ENERGY STAR

Data Center Storage Version 1.0 Program Update

July 25, 2012

1

Page 2: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Introductions

RJ Meyers

EPA, ENERGY STAR

(202) 343-9923

[email protected]

2

John Clinger

ICF International

(202) 572-9432

[email protected]

Al Thomason

TBWC, LLC

(503) 708-7881

[email protected]

Page 3: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

ENERGY STAR Overview

• Federal government product and building labeling program – Established in 1992

– Shared between EPA and DOE

– Voluntary participation by private sector

– Federal agencies required to buy EStar products

• Label awarded for energy efficiency. – Top 25% of market

• Also promote better practices. – Power management

– Efficiency of buildings

• Save money, protect environment, add value to products.

• Influential brand recognized by over 80% of Americans

Page 4: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

ENERGY STAR in the Data Center

• Product specifications for – Servers: v2.0 under development

– Storage: v1.0 by early Q4

– UPS: v1.0 effective 8/1/12

• Development starting soon on – Large Network Equipment

– Data Center Cooling Equipment

• Provide information to users to control energy costs.

– Portfolio Manager (Buildings)

– Product labeling

– Power and Performance Datasheet (Products)

– Low-carbon IT Program: “Top 12 Data Center Efficiency Strategies”

Data Center

Building Metric

Labeled Products

Low-Carbon

IT Program

Page 5: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Typical ENERGY STAR Product

Specification Development • Recruit participants for spec development/revision process

– Manufacturers, retailers, utilities, industry orgs, interested individuals, etc.

• Try to use international standards for test method – May deviate or develop own testing if necessary

• Stakeholders provide market efficiency data – Used to set efficiency levels.

• Drafting process – Issue draft, then ~1 month comment period.

– All participants may comment, usually hold a stakeholder meeting to discuss.

– We use comments to revise next draft.

– Typically ~3 drafts.

• Publish final document – New product category effective immediately.

– Revisions effective 9 months later.

• Total development time ~12 months.

• Monitor market share of ENERGY STAR – Ideally starts at 25% for a new revision.

– Increases over time.

– If it becomes too large, launch revision of specification to bring levels back to 25%.

– Revisions happen every 2 – 5+ years, depending on product/market. 5

Page 6: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

ENERGY STAR Partners

• Sign a partnership agreement.

• Test products, adhere to labeling guidelines

• More information online:

http://www.energystar.gov/index.cfm?c=join.manuf_retail_agree

6

Page 7: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Why Should I Get Involved in

ENERGY STAR?

• Get your products labeled – Ensure that they can be purchased by federal

agencies.

• Gain national recognition – As energy and environmentally conscious business.

– Use ES logo in promotional materials. • Widely recognized

– Potential for ES awards such as Partner of the Year.

• Provide information and guidance in development of specifications – Ensure that our efficiency levels, product definitions,

scopes, and processes are appropriate.

7

Page 8: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Storage Specification Update

8

Page 9: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Review of ENERGY STAR Goals

Identify products and configurations that provide superior energy efficiency

Fairly and consistently represent energy

efficiency benefits of valid product

configurations to end users and

sales/fulfillment channels

Minimize testing/reporting

burden for ENERGY STAR partners

Page 10: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

History

• Kick-off: April 2009

• Draft 1: April 2010

• Draft 2: October 2011

• Draft 3: June 2012

• Draft 4: August 2012 (TBD)

• Final: November 2012

• Effective: Jan/Feb 2013 (3 months after final)

• Great deal of support from SNIA, TGG

• Input from EU, manufacturers, industry associations, government agencies.

10

Page 11: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Review of Storage Draft 3

• Product Scope

• Power Supply Requirements

• Product Family

• Energy Efficient Feature Requirements

• Information Reporting Requirements

• Performance Data Measurement and Output Requirements

• Testing / Test Method

• Additional Topics

11

Page 12: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Broad View of Storage Products

• SNIA Taxonomy

• Many different approaches to storage

• Differences in

– Performance

– Energy consumption

– End-uses

– Technology type

– And more!

12

Page 13: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Draft 3 Scope Overview

• Version 1.0

focuses on the

following

categories:

– Online 2*

– Online 3

– Online 4

13 “Table 4 –Online Classifications” taken from the SNIA Emerald™ Power Efficiency Specification V1.0

* Note: Additionally, all systems must contain RAID

controller with the storing product offering.

Systems which utilize server based RAID

controllers (JBODs) are excluded from the

ENERGY STAR scope

Page 14: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Draft 3 Scope Subtleties

• Scale-up vs. Scale-out

• Inclusion of Block I/O capable NAS

• Additional exclusions

– NAS File I/O-only Storage Products

– Blade Storage Products

– JBODs

– Object Storage Products

14

Page 15: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Power Supply Requirements

• Levels consistent with CSCI Silver

• PSU requirements only apply to PSUs that

power primary equipment

– Controllers and Drawers

• EPA encourages the use of ENERGY

STAR qualified products that can be used

in conjunction with qualified storage

products when possible

15

Page 16: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Workloads Recognized in Draft 3

• Transaction (IOPS/W)

• Streaming (Mbps/W)

• Capacity (GB/W)

• Compromise based on real-world

workloads

• Intended to reasonably cover most use

cases

16

Page 17: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Product Families in ENERGY

STAR

• Rather than test every configuration,

ENERGY STAR defines product families

• Test one or a few representative

models/configs

– Allows one or a few tests to represent many

products/configurations

• Reduce testing burden for highly

configurable products

17

Page 18: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Common Product Family

Attributes for Storage

– Made by the same manufacturer

– Be from the same model line or machine type

– Utilize the same model of Storage Controller

– Fall under the same SNIA taxonomy category

– Controller(s) contain equal or greater amount

of cache than the corresponding qualified

configuration

18

Page 19: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Difficulty in Defining a Product

Family

• Challenge:

• How do you define a representative model for storage when the products – Are hugely

configurable/flexible?

– Have very different energy efficiency profiles based on workload and hardware configuration?

– Can incorporate newer components (HDDs, etc.) over their lifetime?

19

Page 20: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Defining a Family in Practice

• Draft 3 proposal: – Optimal system testing: Test configurations optimized

for single, specific workload • Choose Transaction and/or Streaming, can add a Capacity

system.

• Test a range of systems sizes, since energy efficiency varies with size.

– System combinations: Allow for combinations of optimized systems to be labeled ENERGY STAR.

– Storage media substitutions: Allow for reasonable HDD, SSD substitutions to be made as drive technology improves.

20

Page 21: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Defining a Family in Practice

• System sizes tested: – Optimal: Manufacturer-defined optimal energy efficiency point.

– Maximum: 15% larger in storage device count than optimal configuration

– Minimum: 40% smaller in storage device count than optimal configuration

• System sizes qualified: – Maximum: 5% larger

– Minimum: 20% smaller

– Everything between max and min

– (Optional) Alternative Minimum: Beyond 20% smaller allowed with optional submission of additional physical data point(s) below the Minimum which:

• Are within 10% of the Optimal Configuration performance (Work/Watt),

• Applicable ONLY to Transaction or Streaming optimized configurations.

21

Page 22: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Optimal System Testing Points

22

Page 23: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Combinations

Greater flexibility of configuration and delivery of qualified ENERGY STAR systems

• System Combinations: – Combine optimal configurations using % allocation of Storage

Media from testing

– Applicable with all Optimization types (Transaction, Streaming, Capacity)

• And Block-I/O portion of NAS system

• Storage Media Substitutions: – Storage media performance changes rapidly

– Avoid burden of system retesting

– Limited to like storage media, and stated system performance must remain within 20% of original approved system

23

Page 24: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Energy Efficient Features

• Make available at least Parity RAID

• Revised COM approach

24

Page 25: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Recognized COM Features

• The following COMs are currently recognized by EPA – Thin Provisioning

– Data Deduplication

– Compression

– Delta Snapshots

• The COMS listed above will be verified using the verification procedures found in the SNIA EmeraldTM Power Efficiency Measurement Specification Version 1.0 (8/23/11)

• Will accept additional COMS as verification procedures become available in the future.

25

Page 26: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

COM Requirements

• EPA proposes to require a certain number

of recognized COMs be made available for

purchase, with this number determined by

the size of the system

26

Page 27: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Information Reporting

Requirements

• Active and Idle State Efficiency Disclosure

Requirements

• Power and Performance Datasheet

(PPDS)

• Data Measurement and Output

Requirements

• Test Method

27

Page 28: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Active and Idle State Efficiency

Disclosure Requirements

• EPA proposes to make data for all

required fields public for Version 1.0

28

Page 29: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Storage PPDS

• Power and Performance Datasheet

• For complex products, simple label won’t suffice

– Provide additional information about product

– Energy performance, etc.

• EPA will develop an online Storage PPDS widget

– Used to directly compare qualified systems

– Widget can be used on ENERGY STAR website or embedded in stakeholder websites

• PPDS information will be pulled from product certification submissions

29

Page 30: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Performance Data Measurement

and Output Requirements

• Power and temperature measurements can be made via: – Embedded measurement solutions

– External solutions • iPDUs

• Must meet accuracy reqts of embedded, make available for purchase to customers

– Will pursue embedded solutions only in v2.0.

• Note: Temperature measurements optional for v1.0 – Intend to pursue further in v2.0

30

Page 31: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Testing / Test Method

• Current test method references the SNIA EmeraldTM Power Efficiency Measurement Specification V1.0

• But, some proposed deviations in Draft 3:

– Online 2 Storage products must include RAID controller

– 24 hour Ready Idle Test

– COMs must be disabled during active testing

– Additional directions for testing NAS products w/ Block I/O

31

Page 32: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Remaining topics

• Power Modeling Presale Tool

• Development of updated SNIA tool

• Development of NAS file based energy

efficiency performance tool

32

Page 33: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Remaining Version 1.0 Timeline

• Draft 4 release in August

• Final Draft in late September / early October

• Final spec in October/November

33

Page 34: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

References and resources

• ENERGY STAR Data Center Storage

specification revision:

– www.energystar.gov/NewSpecs

– Select “Data Center Storage”

34

Reminder Written comments on Draft 3 due to EPA no later

than July 27, 2012. [email protected]

Page 35: ENERGY STAR Data Center Storage Version 1 Portland... · 2019. 12. 21. · ENERGY STAR Overview • Federal government product and building labeling program –Established in 1992

Thank You!

RJ Meyers

EPA, ENERGY STAR

(202) 343-9923

[email protected]

35

John Clinger

ICF International

(202) 572-9432

[email protected]

Al Thomason

TBWC, LLC

(503) 708-7881

[email protected]