180
BA 034S/04/en/06.04 Nr. 56004242 Guidelines for planning and commissioning PROFIBUS DP/PA Field Communication 8

Endress+Hauser Profibus Planing Guide

Embed Size (px)

Citation preview

Page 1: Endress+Hauser Profibus Planing Guide

BA 034S/04/en/06.04 Nr. 56004242

Guidelines for planning and commissioning

PROFIBUS DP/PAField Communication

8

Page 2: Endress+Hauser Profibus Planing Guide
Page 3: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning

Endress+Hauser 1

Table of Contents

Revision History . . . . . . . . . . . . . . . . . 3

Registered Trademarks . . . . . . . . . . . . 3

1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1.2 Conventions and icons . . . . . . . . . . . . . . . . . . . . . . 6

1.3 Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2 Introduction to PROFIBUS . . . . . . . . . . . . 8

2.1 PROFINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

2.1.1 Component-based Automation . . . . . . . . . 10

2.1.2 I/O integration . . . . . . . . . . . . . . . . . . . . . 12

2.2 PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.2.1 Transmission standards . . . . . . . . . . . . . . . 15

2.2.2 PROFIBUS DP communication protocol . . . 16

2.2.3 Application profiles . . . . . . . . . . . . . . . . . . 19

2.2.4 PROFIsafe . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.2.5 PROFIdrive . . . . . . . . . . . . . . . . . . . . . . . . 20

2.2.6 Integration technologies . . . . . . . . . . . . . . 21

2.2.7 Quality assurance . . . . . . . . . . . . . . . . . . . 21

2.3 PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

2.3.1 Operating principle . . . . . . . . . . . . . . . . . . 24

2.3.2 Applications in hazardous areas . . . . . . . . . 25

2.4 Field Device Tool (FDT) . . . . . . . . . . . . . . . . . . . . 26

3 PROFIBUS DP basics . . . . . . . . . . . . . . . . 29

3.1 Synopsis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

3.2 Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

3.3 Bus access method . . . . . . . . . . . . . . . . . . . . . . . . 34

3.4 Network configuration . . . . . . . . . . . . . . . . . . . . . 35

3.5 Applications in hazardous areas . . . . . . . . . . . . . . . 36

4 PROFIBUS PA Basics . . . . . . . . . . . . . . . . 38

4.1 Synopsis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

4.2 Segment coupler and links . . . . . . . . . . . . . . . . . . . 39

4.2.1 Segment coupler . . . . . . . . . . . . . . . . . . . . 40

4.2.2 Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

4.3 Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

4.4 Bus access method . . . . . . . . . . . . . . . . . . . . . . . . 44

4.4.1 Segment coupler . . . . . . . . . . . . . . . . . . . . 44

4.4.2 Gateway-type segment coupler . . . . . . . . . 45

4.4.3 Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

4.5 Network Configuration . . . . . . . . . . . . . . . . . . . . . 47

4.6 FISCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

4.7 Fieldbus multi-drop barriers . . . . . . . . . . . . . . . . . . 49

5 PROFIBUS PA Planning . . . . . . . . . . . . . 50

5.1 Selection of the segment coupler . . . . . . . . . . . . . . 50

5.2 Cable type and length . . . . . . . . . . . . . . . . . . . . . . 51

5.3 Current consumption . . . . . . . . . . . . . . . . . . . . . . . 52

5.4 Voltage at last device . . . . . . . . . . . . . . . . . . . . . . . 54

5.4.1 Worst case calculation . . . . . . . . . . . . . . . . 54

5.4.2 Accurate calculation . . . . . . . . . . . . . . . . . 55

5.5 Calculation examples for bus design . . . . . . . . . . . . 56

5.5.1 Example 1: Non-hazardous application . . . 56

5.5.2 Example 2: EEx ia application . . . . . . . . . . 58

5.5.3 Example 3: EEx ib application . . . . . . . . . . 60

5.5.4 Example: fieldbus barrier application . . . . . 63

5.6 Data quantity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

5.7 Addressing and cycle times . . . . . . . . . . . . . . . . . . 68

5.7.1 Addressing . . . . . . . . . . . . . . . . . . . . . . . . . 68

5.7.2 Cycle times . . . . . . . . . . . . . . . . . . . . . . . . 68

5.7.3 Example 1: Siemens segment coupler . . . . . 69

5.7.4 Example 2: Pepperl+Fuchs SK1 coupler . . . 70

5.7.5 Example 3: Pepperl+Fuchs SK2 coupler . . . 71

5.7.6 Example 4: Siemens PA link . . . . . . . . . . . . 73

6 Installation PROFIBUS PA . . . . . . . . . . . 74

6.1 Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

6.2 Grounding and shielding . . . . . . . . . . . . . . . . . . . . 75

6.3 Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

6.4 Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . 79

6.5 Installation of the devices . . . . . . . . . . . . . . . . . . . . 80

6.6 Setting addresses . . . . . . . . . . . . . . . . . . . . . . . . . . 82

6.6.1 Using DIP switches . . . . . . . . . . . . . . . . . . 82

6.6.2 Software addressing with FieldCare . . . . . . 83

6.6.3 Software addressing with Commuwin II . . . 84

7 System Integration . . . . . . . . . . . . . . . . . . 85

7.1 Network configuration . . . . . . . . . . . . . . . . . . . . . . 85

7.1.1 Tested systems . . . . . . . . . . . . . . . . . . . . . . 86

7.2 Device database files (GSDs) . . . . . . . . . . . . . . . . . 87

7.2.1 GSD file example . . . . . . . . . . . . . . . . . . . . 89

7.2.2 Full configuration with manufacturer-specific

GSDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

7.2.3 Partial configuration with manufacturer-specific

GSDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

7.2.4 Profile GSD . . . . . . . . . . . . . . . . . . . . . . . . 93

7.3 Cyclic data exchange . . . . . . . . . . . . . . . . . . . . . . . 94

7.3.1 Status codes: Device status BAD . . . . . . . . 95

7.3.2 Status code: Device status UNCERTAIN . . . 96

7.3.3 Status codes: Device status GOOD . . . . . . . 97

7.4 Bus parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

7.4.1 Aligning FieldCare . . . . . . . . . . . . . . . . . . 100

7.4.2 Aligning Commuwin II . . . . . . . . . . . . . . 100

7.4.3 Commissioning the Pepperl+Fuchs SK2 . . 101

7.4.4 Watch Dog Time TWD . . . . . . . . . . . . . . . . . . 103

Page 4: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning

2 Endress+Hauser

8 Device Parametrization . . . . . . . . . . . . 104

8.1 PROFIBUS PA block model . . . . . . . . . . . . . . . . . 105

8.2 PROFIBUS PA profile . . . . . . . . . . . . . . . . . . . . . 106

8.2.1 Block structure . . . . . . . . . . . . . . . . . . . . 108

8.2.2 Device management . . . . . . . . . . . . . . . . 109

8.2.3 Transmitter and actuator blocks . . . . . . . 110

8.2.4 Analysis devices . . . . . . . . . . . . . . . . . . . 113

8.2.5 Function overview . . . . . . . . . . . . . . . . . 114

8.3 FieldCare Asset Management . . . . . . . . . . . . . . . 116

8.3.1 Using FieldCare . . . . . . . . . . . . . . . . . . . 117

8.3.2 Generation of a live list . . . . . . . . . . . . . . 118

8.3.3 Device parametrization . . . . . . . . . . . . . . 118

8.3.4 On-line parametrization . . . . . . . . . . . . . 119

8.3.5 Plant View . . . . . . . . . . . . . . . . . . . . . . . 119

8.4 Commuwin II Operating Program . . . . . . . . . . . . 120

8.4.1 Operation . . . . . . . . . . . . . . . . . . . . . . . . 120

8.4.2 Device menu . . . . . . . . . . . . . . . . . . . . . 121

9 Trouble-Shooting . . . . . . . . . . . . . . . . . 122

9.1 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . 122

9.2 PLC planning . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

9.3 Data transmission . . . . . . . . . . . . . . . . . . . . . . . . 123

9.4 Commuwin II . . . . . . . . . . . . . . . . . . . . . . . . . . 124

10 Technical Data . . . . . . . . . . . . . . . . . . . . 125

10.1 PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . 125

10.2 PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . . . 126

11 PROFIBUS Components . . . . . . . . . . . 127

11.1 Endress+Hauser field devices PROFIBUS PA . . . . 127

11.2 Endress+Hauser field devices PROFIBUS DP . . . . 153

11.3 Network components . . . . . . . . . . . . . . . . . . . . . 160

11.4 Asset management and operating software . . . . . 162

11.5 Supplementary documentation . . . . . . . . . . . . . . 163

12 Terms and Definitions . . . . . . . . . . . . . 164

12.1 Bus architecture . . . . . . . . . . . . . . . . . . . . . . . . . 164

12.2 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165

12.3 Data exchange . . . . . . . . . . . . . . . . . . . . . . . . . . 166

12.4 Miscellaneous terms . . . . . . . . . . . . . . . . . . . . . . 167

13 Appendix: Calculation Sheets . . . . . . 168

13.1 Explosion hazardous areas EEx ia . . . . . . . . . . . . 168

13.2 Explosion hazardous areas EEx ib . . . . . . . . . . . . 170

13.3 Non-hazardous areas . . . . . . . . . . . . . . . . . . . . . 172

Page 5: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning

Endress+Hauser 3

Revision History

Registered Trademarks

• PROFIBUS®

is a registered trademark of PROFIBUS User-Organisation e.V., Karlsruhe, Germany

• Microsoft®, Windows®, Windows NT®, Windows 2000®,Windows XP®

are registered trademarks of Microsoft Corporation, Redmond, Washington, USA

Issue Changes

BA198F/00/en/11.99 Original Version

BA034S/04/en/07.04 Revision of manual to include latest information on PROFIBUS standard

Additional descriptions of new components

Revision of device techniical data

Page 6: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning

4 Endress+Hauser

Page 7: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 1 Safety

Endress+Hauser 5

1 Safety

1.1 General

Approved usage These guidelines have been written with the view of giving the potential PROFIBUS user an

introduction to the planning and commissioning of a PROFIBUS PA network. They are based on the

experience of Endress+Hauser employees who have been actively involved in PROFIBUS projects

and who, in the meantime, have successfully commissioned a large number of plants.

The approved usage of the individual devices that are used in a network can be taken from the

corresponding device operating instructions.

Installation,

commissioning, operation

The field devices, segment coupler, cables and other components must be designed to operate safely

in accordance with current technical safety and EU standards. If installed incorrectly or used for

applications for which they are not intended, it is possible that dangers may arise. For this reason,

the system must be installed, connected, operated and maintained according to the instructions in

this and other relevant manuals: personnel must be authorised and suitably qualified.

Explosion hazardous area If the system is to be installed in an explosion hazardous area:

• Ensure that all personnel are suitably qualified

• Observe the specifications in the certificate

• Observe any national and local regulations.

For PROFIBUS PA, it is recommended components should be designed in accordance with the

FISCO model. This greatly simplifies the acceptance testing of the PROFIBUS PA segment. Where

another scheme is used, e.g. Exe/Exi multibarriers, proof of intrinsic safety must be furnished.

Page 8: Endress+Hauser Profibus Planing Guide

1 Safety PROFIBUS planning and commissioning

6 Endress+Hauser

1.2 Conventions and icons

In order to highlight safety relevant or alternative operating procedures in the manual, the following

conventions have been used, each indicated by a corresponding icon in the margin.

Safety conventions .

Explosion protection .

Electrical symbols .

Icon Meaning

A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation

or may lead to an instrument response which is not planned

Caution!

Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or

incorrect functioning of the instrument

Warning!

A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury,

a safety hazard or destruction of the instrument

Icon Meaning

Device certified for use in explosion hazardous area

If the device has this symbol embossed on its name plate it can be installed in an explosion hazardous area

in accordance with the specifications in the certificate or in a safe area

Explosion hazardous area

Symbol used in drawings to indicate explosion hazardous areas. Devices located in and wiring entering

areas with the designation “explosion hazardous areas” must conform with the stated type of protection

Safe area (non-explosion hazardous area)

Symbol used in drawings to indicate, if necessary, non-explosion hazardous areas. Devices located in safe

areas stiill require a certificate if their outputs run into explosion hazardous areas.

Icon Meaning

Direct voltage

A terminal to which or from which a direct current or voltage may be applied or supplied

Alternating voltage

A terminal to which or from which an alternating (sine-wave) current or voltage may be applied or

supplied

Grounded terminal

A grounded terminal, which as far as the operator is concerned, is already grounded by means of an earth

grounding system

Protective grounding (earth) terminal

A terminal which must be connected to earth ground prior to making any other connection to the

equipment

Equipotential connection (earth bonding)

A connection made to the plant grounding system which may be of type e.g. neutral star or equipotential

line according to national or company practice

Page 9: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 1 Safety

Endress+Hauser 7

1.3 Documentation

The guidelines are structured as follows:

Chapter Title Content

Chapter 1 Introduction Advantages of a bus as well as general information about the

PROFIBUS standard

Chapter 2 Introduction PROFIBUS An overview of PROFIBUS standards for factory and process

automation

Chapter 3 PROFIBUS DP Basics Information about PROFIBUS DP

Chapter 4 PROFIBUS PA Basics Information about PROFIBUS PA, couplers, links and use in

explosion hazardous areas (FISCO-Model)

Chapter 5 PROFIBUS PA Planning What must be observed when planning PROFIBUS DP/PA

systems, with examples

Chapter 6 PROFIBUS PA Installation Notes on the installation of devices in a PROFIBUS DP/PA

system

Chapter 7 System Integration Notes on mapping PROFIBUS PA devices in a PLC

Chapter 8 Device Configuration General information on setting the parameters in

Endress+Hauser devices PROFIBUS applications

Chapter 9 Trouble-Shooting Causes and remedies for general faults that may occur during

the commissioning of a system

Chapter 10 Technical Data Principle technical data of PROFIBUS PA and PROFIBUS DP

Chapter 11 PROFIBUS Components Profiles of the Endress+Hauser PROFIBUS DP and PROFIBUS

PA devices

Chapter 12 Terms and Definitions Explanation of the terminology used to describe bussystems

Chapter 13 Appendix Calculation sheets for your applications

Page 10: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

8 Endress+Hauser

2 Introduction to PROFIBUS

PROFIBUS is a standardized, open communications system for all areas of application in factory and

process automation. The technology was introduced in the early 1990s and has been developed

continuously ever since. The PROFIBUS DP and PROFIBUS PA technologies are specified in the

international standards EN 50170 and IEC 61158 and are suitable for replacement of discrete and

analog signals in control systems.

PROFIBUS DP The original specification was aimed primarily at the requirements of Factory Automation, but this

was quickly extended to include the requirements of process automation, in particular the need for

intrinisically safe bus powering of devices. This is mirrored in the PROFIBUS PA specifications. As

its popularity increased, the PROFIBUS DP specifications were extended to include a number of

common but optional application profiles for e.g. safety, time stamping etc.. Similarly several

application profiles were developed to meet the needs of specific device types, e.g. measuring

devices, drives, remote I/O etc..

By the turn of the century, the PROFIBUS DP/PROFIBUS PA standard had covered many of the

requirements of both Factory and Process Automation from field to control level - as shown by

Fig. 2-1. It was rewarded by a large degree of support from both equipment manufactures and users,

and today has an installed base of over 10,000,000 I/0 points.

Fig. 2-1: Overview of PROFIBUS technologies

PROFINET At this point in time, however, Ethernet had already begun to work its way down from the office

environment on to the factory floor, and was being seen as the future standard for control system

backbones. Office Ethernet is in itself not suitable for control systems, since media access is

stochchastic (CSMA/CD), not deterministic, so there was a need to develop a further standard for

the operations level. The result is the PROFINET specification, which not only addresses the

problems of deterministic control for real time and isochronic real time applications, but also those

of network engineering, operation and I/O integration of control and fieldbus networks. PROFINET

is only just at the beginning of its development, but promises many exciting solutions for the future.

PROFIBUS User

Organisations

PROFIBUS is supported by PROFIBUS International, which is a world-wide association of

PROFIBUS user organisations. It is responsible for the development of the standard, its

maintenance, the conformance testing of PROFIBUS devices as well as the issuing of device

certificates. It has a number of independent accredited PROFIBUS Competence Centers thoughout

the world (one is located Endress+Hauser Process Solutions AG) which maintain test facilities that

are accessible for users and offer training courses for prospective PROFIBUS engineers.

MBP (IEC 61158-2)

PLC IPC

12:00 14:00 16:00 18:00 20:00 22:00

Internet

OSES

RS-485/FO

Ethernet TCP/IP

HART, ASi

OPERATIONS: PROFINET

FACTORY: PROFIBUS DP PROCESS: PROFIBUS DP

Page 11: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 9

2.1 PROFINET

As can be seen from Fig. 2-1, PROFINET is the Ethernet-based automation standard of PROFIBUS

International. It intended for use in a wide range of industrial applications, for example in:

• Production systems

• Assembly systems

• Systems in the automotive industries

• Systems in the food and beverage industries

• Packaging systems

PROFINET allows the implementation of distributed automation structures, integration of simple

decentralized field devices as well as the operation of motion control applications. As can be seen

in Fig. 2-2, each of these applications places different demands on the system with regard to

response times and real time operation.

Fig. 2-2: PROFINET allows the parallel operation of several "Control Islands" via Ethernet TCP/IP

PROFINET recognises this fact and provides a modular solution which treats each application as a

separate "Control Island". Such islands might be for example, a SCADA system for monitoring and

operating the plant, a control network for flow, ratio and level control of a reactor, a complete filling

machine or an industrial robot. PROFINET specifies those functions that allow implementation of

an integrated automation solution from network installation to web-based diagnosis. The modular

structure of PROFINET permits extremely easy expansion. PROFINET operates over a high speed

(100 Mbit/s) switched Ethernet TCP/IP backbone. This ensures:

• Full duplex communication

• Isochronous communication

• Priorization of Real-Time Frames (Quality of Service)

A specially developed PROFINET chip enables switch integration into a device and controller.

The specification itself has two facets:

• PROFINET CbA (Component-based Automation)

• PROFINET I/O (Integration of PROFIBUS devices in PROFINET)

These are discussed in more detail in the following sections

Internet

Controller and HMI Field Devices Motion Control

TCP/IP Real Time Isochronic Real Time

100ms 10ms <1ms

Real Time

Page 12: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

10 Endress+Hauser

2.1.1 Component-based Automation

Component-based Automation is best explained by taking the practical example that PROFIBUS

International uses in its own presentations, that of bottling in brewing or soft drinks production. The

bottling is done by a number of machines that wash, fill, close and pack the bottles. Prior to this the

product must be manufactured, a classical process control application. Fig. 2-3 illustrates the task

in question.

Fig. 2-3: Schematic diagram of automation tasks in a brewery or soft drinks plant

Network architecture The network architecture depends on the nature of the processes involved and the demands they

make on control. Typically, however, the closing and packing of bottles are purely factory

automation tasks requiring isochronous real time communication, washing and filling are hybrid

tasks and the production of the beer or soft drink is a process automation task. Fig. 2-4 illustrates

the type of architecture to be expected, the production process being a PROFIBUS DP/PA task and

the washing and filling a typical PROFIBUS DP task today.

Fig. 2-4: Possible plant architecture for brewery or soft drinks plant

Technological module PROFINET considers machines and systems to be divided into technological modules, each of

which comprises of mechanical, electrical and software components. The functionality of the

technological modules is encapsulated in the form of PROFINET components. These have standard

interfaces for use in a PROFINET engineering tool. They can be used as building blocks, combined

as required and are easily reused. The PROFINET components for all technological modules in a

machine or component assembly are supplied by the manufacturer. on e.g. a CD-ROM.

Production

PackCloseWash Fill

Machine 1 Machine 2 Machine 3

Horizontal integration along the production line

Data exchange between intelligent devices within the machine

PackClose

Wash Fill

Machine 1

Machine 2 Machine 3

PROXY

Mash Ferment

Production

PROXY

Filter

ESEngineering

PROFIBUS DP/PA PROFIBUS DP

Ethernet

Page 13: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 11

CbA engineering The technological modules are basically Global Function Blocks for the machine or component

assemblies in the plant and can be used within a PROFINET Engineering Tool to build up a logical

view of the plant. The standard interfaces allow the logical sequences to be programmed in a

graphical environment. Thus for instance, a connection between the "Finished" output of one

machine to the "Start" input of another, will cause the appropriate message to be sent over Ethernet

and the downstream machine will start up when the upstream machine has finished its task.

Fig. 2-5: Machine and component assembly manufacturer’s deliver standardised function blocks for their equipment

The Engineering Tool is also used to build up a view of the the PROFINET and PROFIBUS network,

the technical modules forming the link between the two views. When the tool goes on-line, i.e. the

various components are connected physically to the network, the logical project is downloaded to

the connected machines and devices. The system can then be started up with preconfigured links.

Fig. 2-6: The links are downloaded to the machines and the system is ready for start-up

Manfacturer AComponent

Editor Interface

Manufacturer's programmingand configuration tools

Manfacturer BComponent

Editor Interface

Manfacturer CComponent

Editor Interface

PROFInet ConfigurationEditor

PackClose

Wash Fill

Machine 1

Machine 2 Machine 3

PROXY

Mash Ferment

Production

PROXY

Filter

Download

Page 14: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

12 Endress+Hauser

2.1.2 I/O integration

PROFINET I/O devices PROFINET allows direct interfacing of decentralized field devices on Ethernet. This supports flat

communication hierarchies in automation. All the devices used are connected in a consistent

network structure and therefore provide open communication throughout the entire production

system. PROFINET defines three types of I/O device:

• I/O controller, the device containing the control program and managing data exchange to

assigned field devices

• I/O device, the field device connected to the I/O controller

• I/O supervisor, the HMI and diagnostic station

Fig. 2-7 shows the types of data that are exchanged between the three components.

Fig. 2-7: Data exchange between PROFINET I/O devices

PROFINET communication In order to achieve the very short response times required in motion control a special ASIC chip is

available. The communication stack is shown in Fig. 2-8.

Fig. 2-8: PROFIBUS communication stack

I/O DeviceField Device

I/O Controllere.g. PLC

Ethernet

I/O Supervisore.g. SCADA or Configuration

DiagnosticStatus controlParametrization

ConfigurationProduction DataAlarms

DiagnosisUp/Download

Real Time Switch ASIC

Ethernet Real Time

IRTRT

IP

TCP UDP

ITapplications

HTPPSMNPDHCP...

PROFIBUS applications

Standarddata

Real-timedata

Rea

l-tim

e

Page 15: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 13

It can be seen that PROFINET uses Ethernet at three performance levels for communcation between

I/O devices:

• Engineering and time-uncritical data are transferred via TCP/IP and DCOM.

• For time-critical process data, e.g. alarms, a real-time channel is available(RT). It is

implemented as software based on available controllers.

• For motion control isochronous real-time communication (IRT) is available which allows jitter

accuracy of 1 µs at a clock rate of 1 ms.

The integration of existing field bus applications is accomplished with the proxy concept. The proxy

is the representative of the field bus devices on the PROFINET, see Fig. 2.4.

The network management covers all the functions for the administration of PROFINET devices in

Ethernet networks:

• Device and network configuration, e.g. issue of IP parameters based on standards like DHCP;

Network diagnosis based on standards like SNMP

• Integration of Web functions, e.g. access to components by means of standard technologies

from the Internet field such as HTTP, XML, HTML and addressing with scripting.

Field device integration The signals from the (PROFIBUS DP/PA) field devices (decentralized peripherals) are processed

directly in the assigned controller. The controller communicates with other PROFINET I/O devices

via a proxy. Devices are integrated in the controller by means of standard GSD files.

Integration of the decentralized field devices is an in the PROFINET system is optional add-on to

distributed automation. Here a special GSD file, GSDML written in XML is used for integration. A

combination of the standard and top-level integration can be implemented in a PROFINET network

at any time.

Installation The specific requirements for Ethernet networks in an industrial environment are:

• System-specific cable routing

• Specific degree of networking for each machine/system

• Linear network structures

• Rough industry-compatible cables and connectors with special requirements fulfilled in terms

of EMC and temperature.

PROFINET installations are based on these principles and provide the device manufacturer with

clear specifications for device interfaces and the wiring for them. The PROFINET Installation Guide

provides the system manufacturer/operator with simple rules for the installation of Ethernet

networks.

More information on PROFINET can be found at www.profibus.com.

Page 16: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

14 Endress+Hauser

2.2 PROFIBUS DP

Fig. 2-9: Overview of PROFIBUS standards

Fig. 2-9 gives an overview of PROFIBUS DP system standards: DP stands for Decentralised

Periphery. The standards comprise the following groups:

• Transmission Technology

PROFIBUS signal transmission is based on the RS-485, fibre optics or IEC 61158-2 standards.

In the latest literature the latter is also referred to as MBP or MBP-IS (Manchester Bit Protocol).

• Communication Technology

The PROFIBUS DP communication protocol is at the core of the standard. It is available in

three variants, DP-V0, DP-V1 and DP-V2.

• Common Application Protocols

A set of optional protocols for network management.

• Device Application Protocols

A set of protocols for particular device types or applications, e.g. measuring devices or motion

control.

• Integration Technology

These standards determines how field devices can be integrated into PROFIBUS systems.

• System Profiles

Contain specifications regarding conformance classes, interfaces and constraints.

The standards of interest to process automation are described in the following sections. Table 2.1

gives an overview of where these are used.

Table 2-1: Target applications and typical use of PROFIBUS standards

Target Application Factory Automation Motion Control Process

Automation

Safety

Typical designation PROFIBUS DP PROFIdrive PROFIBUS PA PROFIsafe

Application profile None or specific PROFIdrive PA device PROFIsafe

Communication PROFIBUS DP

protocol

PROFIBUS DP

protocol

PROFIBUS DP

protocol

PROFIBUS DP

protocol

Transmission RS-485 RS-485 RS-485

MBP-IS

RS-485

MBP-IS

PROFIBUS DPIEC 61158/61784

DP-V0...V2

Common Application Profiles (optional):PROFISAFE, Time Stamp, Redundancy, etc.

RS485:

RS485-IS:

NRZ

Intrinsic Safety

Fiber:

Optics:

MBP *):

MBP-LP:

MBP-IS:

Glass Multi Mode

Glass Single Mode

Manchester Bus Powered

Low Power

Intrinsic SafetyPCF / Plastic Fiber

Application

Application

Communication

Transmission

Profiles II

Profiles I

Technologies

Technologies

PA D

evic

es

RIO

for P

A

SEM

I

PRO

FIdr

ive

Inde

nt S

yste

ms

Wei

ghin

g &

Dos

ing

Enco

der

Inte

grat

ion

Syst

em

- Des

crip

tion

(GSD

, ED

D)

- Mas

ter C

onfo

rman

ce C

lass

es

- Too

ls (D

TM, C

ofig

urat

ors)

- Int

erfa

ces (

Com

m-F

B, F

DT,

etc

.)- C

onst

rain

ts

Tech

nolo

gies

Prof

iles 1

...x

Page 17: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 15

2.2.1 Transmission standards

PROFIBUS provides for three different transmission technologies, RS-485, Fibre Optics and MBP

(Manchester Coding/Bus Powered). Both RS-485 and IEC 61158-2 make provision for intrinsically

safe transmission in hazardous areas.

RS-485 RS-485 is used for tasks that require high transmission rates. The transmission technology is simple

and cost-effective: no expert knowledge is required for installation of the cable. STP copper cable

(shielded, twisted pairs) with one conductor pair is used. RS-485 allows a bus structure to be built

that allows addition or removal of stations or the step-by-step commissioning of the system without

influencing other stations. Subsequent expansions (within defined limits) have no effect on stations

already in operation. The transmission rate can be set between 9.6 Kbit/s and 12 Mbit/s, however,

all PROFIBUS DP within a system must operate at the same rate.

Up to 32 stations (master or slaves) can be connected to a single segment. If more than 32 stations

are required, repeaters may be used. The maximum permissible line length depends on the

transmission rate. Four RS-485 cable types (Types A - D) for designed for different applications are

available on the market. PI recommends the use of cable type A.

More details on designing networks are to be found in Chapter 3.

RS-485 IS RS-485 IS is a recent innovation in response to an increasing market demand for the use of RS-485

in explosion-hazardous areas. A corresponding PROFIBUS guideline is now available that specifies

the configuration of intrinsically safe RS-485 solutions with simple device interchangeability. It

details the current and voltage levels that must be adhered to by all stations in order to ensure safe

functioning during interconnection. When active sources are connected, the sum of the currents of

all stations must not exceed the maximum permissible current allowed by the circuitry. In contrast

to the FISCO model (see below), all stations represent active sources. Up to 32 stations can be

connected to the intrinsically safe bus circuit.

MBP IEC-61158-2 physical layer describes several connection technologies. PROFIBUS uses only one:

MBP ("Manchester Coding" and "Bus Powered"). To avoid confusion, PROFIBUS International has

decided to use MBP in all its literature in future.

MBP is synchronous transmission at a defined transmission rate of 31.25 Kbit/s using Manchester

coding. It is used in process automation as it also satisfies the key demands for intrinsic safety and

two-wire bus power. MBP transmission technology is usually limited to specific segments within a

plant, which are then linked to a RS485 segment via a segment coupler or link, see Chapter 4. Tree

or line structures (and any combination of the two) are network topologies supported by PROFIBUS

with MBP transmission with up to 32 stations per segment and max. 126 per network.

FISCO Model The FISCO model (Fieldbus Intrinsically Safe Concept) considerably simplifies the planning,

installation and expansion of PROFIBUS networks in explosion-hazardous areas. It stipulates that a

network is intrinsically safe and requires no individual intrinsic safety calculations provided the four

relevant bus components (field devices, cables, segment couplers and bus terminators) fall within

predefined voltage, current, output, inductance and capacity limits. The corresponding proof is

provided by certification of the components through authorized accreditation agencies, such as PTB

and BVS (Germany) or UL and FM(USA). When FISCO-approved devices are used, not only is it

possible to operate more devices on a single line, but the devices can also be replaced or the line can

be expanded during operation without the need for time-consuming calculations or system

certification. MBP with FISCO model is sometimes referred to as MBP-IS.

Fiber optics Fiber optic transmission is used for fieldbus applications that preclude the use of copper wires, e.g.

for environments with very high electromagnetic interference or when particularly large distances

need to be covered. PROFIBUS guideline (2.021) for fiber optic transmission specifies the

technology available for this purpose, including multimode and single mode glass fiber, plastic fiber,

and HCS® fiber. When determining these specifications, great care was naturally taken to allow

problem-free integration of existing PROFIBUS devices in a fiber optic network without the need to

change the protocol behavior of PROFIBUS. This ensures backward compatibility with existing

PROFIBUS installations.

Page 18: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

16 Endress+Hauser

2.2.2 PROFIBUS DP communication protocol

PROFIBUS DP is designed for fast data exchange at control and field level. The exchange of data

with distributed devices is primarily cyclic and the associated communication functions are specified

by the basic PROFIBUS DP protocol (version DP-V0). The special demands of particular applications

have meant that the basic functionality has been gradually expanded, so that now three versions are

available: DP-V0, DP-V1 and DP-V2. All versions are specified in IEC 61158.

System configuration and

device types

DP supports implementation of both mono-master and multi-master systems. This affords a high

degree of flexibility during system configuration. A maximum of 126 devices (masters or slaves) can

be connected to a bus. In mono-master systems, only one master is active on the bus during

operation of the bus system. The device types are as follows:

• DP master class 1 (DPM1) is a central controller that cyclically exchanges information with the

distributed stations (slaves) at a specified message cycle. Typical DPM1 devices are

programmable logic controllers (PLCs) or PCs. A DPM1 has active bus access with which it

can read measurement data (inputs) of the field devices and write the setpoint values (outputs)

of the actuators at fixed times. This continuously repeating cycle is the basis of the automation

function.

• DP master class 2 (DPM2) are engineering, configuration or operating devices. They are

implemented during commissioning and for maintenance and diagnostics in order to configure

connected devices, evaluate measured values and parameters and request the device status. A

DPM2 does not have to be permanently connected to the bus system. The DPM2 also has

active bus access .

Slaves are peripherals (I/O devices, drives, HMIs, valves, transducers, analyzers) that read in

process information and/or use output information to intervene in the process. There are also

devices that solely process input information or output information. As far as communication

is concerned, slaves are passive devices, they only respond to direct queries. This behavior is

simple and cost-effective to implement (in the case of DP-V0 it is already completely included

in the hardware).

Figure 2-10 shows the system configuration of a mono-master system. The PLC is the central

control component. The slaves are decentrally coupled to the PLC over the transmission medium.

This system configuration enables the shortest bus cycle times. In multi-master systems several

masters are connected to one bus. They represent either independent subsystems, comprising one

DPM1 and its assigned slaves, or additional configuration and diagnostic devices.

Fig. 2-10: Basic principle of Version DP-V0 in mono-master system

Version DP-V0 Version DP-V0 provides the basic functionality for a mono-master architecture with high-speed,

deterministic master-slave communication, see Fig. 2-10, including:

• cyclic data exchange

• station, module and channel-specific diagnostics

• four different interrupt types for diagnostics and process interrupts

• pulling and plugging of stations.

The master can be a personal computer or programmable logic controller.

Controller

Cyclic communication in master-slave relationship

PROFIBUS DP

Page 19: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 17

Version DP-V1 Fig. 2-11 shows the standard architecture for PROFIBUS DP, Version DP-V1. This contains

enhancements for process automation, in particular acyclic data communication for parameter

assignment, operation, visualization and interrupt control of intelligent field devices from a so-called

Class 2 master. In addition, it offer three additional interrupt types: status interrupt, update interrupt

and a manufacturer-specific interrupt.

Fig. 2-11: Standard architecture for Version DP-V1

Cyclic and acyclic

communication

Cyclic data communication between the DPM1 and its assigned slaves is automatically handled by

the DPM1 in a defined, recurring sequence. The user defines the assignment of the slave(s) to the

DPM1 when configuring the bus system. The user also defines which slaves are to be included/

excluded in the cyclic user data communication. Data communication between the DPM1 and the

slaves is divided into parameterization, configuration and data transfer. Before the master includes

a DP slave in the data transfer phase, a check is run during the parameterization and configuration

phase to ensure the correct configuration.

In addition to the station-related user data communication, which is automatically handled by the

DPM1, the master can also send control commands to all slaves or a group of slaves simultaneously.

These control commands are transmitted as multicast commands and enable sync and freeze modes

for event-controlled synchronization of the slaves.

For safety reasons, it is necessary to ensure that DP has effective protective functions against

incorrect parameterization or failure of transmission equipment. For this purpose the DP master and

the slaves are fitted with monitoring mechanisms in the form of time monitors. The monitoring

interval is defined during configuration.

Acyclic data communication is the key feature of version DP-V1. This forms the requirement for

parameterization and calibration of the field devices over the bus during runtime and for the

introduction of confirmed alarm messages. Transmission of acyclic data is executed parallel to cyclic

data communication, but with lower priority.

Addressing with slot and index is used both for cyclic and acyclic communication services. When

addressing data, PROFIBUS assumes that the physical structure of the slaves is modular or can be

structured internally in logical functional units, so-called modules. The slot number addresses the

module and the index addresses the data blocks assigned to a module. Compact devices are

regarded as a unit of virtual modules. These can also be addressed with slot number and index.

Class 1 masterController

Cyclic communication in master-slave relationship

PROFIBUS DPO

rder C

od

e XX

XX

XX

XX

XX

XX

XX

XX

XX

Ser.-No. X

X X

XX

XX

Mat. 1.4571 / A

l3 O2 / FP

MIP

65

P -1 ... 2 b

ar

U 10,5 ... 45 V

DC

P 20 b

ar

4...20 mA

Inten

sor

P Sp

an 100 m

bar

min

max

Patented

Acyclic communication in master-slave relationship

Class 2 mastere.g. ParametrizationMedium access

by token passing

PROFIBUS PA

Coupler

Page 20: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

18 Endress+Hauser

Version DP-V2 Version DP-V2 contains further enhancements to DP-V1 and is geared towards the demands of

drive technology. Due to additional functionalities, such as isochronous slave mode and lateral slave

communication (DXB) etc., DP-V2 can also be implemented as a drive bus for controlling fast

movement sequences in drive axes.

Fig. 2-12: Slave-to-slave communication with Version DP-V2

The enhancements are as follows:

• Slave-to-Slave Communication enables direct, time-saving, communication between slaves

without the detour over a master. Figure 2-12 shows the mechanism. On the command of the

master, one slave acts as "publisher" and broadcasts its information to other slaves embedded

in the sequence, the so-called "subscribers". This enables slaves to sense data from other slaves

and use them as their own input. This not only opens up a new range of applications, it also

reduces response times on the bus by up to 90 %.

• Isochronous mode enables clock synchronous control in masters and slaves, irrespective of the

bus load. The function enables highly precise positioning processes with clock deviations of less

than a microsecond. All participating device cycles are synchronized to the bus master cycle

through a "global control" broadcast message. A special sign of life (consecutive number) allows

monitoring of the synchronization.

• Clock control synchronizes all stations to a system time with a deviation of less than one

millisecond. This allows the precise tracking of events. This is particularly useful for the

acquisition of timing functions in networks with numerous masters. It facilitates the

diagnostics of faults as well as the chronological planning of events.

• Upload and download allows the loading of any data area in a field device, irrespective of size,

with a single command. This enables, for example, programs to be updated or devices replaced

without the need for manual loading processes.

Input data via broadcastOutputdata

Slave-to-slave communcation

PROFIBUS DPMaster Class 1

Publishere.g. light array

Slave

Subscribere.g. drive

Slave

Subscribere.g. drive

Slave

Page 21: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 19

2.2.3 Application profiles

PROFIBUS offers a range of application profiles that simplify its use in specific industries or

applications. Profiles are manufacturer and user specifications that determine properties,

performance features and behavior for a particular set of devices or system. They take into account

application, field device type characteristics, control features and the means of integration

(engineering). Conformance with the profile facilitates device interoperability and

interchangeability. A profile may encompass only a few specifications for a specific device class or

extend to a set of comprehensive application specifications for a specific industry.

PROFIBUS makes a distinction between common application profiles with implementation options

for different applications, application profiles and system and master profiles. The common profiles

include, for example, PROFIsafe, Redundancy and Time Stamp. PROFIdrive, SEMI or PA Devices

are examples of application profiles. The system and master profiles describe the system

performance that is available to field devices.

A short description of PROFIsafe and PROFIdrive follows this section. More information on the

other profiles can be found on the PROFIBUS web site www.profibus.org.

2.2.4 PROFIsafe

PROFIsafe is an optional, common application profile that allows safety-relevant devices to be

connected to the same single transmission line as standard devices. These then communicate with

an additional safety programmable logic controller or a combined standard/safety-controller.

For applications such as presses, saws, robots, chemical processes, burners etc., special precautions

are necessary to avoid risk to operators, environment or investment. Traditionally, safety systems

are hard-wired, i.e. based on relays or a similar trusted and tangible technology. In recent years,

however, safety automation has seen an influx of microcontrollers, software and communication

networks, which have now been proven in use in millions of applications. The basis for their use is

laid down in international safety standard IEC 61508. This details the measures required for the

detection and management of errors and failures, together with the description of systematic

software development processes.

PROFIsafe merges standard automation and safety automation in one technology, thus providing

higher efficiency to the user. It is available in products such as programmable and numerical

controllers, remote I/Os, laser scanners, light curtains, motor starters, frequency converters, drives,

gas and fire sensors etc.. Its safety measures are added to the device as a safety layer on top of the

existing PROFIBUS layers in the communication stack. This layer is responsible for the transmission

of safety relevant process data (safety application) as well as the unchanged existing standard

application for non-safety critical functions, like e.g. diagnosis.

PROFIsafe uses single-channel transfer and its error detection mechanisms are totally independent

of the underlying PROFIBUS DP (black channel principle). The safety data are packed in the

PROFIBUS telegram frame as a supplement to the standard data. This is then passed completely

unmodified from a (safety) sender to a (safety) receiver no matter what kind of transmission system

is used. Different industry requirements are taken into account. Factory automation deals with short

signals processed at very high speed, while process automation involves longer process values that

may take more time. PROFIsafe therefore offers two different process data lengths limited to a

maximum of 12 bytes and 122 bytes respectively.

Page 22: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

20 Endress+Hauser

2.2.5 PROFIdrive

PROFIdrive is an application profile that addresses the specific requirements of motion control. It

utilises the new functions realised in PROFIBUS Version DP-V2: clock cycle synchronisation and

slave-to-slave communication. PROFIdrive allows intelligent drives to be used in decentralised

automation structures. Digital servo-drives can also be synchronised and position control loops can

be closed via PROFIBUS.

Drive application classes The integration of drives into automation solutions depends strongly on the task of the drive. To

simplify use, PROFIdrive defines the following generic application classes:

• Standard drive

In the simplest case, the drive is controlled via a main setpoint (e.g. rational speed) by

PROFIBUS. The complete closed-loop speed control is carried out in the drive controller. The

application case is employed primarily in the area of conventional drive technology, e.g. in

conveying systems.

• Standard drive with technological function

This class is a very flexible variant for realising automation applications. This involves breaking

down the entire automation process into several small subprocesses. The automation functions

are no longer located exclusively in the central automation drive but can be distributed in the

drive controllers. In this respect, PROFIBUS serves as the technology interface. Distribution of

automation functions assumes that communication is possible in all directions. Thus slave-to-

slave communication is required, e.g. between setpoint cascades, winders and applications for

rotational speed synchronisation for continuous web processes.

• Positioning drive

In addition to the drive controller, the drive also contains a position controller. Positioning

tasks are forwarded to the drive controller and started by PROFIBUS. Position drives have a

very wide scope of application, for example, the twisting on and off of lids in a bottling plant,

or the positioning of knives in a foil-cutting maschine.

Device model PROFIdrive defines a device model as it can be found - at least partly - in any drive system. The

device comprises multiple functional modules which work together and thereby reflect the

intelligence of the drive system. Objects are assigned to these functional modules, which then

constitute the interface to the automation process. The objects are described and their functions

defined in the profile. Parameters are assigned to the objects, which are collectively referred to as

the "profile parameters". These include such functions as fault buffers, drive control, device

identification, process data configuration and the overall parameter list.

All other parameters, which can number more than 1000 in the case of complex devices, are

manufacturer-specific. This provides the producers with the utmost flexibility in realising control

functions such as ramp-function generators. The profile does not determine the parameters of the

latter, although it does determine its interface to the control program through the control word. This

means that the control system remains identical, even if a user changes the drive manufacturer.

Since control and parameter creation tools are manufacturer-specific, they can determine and

visualise all the parameter information either directly from the drive or from a device description file.

Central motion control Robotics and tool maschine applications call for a coordinated motional sequence of muliple drives.

The motion is controlled mostly with the aid of a central numerical control system (CNC). The

position control loop is closed via the bus. The clock cycle synchronisation from PROFIBUS Version

DP-V2 is employed in order to synchronise the clock pulses of the position controller in the control

system and the controllers in the devices. The stiffness and the dynamics of the control loop can be

increased significantly by simple means with the aid of the new "dynamic servo control" position

control concept that is also decripted in the profile. Thanks to this concept, even highly demanding

applications with linear motors can be realised.

Page 23: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 21

2.2.6 Integration technologies

Modern field devices in both Factory and Process Automation provide a wide range of information

and execute functions that were previously in the domain of PLCs and control systems. For this

reason, tools for commissioning, maintenance, engineering, and parameterization of these devices

require an exact and complete description of device data and functions. This includes type of

application function, configuration parameters, range of values, units of measurement, default

values, limit values, identification, etc. The same applies to the controller/control system, the

device-specific parameters and data formats of which must also be made known (integrated) to

ensure error-free data exchange with the field devices.

PROFIBUS has developed a number of methods and tools ("integration technologies", GSD, EDD

and DTM) which enable standardization of device management. The performance range of these

tools is optimized to specific tasks (simplest handling, device-tuning at runtime,etc.), which has

given rise to the term scaleable device integration. GSD and EDD are both types of "Electronic

device data sheets", developed with different languages, whilst a DTM (Device Type Manager) is a

software component containing specific field device functions for parameterization, configuration,

diagnostics and maintenance, generated by mapping and to be used together with the universal

software interface FDT (Field Device Tool), which is able to implement software components.

More information on GSD files are to be found in Chapters 3 and 4. Information on EDD can be

found on the PROFIBUS site www-profibus.com. A short overview of FDT technology is to be found

in Section 2.4.

2.2.7 Quality assurance

In order for PROFIBUS devices of different types and manufacturers to correctly fulfil their tasks in

the automation process, it is essential to ensure error-free exchange of information over the bus.

This requires an implementation of communications protocol and application profiles in compliance

with the standard. To ensure that this requirement is fulfilled, the PNO has established a quality

assurance procedure, whereby on the basis of test reports, certificates are issued to devices that

successfully complete the test .

The certification procedure is based on European standard EN 45 000. The PROFIBUS User

Organization has approved independent test laboratories in accordance with the specifications of

this standard. Only these test laboratories are authorized to carry out device tests that form the basis

for certification. The test procedure, which is the same for all test laboratories, is made up of several

parts:

• GSD/EDD Check: ensures that the device description files comply to the specification.

• Hardware Test: tests the electrical characteristics of the device’s PROFIBUS interface for

compliance to the specifications. This includes terminating resistors, suitability of the

implemented drivers and other modules and the quality of line level.

• Function Test: examines the bus access and transmission protocol and the functionality of the

test device.

• Conformity Test: forms the main part of the test. The object is to test conformity of the protocol

implementation with the standard.

• Interoperability Test: checks the test device for interoperability with PROFIBUS devices of

other manufacturers in a multi-vendor plant. This checks that the functionality of the plant is

maintained when the test device is added. Operation is also tested with different masters.

Once a device has successfully passed all the tests, the manufacturer can apply for a certificate from

the PROFIBUS User Organization. Each certified device contains a certification number as a

reference. The certificate is valid for 3 years but can be extended after the devices undergoes a

further test.

Page 24: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

22 Endress+Hauser

2.3 PROFIBUS PA

PROFIBUS PA (Process Automation) is an extension of PROFIBUS DP tailored to the requirements

of process automation. It has two main characteristics:

• Participants can draw (intrinsically safe) power from the bus

• Data transfer is handled according to the international standard IEC 61158-2.

PROFIBUS PA was designed to provide an economic and versatile replacement for convention

process control systems, as shown in Fig. 2-13.

Fig. 2-13: Signal transmission: conventional and via PROFIBUS PA

One obvious advantage of PROFIBUS is the substution of point-to-point wiring, marshalling racks,

barriers and power supplies by a single bus cable. The technology also leaves a much smaller

footprint in the control cabinet.

The other benefits are less tangible, but more important economically. Digital communication

allows comfortable commissioning of field devices from the control room. Individual devices can

not only be configured from a personal computer but the settings can also be archived centrally. If

there are several identical measuring points in an application, the stored parameters can be

downloaded to the devices. An individual configuration of each device is no longer necessary.

Other benefits lie in operation and maintenance. PROFIBUS PA devices (and their DP equivalents)

offer more information. Every parameter in the device can be accessed, provided an appropriate tool

is available. By using Endress+Hauser’s FieldCare asset management tool, for instance, the device

status can be monitored and reports on device health can be generated as desired. The device serial

number can also be read, and linked via Internet to a common equipment record at Endress+Hauser

that contains the device history. The same parameter also gives access to spare parts and e-business

ordering procedures.

Conventional

Con

trol r

oom

Fiel

d

PROFIBUS PA

connectors

process-near component PNC process-near component PNC

I/O assemblies bus couplerEx [i]

marshalling rack

marshalling rack

junction box

Ex [i] power

Page 25: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 23

PROFIBUS PA in process

engineering

Most manufacturing facilities have a mixture of tasks which are associated with both process and

factory automation:

• Process automation: measurement, actuation, control...

• Factory automation: filling, storage, conveyance, drives...

For this reason, Endress+Hauser devices installed in a factory will be integrated into PROFIBUS DP,

PROFIBUS PA or mixed systems.

Fig. 2-14: Prozess automation with PROFIBUS DP and PROFIBUS PA

Fig. 2-14 shows a typical architecture:

• The process is controlled by a process control system or a programmable logic controller (PLC).

The control system or PLC serves as a Class 1 master. It uses the cyclic services to acquire

measurements and output control commands. The operating program, e.g. FieldCare, serves

as a Class 2 master. It uses the acyclic services and serves to configure the bus participants

during installation and normal operation.

• The PROFIBUS DP system is used to handle the communication at the control level. Drives,

remote I/Os etc. may all be found upon the bus. It is also possible to connect externally

powered field devices to this level, e.g. the flowmeters Promass and Promag. PROFIBUS DP

ensures that data are quickly exchanged, whereby in mixed PROFIBUS DP/PA systems the

baudrate supported by the segment coupler is often the limiting factor.

• PROFIBUS PA is used at field level. The segment coupler serves both as interface to the

PROFIBUS-DP system and as power supply for the PROFIBUS PA field devices. Depending

upon the type of segment coupler, the PROFIBUS PA segment can be installed in safe or

hazardous areas.

The practical implementation of such an architecture is the subject of this manual.

e.g. FieldCare PLC / PLS

process control system

PROFIBUS DP

PROFIBUS PA MBPsegment coupler

RS 485up to 12 Mbit/s

Non-hazardous area

Explosion-hazardous area MBP31,25 kBit/s

31,25 kBit/s

Page 26: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

24 Endress+Hauser

2.3.1 Operating principle

The PROFIBUS PA bus system is powered by a segment coupler. The field devices function as

current sinks and draw a direct current of about 10 mA from the bus cable (some participants

require more). This current supplies the energy necessary for operation. If a field device transmits

data, it does so by modulating the current by ±9 mA. The functional principle is displayed in Fig 3.8.

When it is transmitting data, the fieldbus acts as an ohmic resistance. Since the device does not

output power, the intrinsic safety of a bus segment is largely determined by the current and voltage

limitations placed on the bus power supply (segment coupler).

In order that a field device does not block the bus should it fail, its maximum current consumption

is limited by the so-called fault disconnection electronics (FDE). This current must be considered

when the segment is planned. See corresponding examples in Chapter 5.6.

Fig. 2-15: Function of a PROFIBUS PA device

Fault disconnection

electronics

An important requirement for participants on a PROFIBUS PA segment, is that a defective device

may not detrimentally effect the functioning of the system. The fault disconnection electronics

ensure that high current consumption is not possible. An electronic circuit detects the rise in the

basis current above the specified manufacturer's value and either limits the current consumption or

isolates the participant from the bus. The increase in basic current above the normal value in the

event of a fault is designated the fault current.

mac. current

field device current

basic

fault current

current

Page 27: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 25

2.3.2 Applications in hazardous areas

The explosion protection concept for the PROFIBUS PA fieldbus is based on the type of protection

"intrinsic safety i". In contrast to other types of explosion protection, intrinsic safety is not confined

to the individual unit, but extends over the entire electrical circuit. All circuits connected to the

PROFIBUS PA fieldbus must be realised with type of protection "intrinsic safety", i.e. all devices and

terminators that are installed in hazardous areas as well as all associated electrical apparatus (e.g.

PA links or segment couplers) must be approved for the corresponding atmospheres.

FISCO model In order to reduce the proof of intrinsic safety of the fieldbus system, comprising different devices

from different vendors, to a justifiable level, the German PTB and various equipment manufacturers

developed the FISCO model (Fieldbus Intrinsically Safe COncept). Further information on FISCO

is to be found in Chapter 3.8.

The basic idea is that only one device supplies power to a particular fieldbus segment. The model

determines the boundary conditions. The field devices are divided into those that draw their power

from the bus itself and those that must be powered locally. In addition to the type of protection

"intrinsic safety", the latter devices, which require more energy, must also exhibit a further type of

protection. The auxiliary energy required by the segment coupler and the locally powered devices

is galvanically isolated from the intrinsically safe circuits.

As is the case for all intrinsic circuits, special precautions must be observed when installing the bus.

The aim is to maintain the separation between the intrinsically safe and all other circuits.

Grounding The intrinsically safe fieldbus circuit is operated earth-free, which does not preclude that individual

sensor circuits can be connected to ground. If a overvoltage protector is installed before the device,

it must be bonded to the plant grounding system in accordance with the instructions in the

certificate or device manual. Particular attention must be paid to the grounding of the conducting

cable screening because if it is to be earthed at several positions, a high integrity plant grounding

system must be present.

Category The category of the intrinsically safe field bus is determined by the circuit with the worst rating, i.e.

if the fieldbus circuit of one device has the type of protection EEx ib, then the whole fieldbus falls

in the category ib. Devices that must be connected to a circuit with type of protection EEx ia

(requirements as per certificate) may not be operated on field bus circuits with type of protection ib.

Only circuits that are connected directly to the fieldbus must be considered here.

Explosion group Devices that are approved for different explosion groups (IIC, IIB or IIA) can be operated on the

same segment. The permissible explosive atmosphere allowed at a particular device is determined

by the type of protection of that device as well as the explosion group for which the segment coupler

is approved. All devices and terminators that are installed in hazardous areas as well as all associated

electrical apparatus (e.g. PA links or segment couplers) must be approved for the corresponding

atmospheres, e.g. PTB, BVS, FMRC, CSA etc.).

Page 28: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

26 Endress+Hauser

2.4 Field Device Tool (FDT)

Field Device Tool (FDT) provides a standard interface, open to all communication protocols and

software environments that allows any device to be accessed from any host through any protocol.

The essential parts of FDT technology are the frame application and the so-called Device Type

Managers (DTMs), which are available for field devices and communication equipment, see

Fig. 2-16 The two components could be likened to the Print Manager in a Windows Office program

and the Print Drivers that must be installed to make printers work and which contain a graphical

user interface for their configuration.

Fig. 2-16: Schematic diagram of FDT frame

FDT Frame The FDT frame communicates with the hosting or stand-alone application and the device drivers

via a set of standardised interfaces. All data are exchanged through these interfaces, including those

generated within the application for engineering, DTM management and device configuration. It is

no longer necessary to use proprietary interfaces to operate devices or build up communication

paths. Frame applications can be device configuration tools, control system-engineering tools,

operator consoles or asset management tools. The frame application is also open to all

communication technologies, e.g. for HART, PROFIBUS and FOUNDATION Fieldbus, see Fig 2-16.

Proprietary service bus protocols can also be integrated simply into the frame application because of

the standardised interface.

Device DTM The device DTM is a software driver developed by the device manufacturer for each of his devices

or group of devices. The DTM encapsulates all the device-specific data, functions and management

rules such as the device functions, its communication capabilities, internal data structure and

dependencies as well as the user interface elements. It provides functions for accessing device

parameters, configuring and operating the devices, calibrating, and diagnosing problems. DTMs can

range from a simple user interface for setting device parameters to a highly sophisticated application.

They may perform complex calculations for diagnosis and maintenance purposes or display results

in the form of curves, trends and other graphical elements.

Communication DTM For communication equipment, such as gateways, multiplexers and other hardware interfaces a

CommDTM is required. Like any communication driver, this converts data from one protocol to

another, but with the difference that the integration into the system is via a standardised FDT rather

than a proprietary interface. This means that users wishing to integrate existing communication

equipment into a FDT frame application require only the corresponding CommDTMs. Similarly,

vendors need only modify their existing drivers to include a FDT interface and their equipment can

be integrated into any FDT frame application.

FDTframe program

NetworkconfigurationNavigationUser ManagementDTM ManagementData Management

Communication InterfacesHART, PROFIBUS, FF

DTM: Device Type Manager

Plant Network (Devices, Drives, PLCs, etc.)

Page 29: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 2 Introduction to PROFIBUS

Endress+Hauser 27

FDT also includes the concept of 'Nested Communication', so that with the aid of CommDTMs, the

communication hierarchies found in the plant can be replicated simply in the hosting configuration

tool. In this way, the FDT architecture eliminates the integration problems that normally occur

when different devices must communicate with each other. It also provides transparent access to

data at all system levels.

Fig. 2-17: FDT/DTM Technology - Fieldbus- and device management

The FDT standard uses XML and of is modular construction, each standardised interface reflecting

a certain functionality such as configuration or display of measured values. This scalable approach

allows DTMs to be developed that exactly match device capabilities and keep up improvements

within its life-cycle. There is no reduction of functionality here. FDT is also extendable: new

interfaces can be added to cater for functional system enhancements. Not only does this ensure that

the standard will keep pace with technical advance, it also ensures that future developments will

not affect existing solutions.

DTM Production A Device Type Manager file can written from scratch or be produced from a EDD or HART DD file

by running the latter through a special DTM compiler. The Comm DTM is a separate entity that is

used to map the communication infrastructure existing in the field. The DTM compilation process

is largely automatic and as long as an EDD or HCF DD file exists for the device, a corresponding

DTM can be produced. This makes the integration of legacy HART or PROFIBUS devices into an

FDT frame application a practical proposition. The FDT tool can then run in parallel to the existing

system device configuration tool. For new FDT based installations, the frame application may be

stand-alone or integrated into the control system. This has enormous benefits for the user, since he

has freedom of choice in the components he uses. Any device or communication component with

a device DTM or Comm DTM will operate in any FDT-based configuration tool. Seen for the

operators point of view: a single FDT frame can be used to operate a range of devices from a number

of different vendor.

FDT-Applicatione.g. FieldCare

PLC

Segment coupler

PROFIBUS PA

PROFIBUS DP

DTM

DTM

DTM

DTM

DTM

DTM

Communication-

Device-DTMs&

4...20 mAHART

Engineering tool

PROFIBUS PA-Slaves

Remote I/O

DTM

Page 30: Endress+Hauser Profibus Planing Guide

2 Introduction to PROFIBUS PROFIBUS planning and commissioning

28 Endress+Hauser

FDT Joint Interest Group The non profit making FDT Joint Interest Group is an open collaboration of international automation

companies for the proliferation of FDT/DTM technology. The group is open to all companies and

organizations that wish to participate. The mission of the FDT Joint Interest Group is to promote the

acceptance and usage of FDT technology in the factory automation industry, process automation

industry and hybrid application industry.

Endress+Hauser is a founding member of the FDT Joint Interest Group and servers on the

Marketing and Steering Committees. The PROFIBUS User Organisation (PNO) has granted to the

FDT Joint Interest Group ownership rights to use the technology. PNO is the association of users of

Profibus technology. FDT technology is available to all companies that wish to utilize it.

The Groups headquarters are in Germany/America. For more information on FDT technology and

the FDT Joint Interest Group, see web site http://www.fdt-jig.org

Page 31: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 3 PROFIBUS DP basics

Endress+Hauser 29

3 PROFIBUS DP basics

As far as PROFIBUS systems in process engineering are concerned, the versions PROFIBUS DP

(variant DP-V1) and PROFIBUS PA are of interest. This chapter describes the basics of PROFIBUS

DP.

The chapter is structured as follows:

• Synopsis

• Topology

• Bus access method

• Network configuration

• Applications in hazardous areas

3.1 Synopsis

Fig. 3-1: PROFIBUS DP-System, Version DP-V1

Application PROFIBUS DP is used primarily for factory automation. In PROFIBUS PA systems for process

automation, a PROFIBUS DP system is used at the control level for quick transmission of the data.

Here, PROFIBUS DP-V1 is normally used. In addition to the cyclic exchange of data with a PLC,

DP-V1 allows the field devices to be configured via acyclic services. The principle technical data for

PROFIBUS DP are listed in Table 3-1 below.

Table 3-1: Technical data PROFIBUS DP

Class 1Master PLC

Class 2Master

PROFIBUS DP

PROFIBUS DP Slaves

e.g. FieldCare

Standard IEC 61158

Support PROFIBUS User Organisation e.V. (PNO)

Physical layer RS-485 and/or fibre optics

Max. length – max. 1200 m without repeater (RS 485),

max. 9 repeaters

– or several kilometers (fibre optics)

Participants max. 126, including max. 32 as master

Transmission rate 9.6 kBit/s up to 12 MBit/s in defined levels

Bus access method Token passing with master-slave

Protocol DP-V0; DP-V1; DP-V2

Page 32: Endress+Hauser Profibus Planing Guide

3 PROFIBUS DP basics PROFIBUS planning and commissioning

30 Endress+Hauser

Participants Depending upon the application at hand, the participants in a PROFIBUS DP system might be

frequency converters, remote I/Os, actuators, sensors, links, gateways etc. as well as the PLC or

process control system. The following Endress+Hauser devices can be connected directly to a

PROFIBUS DP system:

Table 3-2: Available Endress+Hauser PROFIBUS DP products

Type/Name Function and Application

ASP 2000 Stationary precision water sampler for water and wastewater

applications

FieldCare Plant Asset Mangement - universal, FDT-based, operating

tool for field devices with PROFIBUS PA/DP and other

protocols

Liquisys M pH/ORP, conductivity, oxygen, turbidity, chlorine

measurement for water and waste water

Memo-Graph RSG 10 16/7 channel (analog/digital) videographic display recorder

for where exact recording is required

Promag 53 Magnetic-inductive flow measurement for inductive liquids

Promass 83 Coriolis mass flow measurement for liquids, steam and gases

Prosonic DP (FMU 86x) Ultrasonic level and flow measurement for solids and liquids

Prosonic Flow 93 Ultrasonic flow measurement for liquids

RMS 621 Energy manager for water and steam with up to 10 inputs for

1-3 applications

Smartec S Measurement of conductivity and concentration in highly

conductive liquids

ZA 375 PROFIBUS DP gateway for Commutec

Page 33: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 3 PROFIBUS DP basics

Endress+Hauser 31

3.2 Topology

PROFIBUS DP is based on a linear topology. For lower data transmission rates, a tree structure is

also possible.

Cable (Type A) EN 50 170 specifies two types of bus cable. For transmission rates up to 12 Mbit/s, cable type A is

recommended. The specification is given in Table 3-3:

Table 3-3: Specifications of Cable Type A

Structure The following points should be noted when the bus structure is being planned:

• The max. permissible cable length depends upon the transmission rate. For PROFIBUS RS-485

cable of type A (see table 2.3) the dependency is as follows:

• A maximum of 32 participants per segment is allowed

• A terminating resistance must be installed at both ends of every segment (ohmic load 220 Ω)

• The cable length and/or the number of participants can be increased by using repeaters

• If repeaters are used:

– The first and last segment may contain up to 31 particpants, the segments between repeaters

may contain up to 30 participants.

– The maximum distance between two participants is:

(NO_REP +1) * Segment length

where = NO_REP = max number of repeaters that may be used in series (dependent on type).

Example: According to a manufacturer’s specifications, up to 9 repeaters can be connected in series

on a standard line. The maximum distance between two bus participants for a transmission speed

of 1.5 MBit/s is thus:

(9+1)*200 m = 2000 m

Terminator 135 Ω to165 Ω at a measuring frequency of 3 MHz to 20 MHz

Cable capacitance < 30pF per Meter

Core cross-section > 0.34 mm², corresponds to AWG 22

Cable type twisted pairs, 1x 2, 2x 2 or 1x 4 core

Loop resistance 110 Ω per km

Signal attenuation max. 9 dB over the entire length of the segment

Screening woven copper sheath or woven sheath and foil sheath

Transmission rate (kBit/s) 9.6; 19.2; 45.45; 93.75 187.5 500 1500 3000; 6000; 12000

Cable length (m) 1200 1000 400 200 100

Page 34: Endress+Hauser Profibus Planing Guide

3 PROFIBUS DP basics PROFIBUS planning and commissioning

32 Endress+Hauser

Spurs A spur is the cable connecting the field device to the T-box on the bus.

" Caution!

As a rule of thumb:

• For transmission rates up to 1.5 MBit/s, the total length (sum) of the spurs may not exceed

6.6 m

• Spurs should not be used for transmission rates greater than 1.5 MBit/s.

Examples Figs 3-2 and 3-3 show examples for a linear and tree bus structure.

• Fig 3-2. shows that three repeaters are necessary if the PROFIBUS DP system is to be

developed to the full. The maximum cable length corresponds to 4x the value quoted in the

table above. Since three repeaters are used, the maximum number of participants is reduced

to 120.

• Fig 3-3 shows how several repeaters can be used to create a tree structure. The number of

participants allowable per segment is reduced by one per repeater.

Fig. 3-2: PROFIBUS DP-system with linear structure(T = terminator, R = repeater, 1...n = max. number of field devices on a segment)

Fig. 3-3: PROFIBUS DP-system with tree structure(T = terminator, R = repeater, 1...n = max. number of field devices on a segment)

Page 35: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 3 PROFIBUS DP basics

Endress+Hauser 33

Optical network If the PROFIBUS DP system has to be routed over large distances or in plant with heavy

electromagnetic interference, then an optical or mixed optical/copper network can be used.

Provided that all participants support them, very high transmission rates are possible. Fig. 3-4 shows

a possible structure for an optical network, whereby the technical details can be taken from the

PROFIBUS standard.

Fig. 3-4: Example for a mixed optical/RS-485-network (T = terminator, 1...n = field devices (slaves)

Master(PLC)

RS 485

copper

opticalinterface module

opticalinterface modulel

fibre optics

Page 36: Endress+Hauser Profibus Planing Guide

3 PROFIBUS DP basics PROFIBUS planning and commissioning

34 Endress+Hauser

3.3 Bus access method

PROFIBUS DP uses a hybrid access method of centralised master/slave and decentralised token

passing, see Fig. 3-5. The masters build a logical token ring.

• When a master possesses the token, it has the right to transmit.

• It can now talk with its slaves in a master-slave relationship for a defined period of time.

• At the end of this time, the token must be passed on to the next active device in the token ring.

Master class PROFIBUS DP version DP-V1 differentiates between two classes of master:

• A Class 1 master communicates cyclically with its slaves. The master communicates only with

those slaves that are assigned to it. A slave may be assigned to only one Class 1 master. A typical

class 1 master is a programmable logic controller (PLC) or a process control system.

• A Class 2 master communicates acyclically with its slaves, i.e. on demand. Its slaves may also

be assigned to a Class 1 master. A typical example is a PC with corresponding operating

software, e.g. FieldCare - Plant Asset Management Tool. It is used for commissioning as well

as for device configuration, diagnosis and alarm handling during normal operation.

If a PROFIBUS-DP network has more than one master e.g. because both cyclic and acyclic services

are required, then it is a multi-master system. If, for example, a PLC only is used for control tasks,

then the system is a mono-master system.

Fig. 3-5: Data exchange in a PROFIBUS DP-multi-master system (M = master, S = slave)

Master 1, Class 1has the right to transmit.Data are exchangedcyclically.

Master 2, Class 2receives the right totransmit.It can talk to all slaves.Data exchage, e.g.with slave 3 is acyclic.

logical token ringbetween

Class 1

Class 2

master participants

Page 37: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 3 PROFIBUS DP basics

Endress+Hauser 35

3.4 Network configuration

Data transmission Data are exchanged over PROFIBUS DP by means of standard telegrams which are transmitted via

the RS-485 interface. The permissible telegram length of reference data is specified in the

PROFIBUS DP protocol at 244 bytes. it should be noted, however, that some controllers only

support an maximum telegram length of 122 bytes.

The PROFIBUS DP devices manufactured by Endress+Hauser may transmit both input and output

values, see also Table 5.17. In general:

• Measured value and status inputs are transmitted in 5 bytes.

• Display values and status outputs are transmitted in 5 bytes

• Control output values generally require 1 byte per action, the actual number available being

dependent upon device.

An instrument with several measured values can transmit correspondingly more bytes. In the case

of the flowmeter Promass 63, for example, a cyclic telegram up to 37 bytes (25 bytes input and 12

byte output data) is transmitted at maximum configuration, see Section 3.4.2. The values to be

transmitted are determined during the commissioning of the network. The total number of inputs

and outputs enabled then determine the telegram length. The same telegram is used for

transmission to and from the PLC.

GSD

(device database file)

In order to integrate the field devices into the bus system, the PROFIBUS DP system requires a

description of the device parameters such as output data, input data, data format, data length and

the transmission rates supported. These data are contained in the GSD device database file, which

is required by the PROFIBUS DP master during the commissioning of the communication system.

In addition, device bit maps are required, which appear as icons in the network tree. Further

information on device database files is to be found in Chapter 7.2.

Bus address A prerequisite for communication on the bus is the correct addressing of the participants. Every

participant in the PROFIBUS DP system is assigned a unique address between 0 and 125 (cyclic data

transmission). Normally the low addresses are assigned to the masters. The addresses may be

assigned by DIP switch, on-site operating elements or by an operating program, e.g. FieldCare.

The exact way in which this is done should be taken from the appropriate device manual. For

Endress+Hauser devices, the factory default address is always 126. This must be changed during

commissioning and no device in the system should use it for cyclic communication.

Transmission rate All participants in a PROFIBUS DP system must support the governing transmission rate. This means

that the speed of data exchange is determined by the slowest participant. In the case of

Endress+Hauser devices that are designed for PROFIBUS DP, all transmission rates from 9.6 kbits/

s to 12 Mbit/s are supported. For other manufacturers, please consult the relevant operating

manual.

Bus parameters In addition to the transmission rate, all active participants on the bus must operate with the same

bus parameters. If FieldCare is in use, the bus parameters can be set by using the corresponding

Communication DTM for PROFIBUS. Individual device rates are set within their DTMs. More

information on bus parameters are to be found in the Chapter 4.

Page 38: Endress+Hauser Profibus Planing Guide

3 PROFIBUS DP basics PROFIBUS planning and commissioning

36 Endress+Hauser

3.5 Applications in hazardous areas

All devices and terminators that are installed in hazardous areas as well as all associated

electrical apparatus (e.g. PA links or segment couplers) must be approved for the corresponding

atmospheres.

RS-485 IS RS-485 IS is a recent innovation in response to an increasing market demand for the use of RS-485

in explosion-hazardous areas. A corresponding PROFIBUS guideline is now available that specifies

the configuration of intrinsically safe RS-485 solutions with simple device interchangeability. In

contrast to the FISCO model (see Chapters 2.2.1 and 6.1), for which there is only one active supply

device per segment, all stations represent active sources. The devices are supplied with external

energy and can supply this to the bus. RS-485 IS segments are coupled to RS-485 safe segments by

means of so-called "Fieldbus Isolating Repeaters". Up to 32 stations can be connected to the

intrinsically safe bus circuit, provided the conditions in Table 3-7 arre upheld. More details can be

found in the specification.

Endress+Hauser devices do not support RS-485 IS at the present moment, but offers equivalent

solutions with standard devices.

The following table shows all safety-relevant values for the entire bus system.

Table 3-4: PROFIBUS RS_485 IS: list of safety-relevant parameters

Parameter Description Value Remarks

Bus system

Maximum input voltage Ui [V] ± 4.2

Maximum input current Ii [A] 4.8

Maximum inductance to resistance

ratio

L ’/R’ [µH/Ω] 15 For the whole operation Temperaturee range

of the bus system

Number of devices NTN ≤ 32

Communication device

Maximum output voltage Uo [V] ± 4.2

Maximum output current Iο [mA] 149 Total current from wires A, B and supply for

bus termination

Maximum input voltage Ui [V] ± 4.2

Maximum internal inductance Li [H] 0

Maximum internal capacitance Ci [nF] N/A Insignificant for safety

External active bus termination

Maximum output voltage Uo [V] ± 4.2

Maximum output current Iο [mA] 16

Maximum input voltage Ui [V] ± 4.2

Maximum internal inductance Li [H] 0

Maximum internal capacitance Ci [nF] N/A Insignificant for safety

Page 39: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 3 PROFIBUS DP basics

Endress+Hauser 37

If a PROFIBUS DP segment runs through an explosiion hazardous area, it must be executed with a

degree of protection "increased safety" "e".

• For copper cabling, the number of devices per segment is limited to four.

• Proof of instrinsic safety is required for every segment, since every intrinsically safe component

has different electrical characteristics.

• The cable and spurs must be included in the calculation.

• Exchange of a component from one manufacturer by a component from another manufacture

is always requires renewed proof of intrinsic safety.

Mixed network

PROFIBUS DP/PA

Since PROFIBUS PA systems are designed for use in hazardous areas, it is much easier install a

segment there. For this reason, a PROFIBUS PA segment is used to extend the PROFIBUS DP

segment into a hazardous area.

PROFIBUS PA networks are connected to PROFIBUS DP networks by a segment coupler or link,

see Chapter 3.2.

Fig. 3-6: The PROFIBUS DP system can be extended into a hazardous area by using a segment coupler/link.

PLCClass 1 master Class 2 master

e.g. FieldCare

segment coupler / link PROFIBUS DP

PROFIBUS DP-Slaves

PROFIBUS PA-Slaves

PRO

FIB

US

PA

Page 40: Endress+Hauser Profibus Planing Guide

4 PROFIBUS PA Basics PROFIBUS planning and commissioning

38 Endress+Hauser

4 PROFIBUS PA Basics

This chapter presents the basic principles behind PROFIBUS PA. It is structured as follows:

• Synopsis

• Segment couplers and links

• Topology

• Bus access method

• Network configuration

• Applications in hazardous areas

• Operating mode

• FISCO

• Fieldbus barriers

4.1 Synopsis

Application PROFIBUS-PA has been designed to satisfy the requirements of process engineering. There are three

major differences to a PROFIBUS DP system:

• PROFIBUS PA supports the use of devices in explosion hazardous areas without the need for

specific proof of intrinsic safety.

• The devices can be powered over the bus cable (two-wire devices).

• The data are transferred via the IEC 61158-2 physical layer (MBP), which allows great freedom

in the selection of the bus topology.

The most important technical data are listed in Table 4-1.

Participants Depending upon the application, the participants on a PROFIBUS PA segment might be actuators,

sensors and a segment coupler or link, see Chapter 4.2. Endress+Hauser offers PROFIBUS PA

instrumentation for the most important process variables, i.e. analysis, flow, level, pressure and

temperature. A complete list is to be found in Chapter 10.

Fig. 4-1: PROFIBUS PA-system

PLCClass 1 master Class 2 master

e.g. FieldCare

segment couplerPROFIBUS DP

PROFIBUS PA-Slaves

PROFIBUS PA

DP/PA link or

Page 41: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 4 PROFIBUS PA Basics

Endress+Hauser 39

Table 4-1: Technical data PROFIBUS PA

4.2 Segment coupler and links

PROFIBUS PA is always used in conjunction with a supervisory PROFIBUS DP control system. Since

the physical layer and transmission rates of PROFIBUS DP and PROFIBUS PA are different, see

Tables 3-1 and 4-1, the PROFIBUS PA segment is connected to the PROFIBUS DP system via a

segment coupler or link.

Segment couplers are signal converters that modulate the RS485 signals to the MBP signal level and

vice versa. They are transparent from the bus protocol standpoint. In contrast, links have their own

intrinsic intelligence. They map all the field devices connected to the MBP segment as a single slave

in the RS485 segment.

Fig. 4-2: Integration of a PROFIBUS PA segment into a PROFIBUS DP system using a segment coupler or link

Standard IEC 61158

Support PROFIBUS User Organisation (PNO)

Physical layer IEC 61158-2, Mancester Coding Bus Powered (MBP)

Max. length from segment coupler 1900 m: Standard- und eigensichere Anwendungen der Kategorie ib

1000 m: Eigensicheren Anwendungen der Kategorie ia

Participants max. 10 in hazardous areas (EEx ia)

max. 24 in hazardous areas (EEx ib)

max. 32 in safe areas

Transmission rate 31.25 kBit/s

Bus access method Master-slave

Protocol DP-V1

PLCClass 1 master Class 2 master

e.g. FieldCare

segment coupler

PROFIBUS DP

junction box

PROFIBUS PA

segment coupler

segment coupler / link

Page 42: Endress+Hauser Profibus Planing Guide

4 PROFIBUS PA Basics PROFIBUS planning and commissioning

40 Endress+Hauser

4.2.1 Segment coupler

A segment coupler comprises a signal coupler and bus power unit. Depending upon model, they

may support a fixed or a range of transmission rates on thePROFIBUS DP side. The transmission rate

for PROFIBUS PA is fixed at 31.25 kbit/s.

Three types of segment couplers have been specified according to the type of protection required.

Table 4-2: Segment couplers defined in standard

At the moment two manufacturers have segment couplers available:

Table 4-3: Segment couplers on the market* in coinnection with gateway KLD2-GT-DP.xPA or KLD2-GT-DPR.xPA

** in connection with 6ES7157-0AA8x-0XA0 as DP/PA link, rates from 9.6 kBit/s up to 12 MBit/s are supported.

4.2.2 Link

A link comprises an intelligent interface and one or more segment couplers, whereby the couplers

may exhibit different types of protection. Normally, a range of transmission rates are supported on

the PROFIBUS DP side. The transmission rate for PROFIBUS PA is fixed at 31.25 kbit/s.

Links differ from pure segment couplers by the fact that they are PROFIBUS DP slaves on one side

and PROFIBUS PA masters on the other. There is no direct communication between the

PROFIBUS DP master and the PROFIBUS PA slaves, i.e. the link is not transparent. Futher

information is to be found in the sections on addressing and cycle times.

Segment coupler Type A Type B Type C

Type of protection EEx [ia/ib] IIC EEx [ib] IIB None-Ex

Supply voltage 13.5 V 13.5 V 24 V

Max. power 1.8 W 3.9 W 9.1 W

Max. supply current ≤ 110 mA ≤ 280 mA ≤ 400 mA

No. of devices ca. 10 ca. 20 max. 32

Manufacturer / Model Description Type of

protection

Supply

current

Voltage DP-baudrate

Pepperl+Fuchs SK1 KFD2-BR-1.PA.2 Non-Ex 380 mA 22.0 V DC 93.75 kBit/s

Pepperl+Fuchs SK1 KFD2-BR-1.PA.93 Non-Ex 400 mA 24.0-26,0 V DC 93.75 kBit/s

Pepperl+Fuchs SK1 KFD2-BR-EX1.PA EEx [ia] IIC 100 mA 12.6-13.4 V DC 93.75 kBit/s

Pepperl+Fuchs SK1 KFD2-BR-EX1.2PA.93 EEx [ia] IIC 100 mA 12.6-13.4 V DC 93.75 kBit/s

Pepperl+Fuchs SK1 KFD2-BR-EX1.3PA.93 EEx [ia] IIC 100 mA 12.6-13.4 V DC 93.75 kBit/s

Pepperl+Fuchs SK2 KLD2-PL(2)-1.PA Non-Ex 400 mA 24,0-26,0 V DC 45.45 kBit/s -

12 MBit/s*

Pepperl+Fuchs SK2 KLD2-PL(2)-EX1.PA EEx [ia] IIC 100 mA 12.8 - 13.4 V DC 45.45 kBit/s -

12 MBit/s*

Siemens DP/PA-coupler 6ES7157-0AC80-0XA0 Nicht-Ex 400 mA 19.0 V DC 45.45 kBit/s**

Siemens DP/PA-coupler 6ES7157-0AD00-0XA0 EEx [ia] IIC 90 mA 12.5 V DC 45.45 kBit/s**

Siemens DP/PA-coupler 6ES7157-0AD80-0XA0 EEx [ib] IIC 110 mA 12.5 V DC 45.45 kBit/s**

Siemens DP/PA-coupler 6ES7157-0AD81-0XA0 EEx [ia] IIC 110 mA 13.5 V DC 45.45 kBit/s**

Siemens DP/PA-coupler 6ES7157-0AD82-0XA0 EEx [ia] IIC 110 mA 13.5 V DC 45.45 kBit/s**

Page 43: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 4 PROFIBUS PA Basics

Endress+Hauser 41

4.3 Topology

The field devices on the PROFIBUS PA segment communicate with a master on the PROFIBUS DP

system. The bus is designed according to the rules for PROFIBUS DP up to the segment coupler or

link, see Chapter 3.2. Within the PROFIBUS PA segment, practically all topologies are permissible,

see Fig. 4-3, below.

Fig. 4-3: Bus topologies (A:Tree, B:Bus, C:Bus + Tree, D:Bus + Tree + extension),PNK: process near component, SiK: Signal coupler, SG: Power supply, T: Terminator,

JB: Junction box, R: Repeater, 1...n: Field devices, Sk: Segment coupler

Termination at JB possibleif spurs do not exceed 30 m

Page 44: Endress+Hauser Profibus Planing Guide

4 PROFIBUS PA Basics PROFIBUS planning and commissioning

42 Endress+Hauser

Cable type The fieldbus comprises two-core cable. According to IEC 61158-2 (MBP), four different cable types

(A, B, C, D) can be used, only two of which (cable types A and B) are shielded.

• Cable types A or B are recommended for new installations. Their cable shielding guarantee

adequate protection from electromagnetic interference and thus the most reliable data transfer.

On multi-pair cables (Type B), it is permissible to operate multiple fieldbuses (with the same

degree of protection) on one cable. No other circuits are permissible in the same cable.

• Practical experience has shown that cable types C and D should not be avoided where possible

since the lack of shielding means that electromagnetic interference characteristics generally do

not meet the requirements described in the standard.

Table 4-4 lists the technical data of the four cable types as taken from the informative annex to the

standard (i.e. this has not actually been specified.) The electrical data determine important

characteristics of the design of the fieldbus, such as distances bridged, number of participants,

electromagnetic compatibility, etc.

Table 4-4: Cable types according IEC 61158-2, Annex C

Intrinisic safety Cable for intrinsically safe applications as per the FISCO model must also satisfy the following

additional requirements:

Table 4-5: Safety limits for the bus cable according FISCO

Cable type A Cable type B Cable type C Cable type D

Cable construction twisted pair,

shielded

one or more

twisted pairs,

common

shielded

one or more

twisted pairs,

unshielded

one or more

untwisted pairs,

unshielded

Core cross-section 0.8 mm2

AWG 18

0.32 mm2

AWG 22

0.13 mm2

AWG 26

1.23 mm2

AWG 16

Loop resistance (DC) 44 Ω/km 112 Ω/km 254 Ω/km 40 Ω/km

Characteristic impedance at 31.25 kHz 100 Ω ±20 % 100 Ω ±30 % — —

Attenuation constant at 39 kHz 3 dB/km 5 dB/km 8 dB/km 8 dB/km

Capacitive unsymmetry 2 nF/km 2 nF/km — —

Envelope delay distortion (7.9...39 kHz) 1.7 µs/km — — —

Degree of coverage of shielding 90 % — — —

Max. recommended bus length

(including spurs)

1900 m 1200 m 400 m 200 m

EEx ia/ib IIC EEx ib IIB

Loop resistance (DC) 15...150 Ω/km 15...150 Ω/km

Specific inductance 0.4...1 mH/km 0.4...1 mH/km

Specific capacitance 80...200 nF/km 80...200 nF/km

Max. spur length ≤ 30 m ≤ 30 m

Max. bus length ≤ 1000 m ≤ 1900 m

Page 45: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 4 PROFIBUS PA Basics

Endress+Hauser 43

Cable manufacturers Table 4-6 list examples for Type A PROFIBUS-PA cable available from various manufacturers.

Table 4-6: PROFIBUS PA cable

Maximum overall

cable length

The maximum network length depends on the type of ignition protection and the cable

specifications. The overall cable length is made up of the length of the main cable and the length of

all spurs that are longer than 1 m.

Table 4-7: Maximum permissible overall cable length depending upon the cable type used

! Note!

• In FISCO systems with type of protection EEx ia, the maximum line length 1000 m

• If repeaters are used, the maximum permissible cable length is [length in table x (N+1)],

where N is the number of repeaters.

• A maximum of four repeaters are permitted between station and master.

Maximum spur length The line between distribution box and field device is described as a spur. In the case of non ex-rated

applications the max. length of a spur depends on the number of spurslonger than 1 m:

Table 4-8: Maximum length of a spur depending on the number of spurs

! Note!

• In FISCO systems with type of protection EEx ia, the max. length per spur is 30 m.

Number of field devices As far as the specification is concerned, a maximum of:

• 32 stations per segment in safe areas

• 10 stations in an explosive hazardous arrea (EEx ia IIC)

are possible. The actual number of stations is dependent on several factors, however, and must be

determined during project planning.

Bus termination The start and end of each fieldbus segment must be terminated with a bus terminator. The

terminator may be a separate component or be integrated into a bus component.

! Note!

• If the segment is in an explosion hazardous area, the terminators must be certified to the FISCO

standard.

• In the case of a branched bus segment, the device furthest from the segment coupler represents

the end of the bus.

• If the fieldbus is extended with a repeater then the extension must also be terminated at both

ends.

Manufacturer Order No. Application Specific resistance

Turck Cable 483-*M Standard ≤ 44 Ω/km

Turck Cable 483B-*M EEx ia/ib IIC ≤ 44 Ω/km

Siemens 6XV1830-5FH10 Standard ≤ 44 Ω/km

Siemens 6XV1830-5EH10 EEx ia/ib IIC ≤ 44 Ω/km

Lapp 2170235 Standard ≤ 44 Ω/km

Lapp 2170234 EEx ia/ib IIC ≤ 44 Ω/km

Cable type A Cable type B Cable type C Cable type D

1900 m 1200 m 400 m 200 m

Number of spurs 1...12 13...14 15...18 19...24 25...32

Max. length per spur 120 m 90 m 60 m 30 m 1 m

Page 46: Endress+Hauser Profibus Planing Guide

4 PROFIBUS PA Basics PROFIBUS planning and commissioning

44 Endress+Hauser

4.4 Bus access method

PROFIBUS PA uses the central master/slave method to regulate bus access. The process near

component, e.g. a PLC, is a Class 1 master that is installed in the PROFIBUS DP system. The field

devices are configured from a PROFIBUS PA Class 2 master, e.g. FieldCare. The field devices on the

PROFIBUS PA segment are the slaves.

4.4.1 Segment coupler

Segment couplers are transparent as far as the PROFIBUS DP master is concerned, so that they are

not mapped in the PLC. They simply convert the signals and power the PROFIBUS PA segment. The

do not need to be configured nor are they assigned an address.

The field devices in the PROFIBUS PA segment are each assigned a PROFIBUS DP address and

behave as PROFIBUS DP slaves. A slave may be assigned to only one Class 1 master. A master

communicates directly with its slaves:

• A Class 1 master, e.g. the PLC, uses the cyclic polling services to fetch the data provided by

the field devices.

• A Class 2 master, e.g. FieldCare, transmits and receives field device data by using the acyclic

services.

Fig. 0.1 Data exchange via segment coupler

Segment coupler SK1

from Pepperl+Fuchs

If the SK1 segment coupler is used, the transfer rate for the PROFIBUS DP is fixed at 93.75 kBd. In

this case, if type A cable is used for the PROFIBUS DP the PROFIBUS DP segment can be up to a

length of 1200 m. The length of the PROFIBUS PA segment depends on:

• whether the PROFIBUS PA segment in question is intrinsically safe or not.

• how many PROFIBUS PA stations are connected to the segment.

• how high is the current consumption of the individual PA slaves.

• how the PA slaves are distributed on the PROFIBUS PA segment.

The SK1 segment coupler works transparently. This means that PROFIBUS DP masters have direct

access to every PROFIBUS PA slave. Addresses that have been assigned on a PROFIBUS PA segment

are also occupied on the PROFIBUS DP.

PLCClass 1 master Class 2 master

e.g. FieldCare

Segment

PROFIBUS DP

PROFIBUS PA-slaves

PROFIBUS PA

cyclicdata exchange

acyclicdata exchange

coupler

Page 47: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 4 PROFIBUS PA Basics

Endress+Hauser 45

4.4.2 Gateway-type segment coupler

This type of segment coupler allows several segments to be connected to one central coupler unit,

whilst retaining the transparency of the unit. For the user, however, it operates in exactly the same

manner as the normal segment coupler, see Fig. 4-5.

Fig. 4-4: Bus access using a Pepperl+Fuchs SK2 segment coupler

Segment coupler SK2

from Pepperl+Fuchs

The SK2 segment coupler is a modular unit comprising power pack, gateway with up to four

channels and up to 20 power links. The power links supply (intrinsically safe) power to their

segments, whilst the gateway couples the PROFIBUS PA devices to the PROFIBUS-DP network. A

maximum of five power links per channel is allowed.

The SKs has the following properties:

• No restriction on PROFIBUS PA data volume (244 Byte I/O per slave possible)

• Support of PROFIBUS DP transfer rates (45,45 kBd... 12 MBd)

• No addressing of the segment coupler, either PROFIBUS DP or PROFIBUS PA

• Direct access for the PROFIBUS DP master to the PROFIBUS PA slave (transparency).

The major difference to a standard segment coupler is the variable transmission rate on the DP side.

This allows better cycle times to be attained in mixed DP/PA systems.

! Note!

• When a SK2 coupler is used in a PROFIBUS network, the GSD files of the PROFIBUS PA slaves

to be connected to it must be converted using a special program supplied by Pepperl+Fuchs.

• Despite the conversion, the PNO certificates for these devices still retain their validity.

• No PROFIBUS PA slave may be assigned the address 1.

PLCClass 1 master

Class 2 mastere.g. FieldCare

Segment coupler

PROFIBUS DP

PROFIBUS PA-slaves

PROFIBUS PA

cyclicdata exchange

acyclicdata exchange

PROFIBUS PA-slaves

SK 2

Gateway

1 ... max. 5

Page 48: Endress+Hauser Profibus Planing Guide

4 PROFIBUS PA Basics PROFIBUS planning and commissioning

46 Endress+Hauser

4.4.3 Links

In contrast to a segment coupler, a link is recognised by the PROFIBUS DP master and is a

participant in the PROFIBUS DP system. It is assigned a PROFIBUS DP address and thus becomes

opaque to the master. The field devices on the PROFIBUS PA side can no longer be directly polled

using the cyclic services. Instead, the link collects the device data in a buffer, which can be read

cyclically by a Class 1 master. Hence a link must be mapped in the PLC.

On the PROFIBUS PA side, the link acts as the PA master. It polls the field device data cyclically and

stores them in a buffer. Every field device is assigned a PROFIBUS PA address that is unique for the

link, bit which may be used in a segment connected to another link.

When the link is accessed by a Class 2 master with the acyclic services it is quasi-transparent. The

desired field device can be accessed by specifying the link address (DP address) and the device

address (PA address).

Fig. 4-5: Data exchange via a link

Siemens DP-/PA link The Siemens DP/PA link acts as described above. It supports PROFIBUS DP transmission rates from

9.6 kBit/s up to 12MBit/s. As indicated, the DP/PA link is not transparent and must be planned in

the PLC or control system by means of a GSD file. Among other things, all the cyclic I/O data of

the connected slaves must be entered into this file. In order to facilitate the generation of a project

specific GSD file for the link, Siemens supplies a special software application.

The link is limited in the amount of PROFIBUS PA data it can transmit. The total amount of cyclic

I/O data permitted, i.e. the accumulated total from all PROFIBUS PA devices connected to the link,

is 244 bytes for input and 244 bytes for output data.

PLCClass 1 master

Class 2 mastere.g. FieldCare

PROFIBUS DP

PROFIBUS PA-slaves

Cyclic data exchange with

Acyclicdata exchange withClass 2 masterusing themaster-slave method

Class 1 master using themaster-slave method

PROFIBUS PA-slaves

Link

Page 49: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 4 PROFIBUS PA Basics

Endress+Hauser 47

4.5 Network Configuration

Data transmission Data exchange on the PROFIBUS PA segment is handled by the IEC 61158-2 interface. The cyclic

and acyclic polling services are used to transmit data. Since the PROFIBUS PA standard offers the

possibility of interconnecting devices from different vendors, a profile set has been defined that

contains standardised device parameters and functions:

• Mandatory parameters: Every device must provide these parameters. These are parameters,

with which the basic parameters of the device can be read or configured.

• Application parameters: These are optional parameters. These parameters allow a calibration

and, e.g., additional functions such as a linearisation to be performed. In view of the fact that

these functions are dependent upon the measured variable, there are several profile sets, e.g.

for level, pressure, flow etc.. The parameters can be accessed acyclically and require a Class 2

master, e.g. FieldCare, if they are to be read or modified.

Cyclic data exchanged is handled by standard telegrams. The permissible telegram length depends

upon the master used: according PROFIBUS PA-standard, 244 bytes for inputs and 244 bytes for

outputs.

• For PROFIBUS PA devices, analogue measured values and status are transmitted in 5 bytes. If

a device offers more values, more bytes may be transmitted, see Chapter 3.4.

• In the case of the level limit swich Liquiphant M/S, the limit signals are transmitted in 2 bytes

per channel. Byte 1 contains the signal condition, byte 2 the status.

GSD

(device database file)

In order to integrate the field devices into the bus system, the PROFIBUS DP system requires a

description of the device parameters such as output data, input data, data format, data length and

the transmission rates supported. These data are contained in the GSD device database file, which

is required by the PROFIBUS DP master during the commissioning of the communication system.

In addition, device bit maps are required, which appear as icons in the network tree. Further

information on device database files is to be found in Chapter 7.2.

Bus address A pre-requisite for communication on the bus is the correct addressing of the participants. Every

device on the PROFIBUS PA segment is assigned a unique address between 0 and 125. The

addressing is dependent upon the type of DP-/PA-interface used (segment coupler or link) and is

set by DIP switches, via on-site operating elements or by software. The addressing procedure is

described in detail in Chapter 5.5.

Transmission rate The transmission rate on a PROFIBUS PA segment is fixed at 31.25 kbit/s. The transmission rate

on PROFIBUS DP is dependent upon the application and the type of DP-/PA-interface used

(segment coupler or link).

Bus parameters In addition to the transmission rate, all active participants on the bus must operate with the same

bus parameters. For the operating and display program Commuwin II, the bus parameters can be

set by using the DPV1-DDE server (submenu Parameter Settings). For FieldCare the bus parameters

can be set by using the corresponding Communication-DTM.

Page 50: Endress+Hauser Profibus Planing Guide

4 PROFIBUS PA Basics PROFIBUS planning and commissioning

48 Endress+Hauser

4.6 FISCO

To render the proof of Intrinsic Safety as simple as possible, the so-called FISCO model was

developed. FISCO stands for Fieldbus Intrinsically Safe COncept. The German PTB (Federal

Technical Institute) developed the FISCO model and has published details in Report PTB-W-53

"Examination of intrinsic safety for fieldbus systems“. This model is based on the following

prerequisites:

1. To transmit power and data, the bus system uses the physical configuration defined by

IEC 61158-2. This is the case for PROFIBUS PA.

2. Only one active source is permitted on a bus segment (in this case the segment coupler). All

other components work as passive current sinks.

3. The basic current consumption of a bus station is at least 10 mA.

4. It must be ensured for each bus station that

– Ui > Uo of the segment coupler/power link

– Ii > Io of the segment coupler/power link

– Pi > Po of the segment coupler/power link

5. Each bus station must fulfill the following requirement:

– Ci < 5 nFLi

– Li < 10 µH–

6. The permissible line length for EEx ia IIC applications is 1000 m.

7. The permissible spur length for Ex applications is 30 m per spur. The definition of the spur

must be observed in this connection (= lines longer than 1 m).

8. The bus cable used must conform to the following cable parameters:

– Specific resistance: 15 Ω/km < R' < 150 Ω/km

– Specific inductance: 0.4 mH/Km < L' < 1 mH/km

– Specific capacitance: 80 nF/km < C' < 200 nF/km (including the shield)

Taking the shield into consideration, the specific capacitance is calculated as follows:

– C' = C'conductor/conductor + 0.5 * C'conductor/shield, if the bus line is potential free or

– C' = C'shield/shield + C'conductor/shield, if the shield is connected with a terminal of the

segment coupler/power link.

9. The bus segment must be terminated on both ends with a fieldbus terminator. According to the

FISCO model the terminal bus resistance must conform to the following limits:

– 90 Ω < R < 100 Ω

– 0 µF < C < 2.2 µF

On condition that the points 1 up to 9 are all satisfied, the proof of intrinsic safety has been provided

by means of the FISCO model. Points 1, 3 and 5 are automatically satisfied if a product is certified

in accordance with the FISCO model.

More information on the planning of PROFIBUS PA systems is to be found in Chapter 5.

Page 51: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 4 PROFIBUS PA Basics

Endress+Hauser 49

4.7 Fieldbus multi-drop barriers

When a PROFIBUS PA segment is operated according to FISCO, the segment coupler ensures

intrinsic safety by limiting the current available to the bus. This results in the number of devices per

segment being limited to a maximum of 10. If the application demands a large number of

intrinsically safe devices, a correspondingly large number of Exi segment couplers are required.

Multi-drop barriers provide an alternative and more economic solution to such applications.

Fig. 4-6: Use of multi-barriers in explosion-hazardous areas - barriers mounted in Zone 1.

The multi-drop barriers are connected to a non-intrinsically safe PROFIBUS segment. In order that

the barriers can be mounted and operated in Zone 1, however, the segment is executed to

"enhanced safety, Exe" standards. Similarly, the terminals of the barriers are executed to Exe.

Multi-drop barriers have several intrinsically safe outputs (usually four) that conform to the FISCO

model. The PA slaves connected must be intrinsically safe and certified as FISCO devices. Any

externally powered devices must have Exe or Exd power supplies and appropriate connection

compartment certification. The barriers offer additional protection of the PROFIBUS PA trunk cable,

since they have short-circuit protection.

In view of the fact that the trunk cable does not have to be intrinsically safe, the full power of a

standard non-Ex coupler can be used on the segment, typically 400 mA, see Chapter 5.2. This

means that up to 32 devices can be operated per segment, should this be required.

TMULTIDROP

BARRIEREx e/Ex i

MULTIDROPBARRIEREx e/Ex iT

0 - 10 bar 0 - 10 bar

Coupler

Exe power supplyand conditioner

Page 52: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

50 Endress+Hauser

5 PROFIBUS PA Planning

Various aspects must be taken into consideration when a PROFIBUS-PA segment is planned. Since

the importance of each aspect varies from system to system, it is recommended that the following

sections are worked through one after the other. If at some point it becomes obvious that a concept

cannot be realised, then start the whole procedure again from the beginning with a modified

concept.

The chapter is structured as follows:

• Selection of the segment coupler

• Cable type and length

• Current consumption

• Voltage at last device

• Example calculations for bus design

• Data quantity

• Addressing and cycle times

5.1 Selection of the segment coupler

The first step in planning a PROFIBUS-PA system is the selection of the segment coupler according

where the segment is to be operated, see also Chapter 2.3.2. Table 5-1 summerises these:.

Table 5-1: Selection of the segment coupler according to the type of protection and the explosion group of the measured media.

Table 4-3 in Section 4.2.1 lists the couplers currently on the market.

Zone/Explosion

group

Segment coupler Remarks

Zone 0 [EEx ia] IIx Devices that are in installed in Zone 0 must be operated in a segment

with type of protection "EEx ia".

All circuits connected to this segment must be certified for type of

protection "EEx ia".

Zone 1 [EEx ia] IIx

[EEx ib] IIx

Devices that are in installed in Zone 1 must be operated in a segment

with type of protection "EEx ia" or "EEx ib".

All circuits connected to this segment must be certified for type of

protection "EEx ia" or "EEx ib".

Explosion group IIC IIC [EEx ia] IIC If measurements are made in a medium of explosion group IIC, the

devices concerned as well as the segment coupler must be certified

for explosion group IIC.

Explosion group IIB [EEx ia] IIC

[EEx ib] IIB

For media of explosion group IIB, both the devices and the segment

coupler can be certified for both group IIC or IIB.

Non-Ex Non-Ex Devices that are operated on a non-Ex segment may not be installed

in an explosion hazardous area.

Page 53: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 51

5.2 Cable type and length

The bus length is dependent upon the type of protection of the segment and the specification of the

cable. In order that the basic requirements for transmission on the IEC 61158-2 (MBP) physical

layer are fulfilled and that the inductance and capacitance of the cable can be neglected, the bus

length and loop resistance are limited. Table 5-2 lists data from PROFIBUS specifications.

Table 5-2: Standardised power supplies with max. loop resistance and bus length for various applications

Bus length The bus length is the sum of the length of the trunk cable plus all spurs. A spur is any cable

connecting to the trunk line that is over 1 metre in length. If a repeater is used, then the max.

permissible length is doubled.

Spurs The spurs are subject to the following limitations:

• Spurs longer than 30 m are not permissible in explosion hazardous areas.

• For non-hazardous applications, the maximum length of a spur is dependent upon the number

of field devices, see Table 5-3.

• Spurs which are shorter than 1 m are treated as connection boxes and are not included in the

calculation of the total bus length, provided that they do not together exceed 8 m for a 400 m

bus or 2 % of the total length for a longer bus.

Table 5-3: Max. spur length for non-hazardous applications

Max. cable length

(worst case)

The maximum cable length for a particular cable resistance is calculated as follows, whereby the

limits in Table 4.4. must be observed:

Max. cable length (km) = max. loop resistance of the segment coupler (Table 5-2)

specific resistivity of the cable Ω/km

If not given, the loop resistance is (Ω/km) = 2 x (1000 ρ/A)

whereby ρ = specific resistivity Ω mm2/m und A = core cross-section mm2.

Table 4-6 in Chapter 4.3 lists examples for the PROFIBUS-PA cable available from various

manufacturers.

Power supply Type A Type B Type C

Application EEx [ia/ib] IIC EEx [ib] IIB Non-Ex

Supply voltage* 13.5 V 13.5 V 24 V

Max. power* 1.8 Ω 4.2 Ω 9.1 Ω

Max. current consumption* ≤ 110 mA ≤ 280 mA ≤ 400 mA

Max. loop resistance ≤ 40W ≤ 16W ≤ 39 W

Max. bus segment length 1000 m (EEx ia) 1900 m 1900 m

Max. spur length 30 m 30 m see Table 5-3

*see also the technical data supplied by the manufacturer

No. of field devices 25-32 19-24 15-18 13-14 1-12

Spur length ≤ 1 m 30 m 60 m 90 m 120 m

Page 54: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

52 Endress+Hauser

5.3 Current consumption

The primary factors in determining the number of devices on a segment are the current supplied by

the segment coupler and the current consumption of the field devices. For this reason, the current

consumption must be calculated for every segment. As a rule of thumb for general planning:

• Max. 32 devices per segment are permissible in non-hazardous areas

(A repeater allows more devices on the segment).

• Max. 10 devices are permissible in hazardous areas of category ia.

For the calculation, the current supplied by the segment coupler IS, the basic current of every device

IB and the fault current of every device IFDE must be known. From the electrical point of view, a

segment is permissible when:

IS ≥ ISEG

whereby ISEG = ΣIB + max. IFDE

Table 5-4 lists the basic current, the fault current and other specifications of Endress+Hauser

devices. The following examples illustrate how the calculation should be made. Empty forms can

be found in Appendix A.

Device current

consumptionType IB

(mA)

IFDE

(mA)

Supply

current

Ui

(V)

Ii

(mA)

Pi

(W)

Operating

instructions

Safety

instructions

Cerabar S 11 0 from bus 17.5 500 5.5 BA222P/00/en XA096P, XA097P

Cerabar S 11 0 from bus 17.5 280 4.9 BA168P/00/en XA004P

Deltabar S 11 0 from bus 17.5 280 4.9 BA167P/00/en XA003P

Deltapilot S 11 0 from bus 17.5 280 4.9 BA164P/00/en XA007F

FXA164 29 5 from bus 15 215 1.93 --- XA093F,

ATEX 2150

Levelflex M 11 0 from bus 17.5 500 5.5 BA243F/00/en KEMA 02,

ATEX 1109

Liquiphant

M

11 0 from bus 30 500 5.5 BA141F/00/en ATEX 5172X

Liquisys M 11 0 local non

EX

non

EX

non

EX

BA209C/07/en ---

Micropilot II 12 0 from bus 17.5 280 4.9 BA176F/00/en,

BA202F/00/en

XA013F, XA018F,

XA021F

Micropilot M 13 0 from bus 17.5 500 5.5 BA225F/00/en,

BA226F/00/en

XA102F, XA106F

Multicap 14 0 from bus 17.5 500 5.5 BA261F/00/en ---

Mycom

CPM152

11 0 local 17.5 280 4.9 BA143C/07/en XA143C, 130849

Mycom

CPM153

11 0 local 17.5 280 4.9 BA298C/07/en ---

Mypro

CXX431

11 0 from bus 17.5 280 4.9 BA198C/07/en XA173C, 130849

Promag 33 12 0 local 30 500 5.5 BA029D/06/en XA009D

Promag 35 12 0 local non

EX

non

EX

non

EX

BA029D/06/en ---

Promag 50 11 0 local 30 500 5.5 BA055D/06/en ATEX E003U

Promag 53 11 0 local 30 500 5.5 BA053D/06/en ATEX E003U

Page 55: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 53

Table 5-4: PROFIBUS PA data of Endress+Hauser devices

Promass 63 12 0 local 30 500 5.5 BA033D/06/en XA003D

Promass 80 11 0 local non

EX

non

EX

non

EX

BA072D/06/en ---

Promass 83 11 0 local 30 500 5.5 BA063D/06/en ATEX E074X

Prosonic

Flow 93

11 0 local 30 500 5.5 BA076D/06/en ATEX E064X

Prosonic M 12 0 from bus 17.5 500 5.5 BA238F/00/en XA175F-A

Prosonic T 13 0 from bus 17.5 280 4.9 BA166F/00/en XA008F

Prosonic T

FMU232

17 0 from bus 17.5 280 4.9 BA166F/00/en XA008F, XA035F

Prowirl 72 15 0 from bus 17.5 500 5.5 BA085D/06/en XA071DA3

Prowirl 77 12 0 from bus 17.5 280 4.9 BA037D/06/en EX038D

RID261 11 0 from bus 15 --- --- BA098R06/en XA002R, E062

Smartec S 11 0 local non

EX

non

EX

non

EX

BA213C/07/en ---

TMD834 13 0 from bus 17.5 280 4.9 BA090R06/en EX-98.D.089

TMT184 11 0 from bus 17.5 500 5.5 BA115R06/en XA008R

Type IB

(mA)

IFDE

(mA)

Supply

current

Ui

(V)

Ii

(mA)

Pi

(W)

Operating

instructions

Safety

instructions

Page 56: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

54 Endress+Hauser

5.4 Voltage at last device

The resistance of the cable causes a voltage drop on the segment that is greatest at the device farthest

from the segment coupler. It must be checked whether an operating voltage of 9 V (for FEB 24 P in

Zone 0 9.6 V) is present at this device. There are two ways of doing this:

• Worst case calculation:

if the resulting voltage is over 9V, then the segment will work in all cases

• Accurate calculation:

this calculation takes into account the actual physical distribution of the devices and should be

used if the worst case calculation gives a voltage less than 9V

5.4.1 Worst case calculation

The worst case assumes that all devices are located at the end of the bus. The equivalent curcuit

diagram is shown in Fig. 5.1

Fig. 5-1: Voltage calculation and line length (Example 1)

Voltage The length of the bus is known, the voltage at the last device is to be calculated.

Ohm's law is used:

UB = US – (ISEG x RSEG)

whereby: UB = Voltage at last device

US = Output voltage of the segment coupler (manufacturer's data)

ISEG = Current consumed on the segment (ΣIB + max. IFDE, see Section 4.3)

RSEG = Cable resistance = bus length x specific resistance

Bus length The bus length is to be calculated from given conditions on the bus.

A PROFIBUS PA slave requires at least 9 V to function properly (for FEB 24 P in Zone 0 9.6 V).

The following applies to the maximum voltage drop over the bus:

ULmax = US - 9 V

where ULmax = the maximum permissible voltage drop over the bus

US = Output voltage of the segment coupler (manufacturer's data)

The corresponding line length in metres

L = 1000 x ULmax / [ISEG x ρ] metres

where ISEG = Current consumed on the segment in amps (ΣIB + max. IFDE, see Section 4.3)

ρ = specific resistivity of the bus cable in Ω/km

US

ISEGRL

UL

> 9 V

I1In

I2Segmentcoupler

Page 57: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 55

5.4.2 Accurate calculation

This calculation takes into account the actual distribution of the devices on the bus. The equivalent

circuit is shown in Fig. 5-2,where:

RLx = line resistance of line segment x in Ω and

In = current consumption of PA station n in amps

Fig. 5-2: Voltage calculation and line length (Example 2)

Each station causes a voltage drop on the length segment through which its power supply current

flows. For the first station, this would be:

URL1 = I1 x RL1

= I1 x L1 x ρ ;

where ρ = the specific resistance bus cable in Ω/km

L1 = length of line segment 1 in km, measured from the terminals of the coupler

For the second station, the following applies:

URL2 = I2 x (RL1 + RL2)

= I2 x L2 x ρ

In general, the voltage drop over the entire bus segment URL is:

n

URL = ρ x Σ ¨[Ix x Lx]

x=1

The segment is in order when:

URL = US - 9 V

where Us is the supply voltage

If the condition described above is not fulfilled,

• the bus has be shortened or

• a cable with reduced specific resistivity has to be used or

• the number of devices on the segment must be reduced.

Segment couplerUS

RL2RL1

> 9 V

In

L2

L2

L1

i1 I2

Page 58: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

56 Endress+Hauser

5.5 Calculation examples for bus design

5.5.1 Example 1: Non-hazardous application

Calculation example for a PROFIBUS PA segment in a non-hazardous area with the architecture

shown in Fig. 4.3. Used components:

• Segment coupler non-hazardous area: Siemens, Is = 400 mA, Us = 19 V.

• Cable: Lapp, specific resistance of cable = 44 Ω/km

Fig. 5-3: Example 1: Bus installed in non-hazardous area

Cable length

(worst case)

Table 5-5: Cable length (worst case) non-hazardous area

Segment coupler, non-hazardousUs = 19 VIS = 400 mA

Spur

UB = 17.81 V

Trunk cable 40 m

20 m

20 m

5 m

15 m

7 m

20 m

20 m

5 m

15 m

7 m

7 m

20 m

Max. loop resistance, non-hazardous area (see Table 5-2) 39 Ω

Specific resistance of cable 44 Ω/km

Max. length (m)=

1000 x (loop resistance/specific resistance)

1000 x (39 Ω/44 Ω) =

886 m

Length of trunk cable 60 m

Total length of spurs 141 m

Total length of cable (= trunk cable + spurs) LSEG 201 m

Total length of cable LSEG 201 m < Max. length 886 m OK!

Page 59: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 57

Current consumption

Table 5-6: Current consumption (non-hazardous area)

Voltage at last device

Table 5-7: Voltage at last device (non-hazardous area)

Conclusion Result of the calculations:

• Cable length: OK

• Current consumption: OK

• Voltage at last device: OK

From the point of view of the architecture, the segment in Example 1 can be operated with a

standard segment coupler with an output current of 400 mA.

No. Device Manufacturer Tag Basic current Fault current

1 Promass 83 Endress+Hauser FIC122 11 mA 0 mA

2 Positioner –––– FV121 10 mA 0 mA

3 Levelflex M Endress+Hauser LIC124 11 mA 0 mA

4 TMT 184 Endress+Hauser TIC123 11 mA 0 mA

5 Promass 83 Endress+Hauser FIC126 11 mA 0 mA

6 Positioner –––– FV125 10 mA 6 mA

7 Promass 83 Endress+Hauser FIC222 11 mA 0 mA

8 Positioner –––– FV221 10 mA 0mA

9 Levelflex M Endress+Hauser LIC224 11 mA 0 mA

10 TMT 184 Endress+Hauser TIC223 11 mA 0 mA

11 Promass 83 Endress+Hauser FV226 11 mA 0 mA

12 Positioner –––– VIC225 11 mA 4 mA

Max. fault current (max. IFDE) 6mA

Current consurption ISEG = ΣIB + max. IFDE 135 mA

Output current of segment coupler Is 400 mA

Is ≥ ΣIB + max. IFDE ? Yes OK!

Output voltage of segment coupler US (manufacturer’s data) 19.00 V

Specific resistance of cable RK 44 Ω/km

Total length of cable LSEG 201 m

Resistance of cable RSEG = LSEG x RK 8.844 Ω

Current consumption of segment ISEG 135 mA

Voltage drop UA = ISEG x RSEG 1.19 V

Voltage at last device UB = US - UA 17.8 V

≥ 9 V OK!

Page 60: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

58 Endress+Hauser

5.5.2 Example 2: EEx ia application

In Examples 2 and 3, the PROFIBUS PA segment is to operate in an explosion hazardous area. In

accordance with the FISCO model, the devices are operated on two separate segments with type of

protection EEx ia for Zone 0 and EEx ib for Zone 1. Calculations are made for both segments.

Specimen calculation for a bus operating in a hazardous area Zone 0 with the architecture shown

in Fig. 5-4.

• Segment coupler [EEx ia] IIC: P+F, Is = 100 mA, Us = 13 V.

• Cable: Siemens, specific resistance of cable = 44 Ω/km, max. bus length = 1000 m.

Fig. 5-4: Example 2: Calculation of the segment EEx ia, Bus installed with routing to Zone 0 (EEx ia) and Zone 1 (EEx ib)

Cable length

(worst case)

Table 5-8: Cable length (worst case) EEx ia area

Segment coupler [EEx ia] IICIS = 100 mA

US = 13 V

EEx ib

EEx iaTrunk cable 50 m

5 m

15 m

15 m

5 m

Spur

Max. loop resistance, EEx (see Table 4.3) 40 Ω

Specific resistance of the cable 44 Ω/km

Max. length (m)=

1000 x (loop resistance/specific resistance)

1000 x (40 Ω/44 Ω) =

909 m

Length of trunk cable 50 m

Total length of spurs 40 m

Total length of cable (= trunk cable + surs) LSEG 90 m

Total length of cable LSEG 90 m < Max. length 909 m OK!

Page 61: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 59

Current consumption

Table 5-9: Current consumption (EEx ia area)

Voltage at last device

Table 5-10: Voltage at last device (EEx ia area)

Conclusion Result of the calculations:

• Cable length: OK

• Current consumption: OK

• Voltage at last device: OK

From the point of view of the architecture, the segment in Example 2 can be operated with an EEx

ia segment coupler with an output current of 100 mA.

Nr. Device Manufacturer Tag Basic current Fault current

3 Deltapilot S Endress+Hauser LIC124 11 mA 0 mA

4 TMT 184 Endress+Hauser TIC123 11 mA 0 mA

9 Deltapilot S Endress+Hauser LIC224 11 mA 0 mA

10 TMT 184 Endress+Hauser TIC223 11 mA 0 mA

Ma. fault current (max. IFDE) 0 mA

Current consumption ISEG = ΣIB + max. IFDE 44 mA

Output current of segment coupler Is 100 mA

Is ≥ ΣIB + max. IFDE ? Yes OK!

Output voltage of segment coupler US (manufacturer’s data) 13.00 V

Specific resistance of cable RK 44 Ω/km

Total length of cable LSEG 90 m

Resistance of cable RSEG = LSEG x RK 3.96 Ω

Current consumption of segment ISEG 44 mA

Voltage drop UA = ISEG x RSEG 0.17 V

Voltage at last device UB = US - UA 12.83 V

≥ 9 V?∗ OK!

*the operating voltage for the FEB 24 P in Zone 0 is 9.6 V

Page 62: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

60 Endress+Hauser

5.5.3 Example 3: EEx ib application

Specimen calculation for a bus operating in a hazardous area Zone 1 with the architecture shown

in Fig. 5-5.

• Segment coupler [EEx ia/ib] IIC: P+F, Is = 100 mA,

• Us = 13 V. Cable: Siemens, specific resistance of cable = 44 Ω/km

Fig. 5-5: Example 3: Calculation of the segment EEx ib, Bus installed with routing to Zone 0 (EEx ib) and Zone 1 (EEx ia)

Cable length

(worst case)

Table 5-11: Cable length (worst case) EEx ib area

Segment coupler [Ex ia/ib] IICIS = 100 mA

US = 13 V

EEx ib

EEx ia

Trunk cable 60 mUB = 12.31 V

20 m

7 m

Spur

7 m

20 m

20 m

20 m

7 m

7 m

Max. loop resistance, EEx (siehe Tabelle 4.3) 16 Ω

Specific resistance of cable 44 Ω/km

Max. length (m)=

1000 x (loop resistance/specific resistance)

1000 x (40 Ω/44 Ω) =

363 m

Length of trunk cable 60 m

Total length of spurs 108 m

Total length of cable (= trunk cable + spurs) LSEG 168 m

Total length of cable LSEG 168 m < Max. lenght 363 m OK!

Page 63: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 61

Current consumption

Table 5-12: Current consumption (EEx ib area)

Voltage at last device

Table 5-13: Voltage at last device (EEx ia area)

Conclusion Result of the calculations:

• Cable length: OK

• Current consumption EEx ia not permissible, EEx ib: OK

• Voltage at last device: OK

No. Device Manufacturer Tag Basic current Fault current

1 Promass 83 Endress+Hauser FIC122 11 mA 0 mA

2 Positioner –––– FV121 13 mA 0 mA

5 Promass 83 Endress+Hauser FIC126 11 mA 0 mA

6 Positioner –––– FV125 13 mA 6 mA

7 Promass 83 Endress+Hauser FIC222 11 mA 0 mA

8 Positioner –––– FV221 13 mA 0 mA

11 Promass 83 Endress+Hauser FIC226 11 mA 0 mA

12 Positioner –––– FV225 13 mA 6 mA

Max. fault current (max. IFDE) 6 mA

Current consumption ISEG = ΣIB + max. IFDE 102 mA

Output current of segment coupler Is (EEx ia IIC) 100 mA

Is ≥ ΣIB + max. IFDE ? no impossible!

Output current of segment coupler Is (EEx ia IIB) <=280 mA

Is ≥ ΣIB + max. IFDE ? Yes OK!

Output voltage of segment coupler US (manufacturer’s data) 13.00 V

Specific resistance of cable RK 44 Ω/km

Total length of cable LSEG 168 m

Resistance of cable RSEG = LSEG x RK 7.39 Ω

Current consumption of segment ISEG 102 mA

Voltage drop UA = ISEG x RSEG 0.75 V

Voltage at last device UB = US - UA 12.25 V

≥ 9 V?* OK!

*the operating voltage for the FEB 24 P in Zone 0 is 9.6 V

Page 64: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

62 Endress+Hauser

Alternatives The result for a segment with type of protection EEx ib and a segment coupler EEx ia IIC is negative.

A segment coupler with type of protection EEx ib IIB would be permissible but at the moment there

is none on the market. Two possible alternatives are shown in Fig. 5-5:

• Version A:

two segments with type of protections EEx ib are routed to one tank each. In this case, the

current consumption is reduced to 56 mA. A segment coupler with type of protection EEx ia

IIC is adequate for this requirement.

• Version B:

only circuits with type of protection EEx ia are connected to the bus. The plant can then be

equipped with two segments with type of protection EEx ia. The current consumption per

segment is 80 mA.

• VersionC:

Einsatz von Feldbusbarrieren und einem Segmentkoppler in Nicht-Ex-Ausführung.

Fig. 5-6: Example 4: Alternative architectures:Version A – two segments withdgree of protection EEx ib IICVersion B – two segments withdgree of protection EEx ia IIC

T: Terminator

Segment coupler 3x [EEx ia] IIC

EEx ib

EEx ia

Segment coupler 2x [EEx ia] IIC

EEx ib

EEx ib

EEx ia

Page 65: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 63

5.5.4 Example: fieldbus barrier application

Fig. 5-7: Use of multi-barriers in explosion-hazardous areas - barriers mounted in Zone 1.

Pepperl+Fuchs barrier The Fieldbarrier from Pepperl+Fuchs is used to connect up to 4 intrinsically safe PROFIBUS PA

devices to a non-intrinsically safe PROFIBUS PA segment. When the Fieldbus barrier is mounted in

an hazardous area, Zone 1, the PROFIBUS PA trunk has to be realised to Exe "increased safety"

standards. The Fieldbus barrier outputs are intrinsically safe and correspond to the requirements the

FISCO Model. The trunk is galvanically separated from the outputs. No terminators are required on

the barrier output lines.

The complete bus must satisfy the functional considerations cable length, voltage at last device and

current consumption as shown in Examples 1 to 3. The technical safety considerations are based on

the entity concept. In contrast to the standard Ex i concept, however, the technical safety

calculation is made for each individual multidrop barrier. The devices are considered safe if the

junction box output characteristics (Uo, Io, Po, Co, Lo) do not exceed the input parameters of the

field devices (Ui, Ii, Pi, Ci, Li) and the inductance and capacitance are within the permissible limits.

FISCO devices always conform to these requirements.

The output characteristics are as follows:

• Input voltage16 V ... 32 V

• Output voltage ≥0 V

• Output current ≤40 mA

• Spur length ≤120 m in safe areas, ≤30 m in hazardous areas

The total spur length varies according to the manner in which the the barriers are connected to the

trunk line:

• For daisy chains or connections to the trunk less than one metre, each output line on the

barrier counts as a spur from the trunk

• For connections to the trunk greater than one metre, the connection and all output lines count

as one spur and their total length is limited according to Table 5-3, whereby the total length

in Ex areas must be less than or equal to 30 m.

Dimensioning tool To simplify dimensioning of a fieldbus segment, Pepperl+Fuchs has developed a software tool that

makes the necessary calculations. This can be downloaded from the Pepperl+Fuchs home page

www.pepperl-fuchs.com free of charge.

TMULTIDROP

BARRIEREx e/Ex i

MULTIDROPBARRIEREx e/Ex iT

0 - 10 bar 0 - 10 bar

Coupler

Exe power supplyand conditioner

Page 66: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

64 Endress+Hauser

5.6 Data quantity

If the participants communicate directly with the PROFIBUS DP master through a segment coupler,

then the amount of data exchanged sets no limits to the design of the PROFIBUS PA segment. If a

link is used as interface to the PROFIBUS DP system, however, the amount of data that can be

stored in the I/O buffer is limited. According to the PROFIBUS specification, the maximum

telegram length is 244 byte of input data and 244 byte for output data. The system itself may,

however, support less: always check the manufacturer’s specifications!

Fig. 5-8: Example1: Bus installed in non-hazardous area

Example: data quantity Take Example 1 in Fig 5-8: can a link be used? The data for Endress+Hauser devices is to be found

in Table 5-15,overleaf.

Table 5-14: Example: Data quantity of a PROFIBUS PA segment

Depending upon the device configuration, from min. 40 bytes to max. 258 bytes (Inputs) and min.

20 bytes to max. 88 bytes (Outputs) are periodically exchanged with the PLC. In the case of a link,

the data are transmitted to the PLC in a telegram. The telegram length is limited:

a) by the buffer size of the link, e.g. 244 bytes,

b) by the max. telegram length of the PLC, e.g. 122 bytes

c) by the PROFIBUS-PA specification 244 bytes.

It can seen that the use of a link is determined by the configuration of the field devices, see

Chapter 3.4 and the system components used. Should the maximum configuration or 258 bytes be

required, a link could not be used.

Link,

byte

s per

dev

ice

Amount of data 44...284 bytes to PLC

0...1

2

0...4

5

550...1

2

0...4

5

0...1

2

0...4

5

550...1

2Specifications in byte

0...4

5

non-hazardous area

Device No. I 0 Imin Imax Omin Omax Amount of data

1, 5, 7, 11 5-45 0-12 20 180 0 48 I : 40-258 Bytes

O : 20-88 Bytes3, 9 5-10 0-5 10 20 0 10

4, 10 5 0-5 10 10 0 10

Positioner No.

2, 6, 8, 12 0-12 5 0 48 20 20

Page 67: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 65

Endress+Hauser devices Type Cycle data Data amount PLC Response time Blocks

Inputs Outputs depending on

configuration

PB* TB** FB***

Cerabar M Pressure

2. cycle value(1)

Display value(1)

5 Byte

5 Byte

---

---

---

5 Byte

10...11.3 ms 1 1 1 AI

Cerabar S Pressure

2. cycle value(1)

Display value(1)

5 Byte

5 Byte

---

---

---

5 Byte

10...11.3 ms 1 1 1 AI

Deltabar S Differential pressure

2. cycle value(1)

3. cycle value(1)

Display value(1)

5 Byte

5 Byte

5 Byte

---

---

---

---

5 Byte

10 ms...12.6 ms 1 1 1 AI

Deltapilot S Pressure/Level

2. cycle value(1)

Display value(1)

5 Byte

5 Byte

---

---

---

5 Byte

10...11.3 ms 1 1 1 AI

FXA 164 Level limit 2...8 Byte --- 10...13.9 ms 1 4 4 DI

Levelflex M Level

2. cycle value(1)

Display value(1)

5 Byte

5 Byte

---

---

---

5 Byte

10...11.3 ms 1 1 1 AI

Liquiphant M Level limit 2 Byte --- 10 ms 1 1 1 DI

Liquisys M pH Value

Temperature

5 Byte

5 Byte

---

---

11.3 ms 1 --- 1 AI

O2

Temperature

5 Byte

5 Byte

---

---

11.3 ms 1 --- 1 AI

Turbidity

Temperature

5 Byte

5 Byte

---

---

11.3 ms 1 --- 1 AI

Conductivity

Temperature

5 Byte

5 Byte

---

---

11.3 ms 1 --- 1 AI

Chlorid

Temperature

pH Value

Redox

5 Byte

5 Byte

5 Byte

5 Byte

---

---

---

---

11.3 ms 1 --- 1 AI

Micropilot II Level 5 Byte --- 10 ms 1 1 1 AI

Micropilot M Level

2. cycle value(1)

Display value(1)

5 Byte

5 Byte

---

---

---

5 Byte

10...11.3 ms 1 1 1 AI

Multicap Level

Temperature

Display value(1)

5 Byte

5 Byte

---

---

---

5 Byte

10...11.3 ms 1 1 1 AI

Mycom II pH Value

Temperature

5 Byte

5 Byte

---

---

11.3 ms 1 --- 1 AI

Conductivity (ind.)

Temperature

5 Byte

5 Byte

---

---

11.3 ms 1 --- 1 AI

Conductivity (kond.)

Temperature

5 Byte

5 Byte

---

---

11.3 ms 1 --- 1 AI

Mycom S

Page 68: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

66 Endress+Hauser

pH pH Value 1

Temperature 1(1)

5 Byte

5 Byte

---

---

10...15.2 ms 1 4 4 AI

pH Value 2

Temperature 2(1)

5 Byte

5 Byte

---

---

Control CLM(1) --- 2 Byte

Lf (ind.) Conductivity 1 (ind.)

Temperature 1(1)

5 Byte

5 Byte

---

---

10...15.2 ms 1 4 4 AI

Conductivity 2 (ind.)(1)

Temperature 2(1)

5 Byte

5 Byte

---

---

Control CLM(1) --- 2 Byte

Lf (kond.) Conductivity 1 (kond.)(1)

Temperature 1(1)

5 Byte

5 Byte

---

---

10...15.2 ms 1 4 4 AI

Conductivity 2 (kond.)(1)

Temperature 2(1)

5 Byte

5 Byte

---

---

Control CPM(1)

Control CPC(1)

---

---

2 Byte

2 Byte

Mypro Conductivity

Temperature(1)

5 Byte

5 Byte(1)

---

---

10...11.3 ms 1 2 1 AI

pH Value

Temperature(1)

5 Byte

5 Byte(1)

---

---

10...11.3 ms 1 2 1 AI

Promag 33/

35

Mass flow

Totalizer(1)

Control(1)

5 Byte

5 Byte

---

1 Byte 10...11.3 ms 1 1 1 AI

1 TOT

Promag 50 Mass flow

Totalizer(1)

Control(1)

Display value(1)

5 Byte

5 Byte

---

---

---

2 Byte(1)

1 Byte

5 Byte

10...11.3 ms 1 1 1 AI

1 TOT

Promag 53 Mass flow

Totalizer 1 (1)

Totalizer 2(1)

Totalizer 3(1)

Volumetric flow(1)

Control(1)

Display value(1)

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

---

---

---

2 Byte(1)

2 Byte(1)

2 Byte(1)

---

1 Byte

5 Byte

10...15.2 ms 1 1 2 AI

3 TOT

Promass 63 Mass flow

Totalizer 1 (1)

Temperature(1)

Density(1)

Totalizer 2(1)

Volumetric flow(1)

Standard mass flow(1)

Target medium flow(1)

Carrier medium flow(1)

Calculated density(1)

Control(1)

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

---

---

---

---

---

---

---

---

---

---

---

1 Byte

10...21.7 ms 1 1 8 AI

2 TOT

Promass 80 Mass flow

Volumetric flow(1)

Density(1)

Temperature(1)

Totalizer(1)

Display value(1)

Control(1)

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

---

---

---

---

---

---

2 Byte(1)

5 Byte

1 Byte

10...15.2 ms 1 1 4 AI

1 TOT

Page 69: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 67

Table 5-15: PROFIBUS PA data of Endress+Hauser devices

Promass 83 Mass flow

Volumetric flow(1)

Standard mass flow(1)

Density(1)

Standard density(1)

Temperature(1)

Totalizer 1(1)

Totalizer 2(1)

Totalizer 3(1)

Display value(1)

Control(1)

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

5 Byte

---

---

---

---

---

---

---

---

2 Byte(1)

2 Byte(1)

2 Byte(1)

5 Byte(1)

1 Byte(1)

10...20.4 ms 1 1 6 AI

3 TOT

Prowirl 72 "Volumetric flow or

calculated mass flow or

standard mass flow"

Totalizer(1)

Control(1)

5 Byte

5 Byte

---

---

2 Byte(1)

1 Byte

10...11.3 ms 1 1 1 AI

1 TOT

Prowirl 77 Flow

Totalizer(1)

Control(1)

5 Byte

5 Byte

---

---

---

1 Byte

10...11.3 ms 1 1 1 AI

1 TOT

Prosonic Flow

90

Volumetric flow

Speed of sound(1)

Flow rate1)

Totalizer 1(1)

Display value(1)

Control(1)

5 Byte

5 Byte

5 Byte

5 Byte

---

---

---

---

---

2 Byte(1)

5 Byte

1 Byte

10...13.9 ms 1 1 3 AI

1 TOT

Prosonic Flow

93

Flow (optional 11

measured variables)(1)

Totalizer 1(1)

Totalizer 2(1)

Totalizer 3(1)

Display value(1)

Control(1)

5..40 Byte

5 Byte

5 Byte

5 Byte

---

---

---

2 Byte(1)

2 Byte(1)

2 Byte(1)

5 Byte

1 Byte

10...23 ms 1 1 8 AI

3 TOT

Prosonic M Level

2. cycle value(1)

Display value(1)

5 Byte

5 Byte

---

---

---

5 Byte

10...11.3 ms 1 1 1 AI

Prosonic T Level 5 Byte --- 10 ms 1 1 1 AI

RID 261 Display --- --- --- --- --- ---

Smartec S Conductivity

Temperature(1)

MRS(1)

5 Byte

5 Byte

---

---

---

2 Byte

10...11.3 ms 1 2 2 AI

TMD 834 Temperature 5 Byte --- 10 ms 1 1 1 AI

TMT 184 Temperature

Display value

5 Byte

---

---

5 Byte

10 ms 1 1 1 AI

(1) Optional

* PB = Physical Block

** TB = Transducer Block

*** FB = Function Block with AI = Analog Input, DI = Discrete Input and TOT = Totalizer

Page 70: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

68 Endress+Hauser

5.7 Addressing and cycle times

5.7.1 Addressing

Every device in the bus system is assigned a unique address. Valid addresses lie in the range 0...126,

whereby 126 is the address of the delivery status. If the address is not set correctly, the device

cannot communicate.

Networks with coupler or

gateway

The PLC is able to assign up to 126 (0...125) addresses to individual participants at the bus. A device

address may appear only once within a particular PROFIBUS DP system. If a segment coupler is

used, then the addresses assigned to the PROFIBUS PA devices count as PROFIBUS DP addresses.

For a typical bus configuration with PLC and PC, the addresses are assigned as follows:

• the PLC is assigned an address (Class 1 master), typically address 1

• the PC or operating tool is assigned an address (Class 2 master), typically address 0 or 2

• the other addresses are assigned to the field devices.

Networks with links Links act as PROFIBUS DP slaves and receive their own address. The PROFIBUS PA field devices

connected to link, however, form a separate PROFIBUS PA system. These are addressed separately.

The PROFIBUS DP addresses are assigned as follows:

• the PLC is assigned an address (Class 1 master), typically address 1

• the PC or operating tool is assigned an address (Class 2 master), typically address 0 or 2

• every link is assigned an address (e.g. addresses 3, 4, 5, 6, ...)

• the rest of the addresses are assigned to the other field devices that are connected to

transporent segment couples or directly to the PROFIBUS DP system.

On the PROFIBUS PA side, the field devices connected to the link are assigned a unique address for

the PROFIBUS PA segment of which they are part. They are not counted as part of the PROFIBUS-

DP system

• every device is assigned an address between 3 and 125,

• the addresses 0, 1 and 2 cannot be assigned when the link is operating together with a standard

master.

Examples for addressing are to be found in Sections 5.7.3 to 5.7.5

5.7.2 Cycle times

The cycle times must also be considered when the PROFIBUS PA segment is planned. Data

exchange between a PLC (a Class 1 master) and the field devices occurs automatically in a fixed,

repetitive order. The cycle times determine how much time is required until the data of all the

devices in the network are updated.

The more complex a device, the greater the amount of data to be exchanged and the longer the

response time for the exchange between PLC and device. Table 5-15 summarises the amount of

data and the response times for Endress+Hauser devices. The total cycle time for the updating of

network data is calculated as follows:

Total cycle time = Sum of the cycle times of the field devices

+ internal PLC cycle time

+ PROFIBUS-DP transmission time

When links or the transparent SK2 segment coupler are used, the total cycle time of a system can

be reduced.

Page 71: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 69

5.7.3 Example 1: Siemens segment coupler

Fig. 5-9: Network example for Siemens segment coupler

Siemens segment couplers 6ES7-157-0 AD81-0XA0 and 6ES7-157-0 AC80-0XA0, see Table 4-3,

can be used by any PROFIBUS DP master (PLC or process control system) that supports a baudrate

of 45.45 kbit/s. In the example, two couplers for hazardous areas and one for non-hazardous areas

are used.

• A maximum of 126 (0 - 125) addresses can be given to the participants, since

• The segment coupler is transparent.

• 124 addresses are available for assignment to the field devices.

• The addresses 3 - 19 are used.

• The transmission rate is 45.45 kBit/s.

The cycle time for the following example is:

• Σ (cycle time of the devices) + PLC cycle time (ca. 100 ms)

= 17 x 10 ms + 100 ms

= 270 ms

! Note!

• For PROFIBUS DP alone, the DP transmission time must also be considered.

• The (bus) cycle time is the time period required under worse case conditions for the changes

in input data to be transmitted to the master and the changes in output data to the slaves

Power supply CPU

100 ms

DP masteraddress A 1

Operating toole.g. FieldCareaddress A 2

PROFIBUS DP

PRO

FIB

US

PA

PRO

FIB

US

PA

PRO

FIB

US

PA

Standard segment coupler Ex segment coupler Ex segemnt coupler

Explosion hazardous areaNon-hazardous area

A 14

A 15

A 16

A 17

A 19

A 18

A 8

A 9

A 10

A 11

A 13

A 12

A 3

A 5

A 6

A 7

A 4

45.45 kbit/s

Page 72: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

70 Endress+Hauser

5.7.4 Example 2: Pepperl+Fuchs SK1 coupler

Fig. 5-10: Network example for Pepperl+Fuchs segment coupler SK1

The Peppert+Fuchs segment couplers KFD2-BR-EX1.PA and KFD2-BR-1PA.93, see table 4-3, can

be used by any PROFIBUS DP master (PLC or process control system). The Segment coupler SK1

supports both cyclic and acyclic data exchange. It can thus be used in all common PLC or process

control systems. In the example, two couplers for hazardous areas and one for non-hazardous areas

are used.

• A maximum of 126 (0 - 125) addresses can be given to the participants, since the segment

coupler is transparent.

• 124 addresses are available for assignment to the field devices.

• The addresses 3 - 19 are used.

• The transmission rate is 93.75 kbit/s.

The cycle time for the following example is:

• Σ (cycle time of the devices) + PLC cycle time (ca. 100 ms)

= 17 x 10 ms + 100 ms

= 270 ms

! Note!

• For PROFIBUS DP alone, the DP transmission time must also be considered.

• The (bus) cycle time is the time period required under worse case conditions for the changes

in input data to be transmitted to the master and the changes in output data to the slaves

Power supply CPU

100 ms

DP masteraddress A 1

Operating toole.g. FieldCareaddress A 2

PROFIBUS DP

PRO

FIB

US

PA

PRO

FIB

US

PA

PRO

FIB

US

PA

Standard segment coupler Ex segemnt coupler Ex segemnt coupler

Explosion hazardous areaNon-hazardous area

A 14

A 15

A 16

A 17

A 19

A 18

A 8

A 9

A 10

A 11

A 13

A 12

A 3

A 5

A 6

A 7

A 4

93.75 kbit/s

Page 73: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 71

5.7.5 Example 3: Pepperl+Fuchs SK2 coupler

Fig. 5-11: Network example for Pepperl+Fuchs segment coupler SK2

The segment coupler SK2 (KLD2-PL(2)-1.PA with gateway KLD-GT-DP.1PA or KLD2-PL(2)-

Ex1.PA with gateway KLD-GT-DP.1PA) supports both cyclic or and acyclic data exchange of the

PROFIBUS DP V1 protocol. In the example, three segment couplers SK2 are used: two couplers for

hazardous areas and one for non-hazardous areas.

• All data that is to be updated cyclically is automatically updated in the common data area by

the PROFIBUS PA master.

• The update time depends on the data volume transferred via the PROFIBUS PA channel.

Cycle time From the point of view of PROFIBUS DP, the segment coupler represents a multi-slave device. If

the PROFIBUS DP Master sends a request to a slave address existing at the segment coupler, the

gateway answers directly on the request with the data, that are stored in the common data range.

Through this behavior, the PROFIBUS DP master does not need to wait for the PROFIBUS PA slave

to respond. The result of this is that the cycle time of the entire system is calculated as follows:

tCycle = tCycle_PA-channel + tCycle_DP

The time tCycle_PA-channel can be estimated as follows:

tCycle_PA-channel = 10 ms + n*10,5 ms + 0,256 ms*(LE + LA)

where n = the number of PROFIBUS PA slaves

LE = total number of input bytes of all PROFIBUS PA slaves on the channel.

LA = total number of output bytes of all PROFIBUS PA slaves on the channel.

Power supply CPU

100 ms

DP master Operating tool

PROFIBUS DP

PRO

FIB

US

PA

PRO

FIB

US

PA

PRO

FIB

US

PA

Standard power link Ex power link Ex power link

Explosion hazardous areaNon-hazardous area

PA 3

...12 Mbit/s

e.g. FieldCareaddress A 2

address A 1

Gateway GatewayGateway

PA 6

PA 5

PA 4

PA 7

PA 8

PA 9

PA 10

PA 11

PA 12

PA 15

PA 14

PA 13

PA 16

PA 17

PA 18

PA 19

PA 20

PA 22

PA 21

PA 23

PA 26

PA 24

PA 25

Segment 1 Segment 2 Segment 3

Page 74: Endress+Hauser Profibus Planing Guide

5 PROFIBUS PA Planning PROFIBUS planning and commissioning

72 Endress+Hauser

DP cycle time The time tCycle_DP can be estimated as follows:

tCycle_DP = TBit * n * 500 + 11*TBit*(LE +LA)

where n = the number of PROFIBUS DP/PA slaves

LE = total number of input bytes of all PROFIBUS slaves

LA = total number of output bytes of all PROFIBUS slaves

TBit = bit time = 1/transfer rate

For the time tCycle_DP a safety add-on of 10% should be included in the calculation in accordance

with the PROFIBUS User Organization.

The equation above applies given the following pre-conditions:

• The PROFIBUS DP network is operated as a monomaster system, i. e. there is only one master

on the PROFIBUS DP. If you want to use a multimaster system, the token hold time and the

corresponding pause times of the additional masters must be added to the total.

• Only acyclic data exchange takes place. If the master is also supposed to transfer acyclic

telegrams, the time required for acyclic communication must be added in total.

Example The cycle time for the example in Fig. 5.11 is:

Σ1 (Cycle time of the PA network) = PA segment 1 + PA segment 2 + PA segment 3

where Σ1 = cycle PA segment 1 + cycle PA segment 2 + cycle PA segment 3

Σ1 = (10 ms + n*10.5 ms + 0.256 ms*(50)) + (10 ms + n*10.5 ms + 0.256 ms*(40))

+ (10 ms + n*10.5 ms + 0.256 ms*(90))

Σ1 = 117.3 ms + 104.24 ms + 106.54 ms

Σ1 = 328.08 ms

Σ2 (Cycle time of the DP PLC)

where

Σ2 = 1.165 ms + 100 ms

Σ2 = 101.165 ms

tcycle = Σ1 + Σ2

= approx 430 ms

2

1

12------Mbit\s 24 500 11

1

12------Mbit\s 180××+××

100m\s+=∑

Page 75: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 5 PROFIBUS PA Planning

Endress+Hauser 73

5.7.6 Example 4: Siemens PA link

Fig. 5-12: Network example for Siemens DP/PA-link

The Siemens PA-link (6ES7-157-0 AD81-0XA0 with link 6ES7-157-0AA82-0XA0 or 6ES7-157-0

AC80-0XA0 with link 6ES7-157-0AA82-0XA0) can be used by any PROFIBUS DP master (PLC or

process control system). Three links are used in the example, each with two segment couplers

• A maximum of 126 addresses can be assigned to the participants on the PROFIBUS DP system.

• A maximum of 122 PA addresses (address range 3 - 125) can be assigned in the PROFIBUS PA

segments connected to each link.

• The PROFIBUS DP addresses 3 -5 are used to address the links.

• In the PROFIBUS PA segments, the addresses 3-11, 3-10 and 3-9 are used for the PA devices,

whereby addresses 0 - 2 is reserved for the link in each case and not useable for PA devices.

• The transmission rate may be up to 12 Mbit/s.

The cycle time for the example is:

• Σ1 (Cycle time of the PA devices)

PA segment1: 9 x 10 ms = 90 ms

PA segment 2: 8 x 10 ms = 80 ms

PA segment 3: 7 x 10 ms = 70 ms

• Σ2 (Cycle time of the DP devices up to 12 Mbit/s) + PLC cycle time (ca. 100 ms)

3 x 1 ms + 100 ms = 103 ms

! Note!

• For PROFIBUS DP alone, the DP transmission time must also be considered.

Power supply CPU

100 ms

DP master Operating tool

PROFIBUS DP

PRO

FIB

US

PA

PRO

FIB

US

PA

PRO

FIB

US

PA

Standard segment coupler Ex segment coupler Ex segment coupler

Explosion hazardous areaNon-hazardous area

PA 3

...12 Mbit/s

e.g. FieldCareaddress A 2

address A 1

A 3 A 5A 4Link LinkLink

PA 6

PA 5

PA 4

PA 7

PA 8

PA 9

PA 10

PA 11

PA 3

PA 6

PA 5

PA 4

PA 7

PA 8

PA 9

PA 10

PA 3

PA 5

PA 4

PA 6

PA 9

PA 7

PA 8

Segment 1 Segment 2 Segment 3

Page 76: Endress+Hauser Profibus Planing Guide

6 Installation PROFIBUS PA PROFIBUS planning and commissioning

74 Endress+Hauser

6 Installation PROFIBUS PA

The chapter contains information on physical installation of the network. It contains the following

sections:

• Cabling

• Grounding and shielding

• Termination

• Overvoltage protection

• Installation of the devices

• Setting the address

6.1 Cabling

When installing a PROFIBUS network, particular attention must be paid to the cabling. This covers

both choice of cabling, see below, and the way in which the cables are laid in the plant. Thus by

careful routing, e.g. avoidance of potential sources of intense electromagnetic interference, use of

metal trays or separation of power and bus cables in the cable tray, a significant contribution can

sometimes be made to the fault-free running of the bus.

PROFIBUS DP On the PROFIBUS DP side it is usual to make connections via a screw terminals or 9-pin DIN

connectors. Cable specifications are listed in Tables 3-3 and 3-7 in Chapter 3 and suitable cables are

to be found on the market for PROFIBUS DP or RS-485 applications. Junction boxes, terminators

and other connection equipment are also available.

PROFIBUS PA The connection to the segment coupler or link is usually by means of screw terminals. For the

connection of devices and spurs to the trunk cable, the customer has following choices:

• T-box with screw terminals or M12 connectors

• Junction boxes with screw terminals or M12 connectors

• Field barriers with M12 connectors

Chapter 4, Tables 4-4 and 4-5 contain cable specifications and Table 4-6 a list of manufacturers

(partial). PROFIBUS PA cables are available on the market for both safe and FISCO applications, and

cord sets with M12 connectors are readily available in different lengths. In all cases, however, care

must be taken regarding the continuity of the screening and the correct termination of the segment.

For this reason, it is important to consider the grounding scheme to be adopted, before equipment

is purchased.

! Note!

• Where the network is operating in explosion hazardous areas, it is important to remember that

all equipment, including cables, connecting units, terminators etc., has the appropriate

certification. For PROFIBUS PA, the use of FISCO equipment simplifies proof of intrinsically

safety.

• The M12 connector cannot be used for four-wire EEx d devices and only under certain conditions

for EEx e devices.

Endress+Hauser offer a number of products and accessories for PROFIBUS PA. For more

information, please ask for the documentation "Instrumnetation aids and accessories for PROFIBUS.

Page 77: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 6 Installation PROFIBUS PA

Endress+Hauser 75

6.2 Grounding and shielding

This section describes three possible grounding and shielding schemes for a PROFIBUS PA network.

• Full isolation

• Installation with multiple grounding

• Capacitive isolation

The difference between the schemes lies in the grounding of the bus cable shield. In one case it is

connected to a separate ground and in the other integrated into the general plant grounding system.

Plant grounding schemes also differ according to national and or local practice. For example, British

practice is neutral star earth bonding, German practice is the use of a potential equalisation line and

Americans often run cables in grounded steel conduits and enclose control equipment in steel

cabinets.

Fig. 6-1: Device grounding schemes:In neutral star earth bonding it is assumed that the device is electrically connected to the tank via the process connection.

The Tanks are grounded at a central grounding point.

In German practice, each device is connected directly to a thick potential equalisation line which

runs throughout the plant and is connected to a single grounding point.

The purpose of grounding the shielding is to protect the digital signals on the fieldbus from high-

frequency electromagnetic interference caused, e.g., by cellular telephones or harmonics from

frequency converters and other plant equipment. It can be seen, therefore, that local installation

practice may also have some influence on the suitability of a particular scheme. The conditions for

transmission may also be poorer in extensive networks or in networks with many branches. Finally,

Ex considerations may rule out some schemes in some countries.

Applicability The grounding schemes shown overleaf assume that the T-boxes/junction boxes are serving plant

sections that are some distance from each other and the control room, making it likely that each is

connected to a different earth potential. They address the problem of preventing current loops

developing within the cable shield, should a multiple grounding scheme be chosen, see Fig. 6-2. For

simplicity, the wiring is shown with screw terminals. If a M12 connector is used, the device

connection compartment should be opened to check whether the shield wire is already connected

to the internal device grounding terminal. If this is the case, it must be detached and isolated, if a

isolated scheme is required. For T-boxes and junction boxes, the manufacturer’s instructions must

be followed.

Central grounding Potential matching line

Page 78: Endress+Hauser Profibus Planing Guide

6 Installation PROFIBUS PA PROFIBUS planning and commissioning

76 Endress+Hauser

Full isolation Full isolation is the scheme described in IEC 61158-2, and is the favoured method in Britain and

the USA. In this case, the cable shield ground is fully isolated from the device grounds. The shield

is grounded at the power supply or safety barrier only.

The disadvantage of this method is that the bus signal is not optimally protected from high frequency

interference. Just how much this disturbs communication, depends upon the length of the bus, its

topology and the sources of interference. As pointed out at the start of this chapter, if the bus runs

in grounded metal conduits, as e.g. in American installations, then this scheme may work quite well.

Fig. 6-2: Full isolation with optional grounding of devices:1 Power supply/segment coupler, 2 T-Box or junction box, 3 Bus terminator, 4 Grounding point for bus cable shield,

5 Optional grounding of devices, e.g. by neutral star bonding or conduit

Fig. 6-3: Full isolation with optional potential equalisation of devices:1 Power supply/segment coupler, 2 T-Box or junction box, 3 Bus terminator

4 Grounding point for bus cable shield, 5 Local device grounds, 6 Optional potential equalisation line

Page 79: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 6 Installation PROFIBUS PA

Endress+Hauser 77

Multiple grounding Multiple grounding provides enhanced protection against electromagnetic interference in noisy

environments. It is the favoured method in Germany. All devices and cable shields are grounded

locally. Each local ground is connected to a thick potential equalisation line, which itself is grounded

in a safe area.

According to IEC 79-13, Paragraph 12.2.2.3, this method can be used provided that the installation

is effected and maintained in such a manner that there is a high level of assurance that potential

equalisation exists between each end of the circuit. Under these circumstances it fulfils intrinsic

safety requirements.

Fig. 6-4: Multible grounding with neutral star earth bonding:1 Power supply/segment coupler, 2 T-Box or junction box, 3 Bus terminator, 4 Potential equalisation through star bonding

Fig. 6-5: Multible grounding with potential equalisation line:1 Power supply/segment coupler, 2 T-Box or junction box, 3 Bus terminator, 4 Local ground, 5 Potential equalisation line

Page 80: Endress+Hauser Profibus Planing Guide

6 Installation PROFIBUS PA PROFIBUS planning and commissioning

78 Endress+Hauser

Capacitive isolation In the case of capacitive grounding, the shield is connected to the grounding system (here shown

as potential equalisation line) via a capacitor at all points except the power supply or safety barrier,

which is grounded in the normal way. Small capacitors (e.g. 1 nF, 1500 V, dielectric strength,

ceramic) are used and the total capacitance connected to the shielding may not exceed 10 nF. The

capacitors are normally built into the T-box and junction box connectors, and offered as such by the

component manufacturers. This method is not permitted in Ex applications.

Fig. 6-6: Capacitive grounding in a safe area:1 Power supply/segment coupler, 2 T-Box or junction box with capacitive shield grounding,

3 Bus terminator with capacitive shield grounding, 4 Local grounds, 5 Potential equalisation line (optional)

If the bus runs into a hazardous area the T-boxes and junction boxes must be wired in the normal

way and the power supply or barrier grounded via a capacitor.

Fig. 6-7: Capacitive grounding in a explosion hazardous area:1 Power supply/segment coupler with capacitive shield grounding, 2 T-Box or junction box, 3 Bus terminator,

4 Local grounds, 5 Potential equalisation line (optional)

Page 81: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 6 Installation PROFIBUS PA

Endress+Hauser 79

6.3 Termination

The start and end of every PROFIBUS PA segment must be fitted with a bus terminator. For non-

hazardous areas, some T-boxes have an integrated terminating element that can be switched in

when required. If this is not the case, a separate terminator must be used.

• The segment coupler at the beginning of the segment has a built in terminator.

• The terminator in the T-box at the end of the segment must be switched in, or a separate

terminator must be used.

• T-boxes with switchable terminators may not be used in explosion hazardous areas. The

terminator requires the corresponding FISCO approval and is a separate unit.

• For a segment with a tree architecture, the bus ends at the device that is the furthest from the

segment coupler.

• For a junction box, the termination can be made at the box, provided that none of the

connected spurs exceeds 30 m in length.

• If the bus is extended by the use of a repeater, then the extension must also be terminated at

both ends.

The beginning and end of the PROFIBUS DP segment must also be terminated, see Chapter 3. The

terminating resistors are already built into most of the connectors on the market and must only be

switched in.

6.4 Overvoltage protection

Depending upon the application, the PROFIBUS PA segment can also be protected

against overvoltages.

• An overvoltage protector is installed immediately after the segment coupler.

• An overvoltage protector is installed immediately before every device

(between the device and the T-box).

• In the case of hazardous applications, each overvoltage protector must have the corresponding

approval.

• The manufacturer's instructions are to be observed when installing.

The overvoltage protectors HAW 560, HAW 560Z, HAW 562, HAW 562Z, HAW 569 and HAW

569Z are available from Endress+Hauser.

Fig. 6-8: PROFIBUS PA overvoltage protection system

Segment coupler

Field device

Overvoltage protection

Page 82: Endress+Hauser Profibus Planing Guide

6 Installation PROFIBUS PA PROFIBUS planning and commissioning

80 Endress+Hauser

6.5 Installation of the devices

PROFIBUS devices must be installed in accordance with their operating manuals. Table 6-1 lists all

manuals available at the time of writing. Current manuals can be downloaded from the company’s

Internet site: www.endress.com. It should be noted that for some devices, a separate manual is

available covering PROFIBUS installation.

All Endress+Hauser devices have integrated polarity protection and can be commissioned

independent of the actual polarity. If a device without polarity protection is incorrectly wired, then

it will not be recognised by the PLC or operating program. Such an incorrect connection, however,

has no damaging effect on the device or the segment.

! Note!

• All Endress+Hauser devices designed for use in explosion hazardous areas conform to the

FISCO model /Ex ia.

• In the case of four wire devices, the supply connection compartments are designed with type

of protection Ex d and/or Ex e. This usually precludes the use of the standard M12 connector.

• In addition to the general installation guidelines, any special guidelines for installation in

explosion-hazardous areas as well as the guidelines in Chapter 5-1 regarding the

interconnection of devices in explosion hazardous areas must be observed.

Operating manuals . Device Device type ID Code Operating

instructions

Cerabar M PMC41, PMC45, PMP41, PMP45, PMP46, PMP48 151C BA222P/00/en

Cerabar S PMC631, PMC731, PMP635, PMP731 1501 BA168P/00/en

Deltabar S PMD230, FMD230, PMD235, FMD630, FMD633 1504 BA167P/00/en

Deltapilot S DB50, DB50A, DB50, DB50S, DB51, DB51A, DB52, DB52A,

DB53, DB53A, FEB24, FEB24P

1503 BA164P/00/en

PROFIBUS I/O-Box FXA164 1514 ---

Levelflex M FMP40 152D BA243F/00/en

Liquiphant M FDL60, FDL6,1 FEL67, FTL670 152B BA141F/00/en

Liquisys M LF,

pH,

Tu,

O2,

Cl

1515

1516

1517

1518

1519

BA209C/00/en

Micropilot II FMR130, FMR131, FMR230V, FMR231E, FMR230, FMR231,

FMR240, FMR530, FMR531, FMR532, FMR533,

150A BA176F/00/en,

BA202F/00/en

Micropilot M FMR130, FMR131, FMR230V, FMR231E, FMR230, FMR231,

FMR24,0 FMR530, FMR531, FMR532, FMR533,

1522 BA225F/00/en,

BA226F/00/en

Multicap FEC14 153A BA261F/00/en

Mycom II pH Value: CPM152

LF inductive: CLM152

LF conductive: CPM152

1508

1509

150B

1513

BA143C/07/en

BA168C/07/en

BA144C/07/en

Mycom S LF conductive: CLM153

LF inductive: CPM153

pH Value: CPM153

1535

1537

1539

BA234C/07/en,

BA298C/07/en

Mypro LF: CLM431

pH Value: CPM431

150C

150D

BA198C/07/en

Promag 33 33W, 33P, 33H 1505 BA029D/06/en

Promag 35 35W, 35P, 35H 1505 BA029D/06/en

Page 83: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 6 Installation PROFIBUS PA

Endress+Hauser 81

Table 6-1: Endress+Hauser operating manuals for installation of the PROFIBUS PA devices

Device Device type ID Code Operating

instructions

Promag 50 50W, 50P, 50H 1525 BA055D/06/en

Promag 53 53W, 53P, 53H 1527 BA053D/06/en

Promass 63 63A, 63E, 63F, 63H, 63I, 63M 1506 BA033D/06/en

Promass 80 80A, 80E, 80F, 80H, 80I, 80M 1528 BA072D/06/en

Promass 83 83A, 83E, 83F, 83H, 83I, 83M 152A BA063D/06/en

Prowirl 72 72F, 72W 153B BA085D/06/en

Prowirl 73 73F, 73W 153C BA094D/06/en

Prowirl 77 77 1510 BA037D/06/en

Prosonic Flow 90 90W, 90U, 90C 152F BA074D/06/en

Prosonic Flow 93 DDU10, DDU15, DDU18, DDU19 1530 BA076D/06/en

Prosonic M FMU40, FMU41, FMU43 152C BA238F/00/en

Prosonic T FMU130, FMU131, FMU230, FMU231, FMU232, FTU230,

FTU231

1502 BA166F/00/en

Display RID261 BA098R/09/a3

Smartec S CLD132 153E BA213C/07/en

TMD834 TMD834 1507 BA090R/09/en

iTemp PA TMT184 1523 BA115R/09/en

Page 84: Endress+Hauser Profibus Planing Guide

6 Installation PROFIBUS PA PROFIBUS planning and commissioning

82 Endress+Hauser

6.6 Setting addresses

The device address can be set either locally via switch (e.g. DIP, DIL, ...), via local operating

elements or by the appropriate software (e.g. FieldCare or Commuwin II).

• All PROFIBUS devices must have a unique address. Valid addresses lie within the range

0…125. For the rules and examples of address assignment, see Section 5.7.

• If an address is not configured correctly, the device will not be recognised by the master.

• The address 126 is used for initial commissioning and for service purposes. This is normally the

default address of Endress+Hasuer PROFIBUS PA set at the factory.

6.6.1 Using DIP switches

Eight-gang DIP switch All Endress+Hauser devices except the analysis device Mypro or TMT 834 are fitted with an DIP

switch for setting the device address. Fig. 6-9 shows a typical example:

• A = DIP switches 1 - 7: defining the device address

• B = DIP switch 8: address mode (type of addressing)

(ON = software addressing / OFF = hardware addressing)

Fig. 6-9: Example 1: DIP switches for setting the device address

Ten-gang DIP switch The flowmeter Prowirl 72/73 has a ten-gang switch, see Fig. 6-10:

• A = DIP switches 1 - 7 = defining the device address

• B = DIP switches 8 - 9 = not defined

• C = DIP switch 10 = address mode (type of addressing)

(ON = hardware addressing / OFF = software addressing)

Fig. 6-10: Example 2: DIP switches for setting the device address at Prowirl 72/73

Hardware addressing 1. Set switch 8 to OFF. (For Prowirl 72/73 set switch 10 to ON)

2. Set an address with DIP switches 1 - 7: the associated values are shown in the table below.

Table 6-2: Setting the device address

Software addressing 1. Set switch 8 to ON. (For Prowirl 72/73 set switch 10 to OFF)

Switch No. 1 2 3 4 5 6 7

Value in position "off" 0 0 0 0 0 0 0

Value in position "on" 1 2 4 8 16 32 64

Page 85: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 6 Installation PROFIBUS PA

Endress+Hauser 83

6.6.2 Software addressing with FieldCare

If software addressing is used, the devices must be switched on one-by-one or connected point-to-

point to the workstation.

1. Where appropriate, check that software addressing has been enabled at the DIP-switch.

2. In the Network View click on the PROFIdtm and open the Set Device Station Address dialog

Menu Device Operation Device Functions Additional Functions

Set Device Station Address

3. In the dialog, enter the following

– Old Address: Enter the current device address.

– NewAddress: Enter the new device address.

– Click on Set.

4. If changing address was successful, click on Close.

Page 86: Endress+Hauser Profibus Planing Guide

6 Installation PROFIBUS PA PROFIBUS planning and commissioning

84 Endress+Hauser

6.6.3 Software addressing with Commuwin II

If software addressing is used, the devices must be switched on one-by-one or connected point-to-

point to the workstation.To set an address with Commuwin II proceed as follows:

1. Where appropriate, check that software addressing has been enabled at the DIP-switch.

2. Start the DVP1 server with a double click on the DPV1 icon in the Commuwin II program

group.

3. Select the item Set Address in the menu Configure.

4. If a type IM 157 Siemens DP/PA link is being used, enter its DP-address under PA Link Addr.

5. Enter the current address under Old Addr. (= 126 when commissioning).Check the address

entered by clicking on Check Old Address. If a device with the entered address is found, a

message to this effect appears under Device ID. Otherwise the error message "unknown"

appears.

6. Enter the new address in New Addr. Check that there is no address conflict by clicking on

Check New Address. When the button Set Address becomes active, click on it to assign the

new address to the device.

7. When the procedure is completed correctly, the following message appears:

"Address successfully changed!"

Page 87: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 85

7 System Integration

This chapter is concerned with system integration and is structured as follows:

• Network configuration

• Device database files

• Cyclic data exchange

• Bus parameters

7.1 Network configuration

In general, the a PROFIBUS network configuration proceeds as follows:

1. The network participants are stipulated in the configuration program (see Table 7-1). The GSD

files are then loaded into the specified directory of the program and the network is configured

off-line with the planning software.

2. The PLC application program is now written. This is done using the manufacturer's system

programming software. The application program controls the input and output of data and

determines where the data are to be stored.

If necessary, an additional conversion module must be used for PLCs that do not support the

IEEE 754 floating point format. Depending upon the way the data is stored in the PLC (LSB or

MSB), a byte swapping module may be required.

3. After the network has been designed and configured, the result is loaded into the PLC as a

binary file.

4. When the PLC configuration is complete, the system can be started up. The master opens a

connection to each individual device. Now by using a Class 2 master, e.g. FieldCare, the

individual devices can be parametrized from a central workstation.

Table 7-1: Examples of network design software

System Master PROFIBUS

configuration

software

System

programming

software

IEEE

conv.-

block

bytes

swap

Siemens S5 … series

S7 … series

COM PROFIBUS

HW Config

HW Config

Step 5

Step 7

PCS 7

FB 201

___

___

no

Allen Bradley PLC-5

ControlLogix

SLC-500

ProcessLogix

SST PROFIBUS

Configuration Tool

RS Logix-5

RS Logix-5000

RS Logix-500

___

___

yes

Schneider TSX Premium Sycon Hilscher PL7 Pro ___ yes

Schneider

Quantum

Modicon Quantum Sycon Concept ___ yes

Klöckner-Moller PS 416 CFG-DP S 40 ___ yes

ABB Freelance AC 800 F Control Builder F Control Builder F ___ no

Bosch ZS 401 Win DP Win SPS ___ yes

Emerson Delta V Delta V

Explorer

Delta V

Explorer

----- no

––– not necessary, since integrated in software

Page 88: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

86 Endress+Hauser

7.1.1 Tested systems

Table 7-2 lists PROFIBUS DP systems that have been successfully tested by Endress+Hauser. New

systems are tested as they come on the market. For the systems listed coupling documentation is

available on request for customers wishing to integrate Endress+Hauser devices into their systems.

Information on systems not in the list *is available on request.

Table 7-2: Summary of tested PROFIBUS DP-systems

PLC/PCS DP interface Segment coupler

ABB Freelance 2000 FieldController Pepperl+Fuchs

Allen-Bradley PLC-5 SST-PFB-PLC Pepperl+Fuchs, Siemens link

Allen-Bradley PLC-5 SST-PFB-PLC + ZA375 Slave Pepperl+Fuchs

Allen-Bradley SLC-500 SST-PFB-SLC Pepperl+Fuchs, Siemens link

Allen-Bradley ControlLogix SST-PFB-CLX Pepperl+Fuchs, Siemens link

Bosch CL400 BM-DP12 Pepperl+Fuchs, Siemens link

Emerson DeltaV VE4014 Pepperl+Fuchs

HIMA H41 (Modbus) PKV20-DPM (Hilscher) Pepperl+Fuchs

Mitsubishi Melsec AnS A1S-J71PB92D Pepperl+Fuchs

Moeller PS416 PS416-NET-440 Pepperl+Fuchs

Omron CS-1 C200HW-PRM21 Pepperl+Fuchs

Schneider TSX Premium TSXPBY100 Pepperl+Fuchs

Quantum 140 CRP 81100 Pepperl+Fuchs, Siemens link

S7-300 315-2 DP Pepperl+Fuchs, Siemens coupler,

Siemens link

Siemens S7-300 315-2 DP + ZA375 Slave Siemens link

Siemens S7-300 315-2 DP + AS-I Link Siemens link

Siemens S7-300 CP342-5 Pepperl+Fuchs

Siemens S7-400 414-2 DP Pepperl+Fuchs, Siemens coupler,

Siemens link

Siemens S5-115U IM308C Pepperl+Fuchs, Siemens coupler,

Siemens S5-135U IM308C Pepperl+Fuchs, Siemens coupler,

Siemens S5-155U IM308C Pepperl+Fuchs, Siemens coupler,

Siemens link

Softing OPC Server Profiboard / Proficard Pepperl+Fuchs

Page 89: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 87

7.2 Device database files (GSDs)

The PROFIBUS system requires a description of the device parameters, e.g. output data, input data,

data format and supported transmission rate, so that it can integrate the field devices into the bus

system. This data is contained in a PROFIBUS device description file (GSD file) which is placed at

the disposal of the PROFIBUS-DP master when the communication system is being commissioned.

Device bitmaps, which appear as symbols in the network tree, can also be integrated.

If devices are used that support the "PA devices" profile, there are three different versions of the GSD

file:

• Manufacturer-specific GSD):

This guarantees the maximum functionality of the field device. Device-specific process

parameters and functions are available. Two versions of the manufacturer-specific GSD are

available, standard and extended. Use the version supported by you control system.

• Profile GSD:

This contains a fixed number of Analog Input blocks (AI) dependent upon the profile of the

measuring principle. If a system is configured with profile GSDs, it will be possible to exchange

a device supplied by one manuafacturer for one produced by another manufacturer.

• Profile GSD (multi-variable)

with the ID number 9760Hex: This GSD contains all possible function blocks specified in the

device profile such as AI, DO, DI, etc.. It is not supported by Endress+Hauser devices.

A decision on which type of GSD is to be used must be made during the planning of the network.

The configuration can be changed during operation (using a Class 2 master, or sometimes the local

display), but it should be remembered, that if the segment is running at or near maximum capacity,

this could lead to a breakdown in communication because the telegram length exceeds 244 bytes.

Obtaining GSD files The GSD files for all Endress+Hauser devices can be acquired in the following manner:

• Internet (Endress+Hauser) → http://www.endress.com (Download Area)

• Internet (PNO) → http://www.profibus.com (Products - Product Guide)

• On CD-ROM from Endress+Hauser: Order-Code-No. 56003894

Contents of the download file from the internet and the CD-ROM:

• All Endress+Hauser GSD files

• Endress+Hauser bitmap files

• Useful information relating to the devices

All the files which are needed for configuration are contained in one zipped file. During unpacking,

the following structure will be created:

• Version #xx stands for the corresponding device version. Device-specific bitmaps can be found

in the directories “BMP” and “DIB”. The utilisation of these will depend on the configuration

software that is being used.

• The GSD files are saved in the subdirectories “Extended” and “Standard” which can be found

in the “GSD” folder. Information relating to the implementation of the field transmitter and

any dependencies in the device software can be found in the “Info” folder. Please read this

carefully before configuration takes place.

Page 90: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

88 Endress+Hauser

Standard and extended

formats

Some systems require that the modules of the GSD files are transmitted with an extended

identification (e.g. 0x42, 0x84, 0x08, 0x05). The associated GSD files can be found in the

“Extended” folder.

All GSD files that have a standard identification (e.g. 0x94) can be found in the “Standard” folder.

When integrating field transmitters, the GSD files with the extended identification should be used

first. If, however, the integration is not successful, the standard GSD should be used. This

differentiation is the result of a specific implementation in the master systems.

Identification The GSD designations are derived from the PNO device ID or Profile ID numbers as follows:

• Standard GSD: EH3_15xx EH = Endress+Hauser

3 = Profile 3.0, _= standard identification

15xx = Device ID-No.

• Extended GSD: EH3x15xx EH = Endress+Hauser

3 = Profile 3.0, x= extended identification

15xx = Device ID-No.

• Profile GSD PA039741 PA = PROFIBUS PA (DP)

03 = Profile 3.0, PA; 13 = Profile 3.0, DP

9741 = Profile ID number

DP files are required for PROFIBUS DP devices and for PROFIBUS PA devices that are operating

with a Pepperl+Fuchs SK2 coupler, see Section 7.4.1.

Working with GSD files The GSD files must be integrated into the automation control system. Depending on the software

that is being used, the GSD files can be copied to the program-specific directory or can be read into

the database using the import function within the configuration software, see operating manuals of

your system.

Example:

In the case of the configuration software Siemens STEP 7 (Siemens PLC S7-300 / 400)

• The GSD files are copied to the subdirectory ...\ siemens \ step7 \ s7data \ gsd.

• The bitmap files are used to display the measuring points in image form. The bitmap files are

saved to the directory ...\ siemens \ step7 \ s7data \ nsbmp.

Taking the example of the Promag 53, the following sections show how the GSD files are integrated

and used

Page 91: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 89

7.2.1 GSD file example

Example Promag 53 Fig. 7-1 shows the block structure of the Promag 53 flowmeter. It can be seen that the device

supports both a manufacturer specific and a Profile 3.0 configuration. The parameters required for

this are carried by the associated GSD files

Fig. 7-1: Block structure of Promag 53

For the Promag 53, which depending upon type supports PROFIBUS PA or PROFIBUS DP, the

following GSD files and bit maps are available:

Table 7-3: Promag 63 GSD files

Device type File type ID-No. File name

Promag 53 PA

PROFIBUS PA

(IEC 61158-2 (MBP))

Manufacture specific GSD 1527 (Hex) EH3_1527.gsd

EH3x1527.gsd

Profile 3.0 GSD 9741 (Hex) PA139741.gsd

Bitmaps N/A EH_1527_d.bmp/.dib

EH_1527_n.bmp/.dib

EH_1527_s.bmp/.dib

Promag 53 DP

PROFIBUS DP

(RS 485)

Manufacture specific GSD 1526 (Hex) EH3_1526.gsd

EH3x1526.gsd

Profile 3.0 GSD 9741 (Hex) PA039741.gsd

Bitmaps N/A EH_1526_d.bmp/.dib

EH_1526_n.bmp/.dib

EH_1526_s.bmp/.dib

Signal Processing

Physical Block

Transducer Block

AI1: Volume flow

AI2: Mass flow

Totalizer 1

Totalizer 2

Totalizer 3

PROFILEParameters

Manufacturerspecific

parameters

OUT VALUEValue/Status

OUT VALUEValue/Status

TOT1 OUT VALUEValue/Status

TOT2 OUT VALUEValue/Status

TOT3 OUT VALUEValue/Status

DISPLAY VALUEValue/StatusCONTROL

Local Operation

Sensor

PR

OF

IBU

S D

P/P

A

Page 92: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

90 Endress+Hauser

7.2.2 Full configuration with manufacturer-specific GSDs

Example Promag 53 After the device has been connected, a double click on the device node configures the

communication telegram.

Fig. 7-2: Full configuration in Siemens PDM

! Note!

• For level and pressure devices, the telegram frame is empty and the content must be selected from

the blocks offered in the device tree

This form of configuration activates all blocks supported by the device. The parameters SET_TOT

and MODE_TOT must be now configured.

Table 7-4: Full configuration of Promag 53 telegram

Iput

Byte

Output

Byte

Data blocks Status Access

type

Block

Designation

Extended

block ID

Standard

block ID

0 – 4 – Volume flow

+ status

active read AI 0x42, 0x84,

0x08, 0x05

0x94

5 – 9 0 + 1 Totalizer 1

+ status +

control value

active read

+

write

SET_TOT_

MODE_TOT_

TOTAL

0xC1, 0x81,

0x84, ox85

0xC1, 0x81,

0x84, ox85

10 – 14 2 + 3 Totalizer 1

+ status +

control value

active read

+

write

SET_TOT_

MODE_TOT_

TOTAL

0xC1, 0x81,

0x84, ox85

0xC1, 0x81,

0x84, ox85

15 – 19 4 + 5 Totalizer 2

+ status +

control value

active read

+

write

SET_TOT_

MODE_TOT_

TOTAL

0xC1, 0x81,

0x84, ox85

0xC1, 0x81,

0x84, ox85

20 – 24 – Mass flow

+ status

active read

+

write

AI 0x42, 0x84,

0x08, 0x05

0x94

– 6 – 10 Display value

+ status

active write DISPLAY_

VALUE

0x82, 0x84,

0x08, 0x05

0xA4

– 11 Control

variable3

active write CONTROL_

BLOCK

0x20 0x20

Page 93: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 91

VALUE and STATUS The values and status are transmitted in the following formats:

• Volume flow: 32-bit floating point number (IEEE-754) m3/h

• Totalizer 1...3: 32-bit floating point number (IEEE-754) m3 or kg

• Mass flow: 32-bit floating point number (IEEE-754) kg/h

• Display value: 32-bit floating point number (IEEE-754)

• Status: 1 byte bit code

• Control value: 1 byte bit code

Totalizers 1-3 can be configured individually. The following settings are possible (factory setting:

volume flow in m3): Off, Mass flow, Volume flow

Output data The display value allows the transfer of a measured value that has been calculated in the controller

to the Promag display. This value can be assigned to the main line, the secondary line and the info

line of the display. The display value comprises 4 bytes measured value and 1 byte status. The status

is displayed as being OK, UNCERTAIN or BAD.

Control variables The control variables SET_TOT_n and MODE_TOT_n for totalizers 1-3 allow them to be controlled

from the automation control system. The following control variables are possible:

• SET_TOT 0 = Totalize

1= Reset

2= Activate predefined value

• MODE_TOT 0= Balancing

1= positive flow detection

2= negative flow detection

3= Stop totalizing.

The control variable is executed through the cyclic data exchange each time the output byte

changes. It is not necessary to reset to “0” to execute a control variable. The predefined totalizer

value is set via the local display or the Class 2 master!

Example of SET_TOT and

MODE_TOT:

If the control variable SET_TOT is set to “1” (1 = Reset the totalizer), the value of the totalizer will

be set to “0”. The value of the totalizer will now be added up starting from “0”.

If the totalizer is to retain the value “0”, it will be necessary to set the control variable MODE_TOT

to “3” (3 = STOP totalizing). The totalizer will now stop adding up. The control variable SET_TOT

can be set to “1” at a later point in time (1 = Reset the totalizer).

Page 94: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

92 Endress+Hauser

7.2.3 Partial configuration with manufacturer-specific GSDs

Example Promag 53 If not all measured variables are not required, the placeholder “EMPTY_MODULE” (0x00) is used

to to deactivate individual measured variables:

Fig. 7-3: Using place holders in Siemens PDM

! Note!

• The placeholder is sometimes called "FREE_SPACE"

The result is that selected blocks are deactivated and the telegram length is reduced. The totaliser

has been configured "without control variable" in this example, so that it acts as an additional

measured value without control. There is no possiblity to stop or reset it.

Fig. 7-4: Example for parrtial configuration of the Promag 53

Iput

Byte

Output

Byte

Data blocks Status Access

type

Block

Designation

Extended

block ID

Standard

block ID

0 – 4 – Volume flow

+ status

active read AI 0x42, 0x84,

0x08, 0x05

0x94

5 – 9 Totalizer 1

+ status

active read TOTAL 0x81,

0x84, ox85

0x81,

0x84, ox85

– – Placeholder disabled EMPTY_

MODULE

0xC1, 0x81,

0x84, ox85

0xC1, 0x81,

0x84, ox85

– – Placeholder disabled EMPTY_

MODULE

0xC1, 0x81,

0x84, ox85

0xC1, 0x81,

0x84, ox85

– – Placeholder disabled EMPTY_

MODULE

0x42, 0x84,

0x08, 0x05

0x94

– 0– 46 Display value

+ status

active write DISPLAY_

VALUE

0x82, 0x84,

0x08, 0x05

0xA4

– 5 Control

variable3

active write CONTROL_

BLOCK

0x20 0x20

Page 95: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 93

7.2.4 Profile GSD

Example Promag 53 After the device has been connected, a double click on the device node configures the

communication telegram.

Fig. 7-5: Configuration using Profile GSD

Note!

• For level and pressure devices, the telegram frame is empty and the content must be selected from

the blocks offered in the device tree

This form of configuration activates all blocks supported by device profile. The GSD file contains

two AI blocks and a Totalizer block. The first AI block is always assigned to the volume flow. This

guarantees that the first measured variable agrees with the field equipment of other manufacturers.

The second AI block can be freely selected as Promag 53 is capable of producing a calculated mass

flow.

There is no difference between the PROFIBUS DP and PROFIBUS PA Profile GDSs except regarding

the transmission rates supported.

Table 7-5: Example for profile configuration with Promag 53

Iput

Byte

Output

Byte

Data blocks Status Access

type

Block

Designation

Extended

block ID

Standard

block ID

0 – 4 – Volume flow

+ status

active read AI 0x42, 0x84,

0x08, 0x05

0x94

5 – 9 0 + 1 Totalizer 1

+ status +

control value

active read

+

write

SET_TOT_

MODE_TOT_

TOTAL

0xC1, 0x81,

0x84, ox85

0xC1, 0x81,

0x84, ox85

20 – 24 – Mass flow

+ status

active read

+

write

AI 0x42, 0x84,

0x08, 0x05

0x94

Page 96: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

94 Endress+Hauser

7.3 Cyclic data exchange

Transfer of analogue values As mentioned previously, analog process values are transmitted to the PLC cyclically in 5 byte

blocks. The measured value is a four byte floating point number to IEEE 754, see Table 7-6. The

fifth byte contains the associated status information.

Table 7-6: Structure of cyclic analog value

If a device delivers more than one measured value (e.g. Promag), the measured value telegram is

increased accordingly, see Chapter 7.3. The number of measured values that a device transmits is

set while the system planning. Table 5-15 in Chapter 5.6 as well as the device operating manuals

summarise the measured values that can be transmitted by Endress+Hauser devices.

IEEE 754 floating point

number

The measured value is transmitted as a IEEE 754 floating point number, whereby

Measured value = (–1)Sign x 2(E – 127) x (1 + F)

Table 7-7: IEEE 754 floating point number

Example 40 F0 00 00 hex = 0100 0000 1111 0000 0000 0000 0000 0000 binary

Value = (–1)0 * 2(129-127) * (1 + 2-1 + 2-2 + 2-3)

= 1 x 22 x (1 + 0.5 + 0.25 + 0.125)

= 1 x 4 x 1.875

= 7.5

Not all PLCs support the IEEE 754 format. For this reason a conversion module must often be used

or written.

Transfer of discrete values If the field device outputs a level limit signal, e.g. Liquiphant M, the information is transmitted in

two bytes as follows. An exact description of the transmission format is to be found in the operating

instructions.

Table 7-8: Structure of digital cyclic value

Status code The status code correspond to the PROFIBUS profiles 3.0 “PROFIBUS PA profile for Process Control

Devices - General Requirements” V 3.0, and are listed in the following sections

Byte 1 Byte 2 Byte 3 Byte 4 Byte 5

Measured value as IEEE 754 floating point number Status

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

Sign Exponent (E) Fraction (F)

27 26 25 24 23 22 21 20 2-1 2-2 2-3 2-4 2-5 2-6 2-7

Fraction (F)

2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2-16 2-17 2-18 2-19 2-20 2-21 2-22 2-23

Byte 1 Byte 2

Digital value (USGN8) Status

Page 97: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 95

7.3.1 Status codes: Device status BAD

Table 7-9: Status code - device status: BAD

Status code Significance Device status Limits

0x00

0x01

0x02

0x03

= Non-specific BAD OK

LO_LIM

HI_LIM

CONSTANT

0x04

0x05

0x06

0x07

= Configuartion error BAD OK

LO_LIM

HI_LIM

CONSTANT

0x08

0x09

0x0A

0x0B

= Function block not available BAD OK

LO_LIM

HI_LIM

CONSTANT

0x0C

0x0D

0x0E

0x0F

= Device failure BAD OK

LO_LIM

HI_LIM

CONSTANT

0x10

0x11

0x12

0x13

= Sensor failure BAD OK

LO_LIM

HI_LIM

CONSTANT

0x14

0x15

0x16

0x17

= No communication

(last usable value)

BAD OK

LO_LIM

HI_LIM

CONSTANT

0x18

0x19

0x1A

0x1B

= No communication

(no usable value)

BAD OK

LO_LIM

HI_LIM

CONSTANT

0x1C

0x1D

0x1E

0x1F

= Out of order BAD OK

LO_LIM

HI_LIM

CONSTANT

Page 98: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

96 Endress+Hauser

7.3.2 Status codes: Device status UNCERTAIN

Table 7-10: Status code - device status: UNCERTAIN

Status Code Significance Device status Limits

0x40

0x41

0x42

0x43

= Non-specific (Simulation) UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x44

0x45

0x46

0x47

= Last usable value UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x48

0x49

0x4A

0x4B

= Substitute set UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x4C

0x4D

0x4E

0x4F

= Initial value

(values which are not saved after the

device or parameters have been reset)

UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x50

0x51

0x52

0x53

= Sensor conversion not accurate

(measured value of sensor not

accurate)

UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x54

0x55

0x56

0x57

= Engineering unit rage violation UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x58

0x59

0x5A

0x5B

= Subnormal UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x5C

0x5D

0x5E

0x5F

= Configuration error UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x60

0x61

0x62

0x63

= Simulated value UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

0x64

0x65

0x66

0x67

= Sensor calibration not accurate UNCERTAIN OK

LO_LIM

HI_LIM

CONSTANT

Page 99: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 97

7.3.3 Status codes: Device status GOOD

Status code Significance Device status Limits

0x80

0x81

0x82

0x83

= Measuring value OK GOOD OK

LO_LIM

HI_LIM

CONSTANT

0x84

0x85

0x86

0x87

= Update event

(change of parameters)

GOOD OK

LO_LIM

HI_LIM

CONSTANT

0x88

0x89

0x8A

0x8B

= Active advisory alarm

(warning: advance warning limit

exceeded)

(priority < 8)

GOOD OK

LO_LIM

HI_LIM

CONSTANT

0x8C

0x8D

0x8E

0x8F

= Active critical alarm

(critical alarm: alarm limit exeeded)

(priority >8)

GOOD OK

LO_LIM

HI_LIM

CONSTANT

0x90

0x91

0x92

0x93

= Update event

(unconfirmed change of parameters)

GOOD OK

LO_LIM

HI_LIM

CONSTANT

0x94

0x95

0x96

0x97

= Unacknowledged advisory alarm GOOD OK

LO_LIM

HI_LIM

CONSTANT

0x98

0x99

0x9A

0x9B

= Unacknowledged critical alarm GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xA0

0xA1

0xA2

0xA3

= Initiate fail-safe status GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xA4

0xA5

0xA6

0xA7

= Wartung erforderlich GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xC0

0xC1

0xC2

0xC3

= Measured value OK GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xC4

0xC5

0xC6

0xC7

= Initialisierung bestätigt GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xC8

0xC9

0xCA

0xCB

= Initialisierung angefordert GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xCC

0xCD

0xCE

0xCF

= not invited GOOD OK

LO_LIM

HI_LIM

CONSTANT

Page 100: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

98 Endress+Hauser

Table 7-11: Status code - device status: GOOD

0xD0

0xD1

0xD2

0xD3

= reserved GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xD4

0xD5

0xD6

0xD7

= do not select GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xD8

0xD9

0xDA

0xDB

= local override GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xDC

0xDD

0xDE

0xDF

= reserved GOOD OK

LO_LIM

HI_LIM

CONSTANT

0xE0

0xE1

0xE2

0xE3

= Initiate fail-safe status GOOD OK

LO_LIM

HI_LIM

CONSTANT

Status code Significance Device status Limits

Page 101: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 99

7.4 Bus parameters

Transmission rates Endress+Hauser's PROFIBUS DP devices support baudrates up to 12 Mbit/s (depends on version).

The baudrate is automatically adjusted to that used by the master and must not be set at the device.

Similarly, PROFIBUS PA devices do not have to be adjusted, since the transmission rate is fixed.

On the other hand, if FieldCare or Commuwin II is used as a Class 2 master, both the transmssion

rate and other bus parameters must be aligned with those of the segment coupler. The same

PROFIBUS DP baudrate must be also be set in the network configuration software:

• Pepperl+Fuchs segment coupler SK1: 93.75 kBit/s

• Pepperl+Fuchs segment coupler SK2: 45.45 kBit/s - 12 MBit/s

• Siemens DP/PA coupler: 45.45 kBit/s

• Siemens DP/PA link: 9.6 kBit/s - 12 MBit/s

The typical values for the other bus parameters are listed in Table 7-12. Please note that for the

Pepperl+Fuchs SK2 coupler, additional parameters must be set, as described later in theis chapter.

Table 7-12: Bus parameters for FieldCare and Commuwin II

Segment coupler Siemens P+F "old" P+F "new"1)

Slot time 640 10000 4095

Max. station delay time 400 1000 1000

Min. station delay time 11 255 22

Setup time 95 255 150

GAP update factor 1 1 1

Max. retry limit 3 3 3

Target rotation time2) (TTR) TTR calculated by master + 20 000 bit times

1) Segment coupler has the label with 12-3-98 or newer

2) Value must be set in all masters.

Page 102: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

100 Endress+Hauser

7.4.1 Aligning FieldCare

The FieldCare transmission rate is set in the PROFIBUS CommDTM:

1. Add the CommDTM for PROFIBUS to the network.

2. Right click on the CommDTM to opens the context menu. Select Configuration.

3. After changing the baudtrate, update the bus parameters and click on Defaults.

4. If necessary optimise the parameters as the manufacturer's specifications.

7.4.2 Aligning Commuwin II

The Commuwin II transmission rate is set in the DPV1 DDE server.

1. Start the server DPV1 from the File Manager or Explorer by a double click on the DPV1 icon in

the Commuwin II program group.

2. Open the item Parameter Settings in the Configure menu. The baudrate can now be

adjusted.

3. After the baudrate has been entered, update the bus parameters by clicking on Default.

4. If necessary optimise the parameters as the manufacturer's specifications.

Page 103: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 101

7.4.3 Commissioning the Pepperl+Fuchs SK2

PROFIBUS PA-slaves Since the SK2 segment coupler works transparently, PROFIBUS PA stations are treated by the

PROFIBUS DP master as if they were PROFIBUS DP slaves. This also applies to commissioning and

configuration. In order that a PROFIBUS PA slave be placed in operation and be configured by a

configuration tool, the GSD file of the slave must be integrated into the configuration tool.

In view of the fact that the SK2 coupler supports several transmission rates on the PROFIBUS DP

side, the normal PROFIBUS PA GSD file cannot be used. Instead, the PROFIBUS DP GSD file is

required. If the device does not support PROFIBUS DP, the PROFIBUS PA GSD file must be

converted with the conversion program supplied by Pepperl+Fuchs with the SK2. This applies both

to the manufacturer-specific and profile GSDs.

! Note!

• The naming conventions for GSD files are described in Chapter 3.4.1.

• If you uncertain what GSD you have, integrate it into your configuration tool and check the

transmission rates supported:

– If the transmission rate 31.25 kBd is supported, it is a PA GSD.

– If the transmission rates of 9.6 kBd to 1.5 MBd or 12 MBd are supported, it is a DP GSD.

GSD Converter If no PROFIBUS DP GSD exists, the PA GSD must be converted. The software can be downloaded

free-of-charge from www.pepperl-fuchs.com. The task of this conversion software is exclusively

to enter the missing transfer rate and set specific bus parameters to values that allow for problem-

free operation of the PROFIBUS DP.

! Note!

• The PROFIBUS user organization has agreed that certified GSD files that have been modified by

the Pepperl+Fuchs GSD converter software do not lose their certificate.

The conversion of the GSD file imposes the following restrictions if the function was previously

supported by the original GSD file:

• FREEZE and SYNC functionality is deactivated. These functions are used in PROFIBUS DP for

synchronizing sensors/actuators. Since the system is working with transfer rates of up to 12

MBd on the PROFIBUS DP side (host side) and with a transfer rate of 31.25 kBd on the

PROFIBUS PA side (field side) it is not possibleto ensure that this synchronization will work

with no problems.

• A maximum of 4 master Class 2 connections (C2 connections) are supported for each slave.

Some PROFIBUS functions are currently not supported. If the field device is supposed to support

one or more of the following functions, a warning will inform the user that this is no longer the case

after the conversion. This affects the following functions:

• Alarms based on PROFIBUS DP V1

• The following functions of the PROFIBUS DP V2

– - Data Exchange Broadcast (Publisher/Subscriber)

– - Time synchronization

– - Isochronous mode, i. e. cycle-synchronous transfer

Page 104: Endress+Hauser Profibus Planing Guide

7 System Integration PROFIBUS planning and commissioning

102 Endress+Hauser

Using GSD Converter After the program is started (pfgsdcv.exe) the following dialogue appears:

Fig. 7-6: Dialogue box: Pepperl+Fuchs GSD Converter

To convert a GSD file, proceed as follows:

1. Switch to the directory in which the GSD files to be converted are located.

2. Select the GSD files to be converted: You can select one or more files (using Ctrl or Shift) for

conversion.

– Files with + before the file name are the result of a former conversion and generate an error

message if you attempt to convert them again.

– Files with a - are not the result ofa conversion and can be converted. You can open a file to

view it and edit it by double clicking on it.

3. Determine the version number of the GSD file to be converted: the name of a PROFIBUS GSD

file always consists of three parts:

– The manufacturer-specific part (1- 4 characters)

– The device ID number (4 characters)

– The file extension

For converted PROFIBUS PA GSD files, the Profibus User Organization (PNO) has specified

that the charaters "YP0" and a version number as the the manufacturer-specific part of the

name. You can select the version number using a drop-down box (revision) and thus generate

different versions of GSD files for a field device (with the same ID number).

4. Switch to the directory in which the converted GSD files will be stored.

5. Convert the GSD files by clicking on the Process GSD --> button.

You can start the conversion process with this button. Another window appears in which you

are informed of the results of the conversion process.

Page 105: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 7 System Integration

Endress+Hauser 103

7.4.4 Watch Dog Time TWD

PROFIBUS devices can activate a watchdog mechanism that checks whether the PROFIBUS master

is still actives every data exchange cycle. The time is measured in the PROFIBUS slave. If the

watchdog is activated and the time TWD (Watch Dog Time) since the last cyclic call expires, the

device quits cyclic data exchange mode, goes into the original state (Wait_prm) and sets the outputs

to the secure state.

The value of TWD and the activation of the watch dog are transferred in the configuration telegram

sent on start up from the PROFIBUS Master to the PROFIBUS slave (transition to the data

exchange). In general, dimensioning of the time TWD is user-specific (not device-specific and not in

the GSD). The lower limit of the value is given by the cycle time.

As a rule, the configuration tool is used to enter the time TWD. There are configuration tools for

which the watchdog time is set at 1x of PROFIBUS master and others for which the watchdog time

is set individually for each PROFIBUS PA station. The value is the same in both cases.

For many tools, the time TWD is automatically calculated based on the cycle time of the master with

a corresponding transmission rate. At higher transmission rates on the PROFIBUS DP side (for

example 12 MBd) cycle times on the PROFIBUS PA side may be longer by a factor of 300. If

parameters were set directly for a PROFIBUS PA device using a high transmission rate, TWD is

usually less than the PA cycle and the device never exchanges data.

Segment coupler SK2 To ensure reliable operation of the PROFIBUS the following bus parameters should be used:

• Transfer rate 45.45 kBd... 12 MBd

• Watchdog time TWD = 5 s

• PROFIBUS DP standard bus parameter

! Note!

If there are a large number of PROFIBUS PA stations per channel of the SK2 segment coupler, the

watchdog time TWD should be verified. The limit for the above value is about 32 stations, but

depends on the volume of data to be transferred.

Determining TWD The above watchdog time is based on experience. If it is too long (slaves are not switching into the

secure state quickly enough) or too short (slaves are switching into the secure state without the

master ever having failed) this must be taken into the calculation. Depending on the configuration

tool, you can:

• set parameters for only one watchdog time TWD for the entire PROFIBUS system.

In this case, the greatest delay time must be used as the basis for determining TWD.

• set parameters for a watchdog time TWD for each individual slave.

The time TWD set must be greater than the longest delay time TV_max that will occur:

TV_max = TCycle_DP + TCycle_PA_cannel

where TCycle_PA_channel = Cycle time of the PROFIBUS PA channel

TCycle_DP = Cycle time of the PROFIBUS DP side

Pepperl+Fuchs recommends three times the PROFIBUS PA cycle time be used for the SK2.

Calculating TWD The PA cycle time TCycle_PA_channel depends on 1) the number n of stations on a channel and 2) the

effective data length LΣ (total bytes input and output data of all devices/no. of devices): Cycle time

can be calculated in an approximate manner as

TCycle_PA_cannel = n * (0.256 ms * LΣ + 12 ms) + 40 ms

For more information on calculating cycle time, please refer to the P+F instruction manuals.

Page 106: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

104 Endress+Hauser

8 Device Parametrization

This chapter describes the operating concept of the PROFIBUS PA devices and is subdivided as

follows:

• PROFIBUS PA block model

• Functional survey

• FieldCare asset management software

• Commuwin II operating and display program

There are two reasons for parametrizing a PROFIBUS PA or DP device:

• the adjustment of the operating parameters of the device to calibrate it for the application at

hand. In this case the corresponding operating instructions should be used.

• the adjustment of the profile parameters of the device in order to e.g. scale or simulate the

cyclic measured value output to the PLC.

Profile parameters are accessible only through the acyclic services of the PROFIBUS DP system.

Local operation The operating parameters of most Endress+Hauser devices can be set up using the local operating

elements of the device, if they are so equipped. This facility is provided in order that they can be set

up before installation, e.g. on a test bench. It is not advisable to change parameters locally during

the operation of a system, since this may have unforseen consequences, e.g. on control loops. For

this reason, local operating should be disabled when the system is commissioned. More details on

this function and the calibration of Endress+Hauser devices are to be found in the corresponding

manuals.

Remote operation Device parameters can also be adjusted by the acyclic services of the PROFIBUS DP system, with

an appropriate configuration program. This might be embedded within the system or run on an

independent workstation. Endress+Hauser offers two alternatives: the FieldCar asset management

ent software and the Commuwin II operating and display program. The latter is to be found in many

existing plants, but will be gradually replaced over the next year.

This chapter contains a short overviewof the parametrization of devices via both these programs.

Full descriptions must be taken from the appropriatte device manuals.

Page 107: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 105

8.1 PROFIBUS PA block model

The PROFIBUS PA block model describes several parameters that can be used to realise a device.

Mandatory parameters must always be present. Optional parameters are only present when

required, e.g. for a particular transmitter type. Manufacturer-specific parameters are used to realise

device functions that are not in the profile. A manufacturer's operating tool or a device description

is required for their operation.

Based on this general structure, special block characteristics are specified in the PROFIBUS PA

profile. Fig. 8-1 and 8-2 shows the general way in which the blocks are used within the system.

In the case of PROFIBUS PA devices that conform to PROFIBUS PA Profile 3.0 , these parameters

are managed in block objects.

Fig. 8-1: PROFIBUS PA block model of a sensor

Fig. 8-1 shows the block model of a simple sensor. It comprises four blocks: device management,

physical block, transducer block and function block that are described in detail in the following

sections. The sensor signal is converted to a measured value by the transducer block and transmitted

to the function block. Here the measured value can be scaled or limits can be set before it is made

available as the output value to the cyclic services of the PLC.

Fig. 8-2: PROFIBUS PA block model of an actuator

For an actuator, the processing is in the reverse order, see Fig. 8-2. The PLC outputs a setpoint value

that serves as the input value to the actuator. After any scaling, the setpoint value is transmitted to

the transducer block as the output value of the function block. It processes the value and outputs a

signal that drives the valve to the desired position.

Device management

Physical block

Transducer FunctionblockblockSensor signal

Output value of

Measured value

PLC

transmitter/input value of PLC

Device management

Physical block

TransducerFunctionInput value of

Output value

PLC

block block Signal to valveactuator(set point)/output value of PLC

Page 108: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

106 Endress+Hauser

8.2 PROFIBUS PA profile

The PROFIBUS PA profile defines standard block parameters for transmiiters, actuators and

analysers. Fig. 8-3 gives an overview of the devices that have been considered in the specification

of the flow, pressure, temperature, level blocks etc.

Fig. 8-3: Overview of device types covered by the profile blocks

Measuringequipment

Measuring equipmentwith analogue or

digital output

Measuring equipmentLimit detection

D (Density) F (Flow) L (Level) Q (Quality)R T W

(Radiation) (Temperature) (Weight Mass)

E (Electricalvariables)

Differential

Floating

Electro-

Ultrasonic

Vortex

Displacement

Turbine wheel

Coriolis

Thermal

Hydrostatic

Displacement

Float

Ultrasonic

Microwave

Laser/optical

Radiometric

Capacitance

P (Pressure)S (Speed,

Pressure

Differential

Resistance

Pyrometer

Expansion

Bimetallic

Hot/cold

Rotation,Frequency)

pressure

body

magnetic

counter

counter

counter

pressure

thermocouple

strip

conductor

Page 109: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 107

The profile itself defines two block structures, one for transmitters and actuators (Fig. 8-4) and a

second for analysers (Fig. 8-5), whereby the latter differs only by a number of additional functions.

Fig. 8-4: Properties of profile blocks for transmittters and actuators

Fig. 8-5: Properties of profile blocks for anayzers

Physical Block

Administration

Transducer Blocks

Function Blocks

Temperaturee,Pressure,Flow,Level

Electro-pneumatic,ElectricActuation

DiscreteInput

DiscreteOutput

AnalogInput

Totalizer AnalogOutput

DiscreteInput

DiscreteOutput

Cyclic InterfaceMS0

Acyclic InterfaceMS1 und MS2

Remote Access

Sensor(s) Actuator(s)

Physical Block

Administration

Transducer Blocks

Function Blocks

Analyser

AnalogInput

Totalizer AnalogOutput

DiscreteInput

DiscreteOutput

Cyclic InterfaceMSO

Acyclic InterfaceMS1 und MS2

Remote Access

SensorActuator

Transfer Control

Limit Alarm

Page 110: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

108 Endress+Hauser

8.2.1 Block structure

The parameters assigned to the individual blocks use the data structures and data formats that are

specified in the PROFIBUS standard. The structures are designed such that the data are stored and

transmitted in an ordered and interpretable manner.

All parameters in the PROFIBUS-PA profile, whether mandatory or optional, are assigned an address

(slot/index). The address structure must be maintained, even if optional parameters are not

implemented in a device, This ensures that the relative indices in the profile are also to be found in

the devices.

Standard parameters With the exception of the device management, the standard parameters are to be found at the

beginning of every block. They are used to identify and manage the block. The user can access these

parameters using the acyclic services, e.g. by means of the FieldCare asset management software or

the Commuwin II operating and display program. Table 8-1 lists and briefly explains the standard

parameters.

Table 8-1: Standard block parameters

Rel.

Index

Parameter Description R/W M/O

1 BLOCKOBJECT Contains the type of block, e.g. function block, as well as further

classification information in the form of three storey a tree

structure.

R M

2 ST_REV Event counter: Counts every access to a static block parameter.

Static parameters are those device parameters that are not

influenced by the process.

R M

3 TAG_DESC Text for unambiguous identification of the block: In the physical

block, TAG_DESC is used as the measuring

point tag.

R, W M

4 STRATEGY A code number that allows blocks to be grouped together. R, W M

5 ALERT_KEY Identifies the part of the plant where the transmitter is located.

Helps in the localisation of events.

R, W M

6 MODE_BLK Describes the operating mode of the block.

Three parameters are possible:

• Actual_Mode

• Permitted_Mode and

• Normal_Mode.

MODE_BLK allows a functional check of the block. If the block

is faulty, a default value can be output.

R, W M

7 ALARM_SUM Contains the current status of the block alarms. At the moment

only the following are signalled: the change of a static parameter

(10 s) and the violation of the advisory and critical limits in the

analog input block.

R, W M

8 BATCH Provided for batch processes as per IEC 61512 Part 1. Is only to

be found in function blocks.

R, W M

R = Read, W = Write, M/O = Mandatory/Optional parameter

Page 111: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 109

8.2.2 Device management

Device management comprises the directory for the block and device object structure indicating:

which blocks are present in the device, where the start addresses are located (slot/index) and how

many objects each block holds. By using this information, the application program of the master can

find and transmit the mandatory and optional parameters of a profile block, see Fig. 8-3.

Fig. 8-6: Structure and function of the device management (device management block)

Parameters

Table 8-2: Device parameters

Rel.

Index

Parameters Description R/W M/O

0 DIRECTORY_OBJECT_HEADER Header comprising

(see Fig. 7.3 for parameter names)

• Directory code (=0)

• Directory version number

• Number of directory objects

• Number of directory entries

• Index of the first directory entry

• Number of block types

R M

1 COMPOSITE_LIST_DIRECTORY

_ENTRIES/

COMPOSITE_DIRECTORY_ENTRIES

Pointer:

• Abs. index + offset, 1st physical block

• Number of physical blocks

• Abs. index + offset, 1st transducer block

• Number of transducer blocks

• Abs. index + offset, 1st function block

• Number of function blocks

• Pointer 1 to 1st block

• Pointer 2 to 2nd block

.....

• Pointer # to #th block

R M

2 COMPOSITE_DIRECTORY_ENTRIES_

CONTINUOUS

Continuation of

COMPOSITE_DIRECTORY_ENTRIES

or start of the pointer entries

R M

R = Read, W = Write, M/O = Mandatory/Optional parameter

Page 112: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

110 Endress+Hauser

8.2.3 Transmitter and actuator blocks

This section provides an overview of the purpose and properties of the standard transmitter and

actuator blocks as shown in Fig. 8-4.

Physical block

Transducer blocks

Block class Description

Administration

Physical Block The physical block contains the software and hardware characteristics of a

field device that are associated with its resources, e.g. electronics, operating

system, device status, etc.. Similar to the transducer block, the physical block

isolates the application block from the hardware-specific properties of the

device by the provision of a standardised parameter interface. The following

functions are offered through read/write services:

• Nameplate information (read-only)

• Diagnosis information (read-only)

• Write protection management

• Warm and cold start of the device (write)

• Change of identity number (read/write)

Block class Description

Transducer Blocks (TB)

Temperature TB This block describes the characteristics of temperature measurement by

resistance temperature devices, thermocouples and pyrometers. It contains

the following functions:

• Characterization of sensor type with default examples

• Connection type setting (2, 3, or 4 leads)

• Reference temperature compensation

• Loadable linearisation table

• Various measured value combinations from two integrated sensors

• Provision of measured value in at least one of the following units:

K, °C, °F und Rk

• Monitoring of sensor, sensor lead connection and hardware

• Minimum and maximum measured value display

Pressure TB This block describes the characteristics of pressure and differential pressure

measurement for pressure, flow and level measurement applications.

It contains the following functions:

• Characterization of sensor and measuring cell type

• Sensor calibration

• Loadable linearisation table

• Low flow cut-off

• Provision of measured value in the following units:

– Pressure: kPA, bar, psi and Hg

– Flow: m3/h, L/s, CFM cubic feet per minute and lb/s

– Level: %, m und ft

• Provision of medium temperature

• Minimum and maximum temperature value display

Flow TB This block describes the characteristics of flow measurement by the Coriolis,

magnetic, ultrasonic, vortex, variable area and themal mass principles. It

contains the following functions:

• Characterization of sensor type and mounting

• Setting of specific parameters for the various measurement principles, e.g.

ultrasonic frequency, vortex frequency etc.

• Sensor calibration

• Low flow cut-off

• Readable sensor values

• Range limit values with signalling of violations

• Provision of measured value in at least one of the following units:

– m3/h, L/s, CFM cubic feet per minute as well as kg/s and lb/s

• Provision of the temperature and density of the medium

Page 113: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 111

Function blocks

Level TB This block describes the characteristics of level measurement by the radar,

ultrasonic, hydrostatic and capacitive principles. It contains the following

functions:

• Characterization of sensor type and mounting

• Sensor calibration

• Consideration of tank characterisitics

• Loadable linearisation table

• Range limit values with signalling of violations

• Provision of measured value in at least one of the following units:

– Level: %, m and ft

• Provision of the temperature of the medium

• Readbale sensor values

• Minimum and maximum temperature value display

Actuation TB The actuation transducer block describes the characteristics of electro-

pneumatic and electrical positioners and provides the following signals:

• Characterization of positioning principle

• Identification of the control valve and positioner (manufacturer, ...)

• Fail safe position

• Matching of control parameters

• Loadable linearisatioin table

• Suppression of small positioning changes

• Details of positioning time

• Details of torque

• Setting of braking performance

• Details of opening and closing times

• Storage of installation data and date of last maintenance

Discrete Input TB The discrete input transducer block provides the following signal processing

functions:

• Sensor cabling check

• Identification of the sensor (manufacturer, ...)

Discrete Output TB The discrete output transducer block describes the characteristics of electro-

pneumatic positioners and provides the following signal processing functions,

dependent upon actuation priniciple:

• Identification of the control valve and positioner (manufacturer, ...)

• Fail safe position

• Details of positioning time

• Details on the number and limits of the positioning events

• Details on the time span of the start of movement after the change in set

value as well as the time taken to open and close

Block class Description

Transducer Blocks (TB)

Block class Description

Application Function Blocks

Analog Input The analog input function block provides the following signal processing

functions for the measured values arriving from a sensor transducer block:

• Scaling

• Filtering (PT1 element)

• Change of operating mode: hand/automatic

• Special arithmetic functions (e.g. square root for flow values from pressure

measurements)

• Simulation of measured values without the use of a transducer block

• Provision of replacement values on device faults

• Warnings, alarms and limit values

Page 114: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

112 Endress+Hauser

Analog Output The analog output function block provides the following signal processing

functions for setpoint values, which are then passed on to the actuator

transducer block. It is particularly suitable for use woth controlled actuators:

• Scaling

• Change of operating mode: hand/automatic/local override

• Simulation of the actual value of the positioner

• Provision of replacement values (fail-safe) on positioner faults or loss of

communication

Discrete Input The discrete input function block provides the following signal processing

functions for the discrete value of a sensor transducer block:

• Change of operating mode: hand/automatic

• Inversion of discrete value

• Simulation of discrete value

• Provision of replacement values on fault recognition

Discrete Output The discrete output function block provides the following signal processing

functions for set point values, which are then passed on to the actuator

transducer block.It is particularly suitable for on/off actuators:

• Inversion of setpoint value

• Change of operating mode: hand/automatic/local override

• Simulation of the actual value of the positioner

• Provision of replacement values (fail-safe) on loss of setpoint value or loss of

communication

Totalizer The tatalizaer function block provides the following signal processing

functions for the setpoint values that are directly linked to a transducer block

output:

• Change of operating mode: hand/automaticg

• Selection of counting mode (forwards, backwards, positive only, negative

only, halt)

• Reset of totalizer

• Limit value monitoring

Block class Description

Application Function Blocks

Page 115: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 113

8.2.4 Analysis devices

This section provides an overview of the purpose and properties of the special blocks for analysers

as shown in Fig. 8-4.

Physical block

Transducer blocks

Application blocks

Block class Description

Administration

Physical Block see Section 8.2.3

Block class Description

Transducer Blocks (TB)

Analyser TB The analyser transducer block contains the measuring pronciple dependent

conversion of sensor value into a measured value with engineering units. It

contains the follwoing functions:

• Specification of sensor measuring range

• Automatic range switching

• Specification of sampling rate of measuring signal

Transfer TB The transfer function block executes mathematical calculations. It can be

switched in series with the analyser block. It contains the following functions:

• Correction of measured value

• Cross-sensitivity compensation

• Filtering

Control TB The control transducer block offers complex functions that allow it to work as

a device controller. It performs clocked or command-initiated sequential

control of the following field device functions:

• Measurement

• System check

• Cleaning

• Calibration

• Initialisation

Limit TB The limit transducer block provides the following limit monitoring functions

for measured values. In order that they are integrated into cyclic

communication, limit violations can be signalled to a discrete input block as a

binary value.

• Hysteresis

• Pull-up and drop-down delay

• Exceeding of limit values

• Dropping below of limit values

Alarm TB On the basis of the NAMUR status classes ready for operation, maintenance

necessary, functional check or fault, the alarm transducer block provides the

status and predefined texts in the device.

Block class Description

Application Blocks

Analog Input see Section 8.2.3

Analog Output see Section 8.2.3

Discrete Input see Section 8.2.3

Discrete Output see Section 8.2.3

Logbook The logbook is a permanent buffer (ring buffer) for the alarm messages of the

alarm transducer block

Page 116: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

114 Endress+Hauser

8.2.5 Function overview

The block descriptions in Sections 8.2.3 and 8.2.4 are very generalised and highlight selective

functions only. The following table lists more functions of interest to field devices together with their

use within the blocks and position in the profile specification, For detailed information it is

recommended that the original profile specifications are read.

Device function Contained in Reference in PROFIBUS PA-Profile

Function

Block

Transducer

Block (TB)

Physical

Block

Actuator diagnosis X Data sheet Actuator

Additional measured values X Data sheet Transmitter

Alarm summing X X X General Requirement,

Standard parameter ALARM_SUM

Application related

I/O point characterisation

X X X General Requirement,

Standard parameter STRATEGY und

ALERT_KEY

Batch identification to

ISA SP88

X General Requirement FB

Standard function

Block characterisierung X X X General Requirement,

Standard parameter Block Objekt

Calibration X Data sheet Transmitter, Actuator and

Analyser - all TBs

Cascading X Data sheet Actuator (AO)

Check process limit value X Data sheet Transmitter (AI)

Check sensor limits X Data sheet Transmitter, Actuator and

Analyser - all TBs

Correction and compensation

calculations

X Data sheet Analyser, Transducer

Transfer Block

Device function sequential

controller

X Data sheet Analyser - Control

Transducer Block

Device function test X Data sheet Analyser, Physical Block

extensions

Device identication X General Requirement, Physical Block

Device status X Data sheet Analyser:

Additions to Physical Block

Fail-Safe functions X Data sheet Transmitter (AI), Actuator

(AO), Discrete Output (DO)

FB/TB block links X General Requirement, Channel und

Link Object

I/O point designation X X X General Requirement,

Standard parameter TAG_DESC

I/O point definition X Data sheet Transmitter, Actuator and

Analyser - all TBs

Linearisation (X) X General Requirement (Definition), Data

sheet Transmitter (Use) and Aktuator

(Use)

Logbook functions X Data sheet Analyser

Measurement, setpoint and

control signal status

X X General Requirement

Data structure DS-33

Page 117: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 115

Table 8-3: Overview of device functions in PROFIBUS PA Profile Version 3.0

Min/Max pointer function X Data sheet Transmitter - some TBs

Operating mode selection X X X Data sheet Transmitter (AI), Actuator

(AO) Discrete Input (DI) und Discrete

Output (DO), General Requirement

Register parameter changes X X X General Requirement,

Standard parameter ST_REV

Scaling X X Data sheet Transmitter (AI)and

Aktuator (AO)

Sensor and actuator

characterisation

X Data sheet Transmitter, Actuator and

Analyser - all TBs

Sensor and actuator

identification

X Data sheet Transmitter, Actuator and

Analyser - all TBs

Signal diagnosis X X General Requirement, Physical Block

Signal filters X Data sheet Transmitter (AI) and

Analyser (Transfer Transducer Block)

Signal inversion X Data sheet Discrete Input and Discrete

Output

Simulate functions X Data sheet Transmitter (AI Simulate)

and Actuator (AO Simulate)

Table of contents of device - - - General Requirement, Directory,

Mapping Document Directory

Transformation into mapping

variables

X X Data sheet Transmitter (AI-LIN_TYPE)

Warm and cold start of device X General Requirement

Write protection mechanisms X General Requirement, Physical Block

Zero point suppression X Data sheet Transmitter, Actuator -

LOW_FLOW_CUT_OFF

Device function Contained in Reference in PROFIBUS PA-Profile

Function

Block

Transducer

Block (TB)

Physical

Block

Page 118: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

116 Endress+Hauser

8.3 FieldCare Asset Management

FieldCare is Endress+Hauser's FDT based Plant Asset Management Tool. It can configure all

intelligent field devices in your plant and supports you in managing them. By using status

information, it also provides a simple but effective means of checking their health.

• Supports Ethernet, HART, PROFIBUS, and in future FOUNDATION Fieldbus etc.

• Operates all Endress+Hauser devices

• Integrates third-party devices such as actuators, I/O systems and sensors supporting the FDT

standard

• Ensures full functionality for all devices with DTMs

• Offers generic profile operation for any third-party fieldbus device that does not have a vendor.

Installation and

commissioning

FieldCare ensures that devices can be integrated and configured quickly and easily, with the

transparency demanded by good manufacturing practice.

• User Management allows access rights to beassigned according to user authorisation

• Network View aids the building of projects

• Bus Scan automatically finds the devices in the network

• DTM Device Catalogue facilitates DTM handling and improves system reliability

• Device DTMs simplify device configuration,including addressing, advanced diagnosisand

linearisation

• Activity Logging and Reporting ensures that all changes to the application or project are

registered and traceable

• Customisation simplifies handling and improves the availability and accessibility of program

functions

Operations and

Maintenance

FieldCare manages device life-cycle information and presents it quickly and clearly to the user.

• Plant View enables quick retrieval of information by showing your assets structured according

to ISA S88 into sites, areas, process cells etc.

• Document Management allows manuals, SOPs, certificates etc.to be linked to a device

• Placeholders allow display and documentation of transparent or non-communicating

equipment

• Activity Logging registers all user activities with time stampand user ID

• Report Management generates reports on the state of devices, applications and projects

• Condition Monitoring will in future give a quick overview of field devices status with

immediate location of faulty measuring points

Page 119: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 117

8.3.1 Using FieldCare

FieldCare runs on an IBM compatible PC or Notebook under Windows 2000, NT or XP. There are

two basic ways in which it can be used in a PROFIBUS system, see Fig. 8-7:

• The PC is connected directly to the PROFIBUS DP segment via a PROFIBOARD (PC) or

PROFICARD (Notebook) and acts as a PROFIBUS. During system integration the computer is

registered as a Class 2 master.

• The PC is resident on the Ethernet TCP/IP backbone and connected to the PROFIBUS

network via the Fieldgate FXA720 PROFIBUS/Ethernet gateway. During system integration

the Fieldgate is registered as a Class 2 master.

Fig. 8-7: FieldCare architectures: left at DP level, right operating from Ethernet

Operation (Network View) The essence of FieldCare operation is the engineering of the physical network in the so-called

network view. This is done by means of CommDTMs for communication objects such as the

PROFIBUS card or Fieldgate FXA720, DeviceDTMs for the field devices in the network and Profile

DTMs for devices that conform to the PROFIBUS or HART standards, but which do not have a

device-specific DTM, see Fig. 8-8. In order that the full network can be reprresented, placeholder

DTMs are available non-communicating devices. More details are in the FieldCare on-line help.

Fig. 8-8: Mapping of the networks in Fig. 8-7 in FieldCare Network View

The devices are operated by opening the corresponding DTM from the Network View, see e.g.

Section 7.4.1, setting the bus parameters from FieldCare and the example overleaf.

PLC FC

12:00 14:00 16:00 18:00 20:00 22:00

HART

PROFIBUS PA

OSES

PROFIBUS DP

Backbone

PLC

12:00 14:00 16:00 18:00 20:00 22:00

HART

PROFIBUS PA

OSES

PROFIBUS DP

Ethernet

FC

FieldgateFXA720

PC withPROFIBUSinterface

HOST PROFIBUS CommDTM DTM Promass Placeholder DTM Coupler DTM Valve DTM Promag DTM Positioner CommDTM Remote I/O DTM Hart device DTM Hart device DTM Hart device

HOST Fieldgate CommDTM DTM Promass Placeholder DTM Coupler DTM Valve DTM Promag DTM Positioner CommDTM Remote I/O DTM Hart device DTM Hart device DTM Hart device

Page 120: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

118 Endress+Hauser

8.3.2 Generation of a live list

For a PROFIBUS network, the generation of the tree in Network View is practically automatic:

1. Add the PROFIdtmDPV1 to the Host

– The same CommDTM is used for PROFIboard, PROFIcard and Fieldgate

– For Fieldgate, the Host must know the IP address

2. In the Menu bar select Tools Fieldbus Scan Generate Network

3. A live list with TAGs is generated of the devices connected to the PROFIBUS network

8.3.3 Device parametrization

Devices are parametrized by opening the corresponding DTM from the device list. This can be done

both off-line and on-line:

Off-line parametrization: 1. Click on the device you wish to work on.

2. In the menu bar select Device operation Device functions Offline-

Parametrization

3. The device DTM opens: now set the parameters as described in the device manual

Up-/Download: The Upload function allows data from the device to be transferred and stored in FieldCare. With the

Download function, parameters can be transferred from FieldCare and stored in the selected device.

This function must now be used to download the configuration generated during offline

parametrization to connected device.

1. Click on the device you wish to work on.

2. In the menu bar select Device operation Go Online

3. When the green dot appears next to the device, select Device functions Download to

device

Page 121: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 119

8.3.4 On-line parametrization

1. Click on the device you wish to work on.

2. In the menu bar select Device operation Go Online

3. When the green dot appears next to the device, select Device functions Online-

Parametrization

4. The device DTM opens: now set the parameters as described in the device manual

8.3.5 Plant View

Plant View is a logical mapping of the plant built up according to the ISA S88 standard. It gives an

overview of the location of a device within a particular facility.

Fig. 8-9: Plant View is a logical mapping of the plant topology

Plant view forms the basis of FieldCare’s condition monitoring function. It also provides a

convenient way of storing plant documentation, which can be allocated to and retrieved from any

position in the plant view tree. This function is not restricted to PROFIBUS or HART devices, since

a placeholder can be used at any position to represent a non-communicating device. This also

applies to the Network view.

Page 122: Endress+Hauser Profibus Planing Guide

8 Device Parametrization PROFIBUS planning and commissioning

120 Endress+Hauser

8.4 Commuwin II Operating Program

The PROFIBUS DP devices Promass and Promag as well as all PROFIBUS PA devices can be

operated by the operating program Commuwin II (from software version 2.0 upwards) A full

description of Commuwin II is to be found in operating instructions BA124F/00/en. All the

standard functions of Commuwin II are supported excepting envelope curves for ultrasonic and

microwave devices. The device settings can be made using the operating matrix or graphic operating

interface.

! Note!

• Due to the introduction of FieldCare, Commuwin II will be phased out by 2006. While support

will continue over this period, new devices will not be integrated.

Requirements Commuwin II runs on an IBM-compatible PC or Laptop. The computer must be equipped with a

PROFIBUS interface, i.e. PROFIBOARD for PCs and PROFICARD for laptops. Alternatively, a

Fieldgate FXA720 can be be used, see also Fig. 8-7. During the system integration, the computer is

registered as a Class 2 master.

8.4.1 Operation

The PA-DPV1 server must be installed. The connection to Commuwin II is opened from the PA-

DPV1 server.

1. Generate a live list with "Tags"

2. Endress+Hauser operation is selected by clicking on the device name,

e.g. FEB 24 (Deltapilot S).

3. Select profile operation is selected by clicking on the appropriate tag,

e.g. AI: LIC 123 = Analog-Input-Block Deltapilot S.

4. The settings are entered in the device menu.

Page 123: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 8 Device Parametrization

Endress+Hauser 121

8.4.2 Device menu

The device menu allows matrix or graphical operation to be selected.

• In the case of matrix operation, the device or profile parameters are displayed in a matrix. A

parameter can be changed when the corresponding matrix field is selected.

• In the case of graphical operation, the operating sequence is shown in a series of pictures with

parameters. For profile operation, the pictures Diagnosis, Scaling, Simulation and Block are of

interest.

Fig. 8-10: Basic calibration of the Deltapilot S using graphical configuration

The device parameters are set in accordance with the corresponding operating instructions. Tables

of profile functions are also to be found here. The parameter blocks are adapted to the transmitters.

Third-party devices can also be operated via the profile parameters. In this case, standardised

transducer, function or physical blocks appear.

Off-line operation Commuwin also allows the devices to be configured off-line. After all parameters have been

entered, the file generated can be loaded into the connected device.

Up-/download This function allows the parameters of an already configured device to be loaded and stored in

Commuwin II. If several devices (with the same software version) have to be configured in the same

way, the parameters can now be downloaded into the devices.

Scaling Fig. 8-11 shows the graphical operation for the scaling of the Deltapilot S. By selecting the device

profile "AI transmitter block" (acknowledge with .) the parameters PV_SCALE and OUT_SCALE can

be set. Please note that for DPV1 Version 2.0, the unit is not transmitted with the measured value.

The setting of the PV unit also has no effect on the output value OUT.

The operating picture "Diagnosis" shows the current status of the device. "Simulation" allows a

measured value to be simulated, "Block" displays the current setting of the mode block..

Fig. 8-11: Scaling of the PA device output using Commuwin II

Page 124: Endress+Hauser Profibus Planing Guide

9 Trouble-Shooting PROFIBUS planning and commissioning

122 Endress+Hauser

9 Trouble-Shooting

This chapter contains a summary of the most frequent faults and questions concerning PROFIBUS

that have been dealt with by our service department. It is subdivided as follows:

• Commissioning

• PLC network design

• Data transmission

• Commuwin II

9.1 Commissioning

Question/Fault Cause/Remedy

How can I assign an address to a

device?

• With the exception of the analysis device Mypro, all Endress+Hauser devices

have an address switch that allows hardware or software addressing.

• Software address changes can be made via the PROFIdtmDPV1 CommDTM

is FieldCare, the DPV1-DDE server of Commuwin II or any other PROFIBUS

operating tool. See also Chapter 6.6.

Where is the device termination

switch?

PROFIBUS PA:

• There is no termination switch on the device itself.

• The bus is terminated by using a separate terminator or a T-box with a

switchable terminating element

PROFIBUS DP:

• Termination switches are located in the devices. We recommend the use of

PROFIBUS connectors with integrated terminators (in cabinet or field)

When a device is added to the bus,

the segment fails

The segment coupler supplies a defined maximum output current to the

segment. Every device requires a particular basic current (see Chapter 5.3). If

the sum of the basic currents exceeds the output current of the coupler, the bus

become unstable.

• Diagnosis: Measure the current consumption of the devices with an

ammeter.

• Remedy: Reduce the electrical load on the segment concerned, i.e. one or

more devices must be disconnected.

PROFIBUS-PA slave with address 2

cannot be found.

• If a Siemens DP/PA-link Type IM 157 is used, the internal address must be

taken into consideration. On the PROFIBUS-PA side, the link has the fixed

internal address 2. For this reason, the address 2 may not be assigned to any

of the PROFIBUS PA slaves connected to the link.

• Two devices (slave or master) have the same address. Disconnect the slave

with address 2 from the bus and check whether there are others on the bus

with the same address (e.g. with FieldCare of Commuwin II). Readdress as

approprate. Check the settings of the PROFIBUS master as to whether the

address 2 has been allocated twice.

Page 125: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 9 Trouble-Shooting

Endress+Hauser 123

9.2 PLC planning

9.3 Data transmission

Question/Fault Cause/Remedy

The measured value in the Siemens

S5 is incorrect

• The Siemens S5 PLC cannot interpret the IEEE floating point format.

• A conversion module is required that transforms the IEEE floating point

value into Siemens KG format. This can be obtained from Siemens.

• The module is for Types 135 U and 155 U but not for 115 U and 95 U.

The measured value in Siemens S7

PLCs is always zero

• The function module SFC 14 must be used. The SFC 14 ensures that e.g. 5

bytes can be consistently loaded into the SPS. If the SFC 14 is not used, only

4 bytes can be consistently loaded into the Siemens S7.

• Newer versions of the S7 series can access the I/O buffer directly. The SFC

14 is no longer required.

The measured value at the device

display is not the same as that in the

PLC.

• The parameters PV_SCALE and OUT_SCALE are not set correctly.

OUT_SCALE_Min. = PV-Min.

OUT_SCALE_Max. = PV-Max.

Instructions on how to adjust the parameters PV_SCALE and OUT_SCALE

in the function block can be taken from the device operating instructions.

No connection between the PLC

and the PROFIBUS PA network.

• The bus parameters and baudrate were not set when the PLC was

configured. The baudrate to be set depends upon the segment coupler used

(Chapter 7-5).

- Pepperl+Fuchs SK1: 93,75 kBit/s

- Siemens: 45.45 kBit/s

- PA link (Siemens): freely selectable

- Pepperl+Fuchs SK1: 93.75 kBit/s

- Pepperl+Fuchs SK2: freely selectable

• For P+F SK2, the PROFIBUS PA GSD has not been converted

• The bus parameters require adjustment

• The polarity of the PROFIBUS-DP line is reversed (A and B)?

• PROFIBUS-DP bus not terminated?

• Both the beginning and the end of the bus must be terminated.

Question/Fault Cause/Remedy

How are data transferred to the PLC? • The measured values are transmitted in 5 byte long data blocks. 4 bytes are

used to transmit the measured value. The fifth byte contains standardised

status information. Error codes for Endress+Hauser device faults, e.g. E 641,

are not transmitted with the status.

• For limit switches, the information is transmitted in two bytes: Signal

• condition and status information.

• See Chapters 3-4 and 7-2.

What does status information mean? • See Chapter 7.3.

How is data transmitted from the

Promag 53 to the PLC?

• See Chapter 7.2

How can the totalisor of the

Promag 53 be reset?

• Via the output word of the cyclic services for the totalisaer in question, see

Chapter 7.2

How can the PLC switch on the

positive zero return of the Promag 53?

• Via the output word of the cyclic services

How can the totalisor of the

Promass 83 be reset?

• Via the output word of the cyclic services, see corresponding operating

manual

How can I suppress a measured value

in cyclic communcaition?

• By using the placeholder "EMPTY_MODULE" or "FREE_PLACE" during

configuration, see Chapter 7.2.

How can I write a value to the local

display?

• By using the Display_Value model from the GSD (if supported), see

Chapter 7.2.

Page 126: Endress+Hauser Profibus Planing Guide

9 Trouble-Shooting PROFIBUS planning and commissioning

124 Endress+Hauser

9.4 Commuwin II

Question/Fault Cause/Remedy

Commuwin II cannot open the

connection to the PROFIBUS PA

devices.

Commuwin II is a Class 2 master that allows the transmission of acyclic values.

The PROFIBUS-DP baudrate to be set depends upon the segment coupler used.

The connection to the devices cannot

be opened.

• If the PLC and Commuwin II are used in parallel, the bus parameters must

be mutually compatible. The bus parameters must be identical for all

connected masters.

– If Commuwin II is used, the Token Rotation Time (TTR) calculated by the

PLC configuration tool must be increased by 20 000 bit times and the cor-

responding value entered in the Commuwin II DDE server

– In the case of a Siemens S5 system with ComProfibus, the Delta TTR must

be increased by 20 000 bit times.

• The HSA parameter (Highest Station Address) must permit the

Commuwin II address. The HSA specifies the highest address permitted for

active participants (masters) on the bus. Slaves can have a higher address.

• Is the Commuwin II address free or is it being used by another device?

• Is the correct baudrate set?

• Have the drivers and cards been correctly installed? Is the green LED on the

TAP of the Proficard or Profiboard lit?

• Is the GAP update to high (the result is longer waiting times)?

A device does not appear in the live

list.

• Device is not connected to segment.

• Address used twice.

Device cannot be fully operated. • The device version is not supported by Commuwin II. A full device

description is necessary. The default parameters of the PROFIBUS-PA profile

are offered.

• Full operation is possible for Endress+Hauser devices and Samson positioners

only.

A change of unit at the device has no

effect on the value on the bus.

If the measured value at the device display is to be the same as that transmitted

to the PLC, the parameters PV_SCALE and OUT_SCALE must be matched.

- OUT_SCALE_MIN = PV_SCALE_MIN

- OUT_SCALE_MAX = PV_SCALE_MAX

See the device operating instructions.

Page 127: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 10 Technical Data

Endress+Hauser 125

10 Technical Data

10.1 PROFIBUS DP

Identification

Function and system

design

Electrical connection

Human interface

Standards

Designation PROFIBUS DP

Application Fieldbus for factory automation and process control

Bus access method Multimaster with logical token ring and master-slave

Topology See Chapter 2.2

No of participants Max. 126 per Bus, but max. 32 per segment

Segments can be connected together with repeaters

Baudrate up to 12 Mbit, dependent upon transmission medium and cable length

Data transmission Digital, differential signals according RS 485, NRZ

Data storage HD=4, Parity-Bit, Start- and End-Delimiter

Response time Dependent upon the data transmission rate

Bus cable Copper: screened, twisted pairs, screening grounded at both ends.

Cable specifications, see Chapter 3.2

Fibre optics: see PROFIBUS DP specifications

Topology Line topology

Cable length Copper: up to 1200 m, depending upon baudrate, see Chapter 2.2

Spur length Total length of all spurs max. 6.6 m,

for baudrates > 1.5 Mbit/s none

Bus connection Connecting elements: 9-pole Sub-D connectors with RS 485 or T-Box

Bus termination At both ends of every segment

Repeater Max. 9 Repeater

Local operation If appropriate, via keys or touch keys

PC operation Via operating program, e.g. FieldCare or Commuwin II

and PROFIBUS interface card (if supported by PROFIBUS PA profile)

Bus address Set with DIP switch, local operating elements or software

Software/hardware addressing selectable

PROFIBUS DP IEC 61158 and IEC 61784

PNO Guidelines for PROFIBUS DP

Intrinsic safety possible: RS 485-IS with EEx ib

Physical layer RS 485

Page 128: Endress+Hauser Profibus Planing Guide

10 Technical Data PROFIBUS planning and commissioning

126 Endress+Hauser

10.2 PROFIBUS PA

Identification

Function and system

design

Electrical connection

Human interface

Standards

Designation PROFIBUS PA (Process Automation)

Application Intrinsically safe fieldbs for process engineering

Bus access method Multimaster with logical token ring and master-slave

Topology See Chapter 3

No. of participants max. 32 for non-hazardous applications

max. 20 for EEX ib IIB

max. 10 for EEX ia/ib IIC

The actual number is dependent upon the the segment coupler and the current

consumption of the participants

Baudrate 31.25 kBits/s

Data transmission Digital, bit synchron, Manchester II coding

Data storage Präambel, fehlergesicherte Start-End-Delimiter, CRP

Update time Dependent upon the number of devices on the bus:

t = n x 10 ms + PLC program run time + DP transmission time

Bus power supply, typical values EEx ia/ib IIC: 13,5 V, 128 mA

EEx ia/ib IIB: 13,5 V, 280 mA

Nicht-Ex: 24 V, 400 mA

see Chapter 3.2

Bus cable Preferred: screened, twisted pairs, screening ground at both sides

Cable specifications (and other types), see Chapter 3.3

Topology Line- and tree topology, combination possible.

For hazardous applications only line topology possible.

Cable length Dependent upon application and bus coupler, see Chapter 3.3

Spur length Max. 30 m each for hazardous applications, otherwise as in Chapter 3.3

Bus connection Connection elements: T-pieces, junction boxes

Bus termination At both ends

Specifications: R = 100 W ± 2 %, C = 1 mF ± 20 %

Repeater Max. 4 per bus segment

Local operation If appropriate, via keys or touch-keys

PLC operation Via common parameters and profile commands

PC operation Via operating program, e.g. FieldCare or Commuwin II

and PROFIBUS interface card

Bus address Set with DIP switch, local operating elements or software

Software/hardware addressing selectable

PROFIBUS PA IEC 61158 and IEC 61784

PNO Guidelines for PROFIBUS PA

Intrinsic safety EN 50 020, FISCO-model, IEC 79-14

Physical layer IEC 61158-2 (MBP)

Page 129: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 127

11 PROFIBUS Components

11.1 Endress+Hauser field devices PROFIBUS PA

Cerabar M Cerabar M

Process variable Pressure

PROFIBUS ID code (Hex) 151C

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC

9...17.5 VDC according FISCO

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

PMC41

PMC45

PMP41

PMP45

PMP46

PMP48

Start-up current < basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Pressure,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 222P/00/en

PNO certificate Z00628

PROFIBUS DP version available No

Page 130: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

128 Endress+Hauser

Cerabar S Cerabar S

Process variable Pressure

PROFIBUS ID code (Hex) 1501

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC

9...17.5 VDC according FISCO

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

PMC631

PMC731

PMP635

PMP731

PMC71

PMP71

PMP72

PMP75

Start-up current < basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Pressure,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 168P/00/en

PNO certificate Z00656

PROFIBUS DP version available no

Page 131: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 129

Deltabar S Deltabar S

Process variable Differential pressure

PROFIBUS ID code (Hex) 1504

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC

9...17.5 VDC according FISCO

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

PMD230

FMD230

FMD235

FMD630

FMD633

FMD76

FMD77

FMD78

PMD70

PMD75

Start-up current < basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Pressure,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 167P/00/en

PNO certificate Z00655

PROFIBUS DP version available No

Page 132: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

130 Endress+Hauser

Deltapilot S Deltapilot S

Process variable Level

PROFIBUS ID code (Hex) 1503

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

9.6...32 VDC (only for FEB24 P)

• Hazardous area: 9...24 VDC

9...17.5 VDC according FISCO

For FEB24 P, 9.6...

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

DB50

DB50A

DB50

DB50S

DB51

DB51A

DB52

DB52A

DB53

DB53A

FEB24

FEB24P

Start-up current < basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Level,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 164F/00/en

PNO certificate Z00657

PROFIBUS DP version available No

Page 133: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 131

Levelflex M Levelflex M

Process variable Level

PROFIBUS ID code (Hex) 152D

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC

9...17.5 VDC according FISCO

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

FMP40

FMP41C

Start-up current < bsic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Level

(herstellerspezifisch),

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 757F/00/en

PNO certificate Z00657

PROFIBUS DP version available No

Page 134: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

132 Endress+Hauser

Liquiphant M Liquiphant M

Process variable Level, limit switch for liquids

PROFIBUS ID code (Hex) 152B

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC

9...17.5 VDC according FISCO

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

FDL60

FDL61

FEL67

FTL670

FTL50

FTL51

FTL50H

FTL51H

Start-up current < basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Discrete Input,

Transducer Block DI,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 141F/00/en

PNO certificate Z00690

PROFIBUS DP version available No

Page 135: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 133

Liquisys M Liquisys M

Process variable pH-Wert, Conductivity, Trübung,

Sauerstoff, Chlor

PROFIBUS ID code (Hex) 1515 Conductivity

1516 pH-value

1517 Turbidity

1518 Oxygen

1519 Chlorine

Auxiliary energy (local) 100/115/230 V AC +10/-15%, 48...62 Hz

24 V AC/DC +20 / -15%

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

LF

pH

Tu

O2

Cl

CUM223

CUM253

COM223

COM253

CPM223

CPM253

CCM223

CCM253

CLM223

CLM253

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version keine

Acyclic profile data Analog Input,

Transducer Block (manufacturer specific),

Physical Block (manufacturer specific)

Additional signals Relay

Application in hazardous area No

Ex certificate None

PNO certificate None

PROFIBUS DP version available Yes

Page 136: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

134 Endress+Hauser

Micropilot M Micropilot M

Process variable Level

PROFIBUS ID code (Hex) 1522

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC,

9...17.5 VDC according FISCO

Max. basic current (IB) 13 mA

Fault current (IFDE) 0 mA

FMR230V

FMR231E

FMR230

FMR231

FMR240

FMR530

FMR531

FMR532

FMR533

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Level

(manufacturer specific),

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 227F/00/en

PNO certificate Z00629

PROFIBUS DP version available No

Page 137: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 135

Multicap Multicap

Process variable Level

PROFIBUS ID code (Hex) 153A

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC

9...17.5 VDC according FISCO

Max. basic current (IB) 14 mA

Fault current (IFDE) 0 mA

FEC14 Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Level,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 261F/00/en

PNO certificate Z00629

PROFIBUS DP version available No

Page 138: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

136 Endress+Hauser

Mycom S Mycom S

Process variable Conductivity, pH-value

PROFIBUS ID code (Hex) 1535 Conductivity, conductive

1537 Conductivity, inductive

1539 pH-value

Auxiliary energy 100...230 V AC +10/-15%;

24 V AC/DC +20/-15%

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC, 9...17.5 VDC according FISCO

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

CLM153

CPM153

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Analyser Transducer Block,

Physical Block

Additional signals Relay

Application in hazardous area Yes

Ex certificate see BA 234C/07/en, BA 298C/07/en

PNO certificate Z00919, Z00920, Z0921

PROFIBUS DP version available No

Page 139: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 137

Mypro Mypro

Process variable Conductivity, pH-value

PROFIBUS ID code (Hex) 150C Conductivity (inductive/conductive)

150D pH-value

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area:

9...24 VDC

9...24 VDC

9...17.5 VDC according FISCO

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

CPM431

CLM431

CLD431

Start-up current < Basic current

Local operation Yes

Addressing Software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version None

Acyclic profile data Analog Input,

Analyser Transducer Block

(manufacturer specific),

Physical Block

(manufacturer specific)

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 198C/07/en

PNO certificate No

PROFIBUS DP version available No

Page 140: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

138 Endress+Hauser

Promag 33/35 Promag 33/35

Process variable Flow

PROFIBUS ID code (Hex) 1505

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC (only Promag 33)

Max. basic current (IB) 12 mA

33A

33D

33F

33H

33P

33W

35A

35D

35F

35H

35P

35W

Fault current (IFDE) 0 mA

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 2.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals 1 x 4...20 mA Flow

Application in hazardous area Yes (only Promag 33)

Ex certificate see BA 029D/06/en

PNO certificate Z00410

PROFIBUS DP version available Yes

Page 141: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 139

Promag 50 Promag 50

Process variable Flow

PROFIBUS ID code (Hex) 1525

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...32 VDC

Max. basic current (IB) 11 mA

50W

50P

50H

Fault current (IFDE) 0 mA

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 055D/06/en

PNO certificate Z00632

PROFIBUS DP version available No

Page 142: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

140 Endress+Hauser

Promag 53 Promag 53

Process variable Flow

PROFIBUS ID code (Hex) 1527

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...32 VDC

Max. basic current (IB) 11 mA

53W

53P

53H

Fault current (IFDE) 0 mA

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 053D/06/en

PNO certificate Z00633

PROFIBUS DP version available Yes

Page 143: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 141

Promass 63 Promass 63

Process variable Flow

PROFIBUS ID code (Hex) 1506

Auxiliary energy (local) 85...260 V AC (50...60 Hz)

20...55 V AC, 16...62 V DC

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...32 VDC

Max. basic current (IB) 12 mA

63A

63E

63F

63H

63I

63M

Fault current (IFDE) 0 mA

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 2.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals 1 x 4...20 mA (Mass, Density, Temperature)

Application in hazardous area Yes

Ex certificate see BA 063D/06/en

PNO certificate Z00407

PROFIBUS DP version available Yes

Page 144: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

142 Endress+Hauser

Promass 80 Promass 80

Process variable Flow

PROFIBUS ID code (Hex) 1528

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...32 VDC

Max. basic current (IB) 11 mA

80A

80E

80F

80H

80I

80M

Fault current (IFDE) 0 mA

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 072D/06/en

PNO certificate Z00669

PROFIBUS DP version available No

Page 145: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 143

Promass 83 Promass 83

Process variable Flow

PROFIBUS ID code (Hex) 152A

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...32 VDC

Max. basic current (IB) 11 mA

83A

83E

83F

83H

83I

83M

Fault current (IFDE) 0 mA

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 063D/06/en

PNO certificate Z00670

PROFIBUS DP version available Yes

Page 146: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

144 Endress+Hauser

Prosonic Flow 90 Prosonic Flow 90

Process variable Flow

PROFIBUS ID code (Hex) 152F

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...32 VDC

Max. basic current (IB) 11 mA

90W

90U

90C

Fault current (IFDE) 0 mA

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 074D/06/en

PNO certificate Z00871

PROFIBUS DP version available No

Page 147: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 145

Prosonic Flow 93 Prosonic Flow 93

Process variable Flow

PROFIBUS ID code (Hex) 1530

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...32 VDC

Max. basic current (IB) 11 mA

DDU10

DDU15

DDU18

DDU19

Fault current (IFDE) 0 mA

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 076D/06/en

PNO certificate Z00869

PROFIBUS DP version available Yes

Page 148: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

146 Endress+Hauser

Prosonic M Prosonic M

Process variable Level

PROFIBUS ID code (Hex) 152C

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC

9...17.5 VDC according FISCO

Max. basic current (IB) 12 mA

Fault current (IFDE) 0 mA

FMU40

FMU41

FMU43

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Level

(manufacturer specific),

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 283F/00/en

PNO certificate Z00724

PROFIBUS DP version available No

Page 149: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 147

Prosonic T Prosonic T

Process variable Level

PROFIBUS ID code (Hex) 1502

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC

Max. basic current (IB) 13 mA, at FMU 232 max. 17 mA

Fault current (IFDE) 0 mA

FMU130

FMU131

FMU230

FMU231

FMU232

FTU230

FTU231

Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 2.0

Acyclic profile data Analog Input,

Transducer Block Level,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 283F/00/en

PNO certificate Z00402

PROFIBUS DP version available No

Page 150: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

148 Endress+Hauser

Prowirl 72 Prowirl 72

Process variable Flow

PROFIBUS ID code (Hex) 153B

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC,

9...17,5 VDC according FISCO

Max. basic current (IB) 15 mA

Fault current (IFDE) 0 mA

72F

72W

Start-up current < Basic current

Local operation No

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 085D/06/en

PNO certificate Z00835

PROFIBUS DP version available No

Page 151: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 149

Prowirl 73 Prowirl 73

Process variable Flow

PROFIBUS ID code (Hex) 153C

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC,

9...17,5 VDC according FISCO

Max. basic current (IB) 15 mA

Fault current (IFDE) 0 mA

73F

73W

Start-up current < Basic current

Local operation No

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 094D/06/en

PNO certificate requested

PROFIBUS DP version available No

Page 152: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

150 Endress+Hauser

RID 261 RID 261

Process variable Variabel (display function)

PROFIBUS ID code (Hex) None

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...15 VDC

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

RID261 Start-up current < Basic current

Local operation Setting of the address of the monitored

slaves and setting of the process variable

offset via DIP-switch

Addressing None

Cyclic data to PLC None

PA profile version 3.0

Acyclic profile data None

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 098R/09/C4

PNO certificate No

PROFIBUS DP version available No

Page 153: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 151

Smartec S Smartec S

Process variable Conductivity

PROFIBUS ID code (Hex) 153E

Auxiliary energy (local) 100...230 V AC +10/-15% bei 47...64 Hz;

24 V AC/DC +20/-15%

Auxiliary energy Bus communication

• Non-hazardous area: 9...32 V DC

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

CLD132 Start-up current < Basic current

Local operation Yes

Addressing DIP switch, software, local operation

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Analyser,

Physical Block

Additional signals None

Application in hazardous area No

Ex certificate No

PNO certificate Z00955

PROFIBUS DP version available Yes

Page 154: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

152 Endress+Hauser

TMT 184 TMT 184

Process variable Temperature

PROFIBUS ID code (Hex) 1523

Auxiliary energy Power supply via bus

• Non-hazardous area: 9...32 VDC

• Hazardous area: 9...24 VDC,

9...17,5 VDC according FISCO

Max. basic current (IB) 11 mA

Fault current (IFDE) 0 mA

TMT184 Start-up current < Basic current

Local operation No

Addressing DIP switch, software

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Temperature,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 115R/09/A3

PNO certificate Z00694

PROFIBUS DP version available No

Page 155: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 153

11.2 Endress+Hauser field devices PROFIBUS DP

ASP 2000

Liqisys M

ASP 2000

Process variable Stationary sampler

PROFIBUS ID code (Hex) 1533

Auxiliary energy (local) 230 V AC, 50/60 Hz

Supported bus velocities (kBit/s) 45.45, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing DIP switch, local operation

ASP2000 Cyclic data to PLC 60 bytes Inputs + 60 bytes Outputs

PA profile version None

Acyclic profile data None

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 080R/09/en

PNO certificate No

Liquisys M

Process variable pH-value, Conductivity, Turbidity, Oxygen,

Chlorine

PROFIBUS ID code (Hex) 151D Chlorine,

151E Oxygen,

151F Turbidity,

1520 pH-value,

1521 Conductivity

Auxiliary energy (local) 100/115/230 V AC +10/-15%, 48...62 Hz

24 V AC/DC +20 / -15%

Supported bus velocities (kBit/s) 45.45, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) No

Local operation Yes

Adressing DIL switch, software, local operation

CCM223

CCM253

CLM223

CLM253

COM223

COM253

CUM223

CUM253

CPM223

CPM253

Cyclic data to PLC see Chapter 5.6

PA profile version None

Acyclic profile data Analog Input,

Transducer Block

(manufacturer specific),

Physical Block

(manufacturer specific)

Additional signals Relay

Application in hazardous area None

Ex certificate No

PNO certificate No

Page 156: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

154 Endress+Hauser

Memo-Graph DP

(slave)

Promag 33/35

Memo-Graph (DP slave)

Process variable Display several I/O

PROFIBUS ID code (Hex) 150F

Auxiliary energy (local) 115...230 VAC, 50/60 Hz

24 V AC/DC, 0/50/60 Hz

Supported bus velocities (kBit/s) 45.45, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing Local operation

RSG10 Cyclic data to PLC see Chapter 5.6

PA profile version None

Acyclic profile data None

Additional signals Relay, AI, AO, DI, DO

Application in hazardous area No

Ex certificate No

PNO certificate No

Promag 33/35

Process variable Flow

PROFIBUS ID code (Hex) 1511

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Supported bus velocities (kBit/s) 45.45, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing DIP switch, software, local operation

33A

33D

33F

33H

33P

33W

35A

35D

35F

35H

35P

35W

Cyclic data to PLC see Chapter 5.6

PA profile version 2.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals 1 x 4...20 mA Flow

Application in hazardous area Yes (only Promag 33)

Ex certificate see BA 029D/06/en

PNO certificate Z00572

Page 157: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 155

Promag 53

Promass 63

Promag 53

Process variable Flow

PROFIBUS ID code (Hex) 1526

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Supported bus velocities (kBit/s) 45.45, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing DIL switch, software, local operation

53W

53P

53H

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 053D/06/en

PNO certificate Z00631

Promass 63

Process variable Flow

PROFIBUS ID code (Hex) 1506

Auxiliary energy (local) 85...260 V AC (50...60 Hz)

20...55 V AC, 16...62 V DC

Supported bus velocities (kBit/s) 45.45, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing DIP switch, software, local operation

63A

63E

63F

63H

63I

63M

Cyclic data to PLC see Chapter 5.6

PA profile version 2.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals 1 x 4...20 mA (Mass, Density, Temperature)

Application in hazardous area Yes

Ex certificate see BA 063D/06/en

PNO certificate Z00571

Page 158: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

156 Endress+Hauser

Promass 83

Prosonic DP (FMU 86x)

Promass 83

Process variable Flow

PROFIBUS ID code (Hex) 152A

Auxiliary energy (local) 85...260 V AC, 45...65 Hz

20...55 V AC, 45...65 HZ

16...62 V DC

Supported bus velocities (kBit/s) 45.45, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing DIP switch, software, local operation

83A

83E

83F

83H

83I

83M

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 063D/06/en

PNO certificate Z00671

Prosonic DP (FMU 86x)

Process variable Flow

PROFIBUS ID code (Hex) 152E

Auxiliary energy (local) 180…253 AC (50/60 Hz);

90…132 AC (50/60 Hz);

38…55 AC (50/60 Hz);

19…28 AC (50/60 Hz);

20...30 VDC

Supported bus velocities (kBit/s) 9.6, 45.45, 93.75, 187.5, 500, 1500

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing DIP switch, software

FMU86x Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Level,

Physical Block

Additional signals Relay

Application in hazardous area Yes

Ex certificate see BA 100F/00/en

PNO certificate Z00743

Page 159: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 157

Prosonic Flow 93

RMx 621

Prosonic Flow 93

Process variable Flow

PROFIBUS ID code (Hex) 1530

Auxiliary energy (local) 85...260 V AC (50...65 Hz),

20...55 V AC (45...65 Hz),

16...62 V DC

Supported bus velocities (kBit/s) 9.6, 19.2, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing DIP switch, software, local operation

DDU10

DDU15

DDU18

DDU19

Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Totalizer Block,

Transducer Block Flow,

Physical Block

Additional signals None

Application in hazardous area Yes

Ex certificate see BA 076D/06/en

PNO certificate Z00870

RMx 621

Process variable Display several I/O e.g. Pressure,

Temperature, Flow, Steam mass

PROFIBUS ID code (Hex) 153F

Auxiliary energy (local) 24V DC +/-10%

Supported bus velocities (kBit/s) 9.6, 19.2, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation Yes

Adressing DIP switch on HMS Anybus module

RMx621 Cyclic data to PLC max. 240 bytes Inputs

PA profile version None

Acyclic profile data None

Additional signals Relay, AI, AO, DI, DO

Application in hazardous area No

Ex certificate see BA 127R/09/en, BA 144R/09/en

PNO certificate No

Page 160: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

158 Endress+Hauser

Smartec S Smartec S

Process variable Conductivity

PROFIBUS ID code (Hex) 153D

Auxiliary energy (local) 100 ... 230 V AC +10/-15 % at 47...64 Hz;

24 V AC/DC +20/-15 %

Supported bus velocities (kBit/s) 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500

Integrated bus termination (Terminator) No

Local operation Yes

Adressing DIP switch, software, local operation

CLD132 Cyclic data to PLC see Chapter 5.6

PA profile version 3.0

Acyclic profile data Analog Input,

Transducer Block Analyser,

Physical Block

Additional signals None

Application in hazardous area None

Ex certificate No

PNO certificate Z00956

Page 161: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 159

Rackbus Gateway Rackbus Gateway ZA 375

Process variable Several

PROFIBUS ID code (Hex) 1501

Auxiliary energy (local) 20...30 VDC

Supported bus velocities (kBit/s) 9.6, 19.2, 93.75, 187.5, 500, 1500, 3000,

6000, 12000

Integrated bus termination (Terminator) Yes

Local operation No

Adressing DIP switch

ZA375 Cyclic data to PLC max. 38 measured values, every 6 bytes

PA profile version None

Acyclic profile data None

Additional signals None

Application in hazardous area None

Ex certificate None

PNO certificate Z00247

Page 162: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

160 Endress+Hauser

11.3 Network components

Component Description E+H Order No.

Segment coupler SK

1

DP/PA coupler standard 17039-1000

DP-PA coupler EEx (ia) 017039-0000

Segment coupler SK

2

Gateway, 1 PA master 52014393

Gateway, 2 PA master 52014394

Gateway, 3-PA master 52014395

Power link module, standard 52014397

Power link modul, EEx (ia) 52014396

Interfaces converter PROFIBUS RS485 fibre optic cable 52005649

Ethernet/PROFIBUS DP gateway FieldGate FXA 720 FXA720-xxxx

PROFIBUS PA

Fieldbus barrier FieldBarrier Pepperl+Fuchs, Input/Output trunk cable EEx (e),

spurs EEx (ia), cable gland

52014398

Device connector

M12

M20-M12 connector device, Weidmüller, cable length 150 mm 52006628

M20-M12 connector for device, Weidmüller, cable length 300 mm 52006629

M12 connector for cable mounting, Weidmüller 017434-0100

M12 socket for cable mounting, Weidmüller 017434-0110

Bus termination Ex terminator Weidmüller 017481-0001

Ex terminator Turck 52005549

Junction boxes T-Box Weidmüller, spur M12 socket, trunk M16 cable gland, EEx (ia) 52014352

2-way junction box Weidmüller, spur M12 socket, trunk M16 cable gland,

EEx (ia)

52014353

4-way junction box Weidmüller, spur M12 socket, trunk M16 cable gland,

EEx (ia)

52014354

T-Box Weidmüller, spur M12 socket, trunk M16 cable gland, standard 52014358

2-way junction box Weidmüller, spur M12 socket, trunk M16 cable gland,

standard

52014359

4-way junction box Weidmüller, spur M12 socket, trunk M16 cable gland,

standard

52014360

T-piece Turck, spur M12 socket, trunk M12 connector and socket, EEx (ia) 52001029

2-way junction box, spur M12 socket, trunk M12 connector and socket,

EEx (ia)

52001026

4-way junction box, spur M12 socket, trunk cable M12 connector and

socket, EEx (ia)

52001027

T-Box Weidmüller, spur and trunk M16 cable gland, EEx (ia) 52014355

2-way junction box Weidmüller, spur and trunk M16 cable gland, EEx (ia) 52014356

4-way junction box Weidmüller, spur and trunk M16 cable gland, EEx (ia) 52014357

T-Box Weidmüller, spur and trunk M16 cable gland, standard 52014331

2-way junction box Weidmüller, spur and trunk M16 cable gland, standard 52014362

4-way junction box Weidmüller, spur and trunk M16 cable gland, standard 52014363

Page 163: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 161

Cord set,

double sided

M12 connector socket Turck, length 1 m, blue 52001043

M12 connector socket Turck, length 2 m, blue 52001044

M12 connector socket Turck, length 5 m, blue 52001045

M12 connector socket Turck, length 10 m, blue 52001046

M12 connector socket Turck, length 1 m, orange 52001025

M12 connector socket Turck, length 2 m, orange 52001040

M12 connector socket Turck, length 5 m, orange 52001041

M12 connector socket Turck, length 10 m, orange 52001042

M12 connector socket Weidmüller, length 1 m, blue 52014372

M12 connector socket Weidmüller, length 2 m, blue 52014373

M12 connector socket Weidmüller, length 5 m, blue 52014374

M12 connector socket Weidmüller, length 10 m, blue 52014375

M12 connector socket Weidmüller, length 1 m, black 52014384

M12 connector socket Weidmüller, length 2 m, black 52014385

M12 connector socket Weidmüller, length 5 m, black 52014386

M12 connector socket Weidmüller, length 10 m, black 52014387

Cord set,

single sided

M12 connector Weidmüller, length 1 m, blue 52014364

M12 connector Weidmüller, length 2 m, blue 52014364

M12 connector Weidmüller, length 5 m, blue 52014364

M12 connector Weidmüller, length 10 m, blue 52014364

M12 connector Weidmüller, length 1 m, black 52014376

M12 connector Weidmüller, length 2 m, black 52014377

M12 connector Weidmüller, length 5 m, black 52014378

M12 connector Weidmüller, length 10 m, black 52014379

M12 socket Weidmüller, length 1 m, blue 52014368

M12 socket Weidmüller, length 2 m, blue 52014369

M12 socket Weidmüller, length 5 m, blue 52014370

M12 socket Weidmüller, length 10 m, blue 52014371

M12 socket Weidmüller, length 1 m, black 52014380

M12 socket Weidmüller, length 1 m, black 52014381

M12 socket Weidmüller, length 1 m, black 52014382

M12 socket Weidmüller, length 1 m, black 52014383

PROFIBUS DP

Connector M20-M12 connector for device, Weidmüller, cable length 300 mm 52018560

Bus termination Ex terminator T-Box Weidmüller, Output M12 socket, trunk cable M16

cable gland, external power supply 24 VDC

52018563

Junction box T-Box Weidmüller, Output M12 socket, trunk M16 cable gland 52018562

Cord set,

single sided

M12 connector Weidmüller, length 0.3 m, violet 52018561

Component Description E+H Order No.

Page 164: Endress+Hauser Profibus Planing Guide

11 PROFIBUS Components PROFIBUS planning and commissioning

162 Endress+Hauser

11.4 Asset management and operating software

Component Description E+H Order No.

GSD (device data files) GSD-CD-ROM 56003894

or download free of charge at

www.endress.com

Operating program Commuwin II FXS113-xxx

FieldCare Lite 56004080

FieldCare Standard SFE551-xxxx

FieldCare Professional SFE552-xxxx

Page 165: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 11 PROFIBUS Components

Endress+Hauser 163

11.5 Supplementary documentation

PROFIBUS Standard 1. IEC 61158-2:Ed 3, Digital data communications for measurement and control - Fieldbus for

use in industrial control systems - Part 2: Physical layer specification and service definition.

2. IEC 61158-3:Ed 3, Digital data communications for measurement and control - Fieldbus for

use in industrial control systems - Part 3: Data Link Service definition

3. IEC 61158-4:Ed 3, Digital data communications for measurement and control - Fieldbus for

use in industrial control systems - Part 4: Data Link Protocol specification.

4. IEC 61158-5:Ed 3, Digital data communications for measurement and control - Fieldbus for

use in industrial control systems - Part 5: Application Layer Service definition.

5. IEC 61158-6:Ed 3, Digital data communications for measurement and control - Fieldbus for

use in industrial control systems - Part 6: Application Layer protocol specification.

6. IEC 61784-1: 2003 CP3/2, Digital data communications for measurement and control -

Part 1: Profile sets for continuous and discrete manufacturing relative to fieldbus use in

industrial control systems

DIN Standard 1. DIN: 19 245, Teil 1 - 4, Beuth Verlag GmbH, Berlin

PROFIBUS User

Organisation

PROFIBUS User-Organisation e.V.

Haid- und Neu-Strasse 7

D76131 Karlsruhe

Internet: www.profibus.com

1. PNO: PROFIBUS PA Profile for Process Control Devices. Version3.0, October 1999.

2. PNO: PROFIBUS PA User and Installation Guideline, Version 2.2, February 2003

3. PNO: Installation Guideline for PROFIBUS DP/FMS, Version 1.0, September 1998

4. PNO: Technical Overview. April 2002

5. PNO: PROFIBUS Guideline Interconnection technology, Version 1.1, August

6. PNO: PROFIBUS Produkt-Catalogue, Internet: www.profibus.com

Literature A number of books exist on the use of PROFIBUS issued e.g. by the ISA. It is recommended that an

Internet search be made for suitable material.

Page 166: Endress+Hauser Profibus Planing Guide

12 Terms and Definitions PROFIBUS planning and commissioning

164 Endress+Hauser

12 Terms and Definitions

This chapter contains a selection of terms and definitions to bemet in fieldbus technology.

It is subdivided as follows:

• Bus architecture

• Components

• Data exchange

• Miscellaneous terms

12.1 Bus architecture

Table 12-1: Terms and definitions: Bus architecture

Topology The structure of the communication system, e.g. linear (bus), tree, ring, star.

For PROFIBUS, linear and tree structures are permissible.

Participant A device that is connected to and recognised by the communication system.

Every participant has a unique address:

• Active communication participant = master

a device that has the right to initiate communcation

• passive communication participant = slave

a device that may communicate only when it receives the right to do so

from a master

Physical layer The cable and associated hardware that connects the participants together.

Among other things, the physical layer defines how a signal is to be transmitted

over the bus, how it is to be interpreted and how many participants are

allowed on a segment. The following transmission methods are relevant to

PROFIBUS applications:

• RS-485

Standard for transmission on shielded twisted pairs that is used for

PROFIBUS-DP.

• IEC 61158-2 (MBP Manchester Coded Bus Powered)

International fieldbus standard with data transmission and power supply on

shielded twisted pairs that is used for PROFIBUS-PA.

• Fibre optics

Alternative to STP for PROFIBUS DP applications when operating in

environments with heavy electrical interference or when long buses and

high transmission rates are required. Can also be used as a basis for

redundant structures.

Segment In the case of a tree structure, a network section that is separated from the

trunk line by a repeater, segment coupler or link..

• Trunk cable

The longest bus cable, which is terminated at both ends.

• Spur

Line connecting the field device to trunk cable.

For PROFIBUS PA, the number and length of the spurs is limited by the

physics and application (standard or explosion-hazardous area

(spur cable ≤ 30 m, Splice ≤ 1 m).

Page 167: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 12 Terms and Definitions

Endress+Hauser 165

12.2 Components

Table 12-2: Terms and definitions: Components

Process-near component (PNC) A PNC is in direct contact with the fieldbus and manages the communication

with the field devices (= bus master). It can be either a PLC or an operating

programm running on a personal computer.

Signal coupler The interface between a PROFIBUS DP system and a PROFIBUS PA segment.

The signal coupler converts the signal from RS-485 to IEC 61158-2 format and

adapts the transmission rate..

Bus power unit Supplies the devices on the PROFIBUS PA segment with power (except those

which are externally powered). Normally the signal coupler and bus power

unit are contained in a signal unit, e.g. as the segment coupler. The can also be

designed as a PLC interface card.

Segment coupler A device that serves as both signal coupler and bus power unit. In these

guidelines, a segment coupler is considered to be "transparent", i.e. its

existence is not recognised by the communication system. The master

communicates directly with the connected devices. The coupler includes a

terminator and in the case of Ex-versions, a barrier.

Link PROFIBUS DP/PROFIBUS PA interface for the connection of one or more

PROFIBUS segments. A link is not "transparent", i.e. there is no direct

communication between the master and the PROFIBUS PA slaves. Their data

are collected by the links and made available as a whole to the PROFIBUS DP

master. A link is a slave in a PROFIBUS DP system but a master to the

connected PROFIBUS PA segments.

Repeater A repeater amplifies the communication signal, thus allowing the bus length to

be extended. Up to 4 repeaters are allowed per bus segment (PROFIBUS PA).

A repeater is a bus participant.

Field devices Actuators and sensors that are connected to a PROFIBUS PA/PROFIBUS DP

segment. Field devices are normally slave.

(T-Box) Means of connecting individual field devices to the trunk cable. The field

devices can be connected directly to the T-box or via a spur. T-boxes are used

for distribution only had have no intelligence.

Junction box Means of connecting several field devices to the trunk cable. Normally, the

field devices are connected to the junction box by a spur. Junction boxes are

used for distribution only had have no intelligence.

Bus termination

(Terminator)

Component that terminates the beginning and end of the bus segment, in

order to avoid interfering reflections. For PROFIBUS-PA, one terminator is

built inot the segment coupler. Various T-boxes have a built-in terminator that

can be switched on when the box is at the end of the segment. For explosion-

hazardous applications a separate bus terminator must be used.

Page 168: Endress+Hauser Profibus Planing Guide

12 Terms and Definitions PROFIBUS planning and commissioning

166 Endress+Hauser

12.3 Data exchange

Table 12-3: Terms and definitions: Data exchange

Bus access method The mechanism that is used to ensure proper communication between the

participants on the network.

Logical token ring A bus access method for communication systems with several masters

(multimaster system). During the network design stage, a central list

containing every master with its assigned access time is compiled . The master

with the token has the right to transmit for this period of time. Afterwards, the

token is passed on to the next master in the list. After the list has be worked

through, the procedure is started over again.

Token rotation time The time required until all the masters in a token ring have been worked

through. Normally, the token rotation time also corresponds the update time

for the plant data base.

Master-slave method A bus access method in which the right to transmit is assigned to one

participant only (the master), whereas all the other participants (slaves) can

only transmit when requested to do so.

Hybrid method A mixture between two bus access methods, e.g. for PROFIBUS-DP the

masters are linked together in a logical token right, but communicate directly

with their slaves using the master-slave method.

Cyclic data transfer (polling) The regular exchange of data between a master and its slaves. For measuring

instruments, this concerns the measured value and status signals.

Acyclic data transfer The irregular exchange of data between a master and a slave. For measuring

instruments, this usually concerns the adjustment of process-relevant device

parameters during commissioning or operation. Alternatively a detailed error

message may be transmitted when a bad status is detected.

Update time The time required in cyclic data exchange to collect the complete set of data

available on a bus segment.

Bus address A unique device code used to identify a bus participant, which enables the

master to transmit data to a particular slave on the network. The bus address is

normally set via DIP switch or software.

Page 169: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 12 Terms and Definitions

Endress+Hauser 167

12.4 Miscellaneous terms

Table 12-4: Terms and definitions: Miscellaneous terms

FISCO model Basis for the use of PROFIBUS-PA devices in explosion-hazardous areas.

Fault disconnection electronics

(FDE)

Measures aimed at preventing an impermissible current consumption in the

event of a fault, so that a defective bus participant cannot detrimentally affect

the function of the rest of the system.

Fault current The increase in the current consumption with respect to the basic current in

the event of a fault.

Device database file (GSD) Device descriptions and bitmaps required be the master, in order that a device

is recognised as a bus participant. The device database files are required during

the commissioning of the communication system.

Page 170: Endress+Hauser Profibus Planing Guide

13 Appendix: Calculation Sheets PROFIBUS planning and commissioning

168 Endress+Hauser

13 Appendix: Calculation Sheets

Requirements The following data are required to design a PROFIBUS-PA segment:

• Max. output current of the segment coupler Is (mA)

• Output voltage of the segment coupler Us (V)

• Specific resistance of the cable RK ( Ω/km)

• Total length of the spurs ( m)

• Length of the trunk cable ( m)

• Basic and fault currents of the field devices used

(for Endress+Hauser devices see Section 4.3)

13.1 Explosion hazardous areas EEx ia

Current consumption

Cable length

No Device Manufacturer Tag Basic current IB Fault current IFDE

1

2

3

4

5

6

7

8

9

10

Highest fault current (max. IFDE)

Current consumption ISEG = ΣIB + max. IFDE

Output current of segment coupler IS

IS ≥ ΣIB + max. IFDE? Yes=OK

Max. loop-resistance, standard 40 Ω

Specific resistance of cable RK Ω/km

Max. length (m) = 1000 x (40 Ω/ Specific resistance of cable) m

Length of trunk cable m

Total length of spurs m

Total length of cable LSEG m

Total length of cable < Max. length OK!

Page 171: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 13 Appendix: Calculation Sheets

Endress+Hauser 169

Voltage at last device Output voltage of segment coupler US (Manufacturer's data) V

Specific resistance of cable RK Ω/km

Total length of cable LSEG Ω

Resistance of cable RSEG = LSEG x RK

Current consumption of segment ISEG

Voltage drop UA = ISEG x RSEG V

Voltage at last device UB = US – UA V

≥ 9* V?

for FEB 24P ≥ 9.6 V

OK!

Page 172: Endress+Hauser Profibus Planing Guide

13 Appendix: Calculation Sheets PROFIBUS planning and commissioning

170 Endress+Hauser

13.2 Explosion hazardous areas EEx ib

Current consumption

Cable length

No Device Manufacturer Tag Basic current IB Fault current IFDE

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Highest fault current (max. IFDE)

Current consumption ISEG = ΣIB + max. IFDE

Output current of segment coupler IS

IS ≥ ΣIB + max. IFDE? Yes=OK

Max. loop-resistance, standard 16 Ω

Specific resistance of cable RK Ω/km

Max. length (m) = 1000 x (16 Ω/ Specific resistance of cable) m

Length of trunk cable m

Total length of spurs m

Total length of cable LSEG m

Total length of cable < Max. length OK!

Page 173: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 13 Appendix: Calculation Sheets

Endress+Hauser 171

Voltage at last device Output voltage of segment coupler US (Manufacturer's data) V

Specific resistance of cable RK Ω/km

Total length of cable LSEG Ω

Resistance of cable RSEG = LSEG x RK

Current consumption of segment ISEG

Voltage drop UA = ISEG x RSEG V

Voltage at last device UB = US – UA V

≥ 9* V?

for FEB 24P ≥ 9.6 V

OK!

Page 174: Endress+Hauser Profibus Planing Guide

13 Appendix: Calculation Sheets PROFIBUS planning and commissioning

172 Endress+Hauser

13.3 Non-hazardous areas

Current consumption No Device Manufacturer Tag Basic current IB Fault current IFDE

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

Highest fault current (max. IFDE)

Current consumption ISEG = ΣIB + max. IFDE

Output current of segment coupler IS

IS ≥ ΣIB + max. IFDE? Yes=OK

Page 175: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning 13 Appendix: Calculation Sheets

Endress+Hauser 173

Cable length

Voltage at last device

Max. loop-resistance, standard 39 Ω

Specific resistance of cable RK Ω/km

Max. length (m) = 1000 x (39 Ω/ Specific resistance of cable) m

Length of trunk cable m

Total length of spurs m

Total length of cable LSEG m

Total length of cable < Max. length OK!

Output voltage of segment coupler US (Manufacturer's data) V

Specific resistance of cable RK Ω/km

Total length of cable LSEG Ω

Resistance of cable RSEG = LSEG x RK

Current consumption of segment ISEG

Voltage drop UA = ISEG x RSEG V

Voltage at last device UB = US – UA V

≥ 9* V?

for FEB 24P ≥ 9.6 V

OK!

Page 176: Endress+Hauser Profibus Planing Guide

13 Appendix: Calculation Sheets PROFIBUS planning and commissioning

174 Endress+Hauser

Page 177: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning

Endress+Hauser 175

Index

AAdressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Application profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

ASP 2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153

CCalculation Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168

Cerabar M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127

Cerabar S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128

Communication DTM . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Commuwin II . . . . . . . . . . . . . . . . . . . . . . . . 84, 120, 124

Bus parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Device parametrization . . . . . . . . . . . . . . . . . . . . . . . 120

Component-based Automation . . . . . . . . . . . . . . . . . . . . . 10

Cycle time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Cyclic data exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

DDeltabar S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

Deltapilot S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130

Device current consumption . . . . . . . . . . . . . . . . . . . . . . . 52

Device database files (GSD) . . . . . . . . . . . . . . . . . . . 87, 89

Device DTM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Device operating manuals . . . . . . . . . . . . . . . . . . . . . . . . . 80

Device parametrization . . . . . . . . . . . . . . . . . . . . . . . . . . 104

Display value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

EEDD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Electrical symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Engineering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Explosion protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

FFDT

Joint Interest Group . . . . . . . . . . . . . . . . . . . . . . . . . . 28

FDT Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

FDT Joint Interest Group . . . . . . . . . . . . . . . . . . . . . . . . . 28

FDT/DTM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83, 116

Bus parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Device parametrization . . . . . . . . . . . . . . . . . . . . . . . 117

FISCO Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

GGSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

GSD configuration . . . . . . . . . . . . . . . . . . . 89, 90, 92, 93

II/O integration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

IEC-61158-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Integration technologies . . . . . . . . . . . . . . . . . . . . . . . . . . 21

LLevelflex M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39, 40, 46, 73

Liqisys M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153

Liquiphant M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

Liquisys M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

MMaster class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

MBP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Memo-Graph DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154

Micropilot M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134

Multicap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135

must . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

Mycom S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136

Mypro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137

NNetwork configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

OOutput data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

PPROFIBUS

Analysis blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

Block functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

Block structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127

Device management . . . . . . . . . . . . . . . . . . . . . . . . . 109

Netzwerkkomponenten . . . . . . . . . . . . . . . . . . . . . . . 160

Operating tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162

Standardparameter . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Supplementary documentation . . . . . . . . . . . . . . . . . 163

Technologien . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Transmitter and actuator blocks . . . . . . . . . . . . . . . . . 110

PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 14

Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Bus access method . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Field devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153

Hazardous areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Network configuration . . . . . . . . . . . . . . . . . . . . . . . . 35

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Block model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

Bus access method . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Bus parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

Cable manufacturers . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Cable type and length . . . . . . . . . . . . . . . . . . . . . . . . . 51

Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . 52

Datenmenge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Device installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

Erdung und Schirmung . . . . . . . . . . . . . . . . . . . . . . . . 75

Field devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127

Fieldbus barriers . . . . . . . . . . . . . . . . . . . . . . . . . 49, 63

Page 178: Endress+Hauser Profibus Planing Guide

PROFIBUS planning and commissioning

176 Endress+Hauser

FISCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

FISCO-Modell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Hazardous areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

Network configuration . . . . . . . . . . . . . . . . . . . . . . . . 47

Operating principle . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . 79

Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Segment design examples . . . . . . . . . . . . . . . . . . . . . . 56

Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126

Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Übersicht . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Voltage at last devicet . . . . . . . . . . . . . . . . . . . . . . . . 54

PROFIBUS PA profile . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

PROFIBUS User Organisations . . . . . . . . . . . . . . . . . . . . . . 8

PROFIdrive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Profile GSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

PROFINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 9

PROFIsafe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Promag 33/35 . . . . . . . . . . . . . . . . . . . . . . . . . . . 138, 154

Promag 50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

Promag 53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140, 155

Promass 63 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141, 155

Promass 80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142

Promass 83 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143, 156

Prosonic DP (FMU 86x) . . . . . . . . . . . . . . . . . . . . . . . . 156

Prosonic Flow 90 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144

Prosonic Flow 93 . . . . . . . . . . . . . . . . . . . . . . . . . 145, 157

Prosonic M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146

Prosonic T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147

Prowirl 72 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148

Prowirl 73 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149

QQuality assurance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

RRackbus Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159

RID 261 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150

RMx 621 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157

RS-485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

RS-485 IS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

SSafety conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Segment coupler . . . . . . . . . . . . . . 39, 40, 44, 50, 69, 70

Segment coupler SK2 . . . . . . . . . . . . . . . . . . . . . . . . . 45, 71

Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

Sicherheitshinweise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Slave-to-Slave Communication . . . . . . . . . . . . . . . . . . . . . 18

Smartec S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151, 158

Status codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95, 96, 97

Statuscode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

Störungsbehebung

Datenübertragung . . . . . . . . . . . . . . . . . . . . . . . . . . 123

System integration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

System intergration

Tested systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

TTechnical Data

PROFIBUS DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125

Terma and definitions . . . . . . . . . . . . . . . . . . . . . . . . . . 164

TMT 184 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

Transmission standards . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

VVersion DP-V0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Version DP-V1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Version DP-V2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Page 179: Endress+Hauser Profibus Planing Guide
Page 180: Endress+Hauser Profibus Planing Guide

www.endress.com/worldwide