LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012 1
Instlltion InstructionsLINC
LONWORKSIntrntwork Nod Controllr
Imortnt: Rtin ths instructions
Ths instructions shll b usd by trind srvic rsonnl onlyIf the equipment is used in a manner not specied by these instructions, the protection provided by the equipment may be impaired.
1Dimnsions
2Mountin Rquirmnts
3 INSTaLLaTION3.1 Instlltion - Mountin
2 STORINg
1 UNpaCKINg
It is recommended that the installation shouldcomply with the local electrical safety installation
practices (e.g.HSE Memorandum of Guidance
on Electricity at Work Regulations 1989, National
Electric Code)
CONTeNTS
1 Unpacking .....................................................................1
2 Storing ...........................................................................1
3 InstalLation ....................................................................1
3.1 Installat ion - Mounting ...................................................1
3.2 Installat ion - Conguring ...............................................5
4 Disposal.........................................................................8
5 Cleaning and Maintainance ..........................................8
1K2
9K
6
19K2
32 8 4 2
64
16 1
S3
B A U D A D D RE S S
POWER
0V
35 mm
(1.38)160 mm (6.3)
175mm(
6.8
9)
1K2
9K
6
19K2
32 8 4 2
64
16 1
S3
B A U D A D D R E SS
P OWE R
0V
1 K2
9 K
6
1 9 K2
3 2 8 4 2
6 4 1 6 1
S 3
B A UD A DDRE S S
P OWE R
0V
LINC Installation
Instructions, TG103062
Note that this product may involve LONWORKS
system integration as referred to in section
3.2 step 14: this procedure should only be
performed by an installer with LONWORKS
engineering expertise.
H O2
+50 C
(122 F)0 95 %RH
-10 C
(14 F)
!
Cution: The LINC contains static sensitive devices.
Suitable anti-static precautions shoud be
taken throughout this operation to prevent
damage to the unit.
BS EN100015/1 Basic Specification: protection of
electrostatic sensitive devices.
7/27/2019 en-tg103062-uk0yr1112.pdf
2/8
2 LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012
LINC Instlltion Instructions
4Connct powr
2Rquirmnts (continued)
3
Mountin th Nod
3.1 Instlltion - Mountin (continued)
1 K2
9 K
6
1 9 K2
3 2 8 4 2
6 4
1 6 1
S 3
B A UD A DDRE S S
POWER
0V
Protection: IP30
Altitude
7/27/2019 en-tg103062-uk0yr1112.pdf
3/8
LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012 3
Instlltion Instructions LINC
5Connct erth (ground)
6Connct Currnt Loo Ntwork
1K2
9K
6
19K2
32 8 4 2
64
16 1
S3
BAUD ADDRESS
POWER
0V
RESET
SERVICE
1K2
9K6
19K2
32 8 4 2
64
16 1
S3
B A U D A D D RE S S
POWER
0V
RE
SET
SERVICE
2 wir
Normally Locl Ln address =100
4 wir
Network Engineering Manual,
92-1735
Polarity independentTerminal size 0.5 to 2.55 m2 (20 to 14 AWG)
T
R
T
R
T
R
T
R
T
R
T
R
T
R
T
R
T
R
T
R
T
R
T
R
T
R
TR
X
R-
T-
T+
R+
T-
T+
R-
R+
SCNSCN
RR
R R
T T
T T
internal links
X
R+
R-T+
T-
T-
T+
R-
R+
SCNSCN
T T
R R
internal links
Cbl 1k2 bud 4k8 bud 9k6 bud19k2
bud
No. of
Wirs
Belden 91821000 m
(1090 yds)
1000 m
(1090 yds)
1000 m
(1090 yds)
700 m
(765 yds)2
Belden 92071000 m
(1090 yds)
1000 m
(1090 yds)
1000 m
(1090 yds)
500 m
(545 yds)2
TrndTp/1/1/22/HF/200(Belden 8761)
1000 m
(1090 yds)
1000 m
(1090 yds)
700 m
(765 yds)
350 m
(380 yds)2
TrndTp/2/2/22/HF/200(Belden 8723)
1000 m
(1090 yds)
1000 m
(1090 yds)
500 m
(545 yds)
250 m
(270 yds)4
WaRNINg: This apparatus must be earthed
(grounded) using earth (ground) tag.Note that the earth (ground) tag is internally connected to 0V
3.1 Instlltion - Mountin (continued)
7/27/2019 en-tg103062-uk0yr1112.pdf
4/8
4 LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012
LINC Instlltion Instructions
7Connct LONWORKS ntwork
8Clos pnl
3.1 Instlltion - Mountin (Continued)
1K2
9K
6
19K2
32 8 4 2
64
16 1
S3
B A U D A D D R E SS
POWER
0V
RESET
SERVICE
Terminator
Star topology
*
LONWORKS - FTT (free topology)
Terminator
Bus topology
*
Terminator
Loop topology
*
Do not allow wires to cross on a loop
Normal current loop Lan cable is not recommended.Do not use screened cable.
If used with LPT-10 (powered bus),
cable lengths differ - see Link Power
Transceiver Users Guide
(078-0105-01C).
Terminal size 0.5 to 2.55 m2 (20 to 14 AWG)
1K2
9K
6
19K2
32 8 4 2
64
16 1
S3
B A U D A D D R E SS
P OWE R
0V
Cbl Mx bus lnth Mx nod to nod
Belden 85102 500 m 500 m
TrendTP/1/0/16/HF/200(Beldon 8471)
500 m 400 m
UL Level IV, 22 AWG 500 m 400 mJY(St) Y2 x 2 x 0.8 500 m 320 m
TIA568A Cat. 5, 24 AWG 450 m 250 m
*Terminate LONWORKS bus at one end only using IQLROUTER
integrated LONWORKS terminator or LONTERMINATOR
100mF, 50 V min
100 mF, 50 V min
LONTERMINATOR
LonASCN LonB LonASCN LonB
LINC
A
IQLROUTER
B
IQL
xy
A
IQLROUTER
B
zw
IQL
x y zw
T
T T
4 5 6 7 8 9 10 11
4 5 6 7 8 9 10 11
Maximum 64 nodes perLONWORKSsegment
Maximum 40 IQLs (and LONCs) per Lan
Recommend terminate at LINC or Router.
e.g. use IQLRouter integral terminators
LONWORKS network
SCNLonA
LonB
SCN
LonA
LonB
internal links
polarity independent
LONWORKS network
This unit is UL rated as UL916 accessory
to open energy management equipment.
7/27/2019 en-tg103062-uk0yr1112.pdf
5/8
LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012 5
Instlltion Instructions LINC
3St LINC Intrntwork addrss (Lan number)
1Switch off
2On pnl
1K2
9K
6
19K2
32 8 4 2
64 16 1
S3
B A UD A DDRE S S
P OWE R
0V
O
I
1K2
9K
6
19K2
32 8 4 2
64
16 1
S3
BAUD ADDRESS
POWER
0V
RESET
SERVICE
ON
128
416
32
64
1K2
9K
6
19K2
BAUD ADDRESS
SET
NOT SET
e.g.
Address = 2 + 16 = 18
ON
if address < 100, address denes Lan number on Internetwork
(LONWORKS internetwork)
Lan LINCInternetwork on LONWORKS
if address = > 100, address is for conguration only
(Internetwork LONWORKS Extension)
Cution: This LINC contains static sensitivedevices. Suitable anti-static precautions
should be taken throughout this operation
to prevent damage to the unit.
BS EN100015/1 Basic Specification: protection of
electrostatic sensitive devices
WaRNINg: Opening the panel may expose
dangerous voltages.
417-IEC-5036
= D LINC
Lan
Lan/= D Lan/= D
Lan/= D
Address = D
address 1, 4 to 9, 11 to 119
0, 2, 3, 10 or >119
3.2 Installation-Confguration
Inter-
network
Segment ALINC
Internetwork Segment B
on LONWORKS
7/27/2019 en-tg103062-uk0yr1112.pdf
6/8
6 LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012
LINC Instlltion Instructions
4St Ntwork Bud Rt
5Switch On
6St Ntwork Bud Rt
7Chck LINC on LONWORKS ntwork
8Clos pnl
1K2
9K6
19K2
32 8 4 2
64
16 1
S3
B A U D A D D RE S S
POWER
0V
RE
SET
SERVICE
SET
NOT SET
= 19k2 baud
= 9k6 baud
= 1k2 baud
ONLINC
Baud = C
=C
=C
=C
=C
If address < 100,
baud rate of current loop Lan
Lan LINC
Internetwork on
LONWORKS network
If address = > 100,
baud rate of current loop Internetwork (Segment A)
3.2 Installation-Confguration (Continued)
1K2
9K6
19K2
32 8 4 2
64
16 1
S3
B A U D A D D R ES S
POWER
0V
RE
SET
SERVICE
O
I
Check networkcabling for short
circuits with amultimeter
(NOT Megger)
Check baud rate.
Power up other
nodes until faulty
node is found (OK
). Correct fault.
X
O
I
Lan OK (green)
LINC Faulty
Lan OKLan OK
NETB/LINC
If address < 100, current loop Lan
If address = > 100, current loop Internetwork (Segment A)
Lon OK (green)
1K2
9K6
19K2 32 8 4 2
64 16 1
S3
B A U D A D D R E SS
POWER
0V
RE
SET
SERVICE
1 K2
9 K
6
1 9 K2
3 2 8 4 2
6 4
1 6 1
S 3
BAUD ADDRESS
POWER
0V
(Check LONWORKS network,
LINC, LINC,and IQL)
Flashes every 24 s, ON after
1 mins
This unit is UL rated as UL916
accessory to open energy
management equipment.
Inter-network
Segment ALINC
Internetwork segment B
on LONWORKS network
andLINC LINC
LanIQLIQL
or LONWORKS
network
7/27/2019 en-tg103062-uk0yr1112.pdf
7/8
LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012 7
Instlltion Instructions LINC
9ConfgLINC
10St u followin rmtrs
11Otionl Sttins
3.2 Installation-Confguration(continued)
LINC
Lan
I/N
LINC
Lan
e.g. R select addRess module
address 126,local Lan
address 126,
Lan number
set byaddress
switch
SET
SET Manual TE200147
top menu :or
to eXit module having changed parameterX
to Quit module and discard changes Q Note that the LINC can be congured across the LONWORKS
network (using another LINC) if TARP is set to Yes (default) in
both LINCs (see step 14)
Note that a PIN may be required to make changes in conguration mode. If the PIN has been forgotton theusers should contact their supplier (installers contact Technical Support) quoting the generator number (Usermodule) and neuron id (Address module) whereupon a default PIN will be supplied. This will only work during the
same conguration mode session i.e. the utility must not be exited between reading the generator and entering the default PIN.After the PIN is entered a new PIN should be set up and remembered.
*Note that to speed up communications,TARP should be changed to No unless there is more than one LINC physically connected
by the LONWORKS network. Installation on a LONWORKS Management Tool sets TARP to Yes and it can no longer be changed inconguration mode (see step 14).
Sttins tht must b md
prmtr Sttin Function Condition
Address tarP address resolutionprotocol,default=Yes
Switches on or off globaladdress resolution messages
*Change to No unless connected tosecond LINC by LONWORKS network
localalarms
Addr node address node address of LINC alarm target to send current loop network alarms
Remote lan Lan number Lan number of LINC alarm target to send current loop network alarmsint/netalarms
nodE node address node address of LINC alarm target to send alarms from LONWORKS internetwork
remoTe lan Lan number Lan number of LINC alarm target to send alarms from LONWORKS internetwork
Sttins tht my b md
prmtr Sttin Function Condition S Not
User Pin number Protects changes inconguration mode
Default is blank (unprotected).Set up if security required.
1
Address IDentier 15 alphanumericcharacters - not^({;?* characters
identier for this LINC Set up for supervisors, display panels
lonworks Message code code number.Default = 64.
All LINCs/IQLs mustuse same code
If message code being used by otherusers - must be exclusive to IQ system
2
router Buffersize
buffer size (bytes)Default = 146
species smallestrouter buffer on system
If routers separate LINCs and havebuffer size smaller than 146 bytes - setto smallest buffer size. (minimum = 66)
transceiVer number denestransceiver type
Default=0 (FTT-10)
DO NOT CHANGE FROM 0
r-retry time See IQ system LONWORKS ProductsEngineering Guide for detailsi-interpacket
delay
s-service class
Note
1: If PIN is forgotton see note in step 10
2: Message code can only be changed in conguration mode if LONWORKS managed is set to No (i.e. managed by LINC).
If the LINC is installed on LONWORKS Management Tool (see step 14), lonworks managed is set to YES, and Message
code cannot be changed in conguration mode.
Set up the following parameters if required. The table shows setting that may be required for special circumstances
LONWORKS
network
LONWORKS
network
7/27/2019 en-tg103062-uk0yr1112.pdf
8/8
8 LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012
LINC Instlltion Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
2012 Honeywell Technologies Srl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Srl, Z.A. La Pice, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.
Trnd Control Systms LimitdAlbery House, Springeld Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
Trnd Control Systm USa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trendamericas.com
15Chck LINC Ortion
14Instll on LONWORKS Ntwork
Mnmnt Tool (LMT)
12Not Nuron ID
13ExitConfguration
4 DISpOSaL
Weee Dirctiv:At the end of their useful life the packaging, and
product should be disposed of by a suitable
recycling centre.
Do not dispose of with normal household waste.
Do not burn.
addRess/ neuron chip id 00:00:00:00:00:00
X
"exit from Utility
If user wishes to install LINC using
Neuron ID - see step 14 a
a). When installing LINC on LONWORKS tool enter Neuron
ID from step 12 - or press service button.
If a binding IQLs to LONMARK Devices
or b LINCs version