Enhanced Protection for Inverter Dominated

Embed Size (px)

Citation preview

  • 8/12/2019 Enhanced Protection for Inverter Dominated

    1/5

    ENHANCED PROTECTION FOR INVERTER DOMINATED

    MICROGRID USING TRANSIENT FAULT INFORMATION

    X. Li*, A. Dyko*, G. Burt*

    *University of Strathclyde, UK, [email protected]

    Keywords: Transient based protection, inverter dominated

    microgrid, Mathematical Morphology, travelling wave, rateof change of current.

    Abstract

    Protection of an inverter dominated microgrid is always agreat challenge, as inverters are well known for their

    insufficient contribution to the fault current, undermining theaccuracy and viability of traditional overcurrent protectionschemes. Based on the wide review of solutions developed in

    the past, this paper proposes a novel protection strategy, withthe main protection method based on the time and polarityfeatures of initial current travelling waves using mathematicalmorphology (MM) technology and backup protection strategybased on the rate of change of current. Simulation tests inPSCAD/EMTDC considering different fault resistances, fault

    positions and fault inception angles prove this protectionapproach to be sensitive and reliable.

    1 Introduction

    High penetration of distributed generation (DG) is expected tobe a permanent feature of future power systems. One way ofachieving efficient integration of large and diverse amounts of

    DG is to control and regulate a cluster of DGs and customerloads integrally as a microgrid, which can be run in both grid-connected and islanded mode of operation. Studies have beenfocused on both control and protection of the microgrid.Referring to the study of protection, the lack of fault currentcontribution from inverter-interfaced generators (IIG)

    becomes one of the main concerns [1].

    During normal grid-connected operation, the s low fault

    current contribution generally does not interfere with theexisting current grading of the distribution network. Duringislanded operation, however, the lack of effective fault current

    sources weakens the effectiveness of the existing overcurrentrelays. In order to resolve this issue the protection schemeshould ideally be independent of the fault to load current

    ratio. Existing solutions can be classified into three groups:1. Adaptive protection based on overcurrent principles [2];2. Implementation of additional Fault Current Source

    (FCS) devices [3][4];3. Unit type protection current differential [5] or phase

    comparison [1].

    Although efforts have been made to implement adaptiveprotection schemes [2], this group of solutions faces a number

    of challenges such as time consuming pre-planning of settings

    and complicated validation process. As the protectioncontinues to be based on overcurrent principle, the lowcurrent magnitude and time duration still appear to be themajor obstacles. On the other hand, FCS based protectionarrangement can be seen as unreliable from a system

    protection view, as the reliability of the whole protectionsystem relies on a single electrical device, an energy storage

    device with high short-circuit capacity. Even if several FCSsare connected to ensure required reliability, the cost of such

    protection scheme is likely to be prohibitive. Similar to FCSbased protection conventional unit protection approach can

    also face a significant cost in building and maintaining highbandwidth communication channels.

    Very few people have discussed the idea of introducing faultgenerated travelling wave as a guiding principle of themicrogrid protection. The authors of the paper [6] applied this

    idea to a zonal DC marine system. However, with nodedicated signal analysis, fault transients are not properlyextracted, and their arrival time and polarity information are

    vague. Furthermore, the method requires very highcommunication bandwidth to transport high frequencysampled real time current measurements. Reference [7]introduced a hybrid protection idea using fault generated

    current travelling wave and superimposed power frequencyvoltage using multi-resolution wavelet analysis. However, the

    method is not validated through realistic simulation.

    This paper proposes and discusses an efficient microgridprotection strategy combining fault generated current

    travelling wave based primary protection and rate of changeof current based backup protection. The primary protection

    introduces a very efficient and engineering-application-

    friendly signal processing technology mathematicalmorphology (MM). The algorithm is modified by the authorsto meet the requirements of the proposed protection schemewith the capability of extracting polarity features. The casestudy considering different fault conditions is presented toassess the sensitivity of the proposed scheme. The paper is

    organised as follows: Section 2 explains the basic principlesof MM technology and presents the modified MM filter;Section 3 discusses the main travelling wave based algorithm

    and introduces the backup protection principle based on therate of change of current; In section 4 a 20KV microgridbenchmark model is set up to verify the proposed protection

    scheme using PSCAD/EMTDC simulator.

  • 8/12/2019 Enhanced Protection for Inverter Dominated

    2/5

    2 Modified mathematical morphology filter

    (MMF)

    Mathematical morphology (MM)[8][9][10] uses a structuralelement (SE) to extract the necessary features of the original

    signals. Dilation ( ) and erosion ( ) are two basicoperations in MM. Assuming a signal f(n)(0

  • 8/12/2019 Enhanced Protection for Inverter Dominated

    3/5

    In a radial network, this method is sufficient as the routes ofthe travelling waves are one way only. If the topology of themicrogrid is a meshed network, mere polarity information

    may not correctly indicate the faulty line. In this case, acomparison of the time information between the local and

    adjacent units can solve this issue. Therefore, for meshednetworks the main fault detection algorithm is blocked unless:

    (7)Where is the time information from the local unit, and are the times from the adjacent units.This method has the advantages of ultra-high speed faultdetection and low requirement of the communicationbandwidth. However, as an inherent issue within thetravelling wave based methods, fault inception angle is still alimiting factor affecting its performance. Although most of

    the faults occur when voltage is around its peak, backupsolution is still needed to detect the faults occurring at thepoint of voltage zero crossing (POW = 0). In this paper, abackup solution based on the rate of change of current is

    proposed. The indicator is defined as (8):

    (8)

    Where calculates the mean value of the magnitude ofthe current signal f(n) within a window of most recent Numsamples. A fixed threshold considering the maximum rate ofchange of the current IN_Diff_max is assumed. Unlike the main

    protection, this indicator is not affected by the fault inceptionangle. On the other hand, similar to the main protection,polarity information of can also be used to easilydetect the faulty zone.

    The diagram of the proposed protection strategy is depicted in

    Figure 3.

    MMF based

    main protection

    Diff based

    backupprotection

    f(t)OR Trip

    ANDTime delay

    Figure 3: Proposed protection strategy based on two

    independent principles

    4 Simulation case studies

    For the evaluation of the performance of the proposedprotection scheme PSCAD/EMTDC is employed to build a20kV benchmark MV microgrid model [1] as shown in

    Figure 4. The simulation time step is 1S.

    In this microgrid system, four IIGs are connected to buses 2,4, 6 and 8; two microgrid loads (induction motors) are

    connected to buses 3 and 7. The lines are 20kV ABB XPLEcables [13]. The line models were derived using geometricand material cable data as shown in Figure 5. It should be

    noted that PSCAD does not take into account thesemiconducting layer presented in real cables. To simulate the

    cable through a large frequency range, the proper way is toadd semi-conducting screen to the conductor layer [14], sinceit shows good appearance of fault transients in the frequencyrange of 0~4MHz. The power of IIGs is provided by the ideal

    DC sources, which sufficiently emulates the presentmicroturbines and fuel cell systems, or any other source withstorage on the DC side [15].

    Four study cases are conducted to test the protection strategy:

    CASE 1 - Solid fault in zone (line 4-5); CASE 2 - Solid fault out of zone (line 1-4); CASE 3 - High resistance fault (Rf= 50 Ohms); CASE 4 - Fault with POW of 0(a), 5(b) and 90(c); CASE 5 - Close-up fault near bus4 on line 4-5(a), and on

    line 1-4(b).

    Figure 4: The travelling route of the fault transients within a

    radial microgrid

    In the microgrid model, CB1 and CB2 are open to form a

    islanded radial network, and each line is equipped withcurrent instruments at both ends. In practice, high bandwidthRogowski coil current transducers can be used as the current

    instruments. To simplify the test scenarios, all the faultsapplied are single phase-to-earth faults. The final results arelisted in Table 1 and Table 2. For CASE 4b the indicator

    waveforms of both main and backup methods are presented inFigure 6 and Figure 7. It can be seen that the main protectionis able to detect the fault with POW as low as 5, however, itis significantly affected by the zero fault inception angle. Inthis case, the backup protection using rate of the change of

    current detects the fault features within several ms.

  • 8/12/2019 Enhanced Protection for Inverter Dominated

    4/5

    Figure 5: Identical geometric cable parameters of 20kV ABB

    XPLE cable in PSCAD/EMTDC

    Figure 6: The detection of the initial traveling wavefrontsgenerated by fault with POW = 5 using the main protection

    Figure 7: The detection of abrupt change of current by faultwith POW = 5 using backup protection

    Test scenariosPeakvalue

    Polarity Result

    CASE 1Ins. 4-5 0.8248 1

    TripIns. 5-4 0.7162 1

    CASE 2 Ins. 4-5 0.3174 1 Non tripIns. 5-4 0.2834 1

    CASE 3Ins. 4-5 0.1005 1

    TripIns. 5-4 0.1339 1

    CASE4a (0)

    Ins. 4-5 N/A N/A BackupprotectionIns. 5-4 N/A N/A

    CASE4b (5)

    Ins. 4-5 0.0093 1Trip

    Ins. 5-4 0.0123 1

    CASE

    4c (90)

    Ins. 4-5 0.7645 1Trip

    Ins. 5-4 1.0183 1

    CASE

    5a

    Ins. 4-5 0.4290 1Trip

    Ins. 5-4 0.3371 1

    CASE

    5b

    Ins. 4-5 0.4290 1Non tripIns. 5-4 0.3371 1

    Table 1: Results using MMF based main protection

    Test scenariosPeakvalue

    Polarity Result

    CASE4a (0)

    Ins. 4-5 79.2653 1Trip

    Ins. 5-4 121.6911 1

    CASE

    4b (5)

    Ins. 4-5 71.5028 1Trip

    Ins. 5-4 134.1181 1

    Table 2: Results using Diff based backup protection

    A system consisting of the protection strategy stated above is

    composed of mainly three parts:1) Rogowski coil based current instruments connected

    through an integrator to a high speed data acquisitionboard with a sampling rate of 1MHz or more.

    2) Signal transforming block. The three phase currentsignals are transformed into small voltage signals

    before the band-pass filters. After sample-and-holdunits, the signals are transferred to digital signals byhigh speed ADC before processed by MMF algorithm

    and Diff calculation.3) Communication channels with capability of

    transporting signals time and polarity information,

    only activated when disturbance is detected.

    It is believed that with increasing availability and continuingcost reduction of modern data acquisition and processingtechnologies, high sampling rate requirements of the proposedscheme should not be prohibitive in the deployment of

    travelling wave based protection schemes in microgridenvironments. Further work will make an attempt to assessthe overall cost of this type of scheme through building of a

    laboratory prototype demonstrator.

    5 Conclusion

    Protection of inverter dominated microgrids is always a

    challenge. This paper proposes a hybrid approach consistingof the main protection based on travelling wave

    615.77 615.775 615.78 615.785 615.79 615.795 615.8-5

    0

    5

    10

    15x 10

    -3

    X: 615.8

    Y: 0.01229

    Current(kA)

    T(ms)

    X: 615.8

    Y: 0.009261

    i45

    i54

    615.6 615.7 615.8 615.9 616 616.1 616.2-50

    0

    50

    100

    150

    X: 615.8

    Y: 134.1

    dCurrent(kA)/dt(s)

    T(ms)

    X: 615.8

    Y: 71.5

    i45i54

  • 8/12/2019 Enhanced Protection for Inverter Dominated

    5/5

    measurements and backup protection based on the rate ofchange of current. The main protection scheme uses only theinitial travelling wavefronts. The wavefronts are extracted by

    the modified MMF algorithm. This protection is ultra-fast asit can detect a fault within several micro seconds. The dead

    zone dealing with low inception angle faults, which is themain shortcoming of all travelling wave based methods, isaddressed by the backup protection based on the rate ofchange of current. Simulation results using PSCAD/EMTDC

    show that this protection strategy is able to rapidly andreliably detect the fault regardless of fault impedance, faultposition or fault inception angle.

    References

    [1] N. El Halabi, M. Garca-Gracia, J. Borroy, and J. L.

    Applied

    Energy, vol. 88, no. 12, pp. 45634569, Dec. 2011.[2] ork

    Distribution - Part 2, 2009. CIRED 2009. The 20th

    International Conference and Exhibition on, 2009.[3]

    fault level in inverter-dominated net 20thInternational Conference and Exhibition on Electricity

    Distribution - Part 1, 2009. CIRED 2009, 2009, pp. 14.

    [4] N. Jayawarna, M. Barnes, C. Jones, and N. Jenkins, IEEE International Conference on

    , 2007,pp. 17.

    [5] IEEE Power Engineering SocietyGeneral Meeting, 2007, 2007, pp. 16.

    [6] T. David, S. Mark, C. David, C. Ed, W. Xiaohui, and

    - Test Engine as a Weapon III,Portsmouth Historic Dockyard, UK, 2009.

    [7]

    Managing the Change, 10th IET

    International Conference on Developments in PowerSystem Protection (DPSP 2010), 2010, pp. 14.

    [8] -high-speed directional protection of transmission lines using IEEE Transactions onPower Delivery, vol. 18, no. 4, pp. 1127 1133, Oct.2003.

    [9]

    mathematical morphology in power systems A IEEE Power & Energy Society , 2009, pp. 17.

    [10] Overcurrent Protection of Capacitor Banks Using IEEE Transactions onPower Delivery, vol. 26, no. 3, pp. 19721979, Jul.

    2011.

    [11] athematicalmorphology based phase selection scheme in digital

    Generation, Transmission and Distribution,

    IEE Proceedings-, vol. 152, no. 2, pp. 157 163, Mar.2005.

    [12] Classification and Faulted-Phase Selection Based on IEEE Transactionson Power Delivery, vol. 24, no. 2, pp. 552559, Apr.

    2009.[13] ABB,ABB XLPE Cable Guide rev. 1.[14]

    the attenuation behaviour of single- Generation, Transmission and Distribution, IEEProceedings-, vol. 152, no. 2, pp. 271276, Mar. 2005.

    [15] mous control of IEEE Power Engineering SocietyGeneral Meeting, 2006.