1 / 4 RAYSTAT-EX-03-A ELECTRONIC LINE-SENSING THERMOSTAT INSTALLATION INSTRUCTIONS THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceRayStatEX03A-IM-H56496      01/13 DESCRIPTION RAYSTAT-EX-03-A is an electronic line sensing thermostat used to control heating cable cirucits directly or through a suitable contactor. SPECIFICATIONS Enclosure • NEMA 4X; IP66 • Electrostatic-charge-resistant glass- filled engineering polymers, black • Exposed hardware of stainless steel Entries Two 3/4 in conduit through holes (with one hole plugged) Ambient operating range –40°F to 105°F (–40°C to 40°C) Setpoint range 32°F to 930°F (0°C to 499°C) Switch DPDT Switch capacity 16 A (suitable for heating cables on 20 A circuit breakers) Supply voltage AC 100–277 V, 50/60 Hz Accuracy ±1% of set point, minimum 1°C Deadband ±1% of set point, minimum 1°C Sensor type 100 Ω platinum RTD Sensor material Stainless steel Sensor length 6 ft (2 m) Connection terminals Power supply: 12 AWG (4 mm 2 ) Heating cable: 12 AWG (4 mm 2 ) Ground: 10 AWG (6 mm 2 ) This component is an electrical device. It must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions. Component approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape to make connections. WARNING: APPROVALS Hazardous Locations CL I, Zn 1 AEx emia IIC T6 CL I, Zn 1 Ex emia IIC T6 CL I, DIV 2, GPS B, C, D CL II, DIV 1 & 2, GPS E, F, G Class III

En DigiTraceRayStatEX03A IM H56496 Tcm432 26091

  • Upload
    dk1000

  • View
    213

  • Download
    0

Embed Size (px)

DESCRIPTION

ELECTRICAL HEAT TRACING

Citation preview

  • 1 / 4

    RAYSTAT-EX-03-AElEctronic linE-sEnsing thErmostat installation instructions

    THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceRayStatEX03A-IM-H5649601/13

    DEScRIpTIONRAYSTAT-EX-03-A is an electronic line sensing thermostat used to control heating cable cirucits directly or through a suitable contactor.

    SpEcIfIcATIONSEnclosure NEMA4X;IP66

    Electrostatic-charge-resistantglass-filled engineering polymers, black

    ExposedhardwareofstainlesssteelEntries Two3/4inconduitthroughholes(with

    one hole plugged)Ambient operating range 40Fto105F(40Cto40C)Setpoint range 32Fto930F(0Cto499C)Switch DPDTSwitchcapacity 16A(suitableforheatingcableson20A

    circuit breakers)Supply voltage AC100277V,50/60HzAccuracy 1%ofsetpoint,minimum1CDeadband 1%ofsetpoint,minimum1CSensor type 100 platinum RTDSensor material Stainless steelSensor length 6ft(2m)Connectionterminals Powersupply: 12AWG(4mm2)

    Heatingcable: 12AWG(4mm2)Ground: 10AWG(6mm2)

    This component is an electrical device. It must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions.

    Component approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape to make connections.

    WARNING:

    AppROvALSHazardous Locations

    CL I, Zn 1 AEx emia IIC T6CL I, Zn 1 Ex emia IIC T6CL I, DIV 2, GPS B, C, DCL II, DIV 1 & 2, GPS E, F, GClass III

  • THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceRayStatEX03A-IM-H5649601/13 2 / 4

    90

    A

    B

    C

    3/4 in

    Sensor

    2 3

    1

    Awayfromvalves,flanges,supports,pumpsor other heat sinks.

    Atthetopofthepipeforthermallysensitivepipecontents(A).

    Onlowerquadrantofpipe90fromsingleheatingcable(B)

    Onlowerquadrantofpipe centrallybetweenthe heating cables if there aretwoor more(C).

    MounttheRAYSTAT-EX-03-AenclosureeitheronthepipeusingaJB-SB-25bracketoronanearbysupport.ForMIheatingcables(applicationsabove482F(250C)),donotmount the enclosure on the pipe to avoid damage to the electronics.

    Fixsensorfirmlyonsurfacewithadequateglasstapeintwoplaces.

    Fixsensorparalleltopipe. Routeextentioncabletoavoiddamageinuse.Fixtopipewithglasstapewhereappropriate.

    Note: Donotinstallsensoratambienttemperaturesbelow0F(20C).

    Donotbendendofsensor(last2in).Donotbendtheextensioncabletighter than 0.5 in radius.

    A

    B B

    E

    C

    D

    JB-SB-25C75-100-A

    BA C

    KIT cONTENTS

    OpTIONAL MATERIALS

    TOOLS REqUIRED

    A Thermostat enclosure

    B Conduitentries(2x3/4inthroughhole)

    c Temperaturesensingelement(RTD)

    D Stainlesssteelsheathedextensioncableforsensor(6ft./2m)

    E Terminal blocks (max.12AWGforterminals 1-12, max.10AWGforground terminals).

    A 3mmterminalscrewdriver

    B 1/4inflat-bladescrewdriver

    c Glasstape(GT66,GS54orequivalent)

    IfconnectingRaychem'sparallelheatingcablesdirectlyintotheRAYSTAT-EX-03-Aenclosure,useaC75-100-Aconnectionkitmustbeusedtopovidetherequiredsealing and insulating components.

    JB-SB-25supportbracketforpipemounting. Pipestraps(notshown).

    Enclosure Mounting

    Attaching the SensorLocate the RAYSTAT-EX-03-A Sensor

  • 3 / 4THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceRayStatEX03A-IM-H5649601/13

    Heating cable

    NL1

    max.20 A/C

    1 2 3 12

    Sensor

    6 8 9754

    RAYSTAT-EX-03-A

    RTD

    NO C NC CNO NC

    Heating cable

    ContactorDirect connection

    1 2 3 12876 954

    RAYSTAT-EX-03-A

    RTD

    NO C NC CNO

    N

    L1

    max.20 A/C

    L2L3

    Sensor Note:Jumpers are installed at the factory.

    Note:Jumpers are installed at the factory.

    Seal

    Seal

    4

    5 6

    7

    For100132Vsupply, connect to terminals 2 and 3, and move jumper from terminal 1 to terminal 2.

    For208277Vsupply,connect to terminals 1 and 3.

    Removejumpers1-8and3-5ifpoweringheating cable from separate supply.

    Note: Temperature setpoint is in cAdjustdigitalswitchestosetpointtemperature(C)

    SeetableinsidelidtoconvertfromFtoC.

    Installlidandtightenscrews.

    Ensurethatthepipeandsensorare thermally insulated and clad to the design specification after installation of thermostat.

    Sealcladdingwithsuitableseal-ant at locations marked above.

    check: Mounting is firm.Exposedextensioncableisnotdamaged.Conduitandglandentriesaretightenedfirmly. Thermostat operation is correct. Thermostat setting suits application. Lid is closed firmly. Retain this instruction for future use.

    Making Electrical connection

    Setpoint Temperature complete Installation

    Testing

  • 4 / 4THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceRayStatEX03A-IM-H5649601/13

    WWW.THERMAL.PENTAIR.COM

    1999-2013 Pentair. PN 803714-000

    NORTH AMERICATel: +1.800.545.6258Fax: +1.800.527.5703Tel: +1.650.216.1526Fax: [email protected]

    EuROPE, MIddLE EAsT, AfRICATel: +32.16.213.511Fax: [email protected]

    AsIA PACIfICTel: +86.21.2412.1688Fax: [email protected]

    LATIN AMERICATel: +55.11.2588.1400Fax: [email protected]

    Pentair, DigiTrace and RAYSTAT are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.