Introduction to Danfoss 2010 | 1 | 1 One Company Focused on Climate & Energy Case-Study: Fakta Supermarkets Energy savings of Second Generation CO2 Refrigeration Systems

Energy savings of Second Generation CO2 Refrigeration ...hydrocarbons21.com/files/pdf_808.pdfIntroduction to Danfoss 2010 | 7 Energy consumption Fakta 0 2000 4000 6000 8000 10000 12000

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • Introduction to Danfoss 2010 | 1| 1

    One CompanyFocused on Climate & Energy

    Case-Study: Fakta SupermarketsEnergy savings of Second Generation CO2 Refrigeration Systems

  • Introduction to Danfoss 2010 | 2| 2

    Agenda

    11

    22

    33

    CO2 as a Refrigerant

    Fakta Case study

    Conclusion

  • Introduction to Danfoss 2010 | 3

    CO2 as refrigerant

    Non-toxic, Low GWP, Non-flammable

    Energy efficient under the right circumstances – however – observe the limits for outdoor temperature

    Systems and components have improved during the last decade — and since technology is new, compared to HFC systems, improvement is more rapid

    Subcritical CO2

    Transcritical & Subcritical CO2

    Transcritical & Subcritical CO2

    Subcritical CO2

    Efficiency Limits of Transcritical CO2

    Subcritical CO2

    Transcritical & Subcritical CO2

    Transcritical & Subcritical CO2

    Subcritical CO2Subcritical CO2

    Transcritical & Subcritical CO2

    Transcritical & Subcritical CO2

    Subcritical CO2

    Efficiency Limits of Transcritical CO2

    /Efficiency

    Pressure and Temperature

    GWP/ODP

    Low toxicity

    Non-flammable

    CO2

  • Introduction to Danfoss 2010 | 4| 4

    About Fakta: Fakta: Danish supermarket chain, part of Coop Danmark.

    The largest retail company in Denmark. Fakta has been working with lowering the energy consumption

    for the past 15 years, first on there HFC scroll packs and later on there transcritical packs

    More than 15 years of experience in data collection in order to optimise energy consumption and temp quality

    Fakta was one of the first movers on CO2

    More than 378 stores in Denmark. 61+ are transcritical CO2 systems of which 32 are 1st generation systems

    The goal is to install more than 40 CO2 2nd gen systems in 2011 in Denmark

    Cabinets, packs and gas cooler are standardized, but installation differs from site to site

  • Introduction to Danfoss 2010 | 5

    HFC-404AParallel scroll system with very good load adaptation

    • 148 in operation • 10 selected for study

    1st gen CO2 (2007)• Booster system• 2 compressors for MT• 2 compressors for LT• Mechanical gas by pass• First 10 selected

    2nd gen CO2 (2010)• Improvements

    - Inverter on 1 MT comp.- CCM gas by pass valve

    • First 10 selected

    Overview of Systems

  • Introduction to Danfoss 2010 | 6| 6

    More Details… System conditions are very similar:

    Capacity: 9 kW on LT and 28 kW on MT Equivalent opening hours The stores are identical on most parameters Installation differs (but pressure drops doesn’t) Geographically small area, no climate differences

    HFC: Parallel scroll system with very good load adaptation. 148 in operation

    CO2 1st generation (2007-2010) : Transcritical Booster Mechanical gas bypass. Piston Compressors, 2 for LT (33%/67%) &

    2 for MT (33%/67%) 32 systems in operation

    CO2 2nd generation (2010 -… ) : Transcritical Booster CCM gas bypass valve Piston Compressors, 2 for LT (33%/67%) &

    2 for MT (33%/67%). AKD Inverter on MT. 29+ systems in operation

    75 80 85 90 95 100 105 110 115 120Gas cooler pressure [bar]

    0.00

    0.25

    0.50

    0.75

    1.00

    1.25

    1.50

    Ref

    riger

    atin

    g ca

    paci

    ty [k

    W] a

    nd C

    OP

    [-] COP

    QE

    tE = -10 °C, tSH = 10 KtGC,OUT = 35 °C

    OPERATING CONDITION

  • Introduction to Danfoss 2010 | 7

    Energy consumption Fakta

    0

    2000

    4000

    6000

    8000

    10000

    12000

    mar-10 maj-10 jun-10 aug-10 sep-10 nov-10 jan-11 feb-11 apr-11 jun-11

    Time

    KW

    h/m

    onth

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    Am

    bien

    t tem

    pera

    ture

    [C]

    HCF (ref)

    Trans 1

    Trans 2

    Average temperature [℃]

    Results (10 stores average for each system type)

    82851

    109971

    89731

    kWh

    92%2nd gen CO2

    123%1st gen CO2

    100%HFC (reference)

    Index

  • Introduction to Danfoss 2010 | 8

    Solutions ready going forward

    CO2 supermarket systems minimize both direct and indirect emissions: CO2 systems in Fakta consumes less energy than

    the HFC packs used earlier

    2nd gen CO2 systems shows 20 % better energy performance than 1st gen CO2 systems

    Still room for improvement: New generations of valves, compressors and

    controls will show further improvements

    System architecture and control strategies will also improve

    Additional improvements in overall efficiency to be expected when heat recovery systems are implemented as part of the system.

  • Introduction to Danfoss 2010 | 9| 9

    Find more case stories at: http://www.danfoss.com/SolutionsReady/