36
ELTS Normal Emergency Load Emergency Lighting Transfer System (Group 9) User Manual

Emergency Lighting Transfer System (Group 9) … · Emergency Lighting Transfer System (Group 9) ... Welcome to ETC’s Emergency Lighting Transfer System ... ANSI/NFPA 110

Embed Size (px)

Citation preview

ELTSNormal

EmergencyLoad

Emergency Lighting Transfer System (Group 9)

User Manual

2 Electronic Theatre Controls, Inc.

Emergency Lighting Transfer System User Manual 3

Emergency Lighting Transfer System

User Manual

ContentsIntroduction................................................................................................... 5

How to use this manual ........................................................................... 5Codes and standards................................................................................ 5System Diagram....................................................................................... 6

Installation and setup chaptersInstallation..................................................................................................... 7

Unpack and Inspect.................................................................................. 7ELTS Models............................................................................................ 8Mounting the ELTS cabinet...................................................................... 9Installing Remote stations (optional) ...................................................... 11

Connecting power and control wiring to the ELTS cabinet ................... 12Transfer switch, Normal power and lighting load connections .............. 13Control and Sensing wire connections................................................... 15

Testing ......................................................................................................... 18Before you power up for the first time .................................................. 18Turn on system ...................................................................................... 18Functional checkout ............................................................................... 19

Settings ....................................................................................................... 21ELTS timing settings .............................................................................. 21ELTS voltage and frequency settings..................................................... 24

Use and service chaptersOperation..................................................................................................... 25

Automatic operation............................................................................... 25Switching power sources manually ....................................................... 26

Service ......................................................................................................... 27Preventive maintenance......................................................................... 27

Troubleshooting ......................................................................................... 28Emergency or Normal Power Stable LED does not turn on properly..... 28The ELTS will not switch between Normal and Emergency.................. 28Remote stations cannot switch the ELTS.............................................. 29

AppendicesAppendix A: ELTS specifications............................................................... 30Appendix B: Wire connection schematics and diagrams ....................... 31Appendix C: Transfer switch control system schematics....................... 33Appendix D: Transfer switch load switching schematic......................... 34Appendix E: Test and Maintenance Log................................................... 35

4 Electronic Theatre Controls, Inc.

Emergency Lighting Transfer System User Manual 5

Emergency Lighting Transfer System

IntroductionWelcome to ETC’s Emergency Lighting Transfer System (ELTS) User Manual. This manual shows you how to install and use your ELTS system. See ELTSModels on page 8 for a breakdown of ELTS models and configurations.

How to use this manualThis manual is divided into three sections:

▼ Installation on page 7 tells you how to install and test your system

▼ Operation on page 25 tells you how to use and service your system

▼ The Appendix B: Wire connection schematics and diagrams on page 31 contains additional information you may need

Warnings and notice conventionsThese symbols alert you to danger or important information:

Warning! Warns you when electricity may cause injury

Warning! Warns you when there is a possibility of other types of injury

Notice: Alerts you to important information relating to equipment performance or reliability

Contacting ETCFor questions about ELTS system delivery or general information, contact ETC Customer Service at 800/688-4116.

Codes and standardsELTS systems meet the following regulatory standards for emergency lighting transfer devices:

▼ ANSI/UL 1008 – Listed, Automatic Transfer Switches

▼ ANSI/NFPA 110 – Emergency and Standby Power Systems

▼ ANSI/NFPA 70 – National Electric CodeArticle 701 – Legally Required Standby SystemsArticle 700 – Emergency SystemsArticle 540 –11(c) – Motion Picture HousesArticle 520 – 7 – Theatres and Similar LocationsArticle 518 – 3(c) – Places of Assembly

▼ City of New York, Advisory board, Electrical Department

▼ OSHA

▼ Department of Defense

6 Electronic Theatre Controls, Inc.

System Diagram

Figure 1: Diagram of a typical ELTS system

Normal/Emergency loads

Normal/Emergency loads are routed throughthe ELTS. Normal load power comes from thedimming system. If the ELTS detects a loss of

dimmer normal power, it switches thenormal/emergency loads from dimmer normal

power to the emergency power source.

Main power

L1 L2 L3 N

Emergencygenerator

L1 L2 L3 N

Normal power Channels 7–12 (into ELTS)

Normal/Emergency loads Channels 7–12 (from ELTS)

Normal loads

Normal loads are connected directlyto the dimming system. If main power

fails, normal loads are dark.

Fire alarm activationAux activation

Normal loadsChannels 1–6

Up to ten Remote stationscan be connected to the ELTS

L1, L2 and L3sensing wires

GeneratorStart

ELTS cabinet

Dimmer rack

Emergency Lighting Transfer System User Manual 7

InstallationUnpack and Inspect

Before you begin installation, check your shipment so you know it arrived complete and undamaged.

1. Check the shipping container for obvious physical damage:

▼ Torn or opened containers

▼ Water stains or wetness

▼ Crushed or punctured boxes

▼ Other shipping-related damage

2. If you find damage, document it to help with a claim against your shipper.

3. Unpack your order and check the contents against the Bill of Materials to be sure your order is complete.

4. Open the ELTS cabinet door and check for loose connections or broken components caused by shipping vibration.

5. If you discover a problem with your order, call ETC Customer Service at 800/688-4116.

Figure 2: Identifying ELTS components

CONTROL PANEL

ASCO GROUP 9

ASCO

POWER

SUPPLY

PSLUG

GROUND DUE TO SHIPPING, MFG. IS NOT RESPONSIBLE FORLOOSE CONNECTIONS, TIGHTEN ALL CONNECTIONS

BEFORE ENERGIZING.

12 POLE TRANSFER SWITCH

TS1

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN

2N

N1

NL2

NN

3N

L3N

L5N

N4

NN

6N

L6N

N5

13

2

TS2

12 POLE TRANSFER SWITCH

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN

2N

N1

NL2

NN

3N

L3N

L5N

N4

NN

6N

L6N

N5

13

2

TS4

12 POLE TRANSFER SWITCH

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN

2N

N1

NL2

NN

3N

L3N

L5N

N4

NN

6N

L6N

N5

13

2

TS3

12 POLE TRANSFER SWITCH

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN

2N

N1

NL2

NN

3N

L3N

L5N

N4

NN

6N

L6N

N5

12

11

10

9

8

6

7

4

5

3

1

2

T10

T11

T12

T8

T9

T6

T7

T3

T4

T5

T1

T2

6

5

4

3

1

2

R3

R4

R5

R2

R1

1

3

2

F1

F2

1

3

2 A2

A1

6

5

4

3

1

2

G3

G2

G1

6

5

4

3

1

2

NA

NB

NC

6

5

4

3

1

2

EA

EC

TS11

TS29

TS30

TS10

TS12

TB2

TB1

TB3

9

8

6

7

4

5

3

1

2

13

2

EPDB

A B C N

SR3BSR3BSR3B SR3B

8910 7 6 345 2 1

A B C N

CONTROL PANEL

ASCO GROUP 9

ASCO

POWER

SUPPLY

PSLUG

GROUND DUE TO SHIPPING, MFG. IS NOT RESPONSIBLE FORLOOSE CONNECTIONS, TIGHTEN ALL CONNECTIONS

BEFORE ENERGIZING.

12 POLE TRANSFER SWITCH

TS1

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN2

NN1

NL2

NN3

NL3

NL5

NN4

NN6

NL6

NN5

13

2

TS2

12 POLE TRANSFER SWITCH

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN2

NN1

NL2

NN3

NL3

NL5

NN4

NN6

NL6

NN5

12

11

10

9

8

6

7

4

5

3

1

2

T10

T11

T12

T8

T9

T6

T7

T3

T4

T5

T1

T2

6

5

4

3

1

2

R3

R4

R5

R2

R1

1

3

2

F1

F2

1

3

2 A2

A1

6

5

4

3

1

2

G3

G2

G1

6

5

4

3

1

2

NA

NB

NC

6

5

4

3

1

2

EA

EC

TS11

TS29

TS30

TS10

TS12

TB2

TB1

TB3

9

8

6

7

4

5

3

1

2

8910 7 6 345 2 1

13

2

EPDB

A B C N

SR3BSR3BSR3B SR3B

A B C N

Control panel

Transfer switch assemblies

Isolation relays

EmergencyLine and Neutral lugs

ELTS power supply

Isolation relays

ELTS power supply

Emergencyground lug

EmergencyLine and Neutral lugs

Emergencyground lug

Terminal blocks

Terminal blocks

ELTS 850, 1820, 2420

ELTS 450, 620, 1220

8 Electronic Theatre Controls, Inc.

ELTS Models

Figure 3: Large and small ELTS cabinets

Remote station (part # 1093A2023)

▼ Provides front panel keyswitch control at remote locations.

▼ Link up to ten stations with parallel wiring.

▼ Normal and Emergency LEDs indicate ELTS status.

Electronic Theatre Controls Inc.

MODEL ELTS

AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS

ISSUE NO. 934

Operational Current: 200A Max 3 Phase

POWERPOWER

UL1008 Listed

Operational Voltage: 120/208v (3p+N+ )

Frequency: 50/60Hz.

Short-circuit current: 10,000 AIC

Electronic Theatre Controls Inc.Middleton, WI Made in USA

C®®

GENERATOR

EMERGENCY POWER

FIRE ALARM

AUXILIARY

NORMAL POWER

TRANSFER SIGNAL

START

TRANSFER SIGNAL

STABLE

STABLE

42 31 86 75 12119 10

EMERGENCYNORMAL AUTO

EMERGENCYOPERATION

NORMALOPERATION

Electronic Theatre Controls Inc.

MODEL ELTS

AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS

ISSUE NO. 934

Operational Current: 200A Max 3 Phase

POWERPOWER

UL1008 Listed

Operational Voltage: 120/208v (3p+N+ )

Frequency: 50/60Hz.

Short-circuit current: 10,000 AIC

Electronic Theatre Controls Inc.Middleton, WI Made in USA

C®®

GENERATOR

EMERGENCY POWER

FIRE ALARM

AUXILIARY

NORMAL POWER

TRANSFER SIGNAL

START

TRANSFER SIGNAL

STABLE

STABLE

42 31 86 75 12119 10

2413 14 15 16 17 18 2119 20 22 23

EMERGENCYNORMAL AUTO

EMERGENCYOPERATION

NORMALOPERATION

Large ELTS cabinet (30" wide x 54" tall x 9" deep) ELTS 850 8 circuits of 50 ampsELTS 1820 18 circuits of 20 ampsELTS 2420 24 circuits of 20 amps

Small ELTS cabinet (30" wide x 36" tall x 9" deep) ELTS 450 4 circuits of 50 ampsELTS 620 6 circuits of 20 ampsELTS 1220 12 circuits of 20 amps

EMERGENCYNORMAL AUTO

EMERGENCYOPERATION

NORMALOPERATION

POWERPOWER

Figure 4: Remote station

Emergency Lighting Transfer System User Manual 9

Mounting the ELTS cabinetMount the ELTS on a load-bearing wall, in a location where it will not be subject to tampering or vandalism. If possible, install the ELTS where it is most secure from damage by a fire, flood or other incident likely to require its use. Do not install the ELTS inside any other electrical enclosure.

Physical requirements for mountingYou must mount either size ELTS cabinet with sufficient front clearance (30 inches) to allow the door to open completely.

Figure 5: ELTS cabinet mounting dimensions

Notice: When planning your installation, make sure to leave space around the cabinet for entry and exit wire conduit. Emergency line and neutral conduit may require extra space due to increased bend radius requirements for larger cables.

30.000" (cabinet)24.250" (bolts)

37.187"(bolts)

36.000"(cabinet)

9.375"

Electronic Theatre Controls Inc.

MODEL ELTS

AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS

ISSUE NO. 934

Operational Current: 200A Max 3 Phase

POWERPOWER

UL1008 Listed

Operational Voltage: 120/208v (3p+N+ )

Frequency: 50/60Hz.

Short-circuit current: 10,000 AIC

Electronic Theatre Controls Inc.Middleton, WI Made in USA

C®®

GENERATOR

EMERGENCY POWER

FIRE ALARM

AUXILIARY

NORMAL POWER

TRANSFER SIGNAL

START

TRANSFER SIGNAL

STABLE

STABLE

42 31 86 75 12119 10

EMERGENCYNORMAL AUTO

EMERGENCYOPERATION

NORMALOPERATION

Electronic Theatre Controls Inc.

MODEL ELTS

AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS

ISSUE NO. 934

Operational Current: 200A Max 3 Phase

POWERPOWER

UL1008 Listed

Operational Voltage: 120/208v (3p+N+ )

Frequency: 50/60Hz.

Short-circuit current: 10,000 AIC

Electronic Theatre Controls Inc.Middleton, WI Made in USA

C®®

GENERATOR

EMERGENCY POWER

FIRE ALARM

AUXILIARY

NORMAL POWER

TRANSFER SIGNAL

START

TRANSFER SIGNAL

STABLE

STABLE

42 31 86 75 12119 10

2413 14 15 16 17 18 2119 20 22 23

EMERGENCYNORMAL AUTO

EMERGENCYOPERATION

NORMALOPERATION

30.000" (cabinet)24.250" (bolts)

55.187"(bolts)

54.000"(cabinet)

9.375"

Large cabinet Small cabinet

10 Electronic Theatre Controls, Inc.

Planning wire entry into the ELTS cabinetThe Emergency power connections must enter the cabinet from the top or side of the cabinet within six inches of the top left corner.

Control, Normal power sensing and options wires connect most easily if they enter above the Remote station terminal or just below the Emergency sensing terminal on the left side of the cabinet.

Note: Do not run the control, normal power sensing and options wiring in the same conduit as Emergency phase or load power wiring.

Load wires in from the dimmer rack and out to the lighting loads connect most easily if they enter through the bottom of the cabinet either between or beside the transfer switch assemblies.

Note: Except for the emergency power supply wires, which must enter near the top left corner of the cabinet, recommended conduit entry locations may be changed based on the requirements of your installation.

Figure 6: ELTS components

CONTROL PANEL

ASCO GROUP 9

ASCO

POWER

SUPPLY

PSLUG

GROUND DUE TO SHIPPING, MFG. IS NOT RESPONSIBLE FORLOOSE CONNECTIONS, TIGHTEN ALL CONNECTIONS

BEFORE ENERGIZING.

12 POLE TRANSFER SWITCH

TS1

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN2

NN1

NL2

NN3

NL3

NL5

NN4

NN6

NL6

NN5

13

2

TS2

12 POLE TRANSFER SWITCH

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN2

NN1

NL2

NN3

NL3

NL5

NN4

NN6

NL6

NN5

13

2

TS4

12 POLE TRANSFER SWITCH

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN2

NN1

NL2

NN3

NL3

NL5

NN4

NN6

NL6

NN5

13

2

TS3

12 POLE TRANSFER SWITCH

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN2

NN1

NL2

NN3

NL3

NL5

NN4

NN6

NL6

NN5

12

11

10

9

8

6

7

4

5

3

1

2

T10

T11

T12

T8

T9

T6

T7

T3

T4

T5

T1

T2

6

5

4

3

1

2

R3

R4

R5

R2

R1

1

3

2

F1

F2

1

3

2 A2

A1

6

5

4

3

1

2

G3

G2

G1

6

5

4

3

1

2

NA

NB

NC

6

5

4

3

1

2

EA

EC

TS11

TS29

TS30

TS10

TS12

TB2

TB1

TB3

9

8

6

7

4

5

3

1

2

8910 7 6 345 2 1

A B C N

13

2

EPDB

A B C N

SR3BSR3BSR3B SR3B

Emergency power lugs

Control panel

Transfer switch manual operation handle

Remote stations

Fire alarm transfer

Auxiliary transfer

Generator start

Normal sensing

Emergency sensing

Transfer switch assembly

Emergency power conduit entry area

Recommendedcontrol conduit location

Recommendedcontrol conduit location Recommended

load input and output conduit locations

ELTS power supply

Isolation relays

Factory wired terminal

Factory wired terminal

Emergency Lighting Transfer System User Manual 11

Mounting the cabinetAfter determining where you want to install the cabinet, follow these instructions.

1. Install two 3/8" bolts 24.25 inches apart for the lower two support slots (the installer must supply the mounting hardware).

2. Use the mounting dimensions from Figure 5 : ELTS cabinet mounting dimensions on page 9 to drill the holes for the upper two 3/8" bolts.

3. Place the ELTS cabinet on the wall supported by the two lower bolts.

Notice: ELTS cabinets are very heavy. Make sure you have adequate equipment (or help) to lift the cabinet into place and support it while you secure the top two bolts.

4. Secure the ELTS to the wall with the two upper 3/8" bolts.

Installing Remote stations (optional)1. Install a standard two gang backbox (4" x 4" x 3.5") and run wire conduit

from it to the ELTS cabinet.

2. Pull five conductor, Class 2 (12 Vdc) wiring through from the backbox to the cabinet.

3. Connect the wires to the terminal strip on the back of the remote station. Note which terminal each wire connects to.

4. Install the Remote station onto the backbox with four 6 - 32 x 1/2" oval head machine screws (provided).

5. To install multiple Remote stations, repeat steps 1 – 4, wiring in parallel between Remote station terminal blocks.

Refer to Connecting Remote stations to the ELTS on page 16 for instructions for connecting Remote station wiring inside the ELTS cabinet.

12 Electronic Theatre Controls, Inc.

Connecting power and control wiring to the ELTS cabinetWarning! To prevent death or injury due to electrical shock, Normal and

Emergency power to the ELTS must be turned off any time you are connecting or servicing any ELTS.

Connecting Emergency powerThe Emergency power lugs are in the upper left of the ELTS cabinet. The ELTS is available in one or three phase power configurations.

1. Cut a hole within six inches of the top left corner of the ELTS cabinet

2. Install conduit and pull the Emergency power cables into the cabinet.

Note: Top conduit connections are recommended to reduce the cable bending necessary to connect to the lugs.

Table 1: Emergency power lug wire sizes and connection torques

Three phase (4 wire) connections1. Connect each phase power cable to the correct lug. See Figure 7, below,

to identify the lugs.

2. Connect the Neutral cable to the Neutral lug.

3. Connect the Ground cable to the Ground lug.

Figure 7: Connecting Emergency power to the ELTS

Single phase connection (3 wire)1. Connect one phase cable to the Phase A lug and one to the Phase B lug.

See Figure 7, above, to identify lugs.

2. Connect the Neutral cable to the Neutral lug.

3. Connect the Ground cable to the Ground lug

Connection type Wire size Torque

Phase and Neutral lugs (3 phase) 6 AWG to 2/0 275 in/lbs

Phase and Neutral lugs (single phase) 6 AWG to 250 MCM 275 in/lbs

Ground lug (both phase types) 14 AWG to 2/0 50 in/lbs

NCBA

LUG

GROUND DUE TO SHIPPING, MFG. IS NOT RESPONSIBLE FORLOOSE CONNECTIONS, TIGHTEN ALL CONNECTIONS

BEFORE ENERGIZING.

A B C N

Ground lug

Phase A lug

Phase C lug(Three phase ELTS only)

Phase B lug

Neutral lug

Emergency Lighting Transfer System User Manual 13

Transfer switch, Normal power and lighting load connectionsEach transfer switch can have up to six 20 amp circuits or two 50 amp circuits connected to it. You need to connect Line and Neutral inputs from the dimmer rack and outputs to the emergency lighting loads. The Line and Neutral input from Emergency power are delivered prewired.

Table 2Switch assembly wire sizes and connection torques

20 amp dimmer rack Load and Neutral wire input connections1. Attach the conduit for the wires from the dimmer rack to the bottom of

the ELTS cabinet (recommended.)

2. Connect a Neutral wire for each dimmer circuit to terminals NN1 through NN6 on the right side of the transfer switch assembly. See Figure 8, left, to match switch assemblies to loads.

3. Connect a Line wire for each dimmer circuit to terminals NL1 through NL6on the right side of the transfer switch assembly.

4. Repeat steps 2 and 3 for the other transfer switch assemblies.

Figure 9: 20 amp Transfer switch connections for Line and Neutral wires

20 amp lighting load Line and Neutral output connections1. Attach the conduit for the wires to the lighting loads through the bottom

of the ELTS cabinet (recommended).

2. Connect a Neutral wire for each lighting load to terminals LN1 through LN6 on the left side of the transfer switch assembly. See Figure 8, above, to match switch assemblies to loads.

3. Connect a Line wire for each lighting load to terminals LL1 through LL6 onthe left side of the transfer switch assembly

4. Repeat steps 2 and 3 for the other transfer switch assemblies.

Wire size Torque Wire size Torque

14 – 10 AWG 35 in/lbs 8 AWG 40 in/lbs

6 – 4 AWG 45 in/lbs 3 AWG to 2/0 50 in/lbs

Circuits1 – 6

Circuits7 – 12

Circuits13 – 18

Circuits19 – 24

Figure 8: 20 amp Transferswitch circuit assignments

12 POLE TRANSFER SWITCH

TS1

EL4

LL4

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

LL3

EL3

LN3

EN3

LN4

EN4

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

NL4

NL1

NN

2N

N1

NL2

NN

3N

L3N

L5N

N4

NN

6N

L6N

N5

13

2

NL1

NN

2N

N1

NL2

LL5

EL5

LL6

LN5

EL6

EN5

LN6

EN6

Line wire from dimmer

Neutral wire from dimmer

Input connections for Line and Neutral wires from the dimmer rack (Normal power)

Lighting load Neutral output wire

Prewired Emergency Line and Neutral input terminals

Lighting load Line output wire

Lighting load Line and Neutral terminals

Prewired Emergency feeds

14 Electronic Theatre Controls, Inc.

50 amp dimmer rack Load and Neutral wire input connections1. Attach the conduit for the wires from the dimmer rack to the bottom of

the ELTS cabinet (recommended.)

2. Connect a Neutral wire for each dimmer circuit to terminals NN1 and NN2on the right side of the transfer switch assembly. See Figure 10, left, to match switch assemblies to loads.

3. Connect a Line wire for each dimmer circuit to terminals NL1 and NL2 onthe right side of the transfer switch assembly.

4. Repeat steps 2 and 3 for the other transfer switch assemblies.

50 amp lighting load Line and Neutral output connections1. Attach the conduit for the wires to the lighting loads through the bottom

of the ELTS cabinet (recommended.)

2. Connect a Neutral wire for each lighting load to terminals LN1 and LN2 onthe left side of the transfer switch assembly. See Figure 10, to match switch assemblies to loads.

3. Connect a Line wire for each lighting load to terminals LL1 and LL2 on the left side of the transfer switch assembly

4. Repeat steps 2 and 3 for the other transfer switch assemblies.

Figure 11: 50 amp Transfer switch connections for Line and Neutral wires

Circuits1 & 2

Circuits3 & 4

Circuits5 & 6

Circuits7 & 8

Figure 10: 50 amp transferswitch circuit assignments

13

2

4 POLE TRANSFER SWITCH

TS1

LL1

EL1

LN1

EN1

LN2

LL2

EN2

EL2

NL1

NN

2N

N1

NL2

Line wire from dimmer

Neutral wire from dimmer

Input connections for Line and Neutral wires from the dimmer rack (Normal power)

Lighting load Neutral output wire

Prewired Emergency Line and Neutral input terminals

Lighting load Line output wire

Lighting load Line and Neutral terminals

Prewired Emergency feeds

Emergency Lighting Transfer System User Manual 15

Control and Sensing wire connectionsControl and power sensing wires connect to terminal blocks on the left side of the ELTS cabinet.

Terminals can accept from 8 to 22 AWG wires. Torque terminal screws to 18 in/lbs.

1. Install control and sensing wire conduit on the left side of the ELTS cabinet above the remote station connection terminals or below the Emergency power sensing terminals (recommended conduit location).

2. Pull the wires into the cabinet.

Connecting the Normal power sensing wiresNormal power sensing wires connect to the phase lugs of the dimmer rack connected to the ELTS. They attach to the Normal power sensing terminal block. Each sensing wire must connect to the ELTS through a 15 amp circuit breaker located outside the ELTS cabinet.

Note: Power sensing wires must be 12 AWG or larger.1. Connect a sensing wire to each phase lug of the dimmer rack connected

to the ELTS. Mark each wire to identify its phase at the ELTS rack.

2. Connect each sensing wire to a 15 amp circuit breaker close to the dimmer rack. Circuit breakers CANNOT be inside the ELTS cabinet.

3. Pull the wires from the circuit breakers through wire conduit to the Normal power sensing terminal block in the ELTS cabinet.

4. Connect the sensing wires to the Normal power sensing terminal block:

▼ Connect phase A to terminal 1 (across from wire NA)

▼ Connect phase B to terminal 3 (across from wire NB)

▼ Connect phase C to terminal 5 (across from wire NC)

Note: On single phase (three wire) systems, terminal 5 will not be used.

Connecting the Emergency power sensing wiresEmergency power sensing wires on ELTS systems with front panel circuit breaker or fuse panels are wired from the Emergency power lugs to the correct terminals on the Emergency power terminal block at the factory.

Sensing wires on systems without front panel circuit breakers must be wired into the ELTS cabinet.

Note: Emergency power sensing wires must be 12 AWG or larger.1. Connect a sensing wire to phase A and C (A and B on single phase

systems) of the Emergency power supply. Mark each wire to identify its phase at the ELTS rack.

2. Pull the wires through the conduit to the Emergency power sensing terminal block in the ELTS cabinet.

3. Connect the sensing wires to the Emergency sensing terminal block:

▼ Connect phase A to terminal 1 (across from wire NA)

▼ Connect phase C to terminal 5 (across from wire NC)

Note: On single phase (three wire) systems, connect phase B to terminal 5.

1 F1

TS11

TS29

TS30

TS10

TS12

EA

TB2

TB1

TB3

EC

G3

NA

NB

NC

A2

G2

G1

A1

F2

3

2

R3

R4

R56

5

4

3

T10

T11

T12

R2

R11

2

T8

T9

T6

T7

T3

T4

T5

T1

T2

1

3

2

6

5

4

3

1

2

6

5

4

3

1

2

9

8

6

7

4

5

3

1

2

12

11

10

9

8

6

7

4

5

3

1

2

6

5

4

3

1

2

Figure 12: Control and Sensingwire terminal connections

Door control and indicator connections (prewired)

Remote station connections

Fire alarm signal transfer

Auxiliarysignal transfer

Engine/generator start

Normal power sensing

Emergencypower sensing (prewired)

Transfer switch connections(prewired)

16 Electronic Theatre Controls, Inc.

Connecting the Engine/generator starting wiresThe ELTS system can provide both normally open and normally closed starting circuits for engine generator activation.

1. Connect two wires to the terminals of your engine/generator starting circuit.

Note: Consult your generator installation manual for start signal wiring information.

2. Pull the wires through the conduit to the engine/generator start terminal block.

3. Connect one of the starting wires to terminal 3 (across from wire G2).

4. Connect the other starting wire to terminal 1 or 5:

▼ For a closed start signal, connect the wires to terminal 1 (across from wire G1)

▼ For an open start signal, connect the wires to terminal 5 (across from wire G3)

Connecting Remote stations to the ELTSYou can connect up to 10 Remote stations to the ELTS with parallel wiring. For Remote station installation instructions see page 11.

1. Pull the Remote station wires the Remote station terminal.

2. Connect the Remote wire 1 (Common) to terminal 1

3. Connect the Remote wire 2 (Normal Select) to terminal 3

4. Connect the Remote wire 3 (Emergency Select) to terminal 2

5. Connect the Remote wire 4 (Normal indicator LED) to terminal 4

6. Connect the Remote wire 5 (Emergency indicator LED) to terminal 5

G3

G2

G1

6

5

4

3

1

2

Figure 13: Connectionsfor Engine/generator

starting wires

Closed start signal

Open start signal

Alwaysconnected

R3

R4

R56

5

4

3

R2

R11

2

Figure 14: Connectionsfor Remote stations

Remote 1

Remote 3

Remote 5

Remote 4

Remote 2

Emergency Lighting Transfer System User Manual 17

Connecting fire alarm activationYou can connect your ELTS to your fire alarm system so it switches to Emergency when the alarm is triggered. Your fire alarm system must be able to provide an open signal when it activates.

1. Connect two wires to the terminals of your fire alarm activation circuit.

2. Pull the wires through the conduit to the fire alarm terminal block.

3. Remove the shorting wire between terminal 1 and terminal 2.

4. Connect one wire to terminal 1 (across from wire F1).

5. Connect the other wire to terminal 2 (across from wire F2).

Note: If you do not use the fire alarm activation feature, leave the shorting wire in place or the ELTS will not operate properly.

Connecting auxiliary activationYou can connect your ELTS to an auxiliary circuit so it switches to Emergency when the circuit is triggered. Your auxiliary circuit must provide an open signal when it activates.

1. Connect two wires to the terminals of your auxiliary circuit.

2. Pull the wires through the conduit to the auxiliary terminal block.

3. Remove the shorting wire between terminal 1 and terminal 2.

4. Connect one wire to terminal 1 (across from wire A1).

5. Connect the other wire to terminal 2 (across from wire A2).

Note: If you do not use the auxiliary activation feature, leave the shorting wire in place or the ELTS will not operate properly.

1 F1

A2

A1

F2

3

2

1

3

2

Figure 15: Connectingfire alarm and auxiliary

circuit wires

Remove Aux. shorting wire and install Aux. circuit wires in terminals 1 and 2

Remove Fire alarm shorting wire and install Fire alarm circuit wires in terminals 1 and 2

18 Electronic Theatre Controls, Inc.

TestingBefore you power up for the first time

Checking transfer switch operation manually By checking transfer switch manual operation before you apply power, you reduce the possibility of failure caused by mechanically frozen, damaged or obstructed switches. Each switch should rotate without catching or binding.

Warning! Normal and Emergency power should be off when you open the ELTS cabinet for to check switch operation. Opening the cabinet with power applied exposes you to death or injury from electrical shock.

1. Open the ELTS cabinet.

Warning! Rotating the transfer switch assemblies manually with Normal or Emergency power applied may result in the assemblies switching automatically, causing severe hand injuries.

2. Turn the manual operation handle 90 clockwise. E (Emergency) should be visible on the assembly about 1.5 inches above the handle.

3. Rotate the handle 180 counter-clockwise. N (normal) should be visible.

Note: If you have difficulty operating the switch, check for installation debris that may be blocking switch operation.

4. Repeat steps 2 and 3 with the remaining transfer switch assemblies.

Turn on systemVoltage checkout1. Apply power to the ELTS and connected dimmer rack at the main circuit

breaker. The green Normal LED lights.

2. Apply emergency power. The red Emergency light turns on.

Warning! ELTS voltage tests should only be performed by qualified personnel using EXTREME caution. Opening the cabinet with power applied exposes you to death or injury from electrical shock.

3. Open the ELTS cabinet.

4. Use a digital voltmeter (DVM) to test the feed voltage at the Normal power sensing terminal block (Figure 12 on page 15 for location). Phase A is on terminal 1, phase B on terminal 3 and phase C on terminal 5. Voltage must be within 10 percent of the rated voltage for the ELTS.

5. Use the DVM to test the feed voltage at the Emergency power lugs. Phase lugs are labeled either A, B or C. Voltage values must be within 10percent of the rated voltage for the ELTS.

6. Close the ELTS cabinet.

Emergency Lighting Transfer System User Manual 19

Functional checkoutAfter verifying the Normal and Emergency voltages, check the ELTS system functions.

Figure 16: Local control operation and LED indications

Switch function1. Insert the key into the keyswitch on the front panel of the ELTS.

2. Turn the key to EMERGENCY POWER. The red light above EMERGENCYOPERATION turns on and the emergency loads go to full brightness. If Emergency power is provided by an engine/generator, there will be a short delay as the generator turns on and the voltage and frequency stabilize.

3. Release the key. The keyswitch returns to AUTO (center) and the EMERGENCY OPERATION light remains on.

4. Turn the key to the NORMAL POWER position. The green light below NORMAL OPERATION turns on if the system is functioning correctly.

5. Release the key. The keyswitch returns to AUTO and the NORMALOPERATION light remains on.

Remote switch functionsAfter confirming correct function of the keyswitch on the front of the ELTS cabinet, repeat the switch function checkout procedure at EVERY remote station installed on your system.

Operational Current: 200A Max 3 Phase

Electronic Theatre Controls Inc.MODEL ELTS

AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS

ISSUE NO. 934

POWERPOWER

UL1008 Listed

Operational Voltage: 120/208v (3p+N+ )Frequency: 50/60Hz.Short-circuit current: 10,000 AIC

Electronic Theatre Controls Inc.Middleton, WI Made in USA

©®®

GENERATOR

EMERGENCY POWER

FIRE ALARM

AUXILIARY

NORMAL POWER

TRANSFER SIGNAL

START

TRANSFER SIGNAL

STABLE

STABLE

EMERGENCYNORMAL AUTO

EMERGENCYOPERATION

NORMALOPERATION

Lights when Normal power is used

Keyswitch selects ELTS preference between Normal and Emergency

Lights when Emergency power is used

Lit if Normal power is acceptable

Lights when ELTS sends a Generator start signal

Lit if Emergency power is acceptable

Lights when ELTS receives a fire alarm activation

Lights when ELTS receives a auxiliary activation

20 Electronic Theatre Controls, Inc.

Automatic functionThe automatic function tests the ELTS’s ability to switch back and forth from Normal to Emergency when Normal power is interrupted or restored.

1. Make sure the NORMAL OPERATION LED is lit on the ELTS front panel.

2. Turn off the normal power to the dimmer rack connected to the ELTS. The NORMAL OPERATION and NORMAL POWER STABLE LEDs on the ELTS front panel goes out and the ELTS switches to Emergency power (the EMERGENCY OPERATION and EMERGENCY POWER STABLE LEDs light, and the emergency loads go to full brightness.) If Emergency power is provided by an engine/generator, there will be a short delay before switching as the generator turns on and the voltage and frequency stabilize.

3. Turn the Normal power back on. The ELTS switches back to Normal power after the retransfer delay times out (the default setting is one minute). On the front of the ELTS, the EMERGENCY OPERATION and EMERGENCY POWER STABLE LEDs turn off and the NORMALOPERATION and NORMAL POWER STABLE LEDs light. If used, the Emergency power engine/generator turns off when the cool down time is complete.

Options functionELTS systems can also be activated by fire alarm and auxiliary circuits. Both are operated by a normally closed circuit controlled by the fire alarm or auxiliary relays. When the fire alarm or auxiliary circuit activates, the relay opens, causing the ELTS to switch to Emergency power. To test option relay function, either:

▼ Activate the fire alarm or auxiliary relay. The ELTS should switch to Emergency power and the emergency loads should go to full.

▼ If you do not wish to activate the fire alarm or auxiliary circuit, generate an open circuit at the ELTS connection to the fire alarm or auxiliary circuit by disconnecting one of the two wires to the ELTS cabinet. The ELTS will switch to Emergency power and the emergency loads should go to full.

Note: The second method tests the ELTS response to an open circuit, but does not confirm the fire alarm or auxiliary relay’s ability to open the circuit to the ELTS.

Emergency Lighting Transfer System User Manual 21

SettingsELTS timing settings

ELTS timing settings for momentary outage override, transfer to Emergency delay, return to Normal delay, and generator cool down are set at the factory. You can adjust settings for specific applications any time after installation.

Caution: Only make changes to ELTS timing settings if you are familiar with the system and know the reason for making the change.

Table 3: ELTS timing settings

Getting access to the ELTS control panel To make adjustments, you must access the ELTS control panel.

1. Disconnect Normal and Emergency power to the ELTS.

Warning! Opening the ELTS cabinet with power on may result in death or injury from electrical shock.

2. Open the ELTS cabinet.

3. Release the two latches on the control panel cover and remove it. See Figure 17, left.

Figure 18: Adjustment potentiometer and DIP switch locations

Delay type Defaultsetting

Range DIP Switch AdjustmentPot.

Momentary Outage override

1 second 0.5 - 6 seconds P4

Transfer to Emergency delay

0 0 - 60 seconds0 - 8 minutes

SW2 upSW2 down

P2

Return to Normal delay 30 minutes 00.5 - 30 minutes

SW1 upSW1 down

P1

Generator cool down cycle

5 minutes 0 - 8 seconds0.5 - 30 minutes

SW3 upSW3 down

P3

Latch

Cover

Figure 17: Removingthe control panel cover

SW1, SW2 and SW3

Potentiometer P1

Potentiometer P2

Potentiometer P3

Potentiometer P4

22 Electronic Theatre Controls, Inc.

Changing the momentary outage overrideThe momentary outage override is the interval the ELTS will tolerate a Normal power voltage fault without switching to Emergency power. It can be set from 0.5 to 6 seconds using adjustment potentiometer P4.

1. Follow the instructions on page 21 to remove the control panel cover.

2. Locate P4 using Figure 18 : Adjustment potentiometer and DIP switch locations on page 21.

3. Turn P4 clockwise to increase the interval or counterclockwise to decrease it. P4 has a 270 adjustment range.

Note: Potentiometer adjustments change timing as a fractions of the adjustment range. For example, turning the pot half its range changes the timing value by 50%. You will need to use some trial and error and a timing device to achieve exact values.

Figure 19: Changing adjustment potentiometer settings

Changing the Transfer to Emergency delayThe Transfer to Emergency delay sets the time the ELTS waits before switching to Emergency after the Emergency power voltage and frequency stabilize. You can set the delay in two time ranges, from zero to 60 seconds or zero to 8 minutes, using DIP switch SW2 and adjustment potentiometer P2.

1. Follow the instructions on page 21 to remove the control panel cover.

2. Locate SW2 using Figure 18 : Adjustment potentiometer and DIP switch locations on page 21.

3. To select the zero to 60 second adjustment range put SW2 up. To select the zero to 8 minute range, put SW2 down.

4. Locate P2 using Figure 18 : Adjustment potentiometer and DIP switch locations on page 21.

5. After setting the range, turn P2 clockwise to increase the interval or counterclockwise to decrease it. P2 has a 270 adjustment range.

Clockwise to increase

Counterclockwise to decrease

•1 •2 •3 •4

SW 1 2 3

• • • •

DIP switch inUp position

DIP switch inDown position

Figure 20: Setting DIPswitches

Emergency Lighting Transfer System User Manual 23

Changing the Return to Normal delayThe Return to Normal delay sets the time the ELTS waits before switching from Emergency to Normal after Normal power is restored. The delay can be turned off, or set from 0.5 to 30 minutes using DIP switch SW1 and adjustment potentiometer P1.

Note:To disable the delay on a one-time basis (to quickly restart an interrupted performance or for testing purposes) switch the ELTS back to Normal with the front panel Local switch or a Remote keyswitch station.

1. Follow the instructions on page 21 to remove the control panel cover.

2. Locate SW1 using Figure 18 : Adjustment potentiometer and DIP switch locations on page 21.

3. To turn off the delay put SW1 up. To set the range from 0.5 to 30 minutes, put SW1 down.

4. If SW1 is down, locate P2 using Figure 18 : Adjustment potentiometer and DIP switch locations on page 21.

5. Turn P2 clockwise to increase the interval or counterclockwise to decrease it. P2 has a 270 adjustment range.

Changing the Generator cool down intervalThe Generator cool down interval sets the time the ELTS waits before shutting off the Emergency power generator after switching back to Normal power. It can be set from zero to 8 seconds or 0.5 to 30 minutes using DIP switch SW3 and adjustment potentiometer P3.

Caution: Consult your generator user manual for proper cool down times before changing the Generator cool down interval.

1. Follow the instructions on page 21 to remove the control panel cover.

2. Locate SW3 using Figure 18 : Adjustment potentiometer and DIP switch locations on page 21.

3. To make the adjustment range zero to 8 seconds put SW3 up. To make the range 0.5 to 30 minutes, put SW3 down.

4. Locate P3 using Figure 18 : Adjustment potentiometer and DIP switch locations on page 21.

5. After setting the range, turn P3 clockwise to increase the interval or counterclockwise to decrease it. P3 has a 270 adjustment range.

24 Electronic Theatre Controls, Inc.

ELTS voltage and frequency settingsVoltage and frequency settings are set at the factory and should only be adjusted by an authorized ETC representative.

Caution: Indiscriminate changes to voltage and frequency sensing settings may affect normal operation of the ELTS and result in switching function failure.

Table 4: 120 volt ELTS voltage and frequency settings

Table 5: 277 volt ELTS voltage and frequency settings

Description Factory setting Adjustment range

Normal source voltage pickup 108 volts 102 – 120 volts

Normal source voltage dropout 102 volts 81 – 106 volts

Emergency source voltage pickup 108 volts 102 – 120 volts

Emergency source voltage dropout 92 volts No adjustment: 15% below pickup setting

Emergency source frequency pickup 57 hertz 57 – 60 hertz

Emergency source frequency dropout 50 hertz No adjustment: 12% below pickup setting

Description Factory setting Adjustment range

Normal source voltage pickup 249 volts 235 - 277 volts

Normal source voltage dropout 235 volts 187 - 244 volts

Emergency source voltage pickup 249 volts 235 – 277 volts

Emergency source voltage dropout 212 volts No adjustment: 15% below pickup setting

Emergency source frequency pickup 57 hertz 57 – 60 hertz

Emergency source frequency dropout 50 hertz No adjustment: 12% below pickup setting

Emergency Lighting Transfer System User Manual 25

OperationAutomatic operation

During automatic operation the ELTS system switches back and forth from Normal to Emergency when either power supply is interrupted or restored.

Figure 21: Local control LED indications

Selecting the preferred power source: Normal or EmergencyUsing the local keyswitch on the front of the ELTS cabinet or a Remote keyswitch station installed in your facility, you can select either Normal or Emergency as the preferred power source.

1. Insert the key into the keyswitch and select the desired power source:

▼ To select Normal power, turn the key left. The green NORMALOPERATION LED lights.

▼ To select Emergency power, turn the key right. The red EMERGENCYOPERATION LED lights and the emergency loads go to full. If Emergency power is provided by an engine/generator, there will be a short switching delay as the generator turns on and voltage and frequency stabilize.

2. Release the key. The keyswitch returns to center and the indicator light you selected remains on. The ELTS uses the selected power source. If the selected source’s voltage or frequency drops below the limit, the ELTS will switch to the other source.

3. When the voltage and frequency of the selected source returns to acceptable levels, the ELTS will switch back to it.

Remote StationRemote Keyswitch station operation is identical to the local station. Refer to Selecting the preferred power source: Normal or Emergency for instructions.

Fire alarm or Aux signal switchingIf desired, the ELTS system can be activated by fire alarm or auxiliary circuits. When the ELTS receives the fire alarm or auxiliary circuit activation, it will switch to Emergency power.

Note: If you have selected Emergency as the preferred power with either the Local or Remote keyswitch, the ELTS will not switch power sources after receiving a fire alarm or auxiliary activation.

Operational Current: 200A Max 3 Phase

Electronic Theatre Controls Inc.MODEL ELTS

AUTOMATIC TRANSFER SWITCH FOR EMERGENCY SYSTEMS

ISSUE NO. 934

POWERPOWER

UL1008 Listed

Operational Voltage: 120/208v (3p+N+ )Frequency: 50/60Hz.Short-circuit current: 10,000 AIC

Electronic Theatre Controls Inc.Middleton, WI Made in USA

©®®

GENERATOR

EMERGENCY POWER

FIRE ALARM

AUXILIARY

NORMAL POWER

TRANSFER SIGNAL

START

TRANSFER SIGNAL

STABLE

STABLE

EMERGENCYNORMAL AUTO

EMERGENCYOPERATION

NORMALOPERATION

Keyswitch selects ELTS preference between Normal and Emergency

Lit if Normal power is acceptable

Lights when ELTS sends a Generator start signal

Lit if Emergency power is acceptable

Lights when ELTS receives a fire alarm activation

Lights when ELTS receives a auxiliary activation

Lights when Normal power is used

Lights when Emergency power is used

26 Electronic Theatre Controls, Inc.

Switching power sources manuallyIf you need to switch the ELTS from one power source to another when the electronic switching circuits will not function (for example, if you needed to use either Normal or Emergency power, but the voltage or frequency was below the limit) you can set the transfer switch assemblies manually.

1. Disconnect Normal AND Emergency power.

Warning! Turn off Normal and Emergency power to the ELTS at the main circuit breaker.Opening the cabinet with power applied exposes you to death or injury from electrical shock.

2. Open the ELTS cabinet.

3. Disconnect the large brown connector on the lower left side of the control panel.

Figure 22: Removing the control panel connector

Warning! Operating switch assemblies manually without disconnecting the control panel connector may result in the assemblies switching back automatically, causing severe hand injuries.

▼ To switch from Normal to Emergency power: Turn the manual operation handle on the bottom of each transfer switch assembly 90 clockwise. E (Emergency) should be visible just above the handle.

▼ To switch from Emergency to Normal: Turn the manual operation handle on the bottom of each transfer switch assembly 90 counter-clockwise. N (normal) should be visible just above the handle.

4. Close the cabinet door and restore power to the ELTS.

Note: Do not plug the control panel connector back in until you want the ELTS to resume automatic operation.

Restoring automatic operation1. Disconnect Normal AND Emergency power.

Warning! Turn off Normal and Emergency power to the ELTS at the main circuit breaker.Opening the cabinet with power applied exposes you to death or injury from electrical shock.

2. Open the ELTS cabinet.

3. Reconnect the large brown connector on the lower left side of the control panel.

4. Close the cabinet door and restore power to the ELTS.

CONTROL PANEL

ASCO GROUP 9

Squeeze the release tabs on both sides of the socket together and pull the plug out

Emergency Lighting Transfer System User Manual 27

ServicePreventive maintenance

Regular testing and simple maintenance of your ELTS system will result in long service life and reliable performance. To assist in documenting your test and maintenance schedule, a blank Test and Maintenance Log is included on page 35. We suggest you post a copy near your ELTS cabinet.

Warning! Turn off Normal and Emergency power to the ELTS at the main circuit breaker.Opening the cabinet with power applied exposes you to death or injury from electrical shock.

Warning! Rotating the transfer switch assemblies manually with Normal or Emergency power applied may result in the assemblies switching automatically, causing severe hand injuries.

Monthly testing1. Manually test the ELTS’s transfer function at the local keyswitch on the

front of ELTS cabinet. See Switch function on page 19 for keyswitch instructions and indications.

2. Note the test results in the test and maintenance log.

Quarterly testing and maintenance1. Manually test the ELTS’s transfer function at the local keyswitch on the

front of ELTS cabinet. See Switch function on page 19 for keyswitch instructions and indications.

2. Test the ELTS Auto transfer function. See Automatic function on page 20 for automatic transfer instructions and indications.

3. Visually inspect the ELTS cabinet for loose wires or component damage.

4. Note the test results in the test and maintenance log.

Annual testing and maintenance1. Manually test the ELTS’s transfer function at the local keyswitch on the

front of ELTS cabinet. See Switch function on page 19 for keyswitch instructions and indications.

2. Test the ELTS Auto transfer function. See Automatic function on page 20 for automatic transfer instructions and indications.

3. Visually inspect the ELTS cabinet for loose wires or component damage.

4. Retighten ELTS phase, neutral and ground lugs using values in Table 1 :Emergency power lug wire sizes and connection torques on page 12.

5. Vacuum the ELTS cabinet to remove dust and debris that may have collected.

6. Note the test results in the test and maintenance log.

28 Electronic Theatre Controls, Inc.

TroubleshootingIf you have trouble with an installed ELTS system, you can contact ETC Technical Service at 800/775-4382.

Warning! Trouble shooting usually involves opening the ELTS cabinet and metering voltages. Opening the ELTS cabinet with power applied exposes you to death or injury from electrical shock. Use extreme caution during all troubleshooting activities.

Emergency or Normal Power Stable LED does not turn on properlyDuring normal operation, either the Normal Power Stable or Emergency Power Stable LED should be lighted. If one or the other does not light, the problem may be with the LED, Normal or Emergency sensing wiring, or Normal or Emergency power.

1. Switch between Normal and Emergency power on the ELTS control panel keyswitch and observe the results. The ELTS should switch between Normal and Emergency power.

▼ The ELTS switches between Normal and Emergency

1. Check for loose LED wire connections or defective LEDs.

2. Make sure the Control Panel connector is properly seated.

▼ The ELTS does not switch between Normal and Emergency. Go to the next ELTS troubleshooting section.

The ELTS will not switch between Normal and EmergencyIf the system will not switch from Emergency power1. check for tripped Normal power sensing wire circuit breakers.

2. If the circuit breakers are not tripped, meter Normal power using the procedures in Voltage checkout on page 18.

If the system will not switch from Normal power1. Meter Emergency power using the procedures in Voltage checkout on

page 18.

2. If no fire alarm or auxiliary circuits are connected to the ELTS, make sure the terminal jumpers are in place.

3. If fire alarm or auxiliary circuits are connected, meter between the wires to be certain the circuit is closed. An open circuit switches the ELTS to Emergency power.

If the system does not seem to function in either Normal or Emergency power mode1. Make sure the control panel connector is properly seated.

2. Check other wire connections for loose terminals or broken wires.

3. Use the procedures in Checking transfer switch operation manually on page 18 to test the switching mechanism for mechanical problems.

Emergency Lighting Transfer System User Manual 29

Remote stations cannot switch the ELTS 1. Switch between Normal and Emergency power on the ELTS control panel

keyswitch and observe the results.

If the ELTS does not switch locallyFollow the instructions in The ELTS will not switch between Normal and Emergency on page 28.

If the ELTS switches locallyTry switching the ELTS from other Remote station, if multiple stations have been installed

1. If the other stations function, check the wire terminal connections on the problem station. See Installing Remote stations (optional) on page 11 for station connection requirements.

2. If the other stations do not function, or there is only one Remote station installed.

3. Check the wire connections on the Remote station terminal block.

4. Check the Remote station fuse in the ELTS cabinet

Figure 23: Locating the Remote station fuse5. Inspect the wiring between the ELTS cabinet and the stations for defects.

See Connecting Remote stations to the ELTS on page 16 for ELTS connection requirements.

Some ELTS circuits do not switch when the system changes sourcesPartial switching of ELTS circuits indicates one or more transfer switch assemblies, or the wiring to them, is defective.

1. Use the procedures in Checking transfer switch operation manually on page 18 to locate any transfer switch assemblies that have not switched and to manually test their function.

2. If an assembly cannot be switched manually, check for something that could be physically obstructing it. If you find something, remove it and manually test the switch again. If you cannot find and remove the cause of the switching failure, the assembly is defective and must be replaced.

3. If the assembly switches manually, check for loose wire connections to the assembly and look for damaged wires between the assembly and the control panel. Repair any wire problems you find and test the system.

SR3BSR3BSR3B SR3B

Remove this cover on the left side of the Isolation relays to check the Remote station fuse

30 Electronic Theatre Controls, Inc.

Appendix A: ELTS specificationsDimensions

Small cabinet: ELTS 450, ELTS 620, ELTS122036" x 30" x 9" Large cabinet: ELTS 850, ELTS 1820, ELTS 242054" x 30" x 9"

WeightELTS 450, ELTS 620, ELTS1220 – 305 poundsELTS 850, ELTS 1820, ELTS 2420 – 370 pounds

ElectricalOperational voltage

120/240V single phase 250 amp maximum120/208V three phase 175 amp maximum277/480V three phase 175 amp maximumFrequency: 50 – 60HzShort circuit current: 10 kA @ 120/240V

100,000 kA @ 277/480V(5 kA with 50 amp circuit breakers)

Electrical Compliance▼ ANSI/UL 1008 – Listed, Automatic Transfer Switches

▼ ANSI/NFPA 110 – Emergency and Standby Power Systems

▼ ANSI/NFPA 70 – National Electric CodeArticle 701 – Legally Required Standby SystemsArticle 700 – Emergency SystemsArticle 540 –11(c) – Motion Picture HousesArticle 520 – 7 – Theatres and Similar LocationsArticle 518 – 3(c) – Places of Assembly

▼ City of New York, Advisory board, Electrical Department

▼ OSHA

▼ Department of Defense

EnvironmentAmbient temperature between 32 F and 104 F (0 C and 40 C)Humidity between 30 and 95 percent (non-condensing)Altitude below 6500 feet (2000 meters)

Emergency Lighting Transfer System User Manual 31

Appendix B: Wire connection schematics and diagramsWire connection schematics and diagrams are included to help you understand the internal wiring of your ELTS system.

Figure 24: ELTS cabinet wire connection location diagram

#12 WIRE

NØCØBØA

INCOMING POWER

1 2 3 4 531311 62 4 2 24 4

POW

ER T

B

T3 T4 T4T4

N

T2

N

T2

N

T2

T4T4T4T3 T3T3

N

T1

N

T2

N

T2

N

T2

N

T1

N

T1

N

T1

A

11

41 42393633 T3 T3

C

19

C

22

N

T1

N

T1

B

21

C

16

C

13

383532

B

18

B

15

B

12

AAA

3

31 403734

201714

G

GND

LUG

10 9 8 7 6 45 3 2 1

+

+

PS

3

53

F2

1

4

53

T9

1

6

62

2

61

EC

1

EA

1

NC

1

NA

1

52 52 52 52

CP1CP2CP3CP4CP5CP6CP7CP8CP9CP10CP11CP12CP13CP14CP15CP16CP17CP18

CONTROL PANEL

CP-PLUG24

20

16

12

8

4

23

19

15

11

7

3

22

18

14

10

6

2

21

17

13

9

5

1

G11R41R51151G31EC51EA5120691769

19 69NB 1NA 51EA 69G2 118 1NC 51

13

65

T5

1

3

51

4

51

T4

1

7

62

T10

1

T1

1

T8

1

T7

1

CT1

CT2

CT3

CT4

CT5

CT6

CT7

CT8

CT9

CT10

CT11

CT12

CT13

CT14

CT15

CT16

CT17

CT18

CT19

CT20

6 3 5 2 4 1

B 9 8 7 A

6 3 5 2 4 1

B 9 8 7 A

6 3 5 2 4 1

B 9 8 7 A

6 3 5 2 4 1

B 9 8 7 A TR

A1

A2

13

14

51

52

23

24

61

62

33

34

71

72

43

44

81

82D1

X2

X11

X3

D2

X4

X12

X5

D3

X6

X13

X7

24VDCFUSE

5

19

52

EA

1

NA

1

NC

1

17

52

EC

1

20

52

1

1

16

1

R1

61

8

63

T2

1

14

62

T3

1

10

63

T6

1

R3

1

R2

1

2

51

R1

1

52

14

67

10

63

6

51

6

63

10

62

8

66

6

62

6

64

F1

1

12

65

6

63

6

65

A1

1

12

64

6

64

9

63

7

53

9

62

11

64

11

63

T11

1

13

53

T12

1

CR1 CR2 CR3 CR4

6668

123456789101112

TBT110 53T210 67T310 68T49 53T58 53T64 66T73 53T84 53T97 51T105 53T116 64T127 65

STATION (RC)REMOTE CONTROL

TO CUSTOMER

654321 R1 61

R2 67R3 68R4 1R5 1

5252

FACTORY JUMPER

TO CUSTOMERFIRE ALARM CNTRL.

STATION (FA)

TO CUSTOMERAUX. STATION

(AS)

REMOVEAS REQUIRED

3

3

12

12

F1 64F2 51

A1 65A2

TO ENGINEGENERATOR

CONTROL

123456

G1 52

G2 52

G3 521

1

123456

NA 69

NB 52

NC 6951

51

TO CUSTOMER"NORMAL"

MAIN PANEL

TO CUSTOMER"EMERGENCY"

BRANCH PANEL 321

456

EA 69

EC 69

51

51

1 6918 5216 6915 52G2 1G3 1R5 1R4 1

TB1T1TB2T1TB3T1TS11T4TS29T1TS30T1TS10T1TS12T1

123456789

TRANSFER SWITCH12 POLE

LOADSNORMALSOURCE

#12

WIR

E

NTB

LL5

LL2

LL1LN1

LN4

LN3LL3

LL4

LN2

LN6

LN5LL6

NTB

NTB

TB1TB2TB3

NTB

NTB

NTBEL1 NL1

EN1 NN1

EL2 NL2

EN2 NN2

EL3 NL3

EN3 NN3

EL4 NL4

EN4 NN4

EL5 NL5

EN5 NN5

EL6 NL6

EN6 NN6

TB2

TB3

TB1

2931 12 11 10 3230 13

TRANSFER SWITCH12 POLE

LOADSNORMALSOURCE

#12

WIR

E

NTB

LL5

LL2

LL1LN1

LN4

LN3LL3

LL4

LN2

LN6

LN5LL6

NTB

NTB

TB1TB2TB3

NTB

NTB

NTBEL1 NL1

EN1 NN1

EL2 NL2

EN2 NN2

EL3 NL3

EN3 NN3

EL4 NL4

EN4 NN4

EL5 NL5

EN5 NN5

EL6 NL6

EN6 NN6

TB2

TB3

TB1

2931 12 11 10 3230 13

TO LAMP

TRANSFER SWITCH12 POLE

LOADSNORMALSOURCE

#12

WIR

E

NTB

LL5

LL2

LL1LN1

LN4

LN3LL3

LL4

LN2

LN6

LN5LL6

NTB

NTB

TB1TB2TB3

NTB

NTB

NTBEL1 NL1

EN1 NN1

EL2 NL2

EN2 NN2

EL3 NL3

EN3 NN3

EL4 NL4

EN4 NN4

EL5 NL5

EN5 NN5

EL6 NL6

EN6 NN6

TB2

TB3

TB1

2931 12 11 10 3230 13

TRANSFER SWITCH12 POLE

LOADSNORMALSOURCE

#12

WIR

E

NTB

LL5

LL2

LL1LN1

LN4

LN3LL3

LL4

LN2

LN6

LN5LL6

NTB

NTB

TB1TB2TB3

NTB

NTB

NTBEL1 NL1

EN1 NN1

EL2 NL2

EN2 NN2

EL3 NL3

EN3 NN3

EL4 NL4

EN4 NN4

EL5 NL5

EN5 NN5

EL6 NL6

EN6 NN6

TB2

TB3

TB1

2931 12 11 10 3230 13

TO LAMP

BACKWALL

TO LAMP

T2 T2

TS12

1TS

291

TS1B

T2TS

101

TS30

1TS

1AT2

TS1A

T1TS

29T1

TS2B

T3TS

1BT1

TS30

T1TS

2AT3

T3 T3

TO LAMP

TS3A

TS29

TS3B

TS30

TS11

TS616

TS515

TS414

TS313

TS212

TS111

TS11222

TS11121

TS11020

TS919

TS818

TS717

TS1836

TS1735

TS1634

TS1533

TS1432

TS1331

TS2442

TS2341

TS2240

TS2139

TS2038

TS1937

111

T2T2T2 T2

T1

T2T2

T1T1

T4T2

T4T4

T2T2

T3T3T3

TS2A

T2TS

29T2

TS3B

T4TS

2BT2

TS30

T2TS

3AT4 T3 T3 T3 T3 1

T4 T4

32 Electronic Theatre Controls, Inc.

Figure 25: ELTS door panel and breaker bracket wire connection schematics

Figure 26: Transfer switch assembly control wire connections schematic

#12 WIRE

#12 WIRE

#12 WIRE

#12 WIRE

A

TB

B

TB

C

TB

A

TB

B

TB

C

TB

A

TB

B

TB

C

TB

A

TB

B

TB

C

TB

A

TB

B

TB

C

TB

A

TB

B

TB

C

TB

A

TB

B

TB

C

TB

A

TB

B

TB

C

TB

TS1

T1

TS2

T1

TS3

T1

TS4

T1

TS5

T1

TS6

T1

TS7

T2

TS8

T2

TS9

T2

TS10

T2

TS11

T2

TS12

T2

TS13

T3

TS14

T3

TS15

T3

TS16

T3

TS17

T3

TS18

T3

TS19

T4

TS20

T4

TS21

T4

TS22

T4

TS23

T4

TS24

T4

CB15CB14CB13 CB24CB20CB19CB18CB16 CB17 CB23CB21 CB22

CB1 CB2 CB3 CB4 CB5 CB6 CB7 CB8 CB9 CB10 CB11 CB12

Breaker bracket schematicDoor panel schematic

KEYSWITCH CIRCUIT

T7 1

T6 4

T8 1

T6 13

T10 1

T9 6

T11 1

T9 75

T12 1

T9 16

T5 1

T1 109

T4 1

T1 8

T2 1

T3 1

T118

NORMAL POWERSTABLE

G

EMERGENCY POWERSTABLE

G

GENERATORSTART

G

FIRE ALARMTRANSFER SIGNAL

R

AUXILIARYTRANSFER SIGNAL

R

EMERGENCYOPERATION

R

NORMALOPERATION

G

ENA

29

3032

3111

1012

1329

30

31

32

11

1012

13

TB1 TB2 TB3

T2T1

TB3TB2TB1

T3

TB3TB2TB1

13

12 10

11 31

32 30

29

T4

TB3TB2TB1

13

12 10

11 31

32 30

29

SEE CONTROL SCHEMATIC DIAGRAM

FACTORY CONNECTIONS

1

2

3

4

5

6

7

TB1

TB2

TB3

TS11

TS29

TS30

TS10

TO CONTROL MODULE

TERMINAL BLOCK8 TS12

TS1A

TS1B TS2B

TS2A

TS3B

TS3A

TB1

TB2

TB3

TS11

TS12

TS10

TS30

TS29

Emergency Lighting Transfer System User Manual 33

Appendix C: Transfer switch control system schematics

R

G

R

G

G

G

RCR4

1 7CR3

1 7

CR3

CR4

9

1

TR

52 51

S6

S2

CR2

9 6

CR1

3 9

NR

NR

CR1

CR2

TR

24 23

CR3

9 6

CT18

CT9

CT8

CT19

CT12

CT2

CT7

7 5

CT16

CT1

CT17

CT15

CT11

NR

CT10

CT14

CT3

CT4

CR4

6 9

CT6

10 8

3

TR

13 14

S2

S3

S4 S1

S5

S6

4

CR2

1 7

CR1

4 7

6

TR

61 62

2

S1 S4

S5

S3

TR

34 33

TR

SE

SE

SE

SE

ER

ER

JMPR

2

JMPR

3 4 6

+

X3

7

INTERNAL JUMPER

NORM.

(KEY OPER)

N A E

REMOTE CONTROL STATION (RC)

ENGINE-GENERATOR

N

E

R1

R2

R3

G

R

N

E R5

R4

T1

SS

PL1

T3

T2

T4

OPEN CONTACTS

CLOSED CONTACT

FROM NORMAL MAIN PANEL

CONTROL

TO

R1

R2

R3

R1

R3

R2

NORMALLY

NORMALLY

COMMANDSTART-RUNENGINE-GEN.

R4

R5

T1

R4

R5

T1

T2

T3

T4

T3

T2

T4

FIRE ALARM STATION (FA)

AUXILIARY STATION (AS)

LOCAL DIAGNOSTIC PNL. (LD)

EMERG.

LOCAL CONTROL STATION (LC)

NORMAL POWER

EMERG POWER

GENERATOR

TRANSFER SIGNALFIRE ALARM

TRANSFER SIGNALAUXILIARY

STABLE

STABLE

START

AUX T12

E

PL2

N

T5

T6

T7

FIRE

GEN T10

T9

T8

T11

REMOVE AS REQUIREDFACTORY JUMPERS

A1

A2

F2

F1

T12

T5

T6

T7

T5

T7

T8

T9

T10

T11

T10

T9

T8

T11

T12

A1

A2

A1

F1

F2

F1

F2

B A

B A

PS

NA

X11

X6

X2

X13

X4

X12

DRAWING

DRAWING

G2

G3

G1

NB

G3

G2

G1

NB

D2

D1

D3

THIS

THIS

NC

NA

X5

X7

8

14

9MANUAL RELAY

MANUAL RELAY

NC SENSE

NA SENSE

NB SENSE

CP8

CP9

CP17

CP11

CP14

CP13

CP4

CP12

TS-NC

TS-NO

B A

B A10

RETRANSFER

TRANSFER

INTERNAL JUMPER

( 24 Vdc OUTPUT )

TEST-NC

TEST-EMG

TS-NORM

N-OK

E-OK

TS

NR

FUSEFAULTSTATIONCONTROLREMOTE

X10

X1

5A

+ +

GND

INHIBIT

+24VDC

ET-NC

GND

BYPASS

MAN-X

DELAY

GND

13 12

TEST-NC

CP

- -

FROM NORMAL MAIN PANEL208 VAC CKT.

( 208 VAC INPUT )

DRAWING

208 VAC CKT.

DUAL INPUT POWER SUPPLY

FROM EMERGENCY BRANCH PANEL

20

EA

THIS

EC

ISOLATION RELAY

ISOLATION RELAY

11

AUX. STATION

FIRE ALARM

-

1

NC

SCHEMATIC DIAGRAMSEE TRANSFER SWITCHTO TRANSFER SWITCH(ES)FACTORY CONNECTION

DRAWING

DRAWING

DRAWING1TB1

DRAWINGTHIS

TB2

TB3

TS29

TS11

TS30

TS10

TS12

THIS 20

16

THIS

THIS

18

17

15

ECA2 A1

19

EA

CONTROL PANEL

CP2

EA SENSE

EC SENSE

CP3

CP1

CP6

CP10 TS-COM

CP16

CP15

CP5

CP7

T6

- DIODE BLOCKS

- SELECTOR SWITCH, KEY OPERATED

- CONNECTION POINT

- TRANSFER SWITCH TERMINAL CONNECTION

- CONNECTOR PLUG TO CONTROL PANEL- TERMINAL BLOCK

- TRANSFER RELAY- POWER SUPPLY- CONTROL RELAY- CONTROL PANEL

- INDICATING LIGHT

D1- D3

SS

TRPS

CR1- CR4

PL1- PL7

EXPLANATION:CP

XXS1

34 Electronic Theatre Controls, Inc.

Appendix D: Transfer switch load switching schematic

- +

NORMAL SOURCECIRCUIT 4

EMERG. SOURCE

NORMAL SOURCENL1

EMERG. SOURCE

20ACB1

L

TS1

ØA

CIRCUIT 1 CIRCUIT 2 CIRCUIT 3

12 POLE UNIT

N

E

LOADCIRCUIT 2

N

E

N

NN1

E

L

LL1

CIRCUIT 1

LN1

LOAD

TS2

NORMAL SOURCENL2

N

E

L

NN2

L

20ACB2

LL2

EMERG. SOURCE

N ØB N

NORMAL SOURCE

CIRCUIT 3

LL3

N

E

NL3

L

20ACB3

LN2

TS3

NN3

N

E

L

NL4

N

E

L

LN3

LOAD

TS4

20ACB4

EMERG. SOURCE

ØC N ØA

CIRCUIT 5 CIRCUIT 6

L

EMERG. SOURCE

NORMAL SOURCE

20ACB5

NN4

N

E

L

NL5

N

E

L

LN4

CIRCUIT 4

LL4

LOAD

TS5

NN5

L

N

E

LOADCIRCUIT 5

LL5 LN5

TS6

EMERG. SOURCE

N ØB N

CIRCUIT 6

LN6

NORMAL SOURCENL6

N

E

NN6

N

L

E

20ACB6

LL6

LOAD

NØC

29

11

10

30

TS1

TS1

TS1

32

12

13

31

#12 WIRE

TB3TB1 TB2

9

872

71

B

ATS1

69

70

CKT

AC2

COIL

-

AC1REC+

7

6

#12 #12 #12#12#12#12

CIRCUIT 2CIRCUIT 1 CIRCUIT 3 CIRCUIT 4 CIRCUIT 5 CIRCUIT 6

NORMAL SOURCECIRCUIT 10

EMERG. SOURCE

NORMAL SOURCENL7

EMERG. SOURCE

20ACB7

L

TS7

ØA

CIRCUIT 7 CIRCUIT 8 CIRCUIT 9

12 POLE UNIT

N

E

LOADCIRCUIT 8

N

E

N

NN7

E

L

LL7

CIRCUIT 7

LN7

LOAD

TS8

NORMAL SOURCENL8

N

E

L

NN8

L

20ACB8

LL8

EMERG. SOURCE

N ØB N

NORMAL SOURCE

CIRCUIT 9

LL9

N

E

NL9

L

20ACB9

LN8

TS9

NN9

N

E

L

NL10

N

E

L

LN9

LOAD

TS10

20ACB10

EMERG. SOURCE

ØC N ØA

CIRCUIT 11 CIRCUIT 12

L

EMERG. SOURCE

NORMAL SOURCE

20ACB11

NN10

N

E

L

NL11

N

E

L

LN10

CIRCUIT 10

LL10

LOAD

TS11

NN11

L

N

E

LOADCIRCUIT 11

LL11 LN11

TS12

EMERG. SOURCE

N ØB N

CIRCUIT 12

LN12

NORMAL SOURCENL12

N

E

NN12

N

L

E

20ACB12

LL12

LOAD

NØC

29

11

10

30

TS2

TS2

TS2

32

12

13

31

#12 WIRE

TB3TB1 TB2

9

872

71

B

ATS1

69

70

CKT

AC2

COIL

-

AC1REC+

7

6

#12 #12 #12#12#12#12

CIRCUIT 8CIRCUIT 7 CIRCUIT 9 CIRCUIT 10 CIRCUIT 11 CIRCUIT 12

NORMAL SOURCECIRCUIT 15

EMERG. SOURCE

NORMAL SOURCENL13

EMERG. SOURCE

20ACB13

L

TS13

ØA

CIRCUIT 13 CIRCUIT 14 CIRCUIT 14

12 POLE UNIT

N

E

LOADCIRCUIT 14

N

E

N

NN13

E

L

LL13

CIRCUIT 13

LN13

LOAD

TS14

NORMAL SOURCENL14

N

E

L

NN14

L

20ACB14

LL14

EMERG. SOURCE

N ØB N

NORMAL SOURCE

CIRCUIT 15

LL15

N

E

NL14

L

20ACB15

LN14

TS15

NN14

N

E

L

NL15

N

E

L

LN15

LOAD

TS15

20ACB15

EMERG. SOURCE

ØC N ØA

CIRCUIT 16 CIRCUIT 17

L

EMERG. SOURCE

NORMAL SOURCE

20ACB16

NN15

N

E

L

NL16

N

E

L

LN16

CIRCUIT 16

LL16

LOAD

TS16

NN16

L

N

E

LOADCIRCUIT 17

LL17 LN17

TS17

EMERG. SOURCE

N ØB N

CIRCUIT 18

LN18

NORMAL SOURCENL17

N

E

NN17

N

L

E

20ACB17

LL18

LOAD

NØC

29

11

10

30

TS3

TS3

TS3

32

12

13

31

#12 WIRE

TB3TB1 TB2

9

872

71

B

ATS1

69

70

CKT

AC2

COIL

-

AC1REC+

7

6

#12 #12 #12#12#12#12

CIRCUIT 14CIRCUIT 13 CIRCUIT 15 CIRCUIT 15 CIRCUIT 16 CIRCUIT 17

NORMAL SOURCECIRCUIT 22

EMERG. SOURCE

NORMAL SOURCENL19

EMERG. SOURCE

20ACB19

L

TS19

ØA

CIRCUIT 19 CIRCUIT 20 CIRCUIT 21

12 POLE UNIT

N

E

LOADCIRCUIT 20

N

E

N

NN19

E

L

LL19

CIRCUIT 19

LN19

LOAD

TS20

NORMAL SOURCENL20

N

E

L

NN20

L

20ACB20

LL20

EMERG. SOURCE

N ØB N

NORMAL SOURCE

CIRCUIT 21

LL21

N

E

NL21

L

20ACB21

LN20

TS21

NN21

N

E

L

NL22

N

E

L

LN21

LOAD

TS22

20ACB22

EMERG. SOURCE

ØC N ØA

CIRCUIT 23 CIRCUIT 24

L

EMERG. SOURCE

NORMAL SOURCE

20ACB23

NN22

N

E

L

NL23

N

E

L

LN22

CIRCUIT 22

LL22

LOAD

TS23

NN23

L

N

E

LOADCIRCUIT 23

LL23 LN23

TS24

EMERG. SOURCE

N ØB N

CIRCUIT 24

LN24

NORMAL SOURCENL24

N

E

NN24

N

L

E

20ACB24

LL24

LOAD

NØC

29

11

10

30

TS4

TS41

TS4

32

12

13

31

#12 WIRE

TB3TB1 TB2

9

872

71

B

ATS1

69

70

CKT

AC2

COIL

-

AC1REC+

7

6

#12 #12 #12#12#12#12

CIRCUIT 20CIRCUIT 19 CIRCUIT 21 CIRCUIT 22 CIRCUIT 23 CIRCUIT 24

Emergency Lighting Transfer System User Manual 35

Appendix E: Test and Maintenance LogDate installed ___________________________________________

System address _________________________________________

________________________________________________________

Service contact __________________________________________

Date Inspected by Manual transfer Automatic transfer Visual inspection Vacuumed

Americas 3030 Laura Lane, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA Tel: +608 831 4116 +800 688 4116 Fax: +608 836 1736 +800 555 8912Europe Unit 5, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK Tel: +44 (0)20 8896 1000 Fax: +44 (0)20 8896 2000Asia Room 605-606, Tower III Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong Tel: +852 2799 1220 Fax: +852 2799 9325Web: www.etcconnect.com Email: (US) [email protected] (UK) [email protected] (Asia) [email protected]: [email protected] Toll free: 800 775 4382 Comments about this document: [email protected] © 2003 Electronic Theatre Controls, Inc. All Rights Reserved. Product information and specifications subject to change.1093M1101 Rev C Released 01/2003