1 ELG3311: Solutions for Assignment 1 Problem 2-6: A 15-kVA 8000/230-V distribution transformer has an impedance referred to the primary of 80 + j300. The components of the excitation branch referred to the primary side are R C = 350 kand X M = 70 k. (a) If the primary voltage is 7967 V and the load impedance is Z L = 3.0 +j1.5 , what is the secondary voltage of the transformer? What is the voltage regulation of the transformer? (b) If the load is disconnected and a capacitor of –j4.0 is connected in its place, what is the secondary voltage of the transformer? What is its voltage regulation under these conditions? Solution: (a) The turns ratio is 78 . 34 230 / 8000 = = a The load impedance referred to the primary side is + = + = = 1815 3629 ) 5 . 1 0 . 3 ( ) 78 . 34 ( 2 2 j j Z a Z L P L The referred secondary current is A 7 . 29 87 . 1 ) 1815 3629 ( ) 300 80 ( 0 7967 ° = + + + ° = + = j j Z Z V I P L P i P P S The referred secondary voltage is V 1 . 3 7588 ) 1815 3629 )( 7 . 29 87 . 1 ( ° = + ° = = j Z I V P L P S P S The actual secondary voltage is V 1 . 3 2 . 218 78 . 34 1 . 3 7588 ° = ° = = a V V P S S The voltage regulation is % 99 . 4 % 100 7588 7588 7967 = × = = P S P S P V V V VR

ELG3311SA1

Embed Size (px)

DESCRIPTION

book

Citation preview

Page 1: ELG3311SA1

1

ELG3311: Solutions for Assignment 1 Problem 2-6: A 15-kVA 8000/230-V distribution transformer has an impedance referred to the primary of 80 + j300Ω. The components of the excitation branch referred to the primary side are RC = 350 kΩ and XM = 70 kΩ.

(a) If the primary voltage is 7967 V and the load impedance is ZL = 3.0 +j1.5 Ω, what is the secondary voltage of the transformer? What is the voltage regulation of the transformer?

(b) If the load is disconnected and a capacitor of –j4.0 Ω is connected in its place, what is the secondary voltage of the transformer? What is its voltage regulation under these conditions?

Solution: (a) The turns ratio is

78.34230/8000 ==a The load impedance referred to the primary side is

Ω+=+== 18153629)5.10.3()78.34( 22 jjZaZ LPL

The referred secondary current is

A 7.2987.1)18153629()30080(

07967°−∠=

+++°∠

=+

=jjZZ

VI PL

Pi

PPS

The referred secondary voltage is

V 1.37588)18153629)(7.2987.1( °−∠=+°−∠== jZIV PL

PS

PS

The actual secondary voltage is

V 1.32.21878.34

1.37588°−∠=

°−∠==

aVV

PS

S

The voltage regulation is

%99.4%1007588

75887967=×

−=

−= P

S

PSP

VVVVR

Page 2: ELG3311SA1

2

(b) The turns ratio is

78.34230/8000 ==a The load impedance referred to the primary side is

Ω−=−== 4839)0.4()78.34( 22 jjZaZ LPL

The referred secondary current is

A 0.8975.1)4839()30080(

07967°∠=

−++°∠

=+

=jjZZ

VI PL

Pi

PPS

The referred secondary voltage is

V 0.18468)4839)(0.8975.1( °−∠=−°∠== jZIV PL

PS

PS

The actual secondary voltage is

V 0.12.24378.34

0.18468°−∠=

°−∠==

aVV

PS

S

The voltage regulation is

%92.5%1008468

84687967−=×

−=

−= P

S

PSP

VVVVR

Page 3: ELG3311SA1

3

Problem 2-7: A 5000-kVA 230/13.8-kV single-phase power transformer has a per-unit resistance of 1 percent and a per-unit reactance of 5 percent (data taken from the transformer’s nameplate). The open-circuit test performed on the low-voltage side of the transformer yielded the following data: VOC = 13.8 kV, IOC = 15.1 A, POC = 44.9 kW

(a) Find the equivalent circuit referred to the low-voltage side of this transformer. (b) If the voltage on the secondary side is 13.8 kV and the power supplied is 4000

kW at 0.8 PF lagging, find the voltage regulation of the transformer. Find its efficiency.

Solution: (a) The components of the excitation branch relative to the low-voltage side (secondary side) are

Ω===

Ω===

−=°−∠=−=∠=

°−=−=−=

===−=

−−

9360010685.0

11

42400002358.0

110010685.00002358.056.770010942.0

56.77)1.15)(8.13(

9.44coscos

0010942.08.131.15

11

MM

CC

MCEXEX

OCOC

OC

OC

OCMCEX

BX

GR

jjBGYYk

kIV

PkV

IjBGY

θ

θ

The base impedance of this transformer referred to the low-voltage side (secondary side) is

Ω=== 09.385000

)8.13( 22

kk

SVZ

base

basebase

So that

Ω===

Ω===

90.1)09.38)(05.0(%5

38.0)09.38)(01.0(%1

baseEQ

baseEQ

ZX

ZR

The resulting equivalent circuit is shown below

Page 4: ELG3311SA1

4

Ω=

Ω=

4240

38.0

,

,

SC

SEQ

R

R

Ω=

Ω=

936

9.1

,

,

SM

SEQ

XX

(b) The secondary current is

A 87.363.36287.36)8.0(coscos

A 3.362)8.0)(kV 8.13(

kW 4000

11

°−∠=°−=−=−=

===

−−

S

S

outS

IPF

PFVPI

θ

The voltage on the primary side of the transformer (referred to the secondary side) is

V 9.114330)9.138.0)(87.363.362(013800, °∠=+°−∠+°∠=+= jZIVV SEQSSS

P The voltage regulation of the transformer is

%84.3%10013800

1380014330%100 =×−

=×−

=S

SS

P

VVVVR

The transformer copper losses and core losses are

kW 4.484240

)14330()(

kW 9.49)38.0()3.362(22

2,

2

===

===

C

SP

core

SEQScopper

RVP

RIP

Therefore the efficiency of this transformer at these conditions is

Page 5: ELG3311SA1

5

%6.97%100kW 4.48kW 9.49kW 4000

kW 4000%100 =×++

=×++

=corecopperout

out

PPPP

η

Problem 2-8: A 200-MVA, 15/200-kV single-phase power transformer has a per-unit resistance of 1.2 percent and a per-unit reactance of 5 percent (data taken from the transformer’s nameplate). The magnetizing impedance is j80 per unit.

(a) Find the equivalent circuit referred to the low-voltage side of this transformer. (b) Calculate the voltage regulation of this transformer for a full-load current at

power factor of 0.8 lagging. (c) Assume that the primary voltage of this transformer is a constant 15 kV, and plot

the secondary voltage as a function of load current for currents from no load to full load. Repeat this process for power factors of 0.8 lagging, 1.0, and 0.8 leading.

Solution: (a) The base impedance of this transformer referred to the low-voltage side (primary) is

Ω=== 125.1200

)15( 22

Mk

SVZ

base

basebase

So that

Ω===

Ω===

0563.0)125.1)(05.0(%5

0135.0)125.1)(012.0(%2.1

baseEQ

baseEQ

ZXZR

And

Ω=== 90)125.1)(80()80( baseM ZX The equivalent circuit referred to the low-voltage side of this transformer is shown below

spcifiednotRR

PC

PEQ

−=

Ω=

,

, 0135.0

Ω=

Ω=

90

0563.0

,

,

PM

PEQ

XX

Page 6: ELG3311SA1

6

(b) The current on the secondary side of the transformer (referred to the primary side) is

A87.3616667

87.36)8.0(coscos

16667)8.0)(kW 15(

MW 200

11

°−∠=

°−=−=−=

===

−−

PS

S

outPS

I

PF

APFV

PI

θ

The voltage on the primary side of the transformer is

VjZIVV PEQPS

PSP °∠=+°−∠+°∠=+= 24.215755)0563.00135.0)(87.3616667(015000,

Therefore the voltage regulation of the transformer is

%03.5%10015000

1500015755%100 =×−

=×−

= PS

PSP

VVVVR

(c) This problem is repetitive in nature, and is ideally suited for MATLAB. A program to calculate the secondary voltage of the transformer as a function of load is shown below: % M-file: prob2_8.m % M-file to calculate and plot the secondary voltage % of a transformer as a function of load for power % factors of 0.8 lagging, 1.0, and 0.8 leading. % These calculations are done using an equivalent % circuit referred to the primary side. % Define values for this transformer VP = 15000; % Primary voltage (V) amps = 0:166.67:16667; % Current values (A) Req = 0.0135; % Equivalent R (ohms) Xeq = 0.0563; % Equivalent X (ohms) % Calculate the current values for the three % power factors. The first row of I contains % the lagging currents, the second row contains % the unity currents, and the third row contains % the leading currents. I(1,:) = amps .* ( 0.8 - j*0.6); % Lagging I(2,:) = amps .* ( 1.0 ); % Unity

Page 7: ELG3311SA1

7

I(3,:) = amps .* ( 0.8 + j*0.6); % Leading % Calculate VS referred to the primary side % for each current and power factor. aVS = VP - (Req.*I + j.*Xeq.*I); % Refer the secondary voltages back to the % secondary side using the turns ratio. VS = aVS * (200/15); % Plot the secondary voltage (in kV!) versus load plot(amps,abs(VS(1,:)/1000),'b-','LineWidth',2.0); hold on; plot(amps,abs(VS(2,:)/1000),'k--','LineWidth',2.0); plot(amps,abs(VS(3,:)/1000),'r-.','LineWidth',2.0); title ('\bfSecondary Voltage Versus Load'); xlabel ('\bfLoad (A)'); ylabel ('\bfSecondary Voltage (kV)'); legend('0.8 PF lagging','1.0 PF','0.8 PF leading'); grid on; hold off; The resulting plot of secondary voltage versus load is shown below:

Page 8: ELG3311SA1

8

Problem 2-14: A 13.2-kV single-phase generator supplies power to a load through a transmission line. The load’s impedance is Zload = 500 Ω°∠ 87.36 , and the transmission line’s impedance is Zline = 60 Ω°∠ 1.53 .

(a) If the generator is directly connected to the load, what is the ratio of the load

voltage to the generated voltage? What are the transmission losses of the system? (b) If a 1:10 step-up transformer is placed at the output of the generator and a 10:1

transformer is placed at the load end of the transmission line, what is the new ratio of the load voltage to the generated voltage? What are the transmission losses of the system now? (Note: The transformers may be assumed to be ideal.)

Solution: (a) In the case of the directly-connected load, the line current is

A6.3866.2387.365001.5360

kV02.13°−∠=

°∠+°∠°∠

=+

==loadline

Gloadline ZZ

VII

The load voltage is

Page 9: ELG3311SA1

9

kVZIV loadloadload °−∠=°∠°−∠== 73.183.11)87.36500)(6.3866.23(

The ratio of the load voltage to the generated voltage is

896.0kV 2.13kV 83.11

===G

load

VVratio

The resistance in the transmission line is

Ω=°== 36)1.53)(cos60(cosθlineline ZR The transmission losses in the system are

kW 1.20)36()66.23( 22 === linelineloss RIP (b) In this case, a 1:10 step-up transformer precedes the transmission line a 10:1 step-down transformer follows the transmission line. If the transformers are removed by referring the transmission line to the voltage levels found on either end, then the impedance of the transmission line becomes

Ω°∠=°∠==′ 1.5360.0)1.5360()10/1( 22lineline ZaZ

The current in the referred transmission line and in the load becomes

AkVZZ

VIIloadline

Gloadline °−∠=

°∠+°∠°∠

=+′

==′ 89.3637.2687.365001.5360.0

02.13

The load voltage is

kVZIV loadloadload °−∠=°∠°−∠== 02.0185.13)87.36500)(89.3637.26( The ratio of the load voltage to the generated voltage is

9989.02.13

185.13===

kk

VVratio

G

load

The current in the transmission line is

AaII loadline 637.2)37.26)(10/1( === The losses in the transmission line are

Page 10: ELG3311SA1

10

WRIP linelineloss 250)36()637.2( 22 ===

Problem 2-15: A 5000-VA, 480/120-V conventional transformer is to be used to supply power from a 600-V source to a 120-V load. Consider the transformer to be ideal, and assume that all insulation can handle 600 V.

(a) Sketch the transformer connection that will do the required job. (b) Find the kilovoltampere rating of the transformer in the configuration. (c) Find the maximum primary and secondary currents under these conditions.

Solution: (a) The common winding must be the smaller of the two windings, and NSE = 4 NC. The transformer connection is shown below:

(b) The kVA rating of the transformer is

VAN

NNSN

NNSC

CCW

C

CSEIO 6250)5000(4

=+

=+

=

(c) The maximum primary current for this configuration is

AVSI

P

IOP 4.10

6006250

===

The maximum secondary current is

AVSI

S

IOS 1.52

1206250

===

Page 11: ELG3311SA1

11

Problem 2-19: A 20-kVA, 20,000/480-V, 60-Hz distribution transformer is tested with the following results: Open-circuit test (measured from secondary side)

Short-circuit test (measured from primary side)

VOC = 480 V VSC = 1130 V IOC = 1.60 A ISC = 1.00 A POC = 305 W PSC = 260 W

(a) Find the per-unit equivalent circuit for this transformer at 60 Hz. (b) What would be the rating of this transformer be if it were operated on a 50-Hz

power system? (c) Sketch the per-unit equivalent circuit of this transformer referred to the primary

side if it is operating at 50 Hz. Solution: (a) The base impedance of this transformer referred to the primary side is

kΩ 2020

)20000( 22

, ===kS

VZ PPbase

The base impedance of this transformer referred to the secondary side is

Ω=== 52.1120

)480( 22

, kSVZ S

Sbase

The open-circuit test yields the values for the excitation branch (referred to the secondary side)

Ω===

Ω===

−=°−∠=−=∠=

°−=−=−=

===

−−

32700306.0

11

75700132.0

1100306.000132.06.6600333.0

6.66)60.1)(480(

305coscos

00333.0480

60.1

11

MM

CC

MCEXEX

OCOC

OC

OC

OCEX

BX

GR

jjBGYYIV

PVIY

θ

θ

Page 12: ELG3311SA1

12

The excitation branch elements can be expressed in per-unit as

puZ

RRSbase

CpuC 7.65

52.11757

,, === pu

ZXX

Sbase

MpuM 4.28

52.11327

,, ===

The short-circuit test yields the values for the series impedances (referred to the primary side)

Ω=

Ω=

+=°∠=+=∠=

°===

===

−−

1100

260

11002607.761130

7.76)00.1)(1130(

260coscos

113000.1

1130

11

EQ

EQ

EQEQEQEQ

SCSC

SC

SC

SCEQ

XR

jjXRZZ

IVP

IVZ

θ

θ

The resulting per-unit impedances are

pukZ

RR

Pbase

EQpuEQ 013.0

20260

,, === pu

kZX

XPbase

EQpuEQ 055.0

201100

,, ===

Therefore the per-unit equivalent circuit is show below

puRpuR

puC

puEQ

7.65

013.0

,

,

=

=

puXpuX

puM

puEQ

4.28

055.0

,

,

=

=

Page 13: ELG3311SA1

13

(b) If this transformer were operated at 50 Hz, both the voltage and apparent power would have to be derated by a factor of 50/60, so its ratings would be

VVVVVV

kSS

SS

PP

400)480)(60/50()60/50(16667)20000)(60/50()60/50(kVA 67.16)20)(60/50()60/50(

60,50,

60,50,

6050

===

======

(c) The transformer parameters referred to the primary side at 60 Hz are

Ω===

Ω===

Ω===

Ω===

kkXZXMkRZR

kXZXkRZR

puMbaseM

puCbaseC

puEQbaseEQ

puEQbaseEQ

568)4.28)(20(

31.1)7.65)(20(1100)055.0)(20(

260)013.0)(20(

,

,

,

,

At 50 Hz, the resistances will be unaffected but the reactances are reduced in direct proportion to the decrease in frequency.

Ω===

Ω==

Ω===

Ω==

kXXMRR

XXRR

MM

CC

EQEQ

EQEQ

473)568)(60/50()60/50(31.1

917)1100)(60/50()60/50(260

60,50,

60,50,

60,50,

60,50,

The base impedance of the transformer operating at 50 Hz referred to the primary side is

Ω=== kkS

VZ PPbase 67.16

67.16)16667( 22

50,,

Page 14: ELG3311SA1

14

The resulting per-unit equivalent circuit referred to the primary at 50 Hz is shown below

puk

MZ

RR

pukZ

RR

Pbase

CpuC

Pbase

EQpuEQ

5.7867.16

31.1

016.067.16

260

50,,

50,50,,

50,,

50,50,,

===

===

pu

kk

ZX

X

pukZ

XX

Pbase

MpuM

Pbase

EQpuEQ

4.2867.16

473

055.067.16

917

50,,

50,50,,

50,,

50,50,,

===

===