In-Service Inspection and IntegrityAssessment of Above-Ground
Storage TanksDr. Athanasios Anastasopoulos
Presentation forTank Storage ConferenceISTANBUL 3 & 4 November 2010
www.envirocoustics.gr, [email protected], Tel.: (+30) 210-2846801, Fax: (+30) 210-2846805
8/12/2019 Enviro Cous Tics
2/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
OVERVIEW
FAILURE OF TIME-BASED MAINTENANCE & NEEDS FOR ONSTREAM INSPECTION
TANKPACTM : IN SERVICE CONDITION MONITORING FOR TANKFLOORS: Acoustic Emission Tank Floor Testing Overview
Case Studies
Validation and Verification
TALRUTTM: IN-SERVICE CRITICAL ZONE EXAMINATION
LSI TANK SHELL CORROSION AND WEAR MAPPING
PCMS: PLANT CONDITION MONITORING & RISK BASEDINSPECTION SOFTWARE
DISCUSSION AND CONCLUSIONS
8/12/2019 Enviro Cous Tics
3/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Failure of time-based maintenanceHot oil tank, 140C: Internally
inspected 12 months prior to
failure, including UT+MFL. This
collapse was due to a narrowband of annular ring corrosion.
When the ring split the very
rapid loss of hot liquid pulled a
vacuum collapsing the tankshell.
Naphtha Tank: Leaking 100 cubic meters
per day through a 1cm hole. Operations
noticed losses after a week, but no visible
product, which was disappearing intoground. When the plates were cut the
cavity under the floor was several cubic
metres in size.
8/12/2019 Enviro Cous Tics
4/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Copyright 2007Envirocoustics S.A.
Failures of time-based maintenance
Many more examples.
Tanks removed from service, cleaned,sludge dumped, tank inspected...and norepairs required..
Tanks inspected though leaks not alwaysprevented
If time based internal inspectionworked. this would not behappening....
8/12/2019 Enviro Cous Tics
5/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Copyright 2007Envirocoustics S.A.
Tank Floors are the only structural part of a tank
with no access for inspection during operation Access to tank floors for inspection is difficult and costly.
Leakage is no longer environmentally acceptable.
Risk of catastrophic failure with severe annular ring damage. Cleaning costs can be >$200,000, + environmental waste
problem. If no repairs are required these costs are wasted.
Requirements:
To identify tanks which do NOT yet require internal inspectionand repair, this prevents the waste of maintenance resourcesand protects the environment.
To determine the relative condition of damaged floors so that acorrect priority for internal maintenance may be set.
To do the above with as little disruption to operations aspossible.
8/12/2019 Enviro Cous Tics
6/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
TANKPAC: IN SERVICE CONDITION
MONITORING FOR TANK FLOORS
8/12/2019 Enviro Cous Tics
7/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
AE sensor
Tank
AEInstrument
AE Van
Acoustic Emission Tank Floor Testing Overview
AE Sensors (in the Low Ultrasonic Range to
avoid Interference) mounted on tank wall 1-2m above knuckle
3-30 sensors per row used depending upon
size / 1 or 2 rows
Cables go to test instrumentation
8/12/2019 Enviro Cous Tics
8/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Acoustic Sources detectedCorrosion of steel causes
Acoustic Emission (Yuyama,
Condello etc).Sources detected by sensors on
the outside of the tank.
Spalling of corrosion products.
Leak noise: (flow interruption, orturbulence).
External Interference - noise to befiltered:
Roof movement noise, Structuralmovement, External and pipe-bornenoise, Condensation, Particleimpacts, Valve leakage.
Signal amplitude >>
^ Number of emissions
time
Shown above: one hour of emission from a
tank with very severe corrosion, characteristics
of emission change with scaling.
8/12/2019 Enviro Cous Tics
9/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Time (s)
mptu
e
Htrae
AE data analysis
Bottomplate
AE sensorLiquid bornwave
AEsource
Acoustic Emission Tank Floor Testing Overview
The tank is monitored in service, following conditioning (Valves closed, heaters
off, agitators off), for a pre-determined time (6-24 hours in advance of test)
The data is processed to eliminate unwanted sources of noise,
Location of 3+hit sources by triangulation.
The data is evaluated against TANKPAC Technology (database, special
algorithms for location, Correlations, etc.)
8/12/2019 Enviro Cous Tics
10/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Copyright 2007Envirocoustics S.A.
TANKPACTM: CONDITION MONITORING FOR TANK FLOORS
Tank floor top view with
locations of corrosion and/or
leak sources
3D plots of located
corrosion and leak
sources
Separate analysis and
grading of the most
severe corrosion sites
100% FLOOR INSPECTION & ANNULAR RING
Overall Tank Grading, from A (no damage) to E (severe damage), indicate the general
condition of the Floor.Potential Leak Sites Identified & Graded indicating concentrated sources of severe
corrosion or leak.
Combination of Overall Grading with Potential Leak Result in Composite RBI compatible
Matrix .
8/12/2019 Enviro Cous Tics
11/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Recommendations Matrix
Overall Grade A B C D E
PLD Grade I I II (n/a) (n/a) (n/a-doesnt occur)
1 I I II (n/a) (n/a) I > ~4-5 years
2 I I II II (n/a) II > ~2 years
3 II II III III III III ~ 1 year*
4 II III III IV IV IV ~ 0.5 years*
5 III III IV IV IV *or schedule for internal inspection
Clearly leaking tanks often unable to grade, (should be opened anyway).
Active concentrated sources in all data will also increase severity of grading.
8/12/2019 Enviro Cous Tics
12/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Corrosion of Internal Zinc Anodes
Emission reaching three sensors
is located.
Internal sacrificial anodes corrode
in place of tank floor.
Zinc blocks can be large.
Oilfield production tanks use
sacrificial anodes-very active when
has coating failed, until zinc used,
then floor corrodes.
Special procedures used to
separate anode corrosion from
floor corrosion.
Emission from active anodes in a 55
metre tank, 2m x1m in size, (30 in
tank, 4/10/16)
8/12/2019 Enviro Cous Tics
13/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
150 Diameter, Gasoline
ALL DATA
TANK -PAC
GRADE
A
B
C
D
E
North
Channel 1
8/12/2019 Enviro Cous Tics
14/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
TANKPAC: In-Service Floor Plate
Corrosion Assessment
8/12/2019 Enviro Cous Tics
15/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
3-D view of an E grade crude tank
and damage found
8/12/2019 Enviro Cous Tics
16/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Leaking Tanks Cases
Gasoline Tank
Very concentrated source:scale usually 50!
Doesnt show on tank plot, onepixel. On product tanks smallleaks are not easily identified,except by high concentration.
~1mm hole found whenopened.
Naphtha Tank
100 cu.m/day loss
No visible indication of a leak
Faint smell only
TANKPACTM test at 2% sensitivitydue to noise - 2 minutesacquisition only:
1cm hole found at location shown
8/12/2019 Enviro Cous Tics
17/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Copyright 2007Envirocoustics S.A.
NEW TANK LEAKING
DEFECTS IN THE
WELDS.......LEAK
TANKPACTM:/ LEAK DETECTION
8/12/2019 Enviro Cous Tics
18/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Limitations(see method statement)
Detects and grades active corrosion only.
Not suitable for assessing the internal condition of tanks which arecleaned mechanically or chemically as this resets the condition,
(underside OK). Use history!!
Small leaks may be masked by active floor corrosion.
Large leaks will mask overall floor condition.
Activity from active corrosion under insulation may mask floorcondition.
Location may degrade on very active D/E tanks due tosimultaneous sources, (the tank needs opening anyway!).
Not all tanks can be tested, due to noise/condensation etc.
Complex procedure requires extensive training + control.
8/12/2019 Enviro Cous Tics
19/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Copyright 2007Envirocoustics S.A.
TANKPACTM: VERIFIED RELIABILITY
1. TANPAC Tests All around the word (Europe, Middle East, Africa, SouthAmerica, Asia and Far East, North America)
2. PAC TANKPAC Procedure adopted by SAUDI
ARAMCO.3. PAC TANKPAC Procedure adopted by DOW
CHEMICALS
4. PAC TANKPAC Procedure verified by Shell GlobalSolutions (results presented in ECNDT 98)
5. 1999 EEMUA recommendations to members (1996 Usergroup became part of EEMUA, ~30 Cos -Engineering Equipment Material Users Association- experience now
>600 tank floor tests, feedback on internal inspection of >150 tanks, procedure at rev.4.)
6. French Petroleum Institute: UNION FRANCAISE DES INDUSTRIESPETROLIERS (API), Guide Pour Linspection Et La Maintenance Des Reservoirs Mettaliques Aeriens
Cylindriques Verticaux D Hydrocarbures Liquides En Raffinerie, ANNEXE: Recommandations pour lutilization de
lemission acoustique a la verification de l etancheite et a levaluation de l activite des corrosion des reservoirs
verticaux aeriens, Edition Aug. 2000, Paris
8/12/2019 Enviro Cous Tics
20/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Comparison with
Subsequent Inspection
From correlation of TANKPACTM results withinternal inspection and repairs carried out:
100% of A-grade tanks - no repairs ordamage to floor
56% of C-grade tanks - patch repairs
52% of E-grade tanks - floor replaced
8/12/2019 Enviro Cous Tics
21/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Reliability: TANKPACTM
overall grading vs. repairs required*
0
20
40
60
80
100
120
A B C D E
FU 1/2 Minimal damage: no repairsFU 3 Damage: some repairs
FU 4 Significant damage: major repair/new floor
R
elative(%)
AE-grade
Follow-up results versus AE-grades, normalised per AE-grade
population of 157 tanks (Shell, Dow-Stade, DSM, PKE, Total and PAL database)
* P.van de Loo/Shell, B.Hermann/Dow, ECNDT 1998
8/12/2019 Enviro Cous Tics
22/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Overall AE Grade vs. % of Tanks for crude
and product tanks from Major Sites
0
10
20
30
40
50
A B C D E
%CRUDE
%PROD.
%ALL
ALL SITES IN SURVEY% of tanks
TANKPAC
GRADE
sample size 598 tanks 6/96
8/12/2019 Enviro Cous Tics
23/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Copyright 2007Envirocoustics S.A.
TANKPAC is a maintenance planning tool
Significant money savings: No moneywasted for opening of good tanks.
Maintenance prioritisation: The mostseverely damaged tanks are programmed
for internal inspection first. Prevention of environmental losses:Earlyidentification of potential leaks.
Very fast, low-cost inspection withminimal interruption of operations
8/12/2019 Enviro Cous Tics
24/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
TALRUT
In-Service Floor Plate
(Critical Zone)Assessment
Inspects critical area,~30cm in.
Automated UT, Plan image.
40 m/day.
Indicative, notquantitative.
Detects first edge ofcorrosion.
Detects at 30-50%.
8/12/2019 Enviro Cous Tics
25/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Copyright 2007Envirocoustics S.A.
TALRUT Annular Ring Test
Left - Example of Indications from a calibration plate (topof plate is the wall tank shell), Right area withoutindications and close up of the respective A-Scan at
cursor position
SHELL:
PLAN VIEW IMAGE SHOWING
SEVERE UNDERSIDE CORROSION:
Summary ReportingExample
8/12/2019 Enviro Cous Tics
26/32
Shell Corrosion
Surveys Utilizing LSI
8/12/2019 Enviro Cous Tics
27/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
LSI Tank Shell Corrosion
And Wear Mapping 18 meter x 500 mm strip:
10 x2 mm resolution 45 minutes
scan time (5 min/2m). 450,000 readings.
Typically: North, South, East, West(drive around above rings).
Larger tanks add NE, SE, SW, NW Preferential HAZ corrosion and
local thinning by wear
Limitations:
Poor surfaces may loose somedata ( but still hugestatistical sample )
8/12/2019 Enviro Cous Tics
28/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Copyright 2007Envirocoustics S.A.
C-SCAN of TANK SHELL & PROCESSING OF UT DATA
FFS throughout Composite C-Scan imagereconstruction in Nominal-Caution-Reject coloring
mode
8/12/2019 Enviro Cous Tics
29/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
PCMS & RBI TANKREPORTER S/W
Mistras TANKREPORTER and PCMS S/W is usedto enhance reporting and assist assetintegrity management. Capabilities includes3D model of the tank with detail weld seamlocations, nozzle locations, TML locations,repair locations, hyperlinks torecommendations and photos of the defectareas, corrosion rate calculations and RBI.
8/12/2019 Enviro Cous Tics
30/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
In-Service Inspection, using Modern State of the art techniques,
Integrated within Plant Condition Monitoring Software (PCMS) and
Risk Based Inspection lead to reliable Integrity Assessment
offering:
Determine the condition of damaged floors so that a correct
priority for internal maintenance may be set, thus:
Increased Safety, Availability, Reliability
Reduce rate and impact of unexpected failures
Identify tanks which do not require internal inspection and
repair, thus:
Reduce the number and duration of tank shutdownReduce scope of routine activities
Resources prioritized for greatest effect
Reduce costs
CONCLUSIONS
Need to know more about our Group please visit our
8/12/2019 Enviro Cous Tics
31/32
Copyright 2008 Proprietary information: No dissemination, use or duplication without prior written permission from MISTRAS Group, Inc..
Thank you for your attention,
Please let us know
WHAT ARE YOUR QUESTIONS ?
Need to know more about our Group, please visit our
web page:
http://www.mistrasgroup.com/
8/12/2019 Enviro Cous Tics
32/32
API Turnaround Management Pipeline Construction
Aboveground Storage Tanks Automated Ultrasonics PCMS Inspect ion IT & RBI Mechan ical Integri ty (MI)
Pipeline Integrity (PLI) Predictive Maintenance (PdM) Refractory Inspection Rope Access
Smart Grid TransformerReliability
Transportation & Fire Apparatus Tube Inspection Asset Integrity Mgmt. Services(AIMS)
MISTRAS Group Inc.Services DivisionCenters of Excellence