EXAMPLE OF HYDRONIC CONNECTION
EXTERNAL AIR TEMPERATURE [°C]
C.O
.P.
COP - AIRHEAT 48
CHARACTERISTICS
The new Air Heat family has been specificallydesigned to produce hot water up to 90°C. The newproduct combines efficiency with simplicity and theuse of the natural refrigerant CO2.
+10/+55
+10/+65
-10 0
2
3
4
5
6
10 20 30 40
+10/+75
� Plug and Play unit / Easy service / Robust design / Smooth operation� Compactness� Low noise due to special mounting of compressors and cladding protection� Dedicated control logic with COP optimization� User friendly with setting keyboard� Wev Server included for remote monitoring� Variable speed ventilators� Modulating water pump for sanitary applications� Standard design pressure 80 bar Lp side - 130 bar HP side
(a) AirHeat Nominal capacity QthNOM
:water inlet/outlet 10/65°C - Ambient 7°C
enexClima solutions
enexClima solutions
HOT WATER
AIR VENTVALVE
COLDWATER
BAL ANCINGVALVE
CONDENSATE
DRAINAGE
RELIEFVALVE
MODEL Design data WeightMax Power in [kW][kWt] / [ ] Max current in [A] [kg]
DimensionLxWxH [mm]
QthNOM
/COP(a)
AIR HEAT 18 15,8/3,9(a) 6 13 400 1100x800x1890
AIR HEAT 48 48,6/4,0(a) 17 35 750 2300x910x1850
AIR HEAT 24 25,5/4,0(a) 11 26 500 1450x910x1850
ENEX srl|Via Veneto, 12| 31088 Paese (TV)|ITALY|Tel. +39 0422 440429|Fax +39 0422 961021|mail:[email protected]| www.enex.itENEX srl|Via Veneto, 12| 31088 Paese (TV)|ITALY|Tel. +39 0422 440429|Fax +39 0422 961021|mail:[email protected]| www.enex.it
AIRHEATSERIESHigh efficiency heat pumps for sanitary water heating
AIRHEAT
Water TemperatureIN/OUT[°C]
18
+10/+55
-10COP
3,18
3,03
2,86
3,24
3,09
2,92
3,28
3,14
2,97
10,28
10,19
10,15
16,57
16,43
16,37
31,63
31,37
31,25
13,32
13,27
13,22
21,48
21,39
21,31
41,00
40,84
40,69
15,67
15,80
15,84
25,26
25,48
25,54
48,23
48,65
48,76
16,57
16,83
16,88
26,71
27,13
27,22
51,00
51,80
51,96
20,72
20,81
20,74
33,40
33,56
33,43
63,76
64,07
63,83
3,71
3,46
3,30
3,79
3,53
3,37
3,84
3,59
3,42
4,26
3,90
3,63
4,35
3,98
3,70
4,42
4,04
3,76
4,54
4,12
3,78
4,63
4,20
3,86
4,70
4,27
3,92
5,49
4,83
4,33
5,60
4,93
4,42
5,68
5,00
4,49
Qh [kW] COP Qh [kW] COP Qh [kW] COP Qh [kW] COP Qh [kW]
0 +7 +10 +20
+10/+65
+10/+75
+10/+55
+10/+65
+10/+75
+10/+55
+10/+65
+10/+75
24
48
PERFORMANCEAir ambient temperature[°C]
EXTERNAL AIR TEMPERATURE [°C]
Qh
PERFORMANCE
AIRHEAT 18
AIRHEAT 24
-10 0
0
10
20
30
40
50
60
70
10 20 30 40
AIRHEAT 48
APPLICATIONS
Where to use ?Whenever big quantities of hot water are needed and/or big peaks of absorptionare present.� Restaurants - Hotel - Canteens� Laundries - Residential Complex - Sport Centers� Hospitals - Agrifood industry - Gyms
How does it work?Transcritical cycle operated by CO2 is ideal for efficient use of the high tempera-ture glide of refrigerant for heating water from a low temperature.
OPTIONS
� Evaporator with anti-corrosion coating� Stratified water tank� Manometers panel� Electronic soft starter� Metallic mesh for protection of finned coil evaporator� EC ventilators
High pressure CO2 at high temperature circulates in one heat exchanger - singleor double wall- and heats up in a single passage (once-through) mains water,circulated with a variable speed pump so as to reach the set water temperaturein the most efficient way.
The high water temperature makes it possible to store it in a special vessel, soavoiding, as with normal heat pumps, to mix water at different temperatures.
By using this kind of water storage it is possible to operate the heat pump atnight time, taking advantage of lower energy costs.
HEAT PUMP
Absorbedheatfrom air
Supply water
Compressor1
Heat exchanger2
Double wall gas-cooler3
Expansion valve4
High efficiency pump5
Stratified storage tank6
1
STRATIFIEDSTORAGE TANK
32
4
6
5
M
AIRHEATSERIESHigh efficiency heat pumps for sanitary water heating
enexClima solutions
twater,in= + 10 ° Ctwater,out = +65°C