| 1Energy Efficiency Summit, 2011
Emerging Trends in improving
Energy Efficiency in Chillers
| 2CONFIDENTIAL
Chiller Market
Various Types of Chillers & Available Range:
Chiller Market In India:
Total Estimated Market for 2011:
875,000 TR
Type of Chiller Centrifugal
Oil-free Centri
Screw
Scroll
50 100 150 200 250 500 1000 3000
Cooling Capacity, (TR)
| 3CONFIDENTIAL
Selection of Chillers
Other considerations-
•Regulatory Requirements- Eco-friendly Refrigerants, Certification, etc.
•Compliance to ECBC, Green Building, ASHRAE90.1 etc.
•Noise Level
Segment Applications Drivers Type of Chilled Water System
Contractor/
Builder
Commercial,
Shopping Malls
Equipment, Specs,
First Cost
Scroll/ Screw, DX type
Standard AHU
Consulting
Engineers,
Developers/
Architects
Large Offices, IT
Parks,
Hotels,
Hospitals
Equipment, Specs,
Life Cycle Cost
Screw/ Centri/Turbocor, Flooded type
AHU & Pumps with VFD
System & Building
Design
VSD Centrifugal, Oil-free Centri,
Variable Air & Water integrated with
BMS
Industrial &
Special
Applications
Data CentresReliability,
Redundancy,
Temp Control,
Efficiency
Scroll/ Screw, DX type
Precision Control AHU
Process Cooling Scroll/ Oil-free Centri, DX/Flooded type
| 4CONFIDENTIAL
Energy Efficiency (AHRI-550/590)
Coefficient of Performance (COP)
- Ratio of the rate of heat removal to the rate
of energy input
- Measured at full load (100% capacity) under
standard rating conditions
Integrated Part-Load Value (IPLV)
- Equipment is selected to meet the load
under maximum operating conditions
- In actual, equipment operate at part load for
most of the run time
- IPLV represents a single number figure of
merit expressing part load efficiency on the
basis of weighted operation at various load
capacities
Plant Efficiency (Not covered in AHRI-550/590)
- Auxiliary equipment (such as pumps, fan & blowers) and design conditions (such as 'appoach
temperatures') can have have substantial effects on overall plant efficiency
- Staging of multiple chillers for the best plant efficiency & operation of isolation valves with variable
water flow can be managed with intelligent Plant Manager System.
IPLV = 0.01*A + 0.42*B + 0.45*C + 0.12*D
A: EER at 100% capacity
B: EER at 75% capacity
C: EER at 50% capacity
D: EER at 25% capacity
| 5CONFIDENTIAL
Energy Efficiency RegulationsEnergy Conservation Building Code
(ECBC):
- Launched by Ministry Of Power, Govt of
India in May 2007; revised in May2008
- Applicable to buildings or complexes that
have a connected load of 100kW or greater
or a contract demand of 120kVA or greater
- Under voluntary adoption in the country
- Code defines minimum energy efficiency
level for HVAC systems, components &
controls
Code recommends: 1) variable Speed
drives for water circulation pumps, AHU
motors and cooling tower fans, 2) 2-way
isolation valves for load balancing and
3) VAV diffusers, low pressure drop duct
ASHRAE 90.1
- Define Minimum Energy Efficiency of HVAC
systems
- Provide robust framework for ECBC guidelines
| 6CONFIDENTIAL
DX & Flooded EvaporatorsCategory DX Evaporator Flooded Evaporator
Construction • Shell & Tube Type
• Refrigerant Flows through Tubes
• Water Flow through Shell
• Inner Grooved Tubes
• 5 - 10oC superheat
• Shell & Tube Type
• Water Flows through Tubes
• Refrigerant in Shell
• Tubes with fins from both Inside & Outside
• Negligible superheat
Cost • Lower
• Limited Refrigerant Quantity
Efficiency
Air-cooled
Water-cooled
• Low due to lower evaporating temp
• 1.15 ~ 1.2 IKW/TR
• 0.72 ~ 0.8 IKW/TR
• High
• Large Refrigerant Quantity
• High due to higher evaporating temp
• 1.05~ 1.08 IKW/TR
• 0.57 ~ 0.65 IKW/TR
WATER OUT
44°F
WATER IN
54°F
GAS
REFRIGERANT LIQUID IN
35°F
REFRIGERANT
COOLER APPLICATIONREFRIGERANT
LIQUID IN
510F
REFRIGERANT
GAS
| 7CONFIDENTIAL
District Cooling Systems
Cost Effective Hydronic Circuits
- Lower pump size, smaller pipe diameters
- Lower Pumping Cost
- Cooling coils must be oversized Higher Installation Cost
| 8CONFIDENTIAL
Constant Speed Compressors- Tandem
Scroll Chillers•A ‘tandem scroll’ consists of two identical scroll
compressors linked in parallel to function as
one compressor.
• It increases the operating efficiency, whenever
the chiller operates under ‘part load’ conditions.
• Power savings up to 20% can be achieved by
utilizing the entire condenser area for heat
rejection, even when one compressor in the
circuit is in operation.
| 9CONFIDENTIAL
Performance: Tandem Scroll Vs Screw
At ARI Reduced Ambient At 35C Constant Ambient
• Performance of scroll chillers & screw chillers similar at ARI part load test
conditions, hence rated COP & IPLV values are comparable.
• Performance of scroll chillers is significantly better than that of screw chillers
during part load operation at high ambient conditions, which are common in
India.
| 10CONFIDENTIAL
Advantages of Scroll over Screw
Design
- Lower Sound Level : Quiet operation
- Low Starting Current : Smaller Generator
Screw Chiller : 450 Amps for 110TR
Scroll Chiller : 360 Amps for 120TR
- DOL starting: Less Switchgear
- Only three connections: Suction, Discharge &
Oil Equilizer.
Service & Maintenance
- Simple design, Highly trained serviceman not
required.
- Due to multiple circuits, complete shutdown is
not necessary for servicing.
- Redundancy during failure.
- Runtime equalization of compressors - enhanced
life of compressors.
- Low weight compressor- ease of
handling/replacement.
Reliability
- Oil is on suction side at lower temperature : No oil
cooling required.
- Better operating envelope: can operate at high
condensing temperature.
- No Liquid Injection required for motor cooling
- Unloading of chiller by switching off compressors;
no moving part for unloading.
| 11CONFIDENTIAL
Variable Speed Compressors: Oil-free
Centrifugal Chillers• Compressor speed
adjusts automatically to match
the load and current operating
conditions so that optimum
efficiency is gained.
• Primary capacity control is done
using the onboard VFD and only
use the Inlet Guide Vanes to
supplement VFD controls. IGVs
prevent surge conditions at low
turndown. IGVs normally
operate at the 110% position.
• The slower the compressors,
the greater the efficiency. As
speeds is reduced, energy
consumption is reduced by the
cube.
"Best In Class" Sound Level
72 dBA at 1m
| 12CONFIDENTIAL
Compressor: Oil Free, Magnetic Bearings
Pressure and
temperature
sensors
Inverter speed
control
Synchronous
brushless DC
motor
Motor and
bearing control
Inlet Guide
Vanes
2 stage centrifugal
compressor
Soft-Start
(<2amps Inrush)
| 13CONFIDENTIAL
Magnetic Bearing System
The rotor shaft is held in position
with ten separately controlled
electro-magnetic cushions which
continually change the strength
to keep the shaft centrally
positioned.
| 14CONFIDENTIAL
Advantages of Oil Free CompressorPercentage of Oil in the System
Chiller
Effic
iency
Loss
Percentage of Oil in the System
•A study was conducted by ASHRAE to determine the average quantity of oil as a percentage in older chillers.
Average oil quantity was found to be 12.88%.
| 15CONFIDENTIAL
Part Load Efficiency
0
0.2
0.4
0.6
0.8
1
20% 40% 60% 80% 100%
Percent Load
kW/Ton
Oil-free Centri Centrifugal W/C Screw W/C Recip
Performance of Centrifugal Chiller with VSD will be similar to Oil-Free Centri. Chiller
| 16CONFIDENTIAL
Overall Benefits
• 100% Oil Free eliminates oil
system maintenance costs.
• R134a Refrigerant meets
Montreal protocol and is not
subject to phase-out.
• Magnetic Bearings eliminate
frictional losses.
• One moving part assures
long service life.
• Unmatched Efficiency as low
as 0.36 kw/ton IPLV.
• Low In-Rush Current reduces
installed cost and peak load.
• Lowest Noise- Only 72 dBa.
| 17CONFIDENTIAL
Efficiency of Central Plants
- Simply selecting a high efficiency
chiller does not guarantee high
system performance.
- Auxiliary equipment (AHUs,
cooling towers, pumps, control
valves, fan & blowers) and design
conditions (appoach temperatures)
can have have substantial effects
on overall plant efficiency.
- Attention to overall system design
& auxiliary components is critical to
achieving optimal performance &
comfort.
| 18CONFIDENTIAL
Energy consumption Running costs
Environment Comfort
Thank You