DC earth leakage monitors
ELM 25 and ELM 125
For earth leakage protection in d.c. distribution systems
25 A, sensitivity 5 or 20 mA
125 A, sensitivity 20 or 100 mA
The ELM principle of operation is based on current balance monitoring
of the conductors in a DC system. The monitor reacts on the residual
magnetic field that is formed when an earth fault occurs, and a differential
current is produced.
see page 8
see page 8
dimensions
techn. data
Characteristics
Rapid fault location by earth leakage detection in every outgoing group;
LED fault signalling;
High detection sensitivity;
Low power consumption;
Manual or automatic reset;
Small dimensions.
Earth leakage monitors type ELM 25
I
I
n
I
U
e
I
I
I
type
I
packing
I
Holec no.
I
ref. no.
quantity
25 A 24 - 48 V 5 mA ELM 25 1 1341 033 21285 5
25 A 24 - 48 V 20 mA ELM 25 1 1341 034 29285 7
25 A 110 - 220 V 5 mA ELM 25 1 1341 035 38285 5
25 A 110 - 220 V 20 mA ELM 25 1 1341 036 62285 2
Earth leakage monitors type ELM 125
125 A 24 - 48 V 20 mA ELM 125 1 1341 037 50285 7
125 A 24 - 48 V 100 mA ELM 125 1 1341 038 71285 0
125 A 110 - 220 V 20 mA ELM 125 1 1341 039 77285 4
125 A 110 - 220 V 100 mA ELM 125 1 1341 040 85285 3
DC
e
arth
-le
ak
ag
e m
on
ito
rs ty
pe
E
LM
7
Technical data and dimensions
DC earth-leakage monitors
ELM 25 ELM 125
U
n
24 - 48 V / 110 - 220 V max. 500 V
- 24 - 48 V / 110 - 220 V
I
n
25 A 125 A
5 mA or 20 mA 20 mA or 100 mA
+ 30% Un - 15% U
n
+ 30% Un - 15% U
n
< 2.5 W < 2.5 W
25 C to +50 C 25 C to +50 C
40 C to +80 C 40 C to +80 C
5 x U
n
during 10 ms 5 x U
n
during 10 ms
380 V~, 8 A 380 V~, 8 A
250 V , 0.4 A 250 V , 0.4 A
24 V , 8 A 24 V , 8 A
EN 50081-2 and EN 50082-2 EN 50081-2 and EN 50082-2
LED LED
manual
*)
manual
*)
suitable for top hat rail suitable for top hat rail
2.5 mm
2
direct; throughgoing cables, max. 2 x 35 mm
2
,
6 mm
2
via Burndy clamps auxiliaries 2.5 mm
2
*) To be changed to automatic reset by means of switch on PCB.
Principal diagram ELM
Dimensions (mm)
type:
system d.c. voltage:
auxiliary voltage:
rated current:
earth-leakage current:
voltage tolerance:
power consumption:
ambient temperature:
storage temperature:
overvoltage:
auxiliary contact (1 changeover):
Electromagnetic Compatibility:
signalling:
reset:
mounting:
connecting capacity:
load loadaux. voltage
70
11735
45
3.5
55
5.5
109
71
60
91
111
8
Te
ch
nica
l d
ata
a
nd
d
im
en
sio
ns D
C e
arth
-le
ak
ag
e m
on
ito
rs ty
pe
E
LM