74
NCC 2019 Energy Efficiency Commercial Buildings Premium office - Case Study 1 Supporting Document

Energy Efficiency - Commercial Buildings - Premium office - Case Study 1 … ·  · 2018-03-26Case Study: Energy Efficiency for Commercial Buildings Premium Office ... a mixed use

  • Upload
    lamdien

  • View
    234

  • Download
    6

Embed Size (px)

Citation preview

  • NCC 2019

    Energy EfficiencyCommercial Buildings

    Premium office - Case Study 1

    Supporting Document

  • Case Study: Energy Efficiency for Commercial Buildings Premium Office Case Study 1

    2018 Commonwealth of Australia and States and Territories of Australia

    The information in this document is intended to be used as guidance material only, and is in no way a substitute for the NCC and related State

    and Territory legislation. The General Manager of the Australian Building Codes Board (ABCB) Office, as agent for the Commonwealth of

    Australia and States and Territories of Australia, does not accept any liability howsoever arising from or connected to the use or reliance on any

    information in this publication to the maximum extent permitted by law. The information in this publication is provided on the basis that all persons

    accessing the information undertake responsibility for assessing the relevance and accuracy of the information to their particular circumstances.

    Australian Building Codes Board Page 1

    This document provides a case study for a premium office to assist in explaining the key

    changes proposed to the energy efficiency provisions for commercial buildings in the

    National Construction Code (NCC) 2019 Volume One.

    Case Study Summary

    Type of Compliance Solution:

    NCC References:

    Climate Zone:

    Building Classification:

    Construction Type:

    Combination of a Performance and a Deemed-To- Satisfy Solution

    NCC 2016 Volume One and NCC 2019 Volume One

    Public Comment Draft; JV3, DTS Provisions

    (Section J) and JV2 (Green Star)

    6

    Mixed Use: Class 2, 3, 5 and 7

    Mixed use space of premium office, 5 star hotel and

    residential apartments

    Background

    Under the Council of Australian Governments (COAG) 2015 National Energy Productivity

    Plan (NEPP), and with endorsement by the Building Ministers Forum, the Australian

    Building Codes Board (ABCB) was requested to update the energy efficiency provisions in

    NCC 2019.

    The NEPP is a COAG Energy Council agreed package of measures, which aims to

    improve Australias energy productivity by 40 per cent by 2030. Measure 31 of the NEPP

    forecasts strong productivity and emissions reduction benefits from revising the NCCs

    energy efficiency provisions, particularly for commercial buildings.

    On this basis, for NCC 2019 the ABCB was instructed to focus on increasing the

    stringency of the energy efficiency provisions for commercial buildings (the subject of this

    document).

    Introduction

    This case study is one of a series produced by the ABCB to support the Public Comment

    Draft of 2019 NCC. The purpose of this Case Study is to help illustrate the impact of the

    proposed changes to Section J of Volume One of the NCC. It shows what changes, if

    any, a building designed to meet the 2016 NCC provisions of Section J would need to

    make in order to comply with those of the NCC 2019.

  • Case Study: Energy Efficiency for Commercial Buildings Premium Office Case Study 1

    Australian Building Codes Board Page 2

    Note that any opinions on the impact of the proposed changes to Section J are expressed

    by the Case Study author. It should not be regarded as those of the ABCB nor an

    indication that the NCC will be changed to reflect these opinions.

    It should be further noted that part of the proposed changes to Section J in NCC 2019

    include changes in the calculation methodologies used to determine predicted energy use

    by components in a building. This can make direct comparison between the 2016 and

    2019 versions of a building solution difficult. Instances where this issue arises are

    highlighted in the text.

    Acknowledgements

    The ABCB acknowledges the assistance of:

    1. the Building Owners, Cbus Property, ISPT Pty Ltd and the Hotel Operator, for allowing their building to be used for the purposes of this case study, and for providing the necessary information for its completion; and

    2. the Department of the Environment and Energy for peer reviewing the content of this case study.

  • ABCB

    NCC 2019 SECTION J REVISIONS

    CASE STUDY: COLLINS ARCH DEVELOPMENT - 447 COLLINS STREET, MELBOURNE

    FEBRUARY 2018

  • This document may contain confidential and legally privileged information, neither of which are

    intended to be waived, and must be used only for its intended purpose. Any unauthorised copying,

    dissemination or use in any form or by any means other than by the addressee, is strictly prohibited.

    If you have received this document in error or by any means other than as authorised addressee,

    please notify us immediately and we will arrange for its return to us.

    PS107167-180222-JVM-NCC

    2019 447 Collins St Report

    Rev.2

    February 2018

    NCC 2019 Section J Revisions

    Case Study: Collins Arch Development - 447 Collins Street, Melbourne

    ABCB

    WSP

    Level 27, 680 George Street

    Sydney NSW 2000

    GPO Box 5394

    Sydney NSW 2001

    Tel: +61 2 9272 5100

    Fax: +61 2 9272 5101

    wsp.com

    REV DATE DETAILS

    01 1/02/2018 Draft for information

    02 22/02/2018 Including comments from ABCB

  • Page 3

    NAME DATE SIGNATURE

    Prepared by: Jerin Poovely/Brenda Kingston 22/02/2018

    Reviewed by: Katie Fallowfield 221/02/2018

    Approved by: Katie Fallowfield 22/02/2018

  • ...............................................

    .....................................

    DEFINITIONS AND ABBREVIATIONS

    ................................

    ..................................................................

    .........

    III

    ................................

    EXECUTIVE SUMMARY

    ................................

    .............................................................................

    ..........

    1

    ................................

    1 INTRODUCTION

    .....................

    ..................................................................

    ..................

    ...................................

    1

    .

    1.1 About the Building

    ................................................................

    .................................................................

    .............................................

    2

    ................................

    1.2 Architectural plans and Render of the building

    ...............................................................

    ......................................................................................

    4

    ........................

    1.2.1 Architectural plans

    ................................

    ...........................

    .......................................................................

    .........................................................

    4

    ................................

    1.2.2 Architectural Render

    ...............................................................................

    ..................................................................................

    ....................

    5

    ................................

    2 NCC ASSESSMENT SUMMARY

    ............................................................

    .......................................

    ..............................................................................

    8

    .................

    2.1 Part J1: Building Fabric

    ................................................................

    .....................

    ....................................................................

    8

    ...

    2.1.1 J1.3 Roof and Ceiling Construction

    ................................................................

    ..................................................................

    .........................................

    8

    2.1.2 J1.4 Roof Lights 92.1.3 J1.5 Wall-Glazing 102.1.4 J1.6 Floors 13

    2.2 Part J2: Glazing 13

    2.3 Air-Conditioning and Ventilation Systems 13

    2.3.1 Systems Descriptions and Control 132.3.2 Design Criteria 142.3.3 Building Systems Information 142.3.4 Equipment Overview 152.3.5 NCC 2016 DTS Compliance 172.3.6 NCC 2019 DTS Compliance 19

    2.4 Part J6: Artificial Lighting and Power 24

    2.5 J6.7/8 Lifts/Escalators and Moving Walkways 24

    2.6 Part J7: Heated Water Supply and Swimming Pool

    and Spa Pool Plant 25

    2.7 Other Measures Influencing NCC Compliance 25

    3 SIMULATION PARAMETERS 26

    3.1 Weather File 26

    3.2 Building Loads 26

    3.3 Building Geometry 27

    4 SIMULATION RESULTS FOR PERFORMANCE

    BASED CASE 29

    4.1 Thermal comfort assessment. 31

    TABLE OF CONTENTS

  • ...................................................

    ...............

    5

    ................................

    ECONOMIC ANALYSIS

    .................................................

    .............................................................

    33

    ..

    5.1

    ................................

    Building fabric and glazing

    ................................

    ....................................

    33

    ................................

    5.2 ................................Mechanical services................................

    .....................................................

    .....................

    33

    ................................

    5.3 electrical services 34

    6 CONCLUSIONS 35

    7 COMMENTARY ON THE NEW SECTION J

    PROVISIONS 2019 36

    7.1 Parts J1-J2 Building Fabric 36

    7.2 Part J5 Mechanical Services 37

    7.3 Part J6 Electrical Services 38

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page iii

    DEFINITIONS AND ABBREVIATIONS

    ABCB

    Building Fabric

    DB

    DTS

    ESD

    Faade Solar

    Admittance

    FCU

    HVAC

    JV3

    NCC

    PMV

    PV

    R-Value

    SHGC

    Solar Absorptance

    U-Value

    VRF/VRV

    Wall-Glazing

    WB

    WWR

    Australian Building Codes Board

    The basic building structural elements and components of a building

    including the roof, ceilings, walls and floors.

    (C) Dry Bulb. The temperature of air measured by a thermometer freely

    exposed to the air, but shielded from radiation and moisture

    Deemed-to-satisfy.

    Ecologically Sustainable Design

    The fraction of incident irradiance on externally facing wall-glazing

    construction that adds heat to a buildings space.

    Fan Coil Unit.

    Heating, Ventilation and Air-Conditioning. The mechanical

    Verification Method 3 of Section J of the National Construction Code.Reference Building Solution.

    National Construction Code

    Predicted Median Vote. A measure of the thermal perception of building

    occupants determined in accordance with ANSI/ASHRAE Standard 55.

    Photovoltaic, solar panels.

    (m2.K/W) The thermal resistance of a component or element, calculated by

    dividing its thickness by its thermal conductivity.

    Solar Heat Gain Co-efficient. The fraction of incident solar radiation

    admitted through a window, both directly transmitted and absorbed and

    subsequently released inward.

    The proportion of the total incident solar radiation that is absorbed by the

    material.

    (W/m2.K) The thermal transmittance of a component or element,

    calculated by dividing its thermal conductivity by its thickness.

    Variable Refrigerant Flow/Variable Refrigerant Volume

    The combination of wall and glazing components comprising the envelope

    of a building.

    (C) Wet Bulb. The temperature a parcel of air would have if it were

    cooled to saturation (100% relative humidity) by the evaporation of water

    into it, with the latent heat being supplied by the parcel.

    Window to Wall Ratio. The ratio of window to wall area for a faade.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 1

    EXECUTIVE SUMMARY

    WSP has been approached by the ABCB to test the draft revisions of the NCC 2019 Section J revision as it impacts upon

    NCC 2016 compliant buildings. This report outlines the impacts on the Collins Arch Development a mixed use high

    rise building which contains Class 2, 3, Class 5 and Class 7, incorporating residential, retail, hotel and office zones in

    Melbourne, VIC.

    The building was designed with Green Star in mind targeting a 5 star Green Star Design & As-Built v1.1 rating, and 5

    star NABERS rating for the commercial office. Due to these targets, the building is efficient by nature incorporating

    high efficiency air-conditioning systems with extensive shading and a high-performance faade. The building achieves

    NCC 2016 compliance through the verification method JV3 for building fabric (Parts J1 and J2) and DTS compliance for services resulting in a hybrid compliance solution.

    In order to comply with the Draft Section J Requirements for NCC 2019 through Verification Method JV3 no items on the building fabric were altered from those of the existing building (Parts J1 and J2). This results in a null cost impact.

    In order to achieve compliance with the proposed DTS requirements Section J of the NCC 2019, some minor changes

    need to be made to the HVAC and Ventilation systems. This includes doubling the thickness of refrigeration and heating

    hot water pipes. Although theoretically these changes can be made, it would require significant coordination work with

    the architect and other disciplines and there is no guarantee that the spatial requirements would be able to be

    accommodated.

    The lighting design for the Collins Arch project was found to be compliant with the proposed requirements of 2019 with

    the exception of the lighting power density in the hotel and commercial lobbies and hotel standard rooms. Compliance

    could be achieved in this instance through reducing the lighting installed and no cost addition would be expected,

    however the amenity of the spaces may be impacted. Alternatively, the project could seek to demonstrate compliance via a

    JV3 Verification Method for the building services, allowing the higher lighting power density in the hotel and commercial lobbies and the hotel standard rooms to be offset by higher performing spaces elsewhere in the building.

    The lifts proposed for the building are expected to be compliant with the 2019 requirements.

    The building and services were found to be generally in accordance with the new provisions of Section J of the NCC

    2019. Minimal cost impact is expected to make minor changes to the systems design to meet the more prescriptive

    provisions of Parts J5 and J6.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 2

    1 INTRODUCTIONWSP has been approached by the ABCB to test the draft revisions of the NCC 2019 Section J revision as it impacts upon

    NCC 2016 compliant buildings. This report outlines the impacts on the Collins Arch Development located at 447 Collins

    Street in Melbourne. This is a mixed use development (commercial offices, retail, hotel and residential).

    1.1 ABOUT THE BUILDING

    The proposed development at 447 Collins Street, Melbourne (site bounded by Collins St, William St, Market St and

    Flinders Lane) will comprise a mixed use space of basement carpark, premium quality commercial office, 5 star Hotel

    and residential apartments.

    A building overview is as per below:

    1 Hotel

    a 13 levels of hotel, which includes 12 levels of rooms with 294 hotel keys with 12,391 m2 of NLA

    b Hotel guest amenities including pool & spa, day spa, fitness centre on Level 14 and Level 15

    c Ballroom, pre- function areas, and restaurants located on Level 1 and Podium Levels

    d Prominent Ground Floor guest drop off and check-in lobby, with access from Porte-Cochere on Lower Ground

    and pedestrian access from Flinders Lane

    e Ground Floor lobby which includes check-in facilities, all day dining, hotel lounge & reception.

    2 Commercial

    a 24 levels of commercial office space, commencing at Level 4 up to Level 25. The office space has a NLA of

    49343 m2. The retail spaces located on the lower ground levels have a GLAR of 798 m2. The commercial

    component is targeting:

    i 5 star Green Star Design & As Built V1.1,

    ii 5 Star NABERS Energy (5.5 star NABERS aspiration), and

    iii WELL Building Certification

    b Lower ground level commercial end-of-trip facilities

    3 Residential

    a 24 levels of high end residential apartments, commencing at Level 16 through to Level 39

    b Residential apartment of 1-3 bedrooms including balcony & terraced areas

    c Ground Floor residential lobby

    The proposed development was designed with Green Star in mind to target a Design & As-Built certification as listed in

    detail in the Table below (Refer to Table 1.1), due to this the building is efficient by nature incorporating a mixed mode

    ventilation system with extensive shading and a high-performance faade. The building achieves NCC 2016 compliance

    through the Verification Method JV3 for building fabric (Parts J1 and J2) and DTS compliance for services resulting in a hybrid compliance solution.

    Table 1.1 below outlines further information about the proposed project.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 3

    Table 1.1 Collins Arch Building Information

    BUILDING NAME AND

    ADDRESS

    COLLINS ARCH DEVELOPMENT, 447 COLLINS STREET, MELBOURNE,

    3000

    Owners Cbus Property, ISPT Pty Ltd, and the Hotel Operator

    Developer Cbus Property

    Builder Multiplex Pty Ltd

    Architect Woods Bagot and SHoP Architects, and Hachim for the Hotel fitout

    Services consultants NDY Mechanical, VT, Hydraulic

    WSP - ESD, Electrical and Fire protection

    Leasing agent N/A

    Client development manager Victor Istanto, Cbus Property

    End users Various (Including multiple residential owners, commercial and retail tenants, and

    the hotel operator)

    Building classification Class 2, 3 5 and Class 7

    Climate zone 6 Melbourne Airport

    Deemed building hours of

    operation.

    Daytime for Class 5, and potentially 24 hours for most other spaces. Table 2a (Class

    3 simulation profile) used in simulation.

    Size GFA: circa 173,000m2

    Number of stories 49 (5 basement/semi below ground, 44 above)

    Completion date December 2019. Construction commenced mid 2017.

    Construction cost In excess of $1 billion

    Proposed or achieved

    environmental certifications and

    status

    Residential

    - Green Star Design & As-Built v1.1 4 Star

    Hotel

    - Green Star Design & As-Built v1.1 4 Star

    Office

    - WELL Building Certification

    - Green Star Design & As-Built v1.1 5 Star

    - 5 star NABERS Energy

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 4

    1.2 ARCHITECTURAL PLANS AND RENDER OF THE

    BUILDING

    1.2.1 ARCHITECTURAL PLANS

    Figure 1.1 Floor Plan - Collins Street. The site is bound by Collins Street to the North, Market Street (East), William

    Street (West) and Flinders Lane (South)

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 5

    1.2.2 ARCHITECTURAL RENDER

    Figure 1.2 Public Park located on site situated on the corner of Collins Street and Market Street

    Figure 1.3: Commercial Lobby - Situated on Collins Street Level

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 6

    Figure 1.4: Level 14/15 Hotel Amenities - Pool

    Figure 1.5:

    Hotel Porte Cochere - located Flinders Lane

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 7

    Figure 1.6: Hotel Lobby Area - Entrance through Flinders Lane

    Figure 1.7: Hotel - Standard Room Layout

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 8

    2 NCC ASSESSMENT SUMMARYThe NCC assessment comparing compliance with NCC 2016 and NCC 2019 is detailed below divided into Part J1

    through J7 and subsections. Each section assesses separately the compliance requirements and methods used for both

    NCC 2016 and 2019 and the cost and design impact involved in upgrading the provisions to comply with NCC 2019 if

    required.

    2.1 PART J1: BUILDING FABRIC

    The following sections detail the compliance criteria for NCC 2016 and NCC 2019 for the building fabric, identifying whether the criteria are achieved through a deemed-to-satisfy (DTS) solution or Verification Method for both NCC 2016 and NCC 2019.

    2.1.1 J1.3 ROOF AND CEILING CONSTRUCTION

    The following section details the requirements and compliant parameters required for ceiling and roof construction as

    seen below in Table 2.1.

    Table 2.1 Collins Arch - NCC Roof and Ceiling Compliance Comparison

    NCC 2016 COMPARISON NCC 2019 COMPARISON

    NCC DTS Requirements R-Value 3.2 m2.K/W

    Solar absorptance 0.4R-Value 3.2 m2.K/W

    Solar absorptance 0.4

    Total System

    Values

    Achieved

    Simple, unbridged

    calculation

    U Value: 0.31 W/m2.K

    R-Value: 3.2 m2.K/W

    Solar absorptance 0.4As per NCC 2016 Parameters left

    Allowing for the

    effect of thermal

    bridging

    U Value: 0.33 W/m2.K

    R-Value: 3.0 m2.K/W

    Solar absorptance 0.4

    NCC DTS Compliance Achieved NCC 2016 DTS provisions MET NCC 2019 DTS provisions NOT MET

    by existing building

    Compliance Method Achieved through JV3 Achieved through JV3 without

    modification of existing building

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 9

    For a more detailed comparison of the requirements and compliant parameters see Appendix A.

    Figure 2.1 Typical commercial roof and ceiling

    Figure 2.2 Typical Residential and Hotel roof / ceiling

    In order to comply with the Draft Section J Requirements for NCC 2019 through verification method JV3 no items were

    altered from those existing building. This results in a null cost impact.

    2.1.2 J1.4 ROOF LIGHTS

    In order to comply with the Draft Section J Requirements for NCC 2019 through verification method JV3 no items were

    altered from those existing building. No Roof lights exist on the project. This results in a null cost impact.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 10

    2.1.3 J1.5 WALL-GLAZING

    The following section details the requirements and compliant parameters required for walls for NCC 2016 and NCC 2019

    as seen below in Table 2.2. This table also details the Wall-Glazing requirements for NCC 2019 using method 1.

    Table 2.2 Collins Arch NCC Wall Compliance Comparison

    NCC 2016 COMPARISON NCC 2019 COMPARISON

    NCC DTS Requirements External Walls:

    R-Value 2.8 m2.K/W

    Solar Absorptance 0.6

    Internal Envelope Walls:

    R-Value 1.8 m2.K/W

    All Walls

    R-Value 1.0 m2.K/W

    Wall-Glazing

    Class 3 Zones

    Orientations with a WWR > 20%:

    U-Value 1.1 W/m2.K

    Faade solar admittance 0.07

    Solar absorptance: 0.6

    Orientations with a WWR 20%:

    R-Value 2.8 m2.K/W

    Faade solar admittance 0.07

    Solar absorptance: 0.6

    Class 5, 6 Zones

    Orientations with a WWR > 20%:

    U-Value 2.0 W/m2.K

    Faade solar admittance 0.13

    Solar absorptance: 0.6

    Orientations with a WWR 20%:

    R-Value 1.4 m2.K/W

    Faade solar admittance 0.13

    Solar absorptance: 0.6

    Total Wall

    System Values

    Achieved

    Simple, unbridged

    calculation

    External Walls:

    U-Value: 0.38 W/m2.k Solar Absorptance 0.6

    Internal Envelope Walls:

    U-Value: 1.67 W/m2.kAs per NCC 2016 Parameters left

    Allowing for the

    effect of thermal

    bridging

    External Walls:

    U-Value: 0.45 W/m2.k Solar Absorptance 0.6

    Internal Envelope Walls:

    U-Value: 2.0 W/m2.k

    Total Wall-Glazing System Values

    Achieved

    N/A U value: 1.35 3.5 W/m2.kFaade solar admittance: 0.09 0.25

    WWR: 0% 98% (Orientation dependant)

    NCC DTS Compliance Achieved NCC 2016 DTS provisions NOT

    MET

    NCC 2019 DTS provisions NOT MET by

    existing building

    Compliance Method Achieved through JV3 Achieved through JV3 without

    modification of existing building

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 11

    Figure 2.3 Typical wall constructions; Top External wall, Bottom Internal partition.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 12

    The main glazing in Collins Arch is as below:

    Mid-pane glazing parameters

    U value: 1.4 W/m2.K

    SHGC: 0.28

    Typical whole of system window parameters

    U Value: 2.5 W/m2 K

    SHGC: 0.25

    For further detail on wall and glazing elements including a breakdown of WWR per orientation see Appendix A.

    In order to comply with the Draft Section J Requirements for NCC 2019 through verification method JV3 no items were

    altered from those of the existing building. This results in a null cost impact.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 13

    2.1.4 J1.6 FLOORS

    The following section details the requirements and compliant parameters required for walls for NCC 2016 and NCC 2019

    as seen below in Table 2.3.

    Table 2.3 447 Collins Arch - NCC Floor Comparison

    NCC 2016 COMPARISON NCC 2019 COMPARISON

    NCC DTS Requirements Slab on Ground No requirement

    Suspended Slab R-Value 2.0 m2.K/W

    R value 2.0 m2.K/W 1

    Total System

    Values

    Achieved

    Simple, unbridged

    calculationTypical Floor U Value: 2.5 W/m2.K

    R-Value: 0.4 m2.K/W

    As per NCC 2016 Parameters left

    Allowing for the

    effect of thermal

    bridging and using

    CIBSE Guide A

    Section 3.5

    Basement Floor U Value: 0.43 W/m2.K

    R-Value: 2.3 m2.K/W

    Slab on Ground U Value: 0.48 W/m2.K

    R-Value: 2.1 m2.K/W

    Suspended Floor U Value: 2.5 W/m2.K

    R-Value: 0.4 m2.K/W

    NCC DTS Compliance Achieved NCC 2016 DTS provisions NOT MET NCC 2019 DTS provisions NOT MET

    by existing building

    Compliance Method Achieved through JV3 Achieved through JV3 without

    modification of existing building

    1 To be determined in accordance with Section 3.5 of CIBSE Guide A including the effect of ground or subfloor space

    In order to comply with the Draft Section J Requirements for NCC 2019 through verification method JV3 no items were

    altered from those of the existing building. This results in a null cost impact.

    2.2 PART J2: GLAZING

    This section has been removed in NCC 2019, glazing compliance is now demonstrated in Part J1.5. See J1.5 Wall-

    Glazing above.

    2.3 AIR-CONDITIONING AND VENTILATION SYSTEMS

    2.3.1 SYSTEMS DESCRIPTIONS AND CONTROL

    The following section describes, based on the information available, the air conditioning and ventilation systems serving

    the development. This section also describes the arrangements for time of use control, economy cycle control, outside air

    quantity control.

    The development comprises of commercial levels, residential units, hotel room & amenities, and retail shops. Air

    conditioning system is provided via various systems including cooling towers, water cooled chillers, gas fired boilers, air

    cooled packaged AC units, VAV system, VRV split system etc.

    Various areas are served by a mixed mode air conditioning system, where natural ventilation is employed when outdoor

    conditions are suitable. The respective AHU controls were specified to include control for:

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 14

    CO2 monitoring and control system capable of adjusting the outside air rates, and

    To operate with an economy cycle via minimum and economy cycle outside air motorised dampers.

    2.3.2 DESIGN CRITERIA

    The following section describes, based on the information available, the design criteria for the development (what the

    system is designed to achieve).

    Air Design Conditions External Conditions

    - Summer: 35C DB / 21C WB

    - Winter: 4C DB

    Internal Conditions

    - Cooling: 24C DB 1.5C

    - Heating: 21C DB 1.5C

    Refer to specification for detailed conditions for all spaces and occupancies

    Heat Gains Refer to specification

    2.3.3 BUILDING SYSTEMS INFORMATION

    The following tables list the relevant documentation which demonstrates high-level system functional schematics, and

    where relevant information can be found. Where available, the documentation shows plant, key system elements, pipe

    and duct sizes, pipe and duct insulation, heat recovery, economy cycle.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 15

    NAME REFERENCE KEY INFORMATION

    Air Schematic M-SC-021 to M-SC-026 Plant & key system elements

    Economy cycle and heat recovery

    Chilled Water and Condenser Water

    Schematic

    M-SC-001 to M-SC-006 Plant & key system elements

    Heating Hot Water and Gas Piping

    Schematic

    M-SC-011 to M-SC-016 Plant & key system elements

    Floor Plan Layouts NDY DD/Tender Drawings dated

    26.05.17

    Duct sizes and insulation

    Key system elements

    Specification T-03 Updated Final Design

    Development Issue

    Overall system elements and

    equipment schedules

    2.3.4 EQUIPMENT OVERVIEW

    The following section identifies, based on the information available, the chiller, water heater, fan and pump selections,

    including fuel source (e.g. for heating, cooling equipment).

    TYPE NAME DESCRIPTION FUEL SOURCE

    Water-Cooled Chiller CH-CO-B3.01 to CH-CO-

    B3.03, & CH-HT-B3.01 to

    CH-HT-B3.02

    Water-cooled Centrifugal

    chiller with VSD & active

    harmonic filters

    Electric

    Water-Cooled Packaged AC

    Unit

    PAC-RE-33.01 to PAC-RE-

    33.06, PAC-RE-34.01

    Water-Cooled Packaged unit

    serving various residential

    spaces

    Electric

    Air-Cooled Packaged AC

    Unit

    PAC-RE-28.01 Reverse cycle heat recovery

    air handling unit

    Electric

    Chilled Water Pump CHWP-CO-B3.01 to

    CHWP-CO-B3.03

    Office chilled water system Electric

    Heating Hot Water Pump HHWP-CO-40.01 to HHWP-

    CO-40.03

    Commercial heating hot

    water system

    Electric

    Cooling Tower CT-CO-41.01 to CT-CO-

    41.04, CT-HT-41.01 to CT-

    HT-41.02, CT-RE-41.01 to

    CT-RE-41.02, TCT-CO-

    41.01 to TCT-CO-41.03

    Condenser water system Electric

    Boilers B-CO-40.01 to B-CO-40.03,

    B-HT-02.01 to B-HT-02.02,

    B-RE-40.01 to B-RE-40.02

    Condensing Boiler Natural Gas

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 16

    Air Handling Unit All AHUs in NDY

    Specification T-03

    Air Handling Units Electric

    Fan Coil Unit All FCUs in NDY

    Specification T-03

    Fan Coil Units Electric

    Split Systems All split units in NDY

    Specification T-03

    AC Split Units Electric

    Fans Refer to Appendix Miscellaneous ventilation

    fans

    Electric

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 17

    2.3.5 NCC 2016 DTS COMPLIANCE

    The following section describes the relevant NCC 2016 applicable to the case study. Each clause is assessed against the

    case-study for compliance and is indicated as Compliant or Non-Compliant.

    NCC 2016 CLAUSE DESCRIPTION DESIGN COMPLIANCE

    ASESSMENT

    J3.5 Exhaust Fans An exhaust fan must be fitted with a

    sealing device such as a self-closing

    damper, filter or the like when serving

    conditioned spaces.

    Compliant

    J5.2 Air-Conditioning Systems

    Control An air-conditioning system must be able

    to turn off when the served area is

    unoccupied.

    Compliant

    Multi-zone systems must be able to:

    Control each zone temp

    independently

    Not mix heated and cooled air to

    generate desired temp

    Not re-heat supply air more than 7.5K

    Compliant

    Economy cycle must be provided:

    Climate zones 2or3 for >50kWr

    systems,

    Climate zones 4,5,6,7or8 for >35kWr

    systems

    Compliant

    Water flow must be able to be stopped to

    heaters, chillers, or coils not operating

    Compliant

    When supply air is able to be varied, fans

    must be variable speed (excluding

    packaged units)

    Compliant

    For sole-occupancy units in a Class 3

    building, units must not operate if external

    door or the like are open for more than 1

    minute.

    Compliant

    Motorised outside air and return air

    dampers must close if a system is

    deactivated

    Compliant

    Compliance must not hinder smoke hazard

    management or ventilation requirements

    Compliant

    Fans Must comply with Specification J5.2a

    (include in appendix)

    Potential Compliance

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 18

    - Some scheduled fan powers

    exceed fan efficiency

    requirements; however,

    cannot confirm without

    workshop drawings of

    selected fans.

    Pumps Pump powers must comply to Table 5.2. Compliant

    Pumps >3kW pump power and >2L/s

    must be capable of varying its speed in

    response to varied load

    Compliant

    Spray systems for evaporative condensers

    must not use >150W per L/s of spray

    water

    N/A

    Insulation Ductwork must be insulated as per

    Specification J5.2b.

    Compliant

    Piping and ancillaries must be insulated as

    per Specification J5.2c.

    Compliant

    Space Heating Heaters must comply with Specification

    J5.2d.

    Compliant

    Energy Efficiency Ratios Refrigerant chillers and packaged air

    conditioners must comply with

    Specification J5.2e.

    Compliant

    Time Switches Air conditioners >10kWr and heaters

    >10kW must be provided with time

    switch control as per Specification J6.

    Not applicable to a single sole-occupancy

    unit with a Class 2, 3 or 9c building, a

    Class 4 part of a building, or 24hr

    occupancies.

    Compliant

    J5.3 Mechanical Ventilation

    Systems

    The mechanical ventilation system must

    be capable of being deactivated when part

    of the building served by the system is not

    occupied

    Compliant

    J5.4 Miscellaneous Exhaust

    Systems

    Misc. exhaust systems >1000L/s of

    variable demand must be able to stop the

    motor and be variable speed.

    Not applicable to a single sole-occupancy

    unit with a Class 2, 3 or 9c building, a

    Class 4 part of a building, or 24hr

    occupancies, or when exhaust air is

    required to balance outdoor air ventilation

    rates.

    Compliant

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 19

    2.3.6 NCC 2019 DTS COMPLIANCE

    The following section describes the relevant NCC 2019 applicable to the case study. Each clause is assessed against the

    case-study for compliance and is indicated as Compliant or Non-Compliant. Where non-compliant, modifications to

    the design are considered, and then re-assessed for compliance.

    NCC 2019 CLAUSE DESCRIPTION DESIGN

    COMPLIANCE

    ASESSMENT

    MODIFICATIONS

    REQUIRED FOR

    COMPLIANCE

    J3.5 Exhaust Fans An exhaust fan must be sealed with a

    device such as a self-closing damper,

    filter or the like when serving

    conditioned spaces. The penetrations

    must also be sealed.

    Compliant N/A

    J5.2 Air-Conditioning

    System Control

    An air-conditioning system must be able

    to turn off when the served area is

    unoccupied.

    Compliant N/A

    Multi-zone systems must be able to:

    Control each zone temp

    independently

    Not mix heated and cooled air to

    generate desired temp

    Not re-heat supply air more than

    7.5K

    Compliant N/A

    Economy cycle must be provided in

    accordance with Table J5.2 for climate

    zones 4, 5, 6, 7, and 8 unless humidity

    control is required

    Compliant Economy cycle might be omitted for

    several air-conditioning units where

    previously required in NCC2016

    (FCU-HT-02.01, FCU-HT-01.05 &

    FCU-HT-01.06) as the air flow is

    lower than the minimum required in

    Table J5.2. Potential cost & spatial

    savings.

    Water flow must be able to be stopped to

    heaters, chillers, or coils not operating

    Compliant N/A

    When supply air is able to be varied,

    fans must be variable speed (excluding

    packaged units)

    Compliant N/A

    For sole-occupancy units in a Class 3

    building, must not operate of external

    doors are open for more than 1 minute.

    Compliant N/A

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 20

    NCC 2019 CLAUSE DESCRIPTION DESIGN

    COMPLIANCE

    ASESSMENT

    MODIFICATIONS

    REQUIRED FOR

    COMPLIANCE

    Control components that are responsible

    for the delivery of comfort conditions

    must be able to use direct signals to

    regulate the operation of the central

    plant

    Compliant N/A

    Minimum control dead band of 1C

    except where a smaller range is required

    for specialised applications

    Compliant N/A

    Have balancing dampers and valves to

    ensure design flow at each component is

    not exceeded

    Compliant N/A

    Each independently operating space

    >1000m and every separate floor of the

    building must have provision to

    terminate flow independently, sufficient

    to allow for different operating times

    Compliant Motorised dampers not provided to

    every riser take-off at every floor

    served for the hotel tempered outside

    air supply. The outside air balances the

    toilet exhaust to the hotel rooms. The

    dampers would be required to shut

    when the given floor is unoccupied.

    All floors considered occupied

    The current hotel central toilet exhaust

    system does not allow for shut off to

    individual floors. The assumption

    made for hotels is that all floors are

    considered occupied (although there

    will be individual unoccupied rooms),

    thus toilet exhaust will be running for

    each floor, and make up air (via

    outside air) is required to satisfy Part

    F4.

    Have automatic variable temperature

    operation of heated and chilled water

    circuits

    Compliant N/A

    Motorised outside air and return air

    dampers must close if a system is

    deactivated

    Compliant N/A

    Compliance must not hinder smoke

    hazard management or ventilation

    requirements

    Compliant N/A

    Have control sequences to prevent

    operation of opposing heating and

    cooling modes.

    Compliant N/A

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 21

    NCC 2019 CLAUSE DESCRIPTION DESIGN

    COMPLIANCE

    ASESSMENT

    MODIFICATIONS

    REQUIRED FOR

    COMPLIANCE

    Air conditioners >2kWr and heaters

    >1kW must be provided with time

    switch control. Control must be capable

    of switching on/off electric power at

    variable pre-programmed times and on

    variable pre-programmed days.

    Not applicable to a single sole-

    occupancy unit with a Class 2, 3 or 9c

    building, a Class 4 part of a building, or

    24hr occupancies.

    Compliant N/A

    J5.3 Mechanical

    Ventilation System

    Control

    A mechanical ventilation system must

    be able to turn off when the served area

    is unoccupied.

    Compliant N/A

    Either energy reclaiming systems as

    required by Table J5.3 OR demand

    controlled ventilation in accordance with

    AS1668.2 will be provided

    Compliant N/A

    Exhaust systems with air flow rates of

    more than 1000 L/s must be capable of

    stopping the motor [except for a sole-

    occupancy unit in a Class 2, 3, or 9c

    building]

    Compliant N/A

    A time switch must be provided to

    control a mechanical ventilation system

    >1000 L/s

    Compliant N/A

    J5.4 Fan Systems[1] Fans >1000 L/s must be provided with

    variable speed control

    Non-Compliant GEF-CO-29.01 (3000L/s) Lift Motor

    Room will require fan with VSD

    Fans must operate at an efficiency

    greater than or equal to the formula in

    J5.4(b)

    Potential

    Compliance

    Refer to appendix. Actual fan

    efficiencies of installed models

    unknown. Several new fan selections

    were made to check possible

    compliance. Shop drawing from

    contractor required to confirm

    compliance

    Average pressure drop in the longest run

    of all straight sections of rigid ductwork

    must not exceed an average of 1 Pa/m

    Compliant N/A

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 22

    NCC 2019 CLAUSE DESCRIPTION DESIGN

    COMPLIANCE

    ASESSMENT

    MODIFICATIONS

    REQUIRED FOR

    COMPLIANCE

    Pressure drop across coils and filters

    must not exceed values as per Table

    J5.4d, Table J5.4e

    Potential

    Compliance

    Specification states air pressure drop

    not exceeding 100Pa for hot water

    heating coils. Final equipment

    selection required to confirm

    compliance

    Airside components may not exceed

    pressure drops as specified

    Potential

    Compliance

    Final airside component schedule and

    shop drawings required to confirm

    compliance

    J5.5 Ductwork

    Insulation

    Ductwork must be insulated as per Table

    J5.5.

    (include in appendix)

    Compliant N/A

    J5.6 Ductwork

    Sealing

    Ductwork must be sealed in compliance

    with AS 4254 parts 1 and 2

    Compliant N/A

    J5.7 Pumps Pumps must operate at an efficiency

    greater than or equal to the formula in

    J5.7(c)

    Potential

    Compliance

    Design operating head of pumps and

    final pump selection by Contractor

    required to perform calculation of

    minimum required pump efficiency.

    Pipework must not exceed pressure

    drops nominated in Table J5.7b thru

    J5.7e.

    Non-Compliant Specification allows for maximum

    pressure drop of 600 Pa/m and 2.5 m/s.

    Some pipework will need to be

    upsized to reduce pressure drops of

    straight length piping.

    J5.8 Pipework

    Insulation

    Piping must be insulated as per Table

    J5.8a.

    Non-Compliant High temperature refrigerant piping

    and heating hot water piping will need

    to be nominally tripled in thickness.

    J5.9 Space Heating Electric heaters must be in compliance

    with Table J5.9

    N/A N/A

    Water heaters in air conditioning system

    must:

    if rated to consume 500 MJ/hour of

    gas or less, achieve a minimum

    gross thermal efficiency of 86%; or

    if rated to consume more than 500

    MJ/hour of gas, achieve a minimum

    gross thermal efficiency of 90%.

    Compliant N/A

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 23

    NCC 2019 CLAUSE DESCRIPTION DESIGN

    COMPLIANCE

    ASESSMENT

    MODIFICATIONS

    REQUIRED FOR

    COMPLIANCE

    J5.10 Refrigerant

    Chillers

    Chillers must be in compliance with

    energy efficiencies specified in Table

    J5.10a and b.

    Compliant Water cooled chillers compliant based

    on current chiller schedule. subject to

    final selection by Contractor

    J5.11 Packaged air-

    conditioning

    equipment

    Packaged air conditioners 65kWr,

    minimum energy efficiency ratio of 4.0

    for water cooled equipment and 2.9 for

    air cooled equipment.

    Compliant N/A

    J5.12 Fan motor power of cooling towers,

    evaporative condensers, or closed circuit

    coolers must not exceed allowances in

    Table J5.12

    Potential

    Compliance

    Fan motor power not indicated on

    specification schedule. Compliance

    subject to final cooling tower &

    evaporative condenser selection by

    Contractor.

    [1] Fan systems and airside components can be designed to achieve compliance during the design phase. However, thefinal equipment will be selected and installed by the Contractor during construction phase. Contractors will need to

    confirm compliance based on actual equipment installed.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 24

    2.4 PART J6: ARTIFICIAL LIGHTING AND POWER

    The following documents have been referenced to assess compliance with the NCC 2016 and 2019.

    Collins Arch Specialist lighting drawings and schedules, dated May 2017 through to January 2018

    Collins Arch lighting schedules and drawings Design Development Tender issue, dated December 2016

    Only discreet lighting areas were assessed against Part J. These included areas with Architectural Lighting considered

    the most likely to fail compliance. We understand that when implemented, the NCC 2019 proposed clauses J6.2 a and b,

    can be area-weighted over the entire development. The following table describes the key information within these

    documents which refer to the NCC and non-compliances to the DTS which have been found. Refer to Appendix D for

    the lighting power assessment in the selected spaces

    NCC 2019

    RELEVANT

    CLAUSES

    NCC 2016 COMPLIANCE NON-COMPLIANCES TO THE NCC 2019

    J6.2 Table 6.2a

    J6.2 Table 6.2b

    J6.2 Table 6.2c

    J6.3f

    J6.3g

    J6.3h

    J6.7

    Spec J6.4b (v)

    J8.3c

    Compliant No non-compliance of lighting power density

    for the following space types tested:

    - Hotel Lobby

    - Hotel Standard room

    - Commercial Lobby

    For further calculations refer to Appendix D to see a comparison of LPD (lighting power density) for 447 Collins Street.

    2.5 J6.7/8 LIFTS/ESCALATORS AND MOVING WALKWAYS

    A total of 25 lifts and 1 dumb waiter that are present in the building.

    The NCC 2016 contained no requirements for lifts/escalators and moving walkways, therefore the table below describes

    the compliance with the 2019 provisions.

    NCC 2019 CLAUSE COMMENT

    J6.7 (a) lifts must be configured to ensure artificial lighting

    and ventilation in the car are turned off when it is unused

    for 15 minutes.

    Compliant. Specification requires lighting and ventilation

    to automatically switch off 5 minutes after last run.

    J6.7 (b) idle and standby energy performance Not explicitly specified however the selected equipment is

    expected to be Compliant

    J6.7 (c) energy efficiency class Not explicitly specified however the selected equipment is

    expected to be Compliant

    A total of 4 escalators are present in the building.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 25

    NCC 2019 CLAUSE COMMENT

    J68 (a) Escalators must slow to between 0.2m/s and

    0.05m/s when unused for 15 minutes.

    The slow down speed not explicitly specified however the

    variable speed drive and control strategy for slow down is

    specified therefore the selected equipment is expected to be

    Compliant or able to be compliant at no cost.

    2.6 PART J7: HEATED WATER SUPPLY AND SWIMMING

    POOL AND SPA POOL PLANT

    There are two swimming pools present in the building. One for the hotel, and one for the residential apartments.

    NCC 2019 CLAUSE COMMENT

    J7.3 (a) heating source for pool Compliant. Gas fired boiler of sufficient efficiency

    specified.

    J7.3 (b) heat loss reduction. A pool cover and time switch

    on heating source required.

    To be confirmed.

    J7.3 (c) time switch on circulation pump To be confirmed.

    J7.3 (e) programmable time switch where required. To be confirmed.

    J7.3 (f) pipework insulation To be confirmed

    2.7 OTHER MEASURES INFLUENCING NCC COMPLIANCE

    In order to achieve compliance with the proposed requirements Section J of the NCC 2019, some changes need to be

    made to the HVAC and Ventilation systems. Many of these changes are related to sizing of plant and equipment.

    Although theoretically these changes can be made, it would require significant coordination work with the architect and

    other disciplines and there is no guarantee that the spatial requirements would be able to be accommodated.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 26

    3 SIMULATION PARAMETERSIn order to confirm compliance with the draft provisions for NCC 2019 Section J a JV3 an energy simulation wasperformed to compare the proposed compliant design against a reference design determined using the DTS provisions

    identified in NCC 2019. These simulations were based on the following parameters

    3.1 WEATHER FILE

    To accurately model the dynamic nature of buildings thermal response, hourly-recorded weather data is used in the

    thermal simulation. Such weather data contains records of radiation, temperature, humidity, sunshine duration and

    additionally wind speed and direction.

    A Test Reference Year for Melbourne has been used for this study; chosen using an ASHRAE approved procedure. ATest Reference Year is hourly weather data for a year for use in simulation of the performance of active and passive solar

    energy systems, building energy consumption and indoor climate calculations.

    The Validation Protocol states that ACADS-BSG/CSIRO weather data is acceptable. Both ASHRAE and CSIRO procedures use the same weather information and calculations to produce a test reference year. Therefore, the ASHRAE

    test reference years is equivalent to the ACADS-BSG/CSIRO test reference year and meets the requirements.

    3.2 BUILDING LOADS

    Building loads determine the heating and cooling requirements of a building. They come from sources such as occupants,

    equipment, lighting and solar loads. The internal loads; occupant, lighting and equipment loads, are detailed below in

    Table 3.1, Table 3.2 and

    Table 3.3 with values and profiles taken from design team specifications and NCC 2019.

    Table 3.1 Internal Loads

    INTERNAL HEAT GAINS PARAMETER

    Lighting heat gain Table 3.3 of this report

    Equipment heat gain Table 3.3 of this report

    Building Occupancy Table 3.3 of this report

    Outside Air 10L/s/person

    Occupant sensible gain 80 W/person in dining zones

    75 W/person in other zones

    Occupant latent gain 80 W/person in dining zones

    55 W/person in other zones

    Table 3.2 Air Conditioning Set Points and Infiltration Levels

    INFILTRATION AND AIR CONDITIONING PARAMETER

    Infiltration HVAC on 0.35 ACH for all zones while conditioned

    0.70 ACH for all zones while unconditioned

    AC temperature bands Dry Bulb 23C 1.5C

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 27

    Table 3.3 Nominal Occupancy, Lighting and Equipment Loads for each Zone

    ZONE OPERATING PROFILES OCCUPANCY

    (m2/person)

    LIGHTING

    (W/m2)

    EQUIPMENT

    (W/m2 sensible)

    Unconditioned None 0 0 0

    Class 5: Office NCC 2019 JVc Table 2b and 2c 10 4.5 11.0

    Retail Tenancies NCC 2019 JVc Table 2 3 16 5

    Restaurant NCC 2019 JVc Table 2 1 6 5

    Hotel Amenities As per design team specifications 1.5 10 0

    Class 3 Hotel Guest Rooms NCC 2019 JVc Table 2 15 2.5 3.5

    Circulation As per design team specifications 30 2.5 2.0

    Food Preparation As per design team specifications 10 4.0 5.0

    Lounge As per design team specifications 2 3.0 5.0

    Reception NCC 2019 JVc Table 2b 30 4.5 11.0

    3.3 BUILDING GEOMETRY

    The building geometry for both the NCC 2019 reference model simulation and NCC 2019 JV3 compliant model

    simulation were based on the architectural design documents seen in Appendix B. The reference and proposed case

    included the shading that was a fixed part of the structural design as indicated below in Figure 3.1.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 28

    Figure 3.1 Image of the NCC 2019 reference model geometry

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 29

    4 SIMULATION RESULTS FOR

    PERFORMANCE BASED CASEA building simulation was prepared for both NCC 2016 compliance through verification method JV3 and for a 5 Star

    Green Star Design & As Built rating.

    The simulation was performed for both JV3 compliance and the Green Star assessment using EDSL TAS 9.3.3; an EN

    ISO 13791 validated dynamic simulation modelling (DSM) software tool using a TRY (Test Reference Year) weather

    file of Melbourne . The Green Star assessment also involved further additional calculations of energy use estimated through hand calculations.

    A comparison of this simulation against the JV3 assessment results for NCC 2019 are shown below in Table 4.1

    indicating the greenhouse gas reduction for the proposed fabric against the reference model with DTS services.

    Table 4.1 Collins Arch Development - Hotel - Simulation Results Comparison

    GREEN STAR DESIGN & AS-

    BUILT RESULTS

    NCC 2019 JV3 RESULTS FUEL

    TYPE

    PROPOSED

    Annual

    Consumption

    STANDARD

    Annual

    Consumption

    PROPOSED

    Fabric + DTS

    Services Annual

    Consumption

    NCC 2019 DTS

    Fabric + Services

    Annual

    Consumption

    Percentage

    Difference

    HVAC Heating

    (simulated)5,425,090MJ/yr 2,669,080 MJ/yr 2,971,989MJ/yr 3,063,198MJ/yr +3%

    Natural

    gas

    HVAC Cooling

    (simulated)114,869 kWh/yr 211,194 kWh/yr 38,449 kWh/yr 25,657 kWh/yr -33% Electricity

    Lighting

    (hand calculation)178,546 kWh/yr 576,426 kWh/yr 39,711 kWh 79,271kWh +50% Electricity

    Domestic Hot Water

    (hand calculation)1,855,134 MJ/yr 1,924,188 MJ/yr Not assessed Not assessed

    Natural

    gas

    Mechanical exhaust

    (hand calculation)208,204 kWh/yr 277,254 kWh/yr Not Assessed Not Assessed Electricity

    Lifts

    (hand calculation)172,417 kWh/yr 162,893 kWh/yr Not assessed Not assessed Electricity

    External Lighting

    (hand calculation)4,503 kWh/yr 2,106 kWh/yr Not assessed Not assessed Electricity

    TOTAL4,345,532 MJ/yr

    952,585 kWh/yr

    4,905,436 MJ/yr

    1,866,946 kWh/yr

    2,971,989 MJ/yr

    78,160 kWh/yr

    3,063,198 MJ/yr

    104,928 kWh/yr-

    Natural

    gas

    Electricity

    TOTAL GHG

    Emission -kg CO2 599,067,813 642,549,190 178,939,393 192,472,930 7%

    Natural

    Gas /

    Electricity

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 30

    Note, the results for both simulations use distinct modelling criteria. Further, the NCC 2019 JV3 are using DTS services

    provisions in their calculations and the Green Star energy results are for a design rating using tender documentation.

    Table 4.2 Collins Arch Commercial Simulation Results Comparison

    GREEN STAR DESIGN & AS-

    BUILT RESULTS

    NCC 2019 JV3 RESULTS FUEL

    TYPE

    PROPOSED

    Annual

    Consumption

    STANDARD

    Annual

    Consumption

    PROPOSED

    Fabric + DTS

    Services Annual

    Consumption

    NCC 2019 DTS

    Fabric + Services

    Annual

    Consumption

    Percentage

    Difference

    HVAC Heating

    (simulated)3,673,771 MJ/yr 4,148,693 MJ/yr 3,540,237 MJ/yr 3,540,095 MJ/yr -0.004% Natural gas

    HVAC Cooling

    (simulated)138,195 kWh/yr 489,182 kWh/yr 105,313 kWh/yr 98,259 kWh/yr -7% Electricity

    Lighting

    (Internal and

    External)

    377,329 kWh/yr 825,730 kWh/yr 134,082 kWh/yr 184,465 kWh/yr +27% Electricity

    Domestic Hot

    Water

    (hand calculation)

    671,761 MJ/yr 756,743 MJ/yr Not assessed Not assessed Natural gas

    Mechanical

    exhaust

    (hand calculation)

    208,204 kWh/yr 277,254 kWh/yr Not assessed Not assessed Electricity

    Lifts

    (hand calculation)269,427 kWh/yr 217,412 kWh/yr Not assessed Not assessed Electricity

    TOTAL 4,345,532 MJ/yr

    1,370,484 kWh/yr

    4,905,436MJ/yr

    2,635,308kWh/yr

    3,540,237 MJ/yr

    239,395 kWh/yr

    3,645,550 MJ/yr

    282,724 kWh/yr

    Natural gas

    Electricity

    TOTAL GHG

    Emissions -

    kgCO2

    676,184,984 1,122,428,757 259,093,784 278,055,0787%

    improvement

    Natural

    Gas /

    Electricity

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 31

    4.1 THERMAL COMFORT ASSESSMENT.

    A thermal modelling assessment has been performed for Collins Arch to assess the thermal comfort performance of the

    building. The assessment was conducted in compliance with proposed NCC 2019 Section J verification method JV3.

    The results show that most zones have a PMV compliant with the boundaries set forth in Credit 14.1 Thermal Comfort

    (-1 and +1 ) from Green Star Design & As-Built v1.1 were maintained for 98% of the occupied hours of the year over

    98% of the occupied floor area as shown in the following table. The only non compliant spaces are the pool areas.

    Table 4.3 Thermal Comfort PMV Results Hotel

    OCCUPIED ZONE FLOOR AREA COMPLIANT

    AREA

    PERCENTAGE OF THE

    YEAR WITHIN A PMV

    OF -1 AND +1

    PMV

    COMPLIANT

    Ground Floor Restaurant areas 684m2 648 99% Yes

    Ground Floor Kitchen areas 178 178 99% Yes

    Ground Floor - Ballroom 497 497 100% Yes

    Ground Floor / Level 1 Function

    Rooms

    513 513 100% Yes

    Level 2 Hotel Keys

    (Representative of floors 4-10)

    5127 5127 100% Yes

    Level 3 Hotel Keys 930 930 100% Yes

    Level 12 Hotel Keys

    (Representative of level 11)

    951 951 100% Yes

    Level 13 Hotel Keys 498 498 100% Yes

    Level 14 Hotel Keys 58 58 100% Yes

    Level 15 - Amenities (Pool,) 251 126 100% Yes

    Level 15 Amenities (Treatment

    Rooms, Gym)

    303 303 100% Yes

    Total Floor Area 10,594m2

    Percentage of Total Floor Area with Compliant Annual PMV Results 98%

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 32

    The results show that most zones have a PMV compliant with the boundaries set forth in Credit 14.1 Thermal Comfort

    (-1 and +1 ) from Green Star Design & As-Built v1.1 were maintained for 98% of the occupied hours of the year over

    98% of the occupied floor area as shown in the following table.

    Table 4.3 Thermal Comfort PMV Results Office

    OCCUPIED ZONE FLOOR AREA PERCENTAGE OF

    OCCUPIED FLOOR

    AREA

    PERCENTAGE OF

    THE YEAR WITHIN A

    PMV OF -1 AND +1

    PMV

    COMPLIANT

    Mezzanine BOH

    Lunchroom, Security

    Office

    23m2 100% 100% Yes

    Collins Street

    Building Management

    Office and Reception

    179m2 70% 100% Yes

    Level 4 Office NLA 7,837m2 100% 100% Yes

    Level 11 Office NLA 21,054m2 100% 100% Yes

    Level 25 Office NLA 16,956m2 100% 100% Yes

    Flinders Lane Retail

    Tenancy

    146.5m2 0% 88.35% No

    Collins St - Retail

    Tenancy

    467m2 21% 92% No

    L1 Retail Tenancy 253m 100% 100% Yes

    Total Floor Area 46,915m2

    Percentage of Total Floor Area with Compliant Annual PMV Results 98.15%

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 33

    5 ECONOMIC ANALYSISA high level economic analysis of the design changes required to meet compliance with the proposed provisions of

    Section of the NCC 2019.

    5.1 BUILDING FABRIC AND GLAZING

    The assessment of the provisions in relation to the building has found that the building fabric and glazing as per the

    current design is deemed compliant via Verification method JV3. Therefore no changes to the building fabric or glazing

    is required.

    5.2 MECHANICAL SERVICES

    The assessment of the mechanical systems design has found that changes would need to be made to the following

    elements. A high level estimate of the cost impact is provided.

    ITEM DETAIL INDICATIVE 2016

    COMPLIANT COST

    INDICATIVE 2019

    COMPLIANT COST

    Dampers Motorised dampers would be

    needed to be added at every

    riser take-off at every floor.

    The tempered outside air to

    the hotel does not include

    motorised dampers. As this

    balances the toilet exhaust,

    we believe that dampers

    would not be required.

    Nil

    Fans Fan selections may need to

    be adjusted to ensure

    compliance

    Nominal cost difference

    Fans - VSDs GEF-CO-29.01 (3000L/s)

    serving the Lift Motor room

    will require a VSD

    Nominal cost difference

    Pipework Some pipework will need to

    be upsized to reduce

    pressure drops of straight

    length piping

    Nominal cost difference. Coordination issue

    Pipe insulation High temperature refrigerant

    piping and heating hot water

    piping will need to be

    nominally doubled in

    thickness.

    Piping insulation is expected to increase from

    approximately $8/m to $30/m

    Total cost difference Dependent on length of piping

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 34

    The cost difference of the design changes nominated above is expected to be nominal as it is related to the piping

    insulation only.

    5.3 ELECTRICAL SERVICES

    A number of tested areas did not satisfy the proposed 2019 lighting power density requirements. If these non-

    compliances could not be carried by the remainder of compliant spaces over the entire development, then the lighting

    density would need to be reduced. On this project, the net cost result is likely to be a minor saving. There would be

    anticipated to be greater consultancy costs associated with developing solutions that meet compliances, however if the

    solution requires fewer lights, then the installation costs will likely reduce.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 35

    6 CONCLUSIONSIn order to comply with the Draft Section J Requirements for NCC 2019 through verification method JV3 no items were

    altered from those of the existing building. This results in a null cost impact.

    In order to achieve compliance with the proposed requirements Section J of the NCC 2019, some minor changes need to

    be made to the HVAC and Ventilation systems. This includes doubling the thickness of refrigeration and heating hot

    water pipes. Although theoretically these changes can be made, it would require significant coordination work with the

    architect and other disciplines and there is no guarantee that the spatial requirements would be able to be accommodated.

    The lighting design for the Collins Arch project was found to be compliant with the proposed requirements of 2019 with

    the exception of the lighting power density in the hotel and commercial lobbies and hotel standard rooms. Compliance

    could be achieved in this instance through reducing the lighting installed and no cost addition would be expected,

    however the amenity of the spaces may be impacted.

    The lifts proposed for the building are expected to be compliant with the 2019 requirements.

    The building and services were found to be generally in accordance with the new provisions of Section J of the NCC

    2019. Minimal cost impact is expected to make minor changes to the systems design to meet the more prescriptive

    provisions of Parts J5 and J6.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 36

    7 COMMENTARY ON THE NEW

    SECTION J PROVISIONS 2019

    7.1 PARTS J1-J2 BUILDING FABRIC

    The following items are general concerns on wording and clarity that we believe should be incorporated into the code.

    SECTION COMMENT RECOMMENDED RESOLUTION

    Wall-glazing construction

    J1.5 (d) (iii)

    Doesnt clearly indicate that these

    are wall only R-Value

    requirements and whether they

    apply to the total wall for each

    level and orientation or for each

    wall element.

    Indicate whether this is a wall only value

    and whether it should be a minimum for

    each wall element or an average for each

    level and orientation.

    Wall-glazing construction

    J1.5

    No worked example for

    calculating thermal resistance

    values of entire facades. This

    could be a source of confusion as a

    faade with 50% at R1 and 50% at

    R2 is total R1.33.

    Provide a worked example on how to sum

    R/U-values and SHGCs for a faade in

    order to provide clarity.

    Wall-glazing construction

    J1.5 (d) (ii)

    Lack of precise description of

    used to display retail goods in a

    shop or showroom has potential

    to reduce stringency to all retail

    buildings.

    Provide a clear definition of this term

    including the maximum level of

    occupancy required (if any) for this term to

    applicable to a project.

    Wall-glazing construction

    J1.5

    Division of requirements for

    specific class types only ignores

    the extra thermal requirements of

    overnight operating buildings in

    classes other than Class 3 or 9c

    building or a Class 9a ward area.

    Recommend returning to a previous issued

    draft distinction of the two provisions

    which divided the buildings based upon

    hours of overnight use.

    Specification JVc

    Table 2d

    Believed typographic error in

    current draft issued has air-

    conditioning profile at 25%

    between 12am and 7am.

    Return this profile to Off during these

    time periods.

    Wall-glazing construction

    J1.5, and,

    Floors

    J1.6 Table J1.6

    CIBSE Guide A Section 3.5

    includes calculations for basement

    floors and (retaining) walls

    Indicate whether the CIBSE method

    should be applied to envelope elements in

    contact with earth, specifically basement

    floors.

    Also would be desirable to indicate the

    method of calculating the R-values of

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 37

    basement and retaining wall elements as

    Section 3.5 also includes a calculation

    method for basement walls.

    7.2 PART J5 MECHANICAL SERVICES

    This section intends to highlight the major positive and negative impacts of the NCC 2019 founded upon the results of

    this case study.

    - Positives

    o J3.5(c) Allows building designers to enforce contractors to adhere to good building practices in regardto building sealing.

    o J5.2(a)(iii) An improvement to the original criteria for economy cycles; however, could use more

    clarification on what consists of an airside component of an air-conditioning system. i.e. do all the

    FCU airflows added together entail an air-conditioning system, or do they only need to be considered

    individually.

    o J5.2(a)(x) Provides a low cost high impact solution for this project to allow for energy efficiency

    opportunities if only one level of the building is being used outside of normal operating hours. It helps

    ensure energy use during after-hours operation is kept to a minimum.

    o J5.4(b) Provides a path to fan compliance for a variety of real world applications. The NCC2016 was

    not friendly to fan selections in high pressure applications because efficiencies are measure in W/L/s,

    regardless of pressure drop. The NCC2019 simply requires a motor efficiency. In this case study, the

    kitchen exhaust fans were assumed to be non-compliant; however, these fans would become compliant

    under the new requirements. Refer to appendix for more information.

    o J5.7(c) Refer to J5.4(b).

    - Negatives

    o J5.4(b) The methodology for calculating fan efficiencies required is tedious, and requires a selection

    before checking compliance. Therefore, the current process of selecting a fan is iterative. This process

    could be made easier through manufacturer software integration. Checking compliance is one of the

    most difficult aspects because a fan efficiency needs to be provided. Commonly, efficiencies arent listedon schedules, and not all manufacturers provide efficiencies in selections. If checking compliance is notmade simple, there is a risk this section of the code could be overlooked.

    o J5.4(c) & J5.4(d) Requiring a designer to meet specific pressure drop requirements restricts design

    flexibility whilst not necessarily increasing overall building efficiency. Whilst the specified pressure

    drops are in-line with good industry practice, there are times where components would need to exceed

    the limitations for practical reasons (i.e. spatial issues, cost). It may be more beneficial to shift this

    part of the code to the Australian Standards to be enforced as guidelines.

    o J5.7(c) Refer to J5.4(b).

    o Table J5.8(a) The piping insulation requirements for pipework between 30C and 85C (typical

    heating hot water and refrigerant systems) has nearly tripled in R-value. Small refrigerant piping and

    branch piping to hot water coils would need to increase significantly in size, potentially from 25mm to

    75mm. This increase could potentially triple the pipework insulation cost, and it will greatly impact on

    ceiling void coordination. Whilst this increase strives for energy efficiency improvements, it may not bepractically realised in a real world installation. The theoretical losses from the current insulation

    requirements are low enough such that temperature drops through a system are considered negligible.

  • Project No MEL1404400 NCC 2019 Section J Revisions Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page 38

    7.3 PART J6 ELECTRICAL SERVICES

    The more stringent lighting illumination power density requirements proposed for the 2019 amendment appear adequate

    for functional lighting for the areas that have been tested. The spaces tested for this case study showed non-compliances

    for areas subject to a focus on architectural lighting. The proposed calculation methodology and illumination power

    density limits will impact the ability to implement architectural lighting outcomes. As an area-weighted calculation

    allowing some areas to exceed the power density limits over an entire project, there will be the ability to employ

    architectural lighting solutions in select and limited areas on projects.

    The architectural lighting tested for the hotel included floor level, wall panel and ceiling illumination in the hotel foyer,

    and in the hotel rooms, the lighting included lamps, and display lighting that can be controlled by the lighting control

    system. Some potential perverse outcomes of a more stringent lighting limit may include lamps being powered from

    GPOs (not controlled), and vertical panel lighting treated as signage and similarly not as well integrated into the lighting

    control system.

  • BUILDING FABRIC PARAMETER

    COMPARISON

  • Project No MEL1404400 NCC 2019 Section J Revisions

    Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page A-1

    A1 NCC 2016 AND 2019 PARAMETER COMPARISON

    BUILDING

    ELEMENT

    NCC 2016 DTS

    REQUIREMENTS

    COMPLIANCE

    PATHWAY

    NCC 2016 PROPOSED

    PARAMETERS

    NCC 2019 DTS REQUIREMENTS AND

    DESIGN

    COMPLIANCE

    PATHWAY

    NCC 2019

    PROPOSED

    PARAMETERS

    Building

    fabric

    roof (J1.3)

    NCC 2016 calculation

    R value: 3.20 m2.K/W

    U value: 0.31 W/m2.K

    Solar Absorptance:

    0.40

    JV3 NCC 2016 calculation

    R value: 3.20 m2.K/W

    U value: 0.31 W/m2.K

    NCC 2019 calculation

    R value: 3.20 m2.K/W

    U value: 0.33 W/m2.K

    Solar Absorptance: 0.40

    NCC 2019 calculation

    R value: 3.20 m2.K/W

    U value: 0.27 W/m2.K

    Solar Absorptance: 0.40

    JV3 As per NCC 2016

    proposed design

    Building

    fabric

    wall (J1.5)

    External walls

    NCC 2016 calculation

    R value: 2.8 m2.K/W

    U value: 0.36 W/m2.K

    Solar Absorptance:

    0.60

    JV3 External walls

    NCC 2016 calculation

    R value: 1.40 m2.K/W

    U value: 0.38 W/m2.K

    NCC 2019 calculation

    R value: 2.5 m2.K/W

    U value: 0.45 W/m2.K

    Solar Absorptance: 0.60

    Wall-glazing

    requirements

    and compliant

    design

    WWR 20%

    NCC 2019

    calculation

    R value: 0.50

    m2.K/W

    U value: 2.00

    W/m2.K

    WWR 20%

    NCC 2019

    calculation

    R value: 1.4

    m2.K/W

    Wall only compliant

    design

    Lower Basement

    WWR 20%

    NCC 2016 calculation

    R value: 1.40 m2.K/W

    U value: 0.71 W/m2.K

    NCC 2019 calculation

    R value: 1.40 m2.K/W

    U value: 0.71 W/m2.K

    All Other Levels and

    Faades

    WWR 20%

    JV3 New Calculation

    Method:

    Total System Wall-

    Glazing Parameters

    U value: 1.35 4.11

    W/m2.kSHGC: 0.06 0.22

    WWR: 0% 98%

    (Orientation dependant)

    Internal envelope

    walls

    NCC 2016 calculation

    R value: 1.8 m2.K/W

    U value: 0.56 W/m2.K

    Internal envelope walls

    R value: No insulation added

    U value: No insulation added

    Estimated average values

    NCC 2016 calculation

  • Project No MEL1404400 NCC 2019 Section J Revisions

    Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page A-2

    BUILDING

    ELEMENT

    NCC 2016 DTS

    REQUIREMENTS

    COMPLIANCE

    PATHWAY

    NCC 2016 PROPOSED

    PARAMETERS

    NCC 2019 DTS REQUIREMENTS AND

    DESIGN

    COMPLIANCE

    PATHWAY

    NCC 2019

    PROPOSED

    PARAMETERS

    R value: 0.50 m2.K/W

    U value: 2.00 W/m2.K

    NCC 2019 calculation

    R value: 0.40 m2.K/W

    U value: 2.51 W/m2.K

    U value: 0.71

    W/m2.K

    SHGC: 0.13

    Solar

    Absorptance:

    0.60

    Wall only

    minimum

    requirements

    WWR 20%

    R value: 1.00

    m2.K/W

    U value: 1.00

    W/m2.K

    NCC 2016 calculation

    R value: 2.8 m2.K/W

    U value: 0.36 W/m2.K

    NCC 2019 calculation

    R value: 2.50 m2.K/W

    U value: 0.40 W/m2.K

    Solar Absorptance: 0.60

    Floor (J1.6) Slab on ground

    R value: No

    requirement

    U value: No

    requirement

    JV3 Slab on ground

    R value: No insulation added

    U value: No insulation added

    Estimated average values

    R value: 0.40 m2.K/W

    U value: 2.51 W/m2.K

    ignoring effect of adjacent ground

    NCC 2019 calculation

    R value: 2.00 m2.K/W

    U value: 0.50 W/m2.K

    JV3 New Calculation

    Method:

    Basement Floor

    U Value: 0.43 W/m2.K

    R-Value: 2.3 m2.K/W

    Slab on Ground

    U Value: 0.48 W/m2.K

    R-Value: 2.1 m2.K/W

    Suspended Floor

    U Value: 2.5 W/m2.K

    R-Value: 0.4 m2.K/W

  • Project No MEL1404400 NCC 2019 Section J Revisions

    Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page A-3

    BUILDING

    ELEMENT

    NCC 2016 DTS

    REQUIREMENTS

    COMPLIANCE

    PATHWAY

    NCC 2016 PROPOSED

    PARAMETERS

    NCC 2019 DTS REQUIREMENTS AND

    DESIGN

    COMPLIANCE

    PATHWAY

    NCC 2019

    PROPOSED

    PARAMETERS

    Suspended slab

    NCC 2016 calculation

    R value: 2.00 m2.K/W

    U value: 0.50 W/m2.K

    Suspended slab

    R value: No insulation added

    U value: No insulation added

    Estimated average values

    R value: 0.40 m2.K/W

    U value: 2.51 W/m2.K

    As per NCC 2016

    proposed design

    Glazing

    (J2)

    Determined using NCC

    2016 Glazing

    Calculators

    JV3 Mid Pane

    R value: 0.63 m2.K/W

    U value: 1.60 W/m2.K

    SHGC: 0.28

    Whole of System

    R-Value: 0.24 m2.K/W

    U-Value: 4.2 W/m2.K

    SHGC: 0.25

    As Building fabric wall (J1.5) above JV3 As per NCC 2016

    proposed design

  • Project No MEL1404400 NCC 2019 Section J Revisions

    Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page A-4

    A2 FAADE WINDOW TO WALL RATIOS

    LEVEL EASTERN FAADE NORTHERN FAADE SOUTHERN FAADE WESTERN FAADE

    Hotel Commercial Hotel Commercial Hotel Commercial Hotel Commercial

    Lower Basement 1

    - 50% 0% 0% 0%

    Podium Level 0.3

    Collins St61% 62% 54% 68%

    Podium Level 0.2

    Williams St- - 100% -

    Podium Level 0.1

    Flinders Lane32% 52% 56% 53%

    Ground Floor 54% N/a 78% N/a 73% N/a 70% N/a

    Level 01 35% N/a 78% N/a 64% N/a 41% N/a

    Level 02 77% N/a 61% N/a 61% N/a 52% N/a

    Level 03 71% N/a 77% N/a 77% N/a 43% N/a

    Level 4 Representative

    of Level 3

    52% Representative of

    Level 3

    82% Representative of

    Level 3

    82% Representative of

    Level 3

    82%

    Level 11 Representative

    of Level 3

    46% Representative of

    Level 3

    82% Representative of

    Level 3

    82% Representative of

    Level 3

    82%

  • Project No MEL1404400 NCC 2019 Section J Revisions

    Case Study: Collins Arch Development - 447 Collins Street, Melbourne ABCB

    WSP February 2018

    Page A-5

    Level 1271%

    Representative of

    Level 1177%

    Representative of

    Level 1177%

    Representative of

    Level 1143%

    Representative of

    Level 11

    Level 1367%

    Representative of

    Level 11N/a

    Representative of

    Level 1179%

    Representative of

    Level 1122%

    Representative of

    Level 11

    Level 1484%

    Representative of

    Level 1195%

    Representative of

    Level 1197%

    Representative of

    Level 1120%

    Representative of

    Level 11

    Level 1584%

    Representative of

    Level 1195%

    Representative of

    Level 1197%

    Representative of

    Level 1120%

    Representative of

    Level 11

    Level 25 N/a 53% N/a 82% N/a 67% N/a 83%

  • ARCHITECTURAL DRAWINGS

  • C O L L I N

    S S T R E

    E T

    F L I N D E R

    S L A N E

    W I L L I A M S T R E E T

    M A R K E T S T R E E T

    SUBJECT SITE

    RL 14.70

    RL 9.24

    RL 8.98

    RL 14.69 15844' 83.70

    33833'40" 83.61

    24839' 70

    .72

    6834'40"

    70.97

    COLLINS STREETEAST

    RESIDENTIALTOWER

    COLLINSSTREET WESTRESIDENTIAL

    TOWER

    433439

    COLLINS STREETCOMMERCIAL TOWER

    447

    COLLINS STREETHOTEL

    435

    459 COLLINS STMLC TOWER

    CHALLENGE TOWER

    35 WILLIAMS ST

    22 WILLIAMS STSWANN HOUSE

    405 - 411 FLINDERS LNTHE PORT APARTMENTS

    389 FLINDERS LNMINTER ELLISON

    BUILDING

    HOLYMAN HOUSE

    IMMIGRATION MUSEUM

    42-52 MARKET STTREASURY FUNDS

    HOUSE(16 STOREYS)

    60 MARKET STOAKS ON MARKET

    (25 STOREYS)

    425 COLLINS STTRUSTEES HOUSE

    (9 STOREYS)

    422 COLLINS STTEMPLE COURT

    GURNERS LANE

    454COLLINS

    ST

    450COLLINS

    ST

    440 COLLINS ST

    412COLLINS

    ST

    462 COLLINS ST464-466COLLINS ST

    470 COLLINS ST

    480 COLLINS ST

    459 - 469 COLLINS ST

    471 FLINDERS LN

    P.O.S.

    COLLINS STREETHOTEL

    435

    COMMER

    CIAL

    ENTRY

    RE

    SID

    ENTIA

    L

    ENTR

    Y

    RE

    SID

    ENTIA

    L

    ENTR

    Y

    MA

    RK

    ET ST

    AM

    PITH

    EA

    TRE

    FLINDER

    S LN

    LINK ST

    AIR

    HOTEL

    ENTRY

    HOTEL

    ENTRY

    VEHICU

    LAR

    PARKIN

    G

    ENTRY

    WILLIA

    M S

    T

    LINK

    STAIR

    HOTEL

    ENTRY

    LOADIN

    G

    ENTRY

    EO

    T

    BIC

    YCLE

    ENTR

    Y

    Date generated

    Revision

    Status

    Sheet number

    Sheet title

    Scale

    Project number

    Checked Approved

    25mm

    Sheet sizeA0

    Issuer

    Size check

    Project

    Client

    Woods Bagot

    TM

    # Description DateStatusRecent revision history

    A00 - GENERALA10 - EX. CONDITIONS AND DEMOLITIONA11 - SITE PLANSA12 - REFERENCE PLANSA21 - STRUCTURAL SETOUTA22 - FLOOR PLANSA24 - REFLECTED CEILING PLANSA32 - ELEVATIONSA33 - SECTIONSA41 - DETAIL STRUCTURAL SETOUTA42 - DETAIL ENVELOPE SETOUTA43 - DETAIL INTERNAL ARRANGEMENTSA44 - STAIRS AND CONNECTING ELEMENTSA45 - DETAIL APARTMENT LAYOUTSA46 - DETAIL WET AREASA47 - DETAIL LIFT CARSA51 - STRUCTURAL SETOUT DETAILSA52 - CONSTRUCTION ENVELOPE DETAILSA53 - CONSTRUCTION FITOUT DETAILSA60 - WINDOWS SCHEDULEA61 - LOUVRES SCHEDULEA62 - DOORS SCHEDULEA70 - JOINERY & FITTINGSA74 - LINE OF HEIGHTSA90 - FINISHES BOARDSA91 - RENDERS

    DRAWING SERIES

    Contractor must verify all dimensions on site before commencing workor preparing shop drawings. Do not scale drawings.

    Notes & Legend

    DRAWING NUMBERING CONVENTIONEXAMPLE:

    A - 22 2 14

    ARCHITECTURALDRAWING SERIESSEQUENCING NUMBERSTRATA / SUB CATEGORY

    C:\My Documents\Autodesk\Revit\RAC2016\130186_447C_ARCH_CENTRAL_melblp.rvt6-01-17 3:36:45 PM

    A

    1 : 400

    FOR TENDER

    130186

    WB/SHoP WB/SHoP

    CBUS PROPERTY

    433 - 455 COLLINS STREET

    A-11001

    SITE PLANOVERALL

    A 80% DD / TENDER ISSUE 06/01/17

  • CC

    BB

    17 15 13 11 9 7 5 3

    10

    DD

    FF

    81214 4 2

    1

    1

    1A-33104

    1A-33104

    616

    AA

    1A-33003

    1A-33003

    2A-33103

    2A-33103

    1A-33102

    1A-33102

    Da

    Ea

    EE

    1A-33101

    1A-33101

    TITLE

    BOU

    NDAR

    Y

    TITLE BOUNDARY

    TITLE BOUNDARY

    TITL

    E BO

    UNDA

    RY

    OFFICE + RETAILRECYCLING

    12.5m DIAMETERTRUCK TURNTABLE

    CARPARK RAMP 1:5.1THRU TO RESI & COM CAR PARKS

    RAMP 1:9

    RAMP1:20

    TRUCK WAITING BAY AREA

    WASTE COLLECTION DOCKS

    LOADING DOCKSUNLOADING

    ZONE

    HOTEL RECYCLING HOTEL GENERALWASTE

    8.8m TRUCKBAY

    COMM. &RETAIL LOADING(OFFICE TITLE)

    HOTEL LOADING

    RESIDENTIAL LOADING

    COURIER ANDMAIL VAN BAY

    TRUCK ROUTE

    HARDRUBBISHCAGES