ELEQ Transformers for Generator Applications Current and voltage transformers for use in generator terminal boxes with high vibration levels

ELEQ Transformers for Generator Applications · 2019. 2. 25. · IEC 61869-2 / IEEE C57.13 100 x In/1s, max. 50kA/1s 2,5 x Icth 120% 17,5/38/95kV 50/60Hz E 5-1500A 1A or 5A; other

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

  • ELEQ Transformers for Generator Applications

    Current and voltage transformers for use in generator terminal boxes with high vibration levels

  • Low voltage transformers

    Current transformers

    GSQR410 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4

    GSAG200 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5

    IGSG 178 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6

    Medium voltage transformers

    Current transformers

    IGWR C1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7

    IGWR D1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8

    IGWR D25� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9

    Voltage transformers

    Single pole

    UGER C1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10

    UGER D1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 11

    UGER D2 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12

    UGER D25 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13

    Double pole

    UGZR C1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14

    UGZR D25 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15

    Table of contents

  • ELEQ has designed a special line of low and medium voltage transformers for generator applications� The special ELEQ construction combines easy mounting with a high resistance for the vibrations in the generator application�

    The line of current and voltage transformers for generator applications contain low voltage transformers and medium voltage transformers up to 17,5 kV�

    • High resistance for generator vibrations• Easy mounting constructions• Up to 17,5 kV• For measurement and protection measurement

    Transformers for Generator Applications

    3

  • Technical specifications

    GSQR410 – Generator Current Transformer

    Ordering specifications*

    Wiring diagram IEC 61869-2

    The GSQR is used for protection and measurement, e.g. power generators. When properly installed, the low voltage GSQR canbe used also for higher voltage levels as the rated 0,72kV. The special ELEQ generator construction, makes it possible to use theGSQR in applications with shock and/or vibration requirements.

    Dimensions*

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:Optional low temperature:Optional high temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C-40°C+80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP00

    Application conditions

    Standard:IEC 61768-2 specificationRated short-time thermal current (lth):Continuous thermal current (lcth):Rated insulation level:Rated frequency:Class of insulation:Rated primary current:Rated secondary current:

    Rated output:

    Accuracy class:

    Primary window dimensions:Secondary terminal:

    IEC 61869-2 / IEEE C57.13

    100 x In/1s, max. 100kA/1s120%0,72/3/-kV50/60HzE30-15.000A1A or 5A; other options available on requestAs required. For example 2,5, 10, 30VAAs required. For example 0,2S, 5P10Ø 250 mmScrew terminals M5 (max. 2,5Nm)

    Size X Y Secondary current**

    ABCDEF

    6090120150200250

    6696126156206256

    1 or 5A1 or 5A1 or 5A1 or 5A1 or 5A1 or 5A

    * Other dimensions available on request.** Other secondary current on request.Design according to IEC61869-2 , IEEE C 57.13. Other standards are possible on request.

    * Terminal designations according to IEEE is shown. Optional the terminal designation according to IEC (P1 / S1 – S2)

    Article number

    On requestOn requestOn requestOn requestOn requestOn request

    +2 -5

    4

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • Technical specifications

    GSAG200 – Bushing-type Current Transformer

    Wiring diagram IEC 61869-2

    The GSAG200 is used for measurement and protection in applications with vibration requirements like power generators. Thecast resin insulated indoor bushing-type current transformer can be up to 1,2kV. The special ELEQ generator construction,makes it possible to use the GSAG200 with shock and / or vibration requirements. The current transformer is maintenance-freeand mountable in any position.

    Dimensions

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree:

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP20

    Application conditions

    Standard:IEC 61768-2 specificationRated short-time thermal current (lth):

    Rated dynamic current (Idyn):Continuous thermal current (lcth):Rated insulation level:Rated frequency:Class of insulation:Rated primary current:Rated secondary current:

    Rated output:

    Accuracy class:

    Secondary terminal:

    IEC 61869-2 / IEEE C57.13, etc.

    100 x In/1s, max. 100kA/1s, other duration on request2,5 x IthUp to 200%1,2/6/-kV50/60HzE10-5000A1A or 5A; other options available on requestAs required. For example 10, 15VAAs required. For example 0,2, 5P20Screw terminals M5 (max. 2,5Nm)

    Ordering SpecificationsFor the customized design of your ELEQ GSAG200 CurrentTransformer the following information is required:

    Mandatory• Rated primary current• Rated secondary current• Rated output• Accuracy class• Frequency

    Optional• Multi-core transformers• Other relevant requirements

    5

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • Technical specifications

    IGSG 178 –Bushing-type Current Transformer

    Wiring diagram IEC 61869-2

    The IGSG 178 is used for measurement and protection in applications with vibration requirements like power generators. Thecast resin insulated indoor current transformer can be used for 0,72 kV or in a medium voltage area in conjunction with aninsulated connector. The special ELEQ generator construction, makes it possible to use the IGSG 178 with shock and/orvibration requirements. The current transformer is maintenance-free and mountable in any position.

    Dimensions*

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree:

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP55

    Application conditions

    Standard:IEC 61768-2 specificationRated short-time thermal current (lth):

    Rated dynamic current (Idyn):Continuous thermal current (lcth):Rated insulation level:Rated frequency:Class of insulation:Rated primary current:Rated secondary current:

    Rated output:Accuracy class:

    Secondary terminal:

    Secondary terminal cross-section and length:

    IEC 61869-2 / IEEE C57.13, etc.

    100 x In/1s, max. 100kA/1s, other duration on request2,5 x IthUp to 200%0,72/3/-kV50/60HzE10-1500A1A or 5A; other options available on requestAs required. For example 15VAAs required. For example 0,2; 0,5; 5P20PG11 or PG21 cable gland depends size B or F

    4 mm²; 3 m ± 10%

    Ordering SpecificationsFor the customized design of your ELEQ IGSG 178 CurrentTransformer the following information is required:

    Mandatory• Rated primary current• Rated secondary current• Rated output• Accuracy class• Frequency

    Optional• Multi-core transformers• Other relevant requirements

    * Also available for ø 60

    Baugröße/ size X y z

    B 90 125 160 F 250 285 320

    cable gland number of wire PG11 2-4 PG21 6

    Baugröße/ size X y z

    B 90 125 160 F 250 285 320

    cable gland number of wire PG11 2-4 PG21 6

    6

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • Technical specifications

    IGWR C1 – Generator Current Transformer

    Wiring diagram IEC 61869-2

    The IGWR C1 is used for measurement and protection in application with vibration requirements like power generators. The castresin insulated indoor supporting-type current transformer can be used up to 17,5kV. The special ELEQ generator construction,makes it possible to use the IGWR C1 in applications with shock and/or vibration requirements.

    Dimensions

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:Optional low temperature:Optional high temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C-40°C+80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data required

    IP20

    Application conditions

    Standard:IEC 61768-2 specificationRated short-time thermal current (lth):Rated dynamic current:Continuous thermal current (lcth):Rated insulation level:Rated frequency:Class of insulation:Rated primary current:Rated secondary current:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-2 / IEEE C57.13

    100 x In/1s, max. 50kA/1s2,5 x Icth120%17,5/38/95kV50/60HzE5-1500A1A or 5A; other options available on requestAs required. For example 2,5, 10, 30VAAs required. For example 0,2S, 5P10M12 (40Nm)Screw terminals M5 (max. 2,5Nm)

    Ordering SpecificationsFor the customized design of your ELEQ IGWR C1 GeneratorCurrent Transformer the following information is required:

    Mandatory• Rated primary current• Rated secondary current• Rated output• Accuracy class• Frequency

    Optional• Other relevant requirements

    7

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • Technical specifications

    IGWR D1 – Generator Current Transformer

    Wiring diagram IEC 61869-2

    The IGWR D1 is used for measurement and protection in applications with vibration requirements like power generators. Thecast resin insulated indoor supporting-type current transformer can be used up to 17,5 kV. The special ELEQ generatorconstruction, makes it possible to use the IGWR D1 with shock and / or vibration requirements. The current transformer ismaintenance-free and mountable in any position.

    Dimensions

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data required

    IP20

    Application conditions

    Standard:IEC 61768-2 specificationRated short-time thermal current (lth):

    Rated dynamic current (Idyn):Continuous thermal current (lcth):Rated insulation level:Rated frequency:Class of insulation:Rated primary current:Rated secondary current:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-2 / IEEE C57.13, etc.

    100 x In/1s, max. 50kA/1s, other duration on request2,5 x Ith, max. 125kAUp to 200%17,5/38/95kV50/60HzE5-1500A1A or 5A; other options available on requestAs required. For example 2,5, 10, 30VAAs required. For example 0,2S, 5P10M12 (40Nm)Screw terminals M5 (max. 2,5Nm)

    Ordering SpecificationsFor the customized design of your ELEQ IGWR D1 CurrentTransformer the following information is required:

    Mandatory• Rated primary current• Rated secondary current• Rated output• Accuracy class• Frequency

    Optional• Multi-core transformers• Other relevant requirements

    125

    - 10+

    13

    270 - 1,50,0+

    5022

    0-2

    300 - 20+

    170 - 10+

    40 25335 - 2

    0+

    38 - 10+

    M12x23

    220 - 20+

    160 - 20+

    148 - 20+

    8

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • Technical specifications

    IGWR D25 – Generator Current Transformer

    Wiring diagram IEC 61869-2

    The IGWR D25 is used for measurement and protection in applications with vibration requirements like power generators. Thecast resin insulated indoor supporting-type current transformer can be used up to 17,5 kV. The special ELEQ generatorconstruction, makes it possible to use the IGWR D25 with shock and / or vibration requirements. The current transformer ismaintenance-free and mountable in any position.

    Dimensions

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data required

    IP20

    Application conditions

    Standard:IEC 61768-2 specificationRated short-time thermal current (lth):

    Rated dynamic current (Idyn):Continuous thermal current (lcth):Rated insulation level:Rated frequency:Class of insulation:Rated primary current:Rated secondary current:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-2 / IEEE C57.13, etc.

    100 x In/1s, max. 50kA/1s, other duration on request2,5 x Ith, max. 125kAUp to 200%17,5/38/95kV50/60HzE5-1500A1A or 5A; other options available on requestAs required. For example 2,5, 10, 30VAAs required. For example 0,2S, 5P10M12 (40Nm)Screw terminals M5 (max. 2,5Nm)

    Ordering SpecificationsFor the customized design of your ELEQ IGWR D25 CurrentTransformer the following information is required:

    Mandatory• Rated primary current• Rated secondary current• Rated output• Accuracy class• Frequency

    Optional• Multi-core transformers• Other relevant requirements

    9

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • UGER C1 – Generator Voltage TransformerThe UGER C1 is used for measurement and protection in applications with vibration requirements like power generators. The singlepole indoor voltage transformer can be used up to 17,5kV. The special ELEQ generator construction, makes it possible to use theUGER C1 in applications with shock and / or vibration requirements. The voltage transformer is maintenance-free and mountable inany position.

    Technical Specifications

    Ordering Specifications

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP20

    Application conditions

    Standard:

    IEC 61768-3 specification:Rated thermal limiting output (Sth):

    Rated voltage factor:

    Rated insulation level:Rated frequency:Class of insulation:Rated primary voltage:Rated secondary voltage:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-3 / IEEE C57.13; etc.

    500VA measuring winding100VA residual winding1,9 x Un for 8h; 1,2 x Un continuous17,5/38/95kV50/60HzE2/√3kV - 15/√3kV100/√3V or 110/√3V; other options available on requestAs required. For example 10, 15, 30VAAs required. For example 0,2, 3PM10 (20Nm)Screw terminals M5 (max. 2,5Nm)

    Dimensions

    Wiring Diagram IEC 61869-3

    For the customized design of your ELEQ UGER C1 GeneratorVoltage Transformer the following information is required:

    Mandatory• Rated primary voltage• Rated secondary voltage• Rated output• Accuracy class• Frequency

    Optional• Transformer requirement with separated windings• Other relevant requirements

    10

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • UGER D1 – Generator Voltage TransformerThe UGER D1 is used for measurement and protection in applications with vibration requirements like power generators. The singlepole indoor voltage transformer can be used up to 12 kV. The special ELEQ generator construction, makes it possible to use theUGER D1 in applications with shock and / or vibration requirements. The voltage transformer is maintenance-free and mountable inany position.

    Technical Specifications

    Ordering Specifications

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP20

    Application conditions

    Standard:

    IEC 61768-3 specification:Rated thermal limiting output (Sth):

    Rated voltage factor:

    Rated insulation level:Rated frequency:Class of insulation:Rated primary voltage:Rated secondary voltage:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-3 / IEEE C57.13; etc.

    500VA measuring winding100VA residual winding1,9 x Un for 8h; 1,2 x Un continuous12/28/75kV50/60HzE2/√3kV - 11/√3kV100/√3V or 110/√3V; other options available on requestAs required. For example 10, 15, 30VAAs required. For example 0,2, 3PM10 (20Nm)Screw terminals M5 (max. 2,5Nm)

    Dimensions

    Wiring Diagram IEC 61869-3

    For the customized design of your ELEQ UGER D1 GeneratorVoltage Transformer the following information is required:

    Mandatory• Rated primary voltage• Rated secondary voltage• Rated output• Accuracy class• Frequency

    Optional• Transformer requirement with separated windings• Other relevant requirements

    11

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • UGER D2 – Generator Voltage TransformerThe UGER D2 – optional with fuse – is used for measurement and protection in applications with vibration requirements like powergenerators. The single pole indoor voltage transformer can be used up to 17,5kV. The special ELEQ generator construction, makesit possible to use the UGER D2 in applications with shock and/or vibration requirements.

    Technical Specifications

    Ordering Specifications

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:Optional low temperature:Optional high temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C-40°C +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP20

    Application conditions

    Standard:IEC 61768-3 specification:Rated thermal limiting output (Sth):

    Rated voltage factor:

    Rated insulation level:Rated frequency:Class of insulation:Rated primary voltage:Rated secondary voltage:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-2 / IEEE C57.13

    500VA measuring winding100VA residual winding1,9 x Un for 8h; 1,2 x Un continuous17,5/38/95kV50/60HzE15/√3kV100/√3V or 110/√3V; other options available on requestAs required. For example 10, 15, 30VAAs required. For example 0,2, 3PM10 (20Nm)Screw terminals M5 (max. 2,5Nm)

    Optional fuse: HSW 6/12 (EFEN)HSW 15/24 (EFEN)

    Dimensions

    Wiring Diagram IEC 61869-3

    For the customized design of your ELEQ UGER D2 GeneratorVoltage Transformer the following information is required:

    Mandatory• Rated primary voltage• Rated secondary voltage• Rated output• Accuracy class• Frequency

    Optional• Other relevant requirements

    12

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • UGER D25 – Generator Voltage TransformerThe UGER D25 is used for measurement and protection in applications with vibration requirements like power generators. Thesingle pole indoor voltage transformer can be used up to 17,5kV. The special ELEQ generator construction, makes it possible to usethe UGER D25 in applications with shock and / or vibration requirements. The voltage transformer is maintenance-free andmountable in any position.

    Technical Specifications

    Ordering Specifications

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP20

    Application conditions

    Standard:

    IEC 61768-3 specification:Rated thermal limiting output (Sth):

    Rated voltage factor:

    Rated insulation level:Rated frequency:Class of insulation:Rated primary voltage:Rated secondary voltage:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-3 / IEEE C57.13; etc.

    500VA measuring winding100VA residual winding1,9 x Un for 8h; 1,2 x Un continuous17,5/38/75kV50/60HzE2/√3kV - 15/√3kV100/√3V or 110/√3V; other options available on requestAs required. For example 10, 15, 30VAAs required. For example 0,2, 3PM10 (20Nm)Screw terminals M5 (max. 2,5Nm)

    Dimensions

    Wiring Diagram IEC 61869-3

    For the customized design of your ELEQ UGER D25 GeneratorVoltage Transformer the following information is required:

    Mandatory• Rated primary voltage• Rated secondary voltage• Rated output• Accuracy class• Frequency

    Optional• Transformer requirement with separated windings• Other relevant requirements

    13

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • UGZR C1 – Generator Voltage TransformerThe UGZR C1 is used for measurement and protection in applications with vibration requirements like power generators. Thedouble pole indoor voltage transformer can be used up to 17,5kV. The special ELEQ generator construction, makes it possible touse the UGZR C1 in applications with shock and / or vibration requirements. The voltage transformer is maintenance-free andmountable in any position.

    Technical Specifications

    Ordering Specifications

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP20

    Application conditions

    Standard:

    IEC 61768-3 specification:Rated thermal limiting output (Sth):

    Rated voltage factor:

    Rated insulation level:Rated frequency:Class of insulation:Rated primary voltage:Rated secondary voltage:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-3 / IEEE C57.13; etc.

    500VA measuring winding100VA residual winding1,9 x Un for 8h; 1,2 x Un continuous17,5/38/75kV50/60HzE2/√3kV - 15/√3kV100/√3V or 110/√3V; other options available on requestAs required. For example 10, 15, 30VAAs required. For example 0,2M10 (20Nm)Screw terminals M5 (max. 2,5Nm)

    Dimensions

    Wiring Diagram IEC 61869-3

    For the customized design of your ELEQ UGZR C1 VoltageTransformer the following information is required:

    Mandatory• Rated primary voltage• Rated secondary voltage• Rated output• Accuracy class• Frequency

    Optional• Transformer requirement with separated windings• Other relevant requirements

    14

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • UGZR D25 – Generator Voltage TransformerThe UGZR D25 is used for measurement and protection in applications with vibration requirements like power generators. Thedouble pole indoor voltage transformer can be used up to 17,5kV. The special ELEQ generator construction, makes it possible touse the UGZR D25 in applications with shock and / or vibration requirements. The voltage transformer is maintenance-free andmountable in any position.

    Technical Specifications

    Ordering Specifications

    Environmental conditions

    This product is designed to be safeunder the following conditions: Location:Ambient air temperature:

    Storage and transport temperature:Relative humidity:Altitude:

    Protection degree (secondary terminal):

    Indoor use-25°C .. +70°C; other temperatures on request-50°C .. +80°C5% .. 95%, non condensingMax. 1000m above NN; at >1000m data requiredIP20

    Application conditions

    Standard:

    IEC 61768-3 specification:Rated thermal limiting output (Sth):

    Rated voltage factor:

    Rated insulation level:Rated frequency:Class of insulation:Rated primary voltage:Rated secondary voltage:

    Rated output:

    Accuracy class:

    Primary connection:Secondary terminal:

    IEC 61869-3 / IEEE C57.13; etc.

    500VA measuring winding100VA residual winding1,9 x Un for 8h; 1,2 x Un continuous17,5/38/95kV50/60HzE2/√3kV - 15/√3kV100/√3V or 110/√3V; other options available on requestAs required. For example 10, 15, 30VAAs required. For example 0,2, 3PM10 (20Nm)Screw terminals M5 (max. 2,5Nm)

    Dimensions

    Wiring Diagram IEC 61869-3

    For the customized design of your ELEQ UGZR D25 VoltageTransformer the following information is required:

    Mandatory• Rated primary voltage• Rated secondary voltage• Rated output• Accuracy class• Frequency

    Optional• Transformer requirement with separated windings• Other relevant requirements

    15

    info@eleq�com +31 (0) 521 533 333 www�eleq�com

  • 83322 / TfGA-EN1704

    ELEQ b.v.P�O� Box 12, 8330 AA SteenwijkTukseweg 130, 8331 LH Steenwijk The Netherlands

    +31 (0) 521 533 333 info@eleq�com www�eleq�com

    Karl-Ferdinand-Braun-Straße 150170 Kerpen (Sindorf)Germany

    +49 (0) 22 73 / 988 70 info@eleq�com www�eleq�com

    ELEQ designs and manufactures smart electrotechnical applications

    for protecting, measuring and connecting electrical energy and works

    worldwide for renowned power companies, system builders and

    installers. Together with our clients we anticipate on the future and on

    required innovations.

    ELEQ is a true producer and partner of clients and relations who are

    professionally involved in energy and public lighting systems and who

    rely on continuous precision and high services.

    ELEQ delivers all its products and applications in accordance to the high

    Dutch and German quality standards and serves markets in Europe and

    beyond from its locations in the Netherlands (Steenwijk) and Germany

    (Kerpen).