Electro-hydraulic water closets shall comply with ASME A112.19.2/CSA B45.1. P12-0017 Section 421 WHIRLPOOL BATHTUBS 421.1 Approval. Whirlpool bathtubs shall comply with ASME A112.19.7, or/ CSA B45.510 and CSA CAN/CSA-B45 (Supplement 1).. 421.2 Installation. Whirlpool bathtubs shall be installed and tested in accordance with the manufacturer’s installation instructions. The pump shall be located above the weir of the fixture trap. Access shall be provided to the pump. 421.4 Suction Fittings. Suction fittings for whirlpool bathtub shall comply with ASME A112.19.8 7/CSA B45.10. 421.5 Access to pump. Access shall be provided to circulation pumps in accordance with the fixture or pump manufacturer’s installation instructions. Where the manufacturer’s instructions do not specify the location and minimum size of field-fabricated access openings, an opening not less than 12- inches by 12-inches shall be installed to provide access to the circulation pump. Where pumps are located more than 2 feet from the access opening, an opening not less than 18-inches by 18-inches shall be installed. A door or panel shall be permitted to close the opening. In all cases, the access opening shall be unobstructed and of

the size necessary to permit the removal and replacement of the circulation pump. 421.6 Whirlpool enclosure. Doors within a whirlpool enclosure shall conform to ASME A112.19.15. P12-0018 New Section 424.5 & 424.6 424.5 Multiple (gang) showers. Multiple (gang) showers supplied with a single-tempered water supply pipe shall have the water supply for such showers controlled by an approved automatic temperature control mixing valve that conforms to ASSE 1069 or CSA B125.3, or each shower head shall be individually controlled by a balanced-pressure, thermostatic or combination balanced-pressure/thermostatic valve that conforms to ASSE 1016 or ASME A112.18.1/CSA B125.1 and is installed at the point of use. Such valves shall be equipped with a means to limit the maximum setting of the valve to 120°F, which shall be field adjusted in accordance with the manufacturers’ instructions. 424.6 Bathtub and whirlpool bathtub valves. The hot water supplied to bathtubs and whirlpool bathtubs shall be limited to a maximum temperature of 120°F by a water-temperature limiting device that conforms to ASSE 1070 or CSA B125.3, except where such protection is otherwise provided by a combination tub/shower valve in accordance with Section 424.4. 424.5 7 Hose-Connected Outlets. Faucets and fixture fittings with hose-connected outlets shall conform to ASME A112.18.3. or ASME A112.18.1/CSA B125.1. P12-0019 Section 604.11 604.11 Buildings other than dwelling or dwelling units. Shutoff valves shall be installed which permit the water supply to all fixtures and equipment in each separate room to be shut off without interference with the water supply to any other room or portion of the building or each individual fixture and each piece of equipment shall have a shutoff valve or integral stop which will permit each fixture and piece of equipment to be shut off without interfering with the water supply to other fixtures or equipment. P12-0020

TABLE 605.4 WATER SERVICE PIPE

MATERIAL STANDARD

Page 43: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 43 of 48

Acrylonitrile butadiene styrene(ABS) plastic pipe

ASTM D 1527;

ASTM D 2282

Asbestos-cement pipe ASTM C 296

Brass pipe ASTM B 43

Copper or copper-alloy pipe ASTM B 42; ASTM B 302

Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM)

ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447

Chlorinated polyvinyl chloride (CPVC) plastic pipe

ASTM D 2846; ASTM F 441; ASTM F 442; CSA B137.6

Ductile iron water pipe AWWA C115; AWWA C151

Galvanized steel pipe ASTM A 53

Polybutylene (PB) plastic pipe and tubing

ASTM D 2662; ASTM D 2666; ASTM D 3309;

CSA B137.8

Polyethylene (PE) plastic pipe

ASTM D 2239;

CSA CAN/CSA-B137.1

Polyethylene (PE) plastic tubing

ASTM D 2737;

CSA B137.1

Cross-linked polyethylene (PEX) plastic tubing

ASTM F 876; ASTM F 877; CSA CAN/CSA-B137.5

Cross-linked polyethylene/ aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe

ASTM F 1281;

CSA CAN/CSA-B137.10

Polyethylene/aluminum/ polyethylene (PE-AL-PE) pipe

ASTM F 1282;

CSA CAN/CSA-B137.9

Polyvinyl chloride (PVC) plastic pipe

ASTM D 1785; ASTM D 2241; ASTM D 2672;

CSA CAN/CSA-B137.3

Stainless steel pipe (Type 304/304L)

ASTM 312; ASTM A 778

Stainless steel pipe (Type 316/316L)

ASTM 312; ASTM A 778

P12-0021

TABLE 605.5 WATER DISTRIBUTION PIPE

MATERIAL STANDARD

Brass pipe ASTM B 43

Chlorinated polyvinyl chloride (CPVC) plastic pipe and Tubing

ASTM D 2846; ASTM F 441; ASTM F 442; CSA B137.6

Copper or copper-alloy pipe ASTM B 42; ASTM B 302

Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM)

ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447

Cross-linked polyethylene (PEX) plastic tubing

ASTM F 877; CSA CAN/CSA-B137.5

Cross-linked polyethylene/ aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe

ASTM F 1281; CSA CAN/CSA-B137.10

Galvanized steel pipe ASTM A 53

Polybutylene (PB) plastic pipe and tubing

ASTM D 3309; CSA CAN3-B137.8

Stainless steel pipe (Type 304/304L)

ASTM 312; ASTM A 778

Stainless steel pipe (Type 316/316L)

ASTM 312; ASTM A 778

P12-0022 Remove Exception to Section 802.1.1 802.1.1 Food Handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap. Exception: This requirement shall not apply to dishwashing machines and dishwashing sinks. P12-0023 SECTION 912 COMBINATION DRAIN WASTE AND VENT SYSTEM 912.1 Type of fixtures. A combination drain waste and vent system shall not serve fixtures other than floor drains, standpipes, sinks, and lavatories and drinking fountains. Combination drain and vent systems shall not receive the discharge of a food waste grinder or clinical sink. 912.2 Installation. The only vertical pipe of a combination drain waste and vent system shall be the connection between the fixture drain of a sink, lavatory or standpipe, and the horizontal combination drain waste and vent pipe. The maximum vertical distance shall be 8 feet (2438 mm). The vertical distance between a floor drain or floor sink and the horizontal combination drain and vent pipe in a combination drain and vent system shall not exceed 24 inches (609.6 mm) from the drain outlet to the trap weir.shall not exceed 8 feet. 912.2.1 Slope. The slope of a horizontal combination drain waste and vent pipe shall not exceed have a maximum slope of one-half unit vertical in 12 units horizontal (4-percent slope) and shall not be less than that indicated in . The minimum slope shall be in accordance with Table 704.1. 912.2.2 Connection. The combination drain waste and vent pipe system shall be provided with a dry vent connected at any point within the system or the system shall connect to a horizontal drain that is vented in accordance with one of the venting methods specified in this Chapter. or a vent shall connect to the combination drain and vent. Combination waste and

Page 44: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 44 of 48

vent systems connecting to building drains receiving only the discharge from a stack or stacks shall be provided with a dry vent. The vent connecting to the combination drain waste and vent pipe shall extend vertically a minimum of not less than 6 inches (152 mm) above the flood level rim of the highest fixture being vented before offsetting horizontally. The vent shall be provided at the upstream end of each branch, washed by the last fixture. A vent shall be located downstream of all fixtures in the system and before the intersection with any other building drainage system (see Appendix I figure 6). 912.2.3 Vent size. The vent shall be sized for the total drainage fixture unit load in accordance with Section 916.2. 912.2.4 Fixture branch or drain. The fixture branch or fixture drain waste shall connect to the combination drain and vent within a distance specified in Table 906.1. The combination drain and vent pipe shall be considered the vent for the fixture. The combination drain and vent pipe shall be carried full size through the trap to the fixture. 912.3 Size. The minimum size of a combination drain waste and vent pipe shall be in accordance with Table 912.3. The horizontal length of a combination waste and vent system shall be unlimited. 912.4 Limitations. Combination drain and vent systems are limited to those fixtures described in 912.1, other building drainage systems shall be connected below the combination drain and vent system. 912.5 Safe Waste. The use of a safe waste shall have a maximum developed length of 25 feet (7.62 m) from the inlet of the trap to the floor drain or floor sink (see Appendix I figure 7). P12-0024 SECTION 917 AIR ADMITTANCE VALVES 917.1 General. Vent systems utilizing air admittance valves shall comply with this Section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. 917.3 Where Permitted. Individual, branch and circuit vents shall be permitted to terminate with a connection to an individual or branch-type air admittance valve. in accordance with Section 917.3.1. The air admittance valve shall only vent fixtures that are on the same floor level and connect to a horizontal branch drain. The horizontal branch drain shall conform to Subsection 917.3.1 or 917.3.2. Stack vents and vent stacks shall be

permitted to terminate to stack-type air admittance valves in accordance with Section 917.3.2.

917.3.1 Location of Branch. The horizontal branch drain shall connect to the drainage stack or building drain a maximum of four branch intervals from the top of the stack. Horizontal branches. Individual and branch-type air admittance valves shall vent only fixtures that are on the same floor level and connect to a horizontal branch drain. Where the horizontal branch is located more than four branch intervals from the top of the stack, the horizontal branch shall be provided with a relief vent that shall connect to a vent stack or stack vent, or extend outdoors to the open air. The relief vent shall connect to the horizontal branch drain between the stack and the most downstream fixture drain connected to the horizontal branch drain. The relief vent shall be sized in accordance with Section 916.2 and installed in accordance with Section 905. The relief vent shall be permitted to serve as the vent for other fixtures.

917.3.2 Relief Vent. The horizontal branch shall be provided with a relief vent that shall connect to a vent stack or stack vent, or extend outdoors to the open air. The relief vent shall connect to the horizontal branch drain between the stack or building drain and the most downstream fixture drain connected to the horizontal branch drain. The relief vent shall be sized in accordance with Subsection 916.2 and installed in accordance with Section 905. The relief vent shall be permitted to serve as the vent for other fixtures. Stack. Stack-type air admittance valves shall be prohibited from serving as the vent terminal for vent stacks or stack vents that serve drainage stacks having more than six branch intervals.

917.4 Location. The Individual and branch-type air admittance valve shall be located a minimum of 4 inches above the horizontal branch drain or fixture drain being vented. Stack-type air admittance valves shall be located not less than 6 inches above the flood level rim of the highest fixture being vented. The air admittance valve shall be located within the maximum developed length permitted for the vent. The air admittance valve shall be installed a minimum of 6 inches above insulation materials. 917.8 Prohibited Installations. Air admittance valves shall not be installed in non-neutralized special waste systems as described in Chapter 8 except where such valves are in compliance with ASSE 1049, are constructed of materials approved in accordance with Section 702.5 and are tested for chemical resistance in accordance with ASTM F 1412. Valves shall not be

Page 45: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 45 of 48

located in spaces utilized as supply or return air plenums. Air admittance valves without an engineered design shall not be utilized to vent sumps or tanks of any type. P12-0025

TABLE 1003.3.1 CAPACITY OF GREASE TRAPS

TOTAL FLOW THROUGH RATING (gpm)

GREASE RETENTION CAPACITY (pounds)

4 8 6 12 7 14 9 18

10 20 12 24 14 28 15 30 18 36 20 40 25 50 35 70 50 100

1003.3.4 Grease Interceptor Design Criteria 1003.3.4.1 General Minimum size 750 gallons Maximum size of single trap 5,000 gallons 1003.3.4.2 Definitions of food service types: FAST FOOD. Food that uses cooking oils of any type in the preparation or service, and that has an option for carry out orders. Fast food facilities will use a fryer of some type and size for food preparation. DELI STYLE. Food that does not use cooking oil in the preparation or service, and that has an option for carry out orders. Deli style facilities will have no fryers, and be principally cold service foods. STANDARD SERVICE. A sit down facility will include all facilities that serve food in a dining area and utilize washable cutlery and washable plates and glassware, but does not serve alcoholic beverages. FULL SERVICE. A sit-down facility includes all facilities that serve food in a dining area, utilizes washable cutlery, plates and glassware and serves any type of alcoholic beverage. 1003.3.4.3 Procedure for Determining Grease Interceptor Size: 1) Determine the peak flow to the interceptor

a) Determine the number of seats (maximum) and assume 100% use/occupancy.

b) Determine the maximum number of take-out meals served (if any)

c) Apply the flow factors to the above i) 25 gpd/seat ii) 5 gallons/take out meal (non-fast food)

iii) 2.5 gallons/take out meal (fast food) d) Apply the peak factor

i) Use 3.0 times unless documented otherwise

Peak Flow (gpd) = (# Seats X 25 + # take-out meals X (5 or 2.5») X peak factor of 3

2) Determine the type and character of the Facility and interceptor cleaning frequency a) Apply the appropriate service factors for:

i) Operating hours ii) Food service type iii) Proposed cleaning frequency iv) Seat turnover

3) Complete the calculation for the interceptor size Trap Volume = Peak flow (in gpm) x 120 minutes Detention Time x Peak Factor x Cleaning Factor x Open Hours Factor x Service Type Factor x Seat Factor.

4) Select appropriate interceptor size by rounding up to the nearest 100 gallon increment.

5) For trap volumes exceeding 5000 gallons, use multiple units operating in parallel.

Table 1003.3.1 Operational and Facility Factors for Sizing Interceptors

SIZE OF TRAP BASED ON MULTIPLIER

1) Cleaning Frequency of interceptor: a) Standard frequency = 1/quarter b) Minimum frequency = 1/year c) Maximum frequency = 1/month d) Minimal frequency = 2x1yr

1 4

0.33 2

2) Hours of operation of food/kitchen service a:

a) Standard operation = 12 hours/day b) Minimum operation = 8 hours/day c) Maximum operation = 20 hours/day d) Extended operation = 16 hours/day

1

0.6667 1.667 1.333

3) Number of meals served per day (max. day) and

None

4) Number of seats in restaurant a) Standard Turnover ratio: 1/hour b) Maximum Turnover ratio: 2/hour c) Minimum Turnover ratio: 1/2 hours

1 2

0.5

5) Type of food service a) Fast food with or without take-out b) Deli style with or without sit-down facilities c) Sit-down, standard service d) Sit-down, full service

1.2 0.8

1

1.5

a. For operating hours other than those listed, use a ratio of: actual hours/12 Size of interceptor is a function of: 1. Detention time desired in trap, usually this is a minimum of 2 hours 2. Type of drains routed through trap - sanitary drains should be piped separately 3. Water volume or flow rate generated from number of seats and/or meals served

Page 46: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 46 of 48

Basis and Rational for Formula 5 gallons per meal is used as the water volume if meals served is the design basis. 15 - 50 gallons per seat shall be used as the water volume if seats used are the design basis. A minimum of two hours of detention time (DT) in the interceptor is required at peak flow rates (>120 minutes). If the facility is a combination sit-down and take out, then a combination of these shall be used for flow estimation. The number of meals served at the sit down is allowed to be subtracted from the total meals served to calculate flow. Or the number of seats plus the maximum number of meals taken out shall be used for flow calculations

Basic formula shall be:

Trap Volume = Peak flow (in gpm) x 120 minutes Detention Time x Peak Factor x Cleaning Factor x Open Hours Factor x Service Type Factor x Seat Factor.

Flow shall be based on the number of seats or meals served or combination of both times a flow factor for each. 25 gallons per seat is the norm for this criterion, and 5 gallons per meal. However, for fast food and deli service operations, which use primarily paper and plastic cutlery and packaging a figure of 2.5 gallons per meal served shall be used for fast food and deli food style establishments. If the design criteria value used is number of seats, then a factor for the turnover ratio of the seats shall be used.

Standard and full service sit down

Peak flow = (Number of seats X 25 gpd/seat + number of take-out meals (max.) X 5 gal/meal) X Peak factor Peak factor to be 3 times unless justification can be provided to the Building Official substantiating a lesser value.

Deli/ fast food

Peak flow = (Number of seats X 25 gpd/seat + number of take-out meals (max.) X 2.5 gal/meal) X Peak factor Peak factor to be 3 times unless justification can be provided to the Building Official substantiating a lesser value.

EXAMPLES of FORMULA For example, assume a sit down restaurant that is open 12 hours per day, has 120 seats, has one hour per seat turnover and intends to clean their trap quarterly. Also assume they use 25 gallons per seat and a peaking factor of 3. All operational and facility factors would therefore be 1.0. Trap size would be:

Flow = 120 x 25 x3 = 9000 gallons per day Trap Size = 9000/1440 x 120 = 750 gallons, or the minimum size

Now let's assume we have a fast food restaurant that serves 5000 meals a day, is open 16 hours a day, has seating capacity for 40 people, turns the seats over 1/hour, and intends to clean the trap on a quarterly basis. Trap size would be:

Flow = 40 x 25 x 3 = 3000 gallons per day # meals served at sit down = 40 X16 X 1/hr = 640 plus (5000-640) x 2.5 = 10900 gallons Total flow = 13900 gallons Trap size= 13900/1440 x 120 x 1.333 = 1540 gallons or about twice the size of the smallest trap.

Now assume an extreme case, a fast food restaurant serving 15000 meals a day with 200 seats, open 20 hours per day turning over their seats every 30 minutes and intends to clean their trap quarterly. Trap size would be:

Flow = 200 x 25 x 3 = 15000 gpd # meals served at sit down = 200 X 16 x 2 = 6400 plus 15000-6400 X 2.5 = 21500 gallons Trap size = (15000 + 21500)/1440 x 120 x 1.667 = 5079 gallons If this facility only intended to clean their trap 2x1year, the size would double to 10,000 gallons

Now assume the other extreme, a walk up deli style open 8 hours per day with no seats and expecting to service its trap only annually, serving 500 meals per day on a peak day, or about one per minute. Trap size would be:

Flow = 500 x 2.5 x 3 = 3750 gpd, based on meals served only, no sit down. Trap size: 3750/1440 X 120 X 0.667 X 0.5 X 4 = 417 gallons; or a minimum tank of 750 gallons would suffice

Now assume a large full service restaurant with 500 seats, open 16 hours per day, with turnover of seats at once per hour no take out, and a cleaning frequency of quarterly. Trap size would be:

Flow = 500 x 25 x 3 = 37500 gallons Trap size = 37500/1440 X 120 X 1.33 X 1.2 X 1.0 = 4987.5 gallons or say 5000 gallons

P12-0026 New Section 1107.5.1 1107.5.1 Parapet wall scupper shall be sized for the maximum projected roof area in accordance with Table 1107.3. TABLE 1107.3 SCUPPER SIZING TABLE ROOF AREA (square feet)

HEAD (H)

(inches) LENGTH (L) OF WEIR (inches)

4 6 8 12 16 20 24

4 923 1,500 2,076 3,230 4,383 5,537 6,691

6 1,483 2,544 3,602 5,721 7,840 9,959 12,080

8 1,845 2,999 4,152 6,460 8,766 11,073 13,381

Page 47: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

Page 47 of 48

P12-0027 New Section 1112 SECTION 1112 SIPHONIC ROOF DRAINAGE SYSTEMS 1112.1 General. Siphonic roof drains and drainage systems shall be designed in accordance with ASME A112.6.9 and ASPE 45.

Page 48: EPCOT BUILDING CODES 2015 Edition Code Change …* This preface to the EPCOT Codes was written by Marty Sklar, a Walt Disney Imagineering legend, after he had met with Walt Disney,

**Table 6.2

Remove footnote (c)