ELEKTROMED electronic meters are manufactured in Turkey with 20 years of experience. All the design and manufacturing stages are performed hundred percent in own factories.
ELEKTROMED has products for household, commercial, lightning, industrial and energy distribution lines. From residential type single-phase meter to distribution point meters with external current and voltage transformers, ELEKTROMED has all the meter models which distribution companies require.
ELEKTROMED meters are manufactured and sealed according to Europe wide valid Measurement Instrument Directive (MID) regulations and ready for service.
ELEKTROMED is constantly designing and developing new and economical solutions with strong R&D Department and modern production technology.
1
ww
w.e
lekt
rom
ed
.co
m.tr
• Easy Installation and Stylish Industrial Design
ELEKTROMED electricity meters have small and aesthetic design which can easily be replaced with mechanical meters uninstalled from site. Industrial design is performed by taking long term high performance usage, easy installation, usage and future-proof properties into consideration.
• Accurate Metering
ELEKTROMED meters have electronic metering (solid state) structure which enables long term accurate metering service life. Self consumption is lower than standard values and all the components are selected and tested carefully. Reference and base current values are assigned as 5 A to increase the accuracy.
ELEKTROMED meters perform measurement accurately from starting current up to 100 A on direct connection mode, up ot 10 A on current transformer connection mode because dynamic range of metering circuits are wide. Even the current ends are connected reversely, metering accuracy will stay in the same range and consumption will be recorded as its absolute value.
• Custom Display Design
Meter display specially designed large for comfortable reading. Display messages are supported by symbols for better understanding. Backlight is standard for active-reactive meters and optional for residential meters.
• Remote reading
In the near future all meters will be read remotely. For remote reading, meters shall be equipped with communication module. Most common and economical of these module is RS485. For this reason, active-reactive meters held by high consuming customers and have RS485 output as a standart feature. Forresidential single phase and three phase meter have RS485 module as option.
• Environmental Friendly
Elektromed have ISO9001 and ISO18001 certificates from design to production, marketting to sales processes.
All the precautions for protecting and improving the environment are taken and been applied. From battery decision to package design, and all stages this precision is applied. ELEKTROMED proved this structure by ISO 140001 Environment Management System certificate.
2
ww
w.e
lekt
rom
ed
.co
m.tr
co
nte
nt
EC0 & EC1 SERIES• EC058• EC15A• EC15X
EC25 SERIES• EC25TP• EC25TC• EC25TV
A SERIES• A0H• A5• A6
4
ww
w.e
lekt
rom
ed
.co
m.tr
Features• MID certified• Confirm to IEC 50470-1/3 standards • Class B (±1%) active energy metering accuracy• UV protection, polycarbonate IP54 body• Wide working range 150V - 320V Maximum 100A for EC1, maximum 80A for EC0 Outdoor, -40 C .. +70C IP54 protection degree• 4 tariffs, 8 time slices, 3 day type, TOU• 0.5 sec/day real time clock accuracy• Automatic Daylight Saving Application (DST)• Optical port (EN62056-21/61)• Index reading from display during absence of power• Data reading from optical port during absence of power• Custom LCD design• Ergonomic and light weight body• 10 years of battery life
Innovations• 5A basic current• Backlight display• 30 day / 30 min load profile• Monthly demand monitoring• Current and voltage monitoring
Protection Features• Terminal cover open tamper detection• Top cover open tamper detection• Independent terminal and body cover sealing• Password protection for programming mode• Absolute energy value recording when reverse connected• Protection against memory manipulation• Previous months’ values• Last 12 months tariff consumption recording
System Solutions• Optical port conformity to IEC standards• RS485 port (optional)• Optional MODBUS support• Optional DLMS/COSEM support
EC0 & EC1 SERIESRESIDENTIAL TYPE ELECTRICITY METERS
5
ww
w.e
lekt
rom
ed
.co
m.tr
EC058Single Phase Electricity Meter
Specially Designed Small and Light Structure for Residential Type Applications
Connection Type 1 phase 2 wireTechnical Specifications Parameters
Terminal Connection DIN / BSAccuracy Class Class B (TS EN 50470-1/3) (±1%)Application Voltage Range -20% .. +15% Un (Un = 230 V)Frequency 50 HzMeter Constant 1000 imp/kWhBase Current, Iref 5 A, 10 AMaximum Current, Imax 80 A or ≥ 5 x IrefStarting Current, Ist 20 mADisplay LCD 8 digit + symbolsOptical Port Read/Write (TS EN 62056-21)Weight 0.5 kg
Model B C D 155 58 40
A101EC058MBW
Terminal Connection Diagram Model
C
D
LN
LN
LL
NN
(DIN) (BS)
6
ww
w.e
lekt
rom
ed
.co
m.tr
Connection Type 3 phase 4 wireTerminal Connection DINAccuracy Class Class B (TS EN 50470-1/3)Aplicattion Voltage Range -20% .. +15% Un (Un = 3x230/420V)Frequency 50 HzMeter Constant 1000 imp/kWhBase Current,Imax 5 A, 10 AMaksimum Akım, Imax 100 A or ≥ 5 x IrefStarting Current, Ist 20 mADisplay LCD 9 digit + symbolsOptical Port Read/Write (TS EN 62056-21)Weight 0.8 kg
Technical Specifications Parameters
EC15AThree Phase Electricity MeterSpecially Designed Small and Light Structure for Residential Type Applications
Model B C D230 67 51
A160EC15ATBW
A
B
C
D
Terminal Connection Diagram Model
7
ww
w.e
lekt
rom
ed
.co
m.tr
EC15X Three Phase Electricity Meter with
External Current Transformer ConnectionThree Phase Electricity Meter with External Current Transformer Connection
Model B C D 230 67 51
A160EC15XTBW
Technical Specifications ParametersConnection Type 3 phase 4 wireTerminal Connection DINAccuracy Class Class B (TS EN 50470-1/3)Aplicattion Voltage Range -20% .. +15% Un (Un = 3x230/420V)Frequency 50 HzMeter Constant 2000 imp/kWhNominal Current, In 5 AMaximum Current, Imax 6 AStarting Current, Ist 15 mADisplay LCD 9 digit + symbolsOptical Port Read/Write (TS EN 62056-21)Weight 0.8 kg
L1L2L3N
L1L2L3N
A
B
C
D
Terminal Connection Diagram Model
8
ww
w.e
lekt
rom
ed
.co
m.tr
EC25 SERIESTHREE PHASE ACTIVE-REACTIVE ELECTRICITY METERS
Features• MID certified• Conformity to IEC 50470-1/3 stadards • Class B (±1%) active energy metering accuracy• UV protection, polycarbonate IP54 body• Wide working range 40V - 320V Maximum 100A Outdoor, -40C .. +70C IP54 protection degree• 4 tariffs, 8 time slices, 3 day type, TOU• Demand reset button• 0.5 sec/day real time clock accuracy• Automatic Daylight Saving Application (DST)• Index reading from display during absence of power• Data reading from optical port during absence of power• Custom LCD design• Ergonomic and light weight body• 10 years of battery life
Load Profile • 15, 30, 60 min adjustable periods• 3 channel active, inductive and capacitive reactive energy• Total 5832 registers till 8 months
Event registers• 10 records for R,S,T Phase power down • 10 records for electricity power down• 10 records for R,S,T current reverse connection• 10 records for phase sequence errors• 12 records for terminal cover open and quantity• Top cover open
System Solutions• Optical Port (IEC62056-21)• RS485 port (IEC62056-21)• Optional isolated pulse output• Optional MODBUS support• Optional DLMS/COSEM support
Protection Features• Terminal cover open warning notification and record• Top cover open warning notification and record• Independent sealing for terminal and top cover • Demand reset button• Password protected programming mode•Absolute energy value recording on reverse connection• External memory data write protection• Previous months maximum demand values• Last 24 months tariff consumption records • Phase sequence error notification and register• Reverse current connection notification and register
• If the real time clock is in error mode symbol flashes instead of tariff obis codes.
Obis Code Table
LCD Warning Symbols
Technical Specifications ParametersConnection Type 3 phase 4 wireTerminal Connection DINAccuracy Class - active Class B or CAccuracy Class - reactive Class 2Frequency 50 HzProtection Class IP54Electromagnetic Environmental Class E2Mechanical Environmental Class M2Temperature Range -40...+70 ˚CCurrent Circuit Power Consumption < 2W, 10VAVoltage Circuit Power Consumption < 4VADisplay LCD 9 digit + SymbolsDemand Time Interval Load Profile Cumulative Consumption Values (1.8.0, 5.8.0 ve 8.8.0)Load Profile Period Optical Port Mode C Readout, 9600baud (IEC62056-21)Pulse Output 1pulse / WhRS485 Port 2500 V isolation Voltage, Mode C Readout, 9600baud (IEC62056-21)
Obis Code Description0.0.0 Serial Number0.9.1 Meter Time0.9.2 Meter Date0.9.5 Day of Week1.8.0 Cumulative Active Energy ( Import )
1.8.1 Total Energy T11.8.2 Total Energy T21.8.3 Total Energy T31.8.4 Total Energy T41.6.0 Maximum Active Power1.6.0*1 Previous Month Maximum Active Power
Obis Code Description96.71 Last Terminal Cover Open Date96.70 Top Cover Open Date1.8.1*1 T1 Month Starting Consumption Value1.8.2*1 T2 Month Starting Consumption Value1.8.3*1 T3 Month Starting Consumption Value1.8.4*1 T4 Month Starting Consumption Value5.8.0 Reactive Inductive Energy Consumption 8.8.0 Reactive Capacitive Energy Consumption 5.8.0*1 Reactive Inductive Month Starting Value 8.8.0*1 Reactive Capacitive Month Starting Dates 0.1.0 Demand Reset Count
0.1.2*1 Last Demand Reset Date and Time
9
ww
w.e
lekt
rom
ed
.co
m.tr
• Terminal cover open warning.• Top cover open warning.
15 (default), 30 or 60 dk
30 (default), 15 or 60 dk
• Shows that all phases are active.• If any of the phases power down, related phase icon disappears.• If any two of the phases are reverse con-nected, it shows the reverse connected phase symbols.• While meter measures active consumption in correct direction, quadrant is shown with correct arrow direction
• If the current is reverse connected, quadrant flashes the arrow direction and instead of tariff OBIS codes, related phase symbols gjcb flash with (Reverse) symbols
10
ww
w.e
lekt
rom
ed
.co
m.tr
Technical Specifications ParametersVoltage 3x230 / 400VMeter Constant 1000 imp / kWh, 1000 imp / kVArhStarting Current, Ist 20 mAMinimum Current Imin 250 mAReference Current, Iref 5 AMaximum Current, Imax 100 AWeight 1.2 kg
Model B C D 230 73 51
A160EC25TPA3CHB
EC25TPDirect Connected Three Phase Electricity MeterThree Phase Electricity Meter with Active-Reactive Power Measurement
8.8.0 Reactive Capacitive Energy Consumption
1 3 4 6 7 9 10 12
L1L2L3N
L1L2L3N
D
C
B
A
Terminal Connection Diagram Model
11
ww
w.e
lekt
rom
ed
.co
m.tr
Technical Specifications ParametersVoltage 3x230 / 400 VMeter Constant 10000 imp / kWh, 10000 imp / kVArhStarting Current, Ist 10 mAMinimum Current, Imin 50 mANominal Current, In 5 AMaximum Current, Imax 10 AWeight 1.0 kg
Model B C D 230 73 51
A160EC25TC13CHB
EC25TCEC25TC External Current Transformer Connected
Active-Reactive Electricity MeterThree Phase Electricity Meter with Active-Reactive Power Measurement
for High Consuming Commercial Customers
8.8.0 Reactive Capacitive Energy Consumption
L1L2L3N
L1L2L3N
D
C
B
A
Terminal Connection Diagram Model
12
ww
w.e
lekt
rom
ed
.co
m.tr
Technical Specifications ParametersVoltage 3x57,7 / 100VMeter Constant 10000 imp / kWh, 10000 imp / kVArhStarting Current, Ist 10 mAMinimum Current, Imin 50 mANominal Current, In 5 AMaximum Current, Imax 10 AWeight 1.0 kg
Model B C D 230 73 51
A160EC25TV13CHB
EC25TVExternal Current and Voltage TransformerActive-Reactive Electricity MeterThree Phase Electricity Meter with Active-Reactive Power Measurement for Energy Distribution Lines
D
C
B
A
L1
N
X
U
1 3 4 6 7 9 11852
k l
K L K L K L
k l k l
U U
U U U
X X
X X X
L2
L3
L1
L2
L3
Terminal Connection Diagram Model
13
ww
w.e
lekt
rom
ed
.co
m.tr
Features• MID certified• Class B (±1%) active energy metering accuracy• UV protected, policarbonate IP54 body• Wide working range 150V - 320V Maximum 100A Outdoor, -40C .. +70C IP54 protection degree• 4 tariffs, 8 time slices, 3 day type, TOU• Demand reset button• 0.5 sec/day real time clock accuracy• Automatic Daylight Saving Application (DST)• Index reading from display during absence of power• Data reading from optical port during absence of power• Custom LCD design• Ergonomic and light weight body • 10 years of battery life
Internal Turn On-Off Relay• Integrated latched relay• 100A maximum current• 20ms operation time• Conformity to IEC 62054-11 requirements
System Solutions• Smart card with ISO 78186 standard • Optical port conformity to IEC standards• RS485 port (optional)• MODBUS protocol (optional)
Protection Features• Secure IC card application• Previous month consumptions and meter status information carried by card• Terminal cover open detection• Top cover open detection• Independent sealing for terminal and top cover • Absolute energy value recording on reverse connection mode.• External memory data write protection
A SERIESELECTRICITY METERS WITH PREPAYMENT / INTEGRATED RELAY
L L
N N
Terminal Connection Diagram Model
14
ww
w.e
lekt
rom
ed
.co
m.tr
Technical Specifications ParametersRated Voltage 240Voltage Variation -30, +20Frequency 50 (% 5)Base Current 5, 10Maximum Current 30Accuracy Class (ICE 62052-11) Class 1AC Withstand Voltage 440 (Minimum 5 minutes)Impulse Withstand Voltage 6000
RS485 (Optional)Automatic Meter Reading SystemDisplay Backlit LCDInterface Unit Optical Port (IEC 62056-21)Number of Tariff Periods 6Time Deviation (IEC 61038)
Backup Unit
Degree of ProtectionReferans StandartReference Standards
EEPROM Nonvolatile MemoryCommunication Interface
IP 54 Outdoor (IEC 620529)IEC 62053-21, IEC 62052-11
IEC 62056-21/61>20
DLMS (Optional), IEC 62056
- Shelf Life- Operation Life
Lithium Battery (LiSO2CI)10 years4 years
0.5
A0HActive Single Phase Electricity Meter
Model B C D E 193 73 88 115
A118A5
CA
BE
F
+_
+_
LL
NN
In electrical engineering, single phase electric power refers to the distribution of alternating currentelectric power using a system in which all the voltages of the supply vary in unison. Single phase powerdistribution is widely used especially in rural areas.
Elektromed A0H series single phase electricity meters combines unique features in one product. These meters provide high protection against energy theft. With DLMS/COSEM feature which is the common language so that the partners can understand each other, meter is capable for;
• The standardised interface classes and data types; • The object identification system, providing a standar identifier for each and every object; • The possibility to retrieve the resources available in the metering equipment by reading the COSEM association objects.
Basic Features
• Compliant with IEC 62056 • Energy measurement; able to measure both forward and reverse energy. For both conditions consumed energy can be written in a single register (optional) • High protection; able to detect 31 different tamper conditions including neutral missing and neutral disturbance conditions • External AC and DC magnetic field detection Accurate measurement on 0,2 Tesla AC magnetic field Accurate measurement on 0,5 Tesla DC magnetic field • Durablity aganist 35 kV statical voltage discharge • Backlite LCD • Transreceiving data via optical port • Real time clock
15
ww
w.e
lekt
rom
ed
.co
m.tr
T6REVERSE
DLMS
kWhN S
DATA
!
TARIFF6 programmable tariffs
BATTERYBattery level
WARNING (Optional)Terminal cover opening
DLMS (Optional)Communication protocol
kWhActive energy measurement
RESERVEReserve energy flow
EARTHINGEarthing detection
MAGNETIC DETECTIONExternal magnetic field detection
DATA TRANSFER (Optional)AMR applications
16
ww
w.e
lekt
rom
ed
.co
m.tr
TAMPER CONDITIONS
4. CONDITION
PHASE AND NEUTRALCURRENT REVERSED
ETF
LI NI NO LO
REV
LOADLN
3. CONDITION
ETF
LI NI NO LO
REV
LOADNL
FULL LOAD EARTH RETURNED
ETF
LI NI NO LO
REV
LOADLN
5. CONDITION
ETF
LI NI NO LO
REV
6. CONDITIONLOAD
N
L
FULL LOADEARTH RETURNED ANDCURRENT REVERSED
ETF
LI NI NO LO
REV
7. CONDITION
ETF
LI NI NO LO
REV
8. CONDITION
LOADLN
LOAD
NL
1. CONDITION
ETF
LI NI NO
REV
LOADL
N
LO
ETF
LI NI NO LO
REV
LOADNL
2. CONDITION
NORMAL WIRINGNOT TAMPERED
LINE-NEUTRAL NORMAL CONNECTED LINE-NEUTRAL REVERSE CONNECTED
PARTIAL LOADEARTH RETURNED
ETF
LI NI NO LO
REV
LOADL
N
9. CONDITION
ETF
LI NI NO LO
REV
LOAD
NL
10. CONDITION
LOAD
ETF
LI NI NO LO
REV
11. CONDITION
ETF
LI NI NO LO
REV
12. CONDITION
LOAD
LN
LOAD
NL
PARTIAL LOADEARTH RETURNED ANDCURRENT REVERSE
LI: LINE INPUT NI: NEUTRAL INPUT
NO: NEUTRAL OUTPUTLO: LINE OUTPUT
ETF: EARTHING INDICATOR
REV: REVERSE INDICATOR
21. CONDITION
ETF
LI NI NO LO
REV
CURRENT BY-PASSED
LINE-NEUTRAL NORMAL CONNECTED LINE-NEUTRAL REVERSE CONNECTED
17
ww
w.e
lekt
rom
ed
.co
m.tr
LI: LINE INPUT NI: NEUTRAL INPUT
NO: NEUTRAL OUTPUTLO: LINE OUTPUT
ETF: EARTHING INDICATOR
REV: REVERSE INDICATOR
ETF
LI NI NO LO
REV
LOADL
N
13. CONDITION
ETF
LI NI NO LO
REV
14. CONDITION
NEUTRAL CURRENT REVERSED
LOADN
L
ETF
LI NI NO LO
REV
15. CONDITION
ETF
LI NI NO LO
REV
16. CONDITION
PHASE CURRENT REVERSED
LOADL
N
LOADN
L
ETF
LI NI LI NINO LO
REV
LOADL
N
17. CONDITION
ETF
NO LO
REV
18. CONDITION
PARTIAL LOADEARTH RETURNED ANDNEUTRAL CURRENT REVERSED
LOADN
L
ETF
LI LINI NO LO
REV
19. CONDITION
ETF
NI NO LO
REV
20. CONDITION
PARTIAL LOADEARTH RETURNED ANDPHASE CURRENT REVERSED
LOADL
N
LOADN
L
18
ww
w.e
lekt
rom
ed
.co
m.tr
Technical Specifications ParametersConnection Type 1 phase 2 wireTerminal Connection DIN / BS Accuracy Class Class B (TS EN 50470-1/3)Aplication Voltage Range -20% .. +15% Un (Un = 230 V)Frequency 50 HzMeter Constant 1000 imp / kWhBase Current, Iref 5 A, 10 AMaximum Current, Imax 60 A or ≥ 5 x IrefStarting Current, Ist 20 mADisplay AlphanumericalOptical Port Read/Write (TS EN 62056-21)Weight 0,72 kg
A5Single Phase Electricity MeterResidential Type Prepayment and Remote Open Close Applications
Model B C D 193 73 75
A118A5
L N
L N
L L
N N
A C
B
D
Terminal Connection Diagram Model
(DIN) (BS)
19
ww
w.e
lekt
rom
ed
.co
m.tr
ParametersConnection Type 3 phase 4 wireTerminal Connection DINAccuracy Class Class B (TS EN 50470-1/3)Aplication Voltage Range -20% .. +15% Un (Un =3x230/420V)Frequency 50 HzMeter Constant 500 imp / kWhTemel Akım, Iref 5 A, 10 AMaximum Current, Imax 100 A or ≥ 5 x IrefStarting Current, Ist 20 mADisplay AlphanumericalOptical Port Read/Write (TS EN 62056-21)Weight 1.0 kg
A6Three Phase Electricity Meter
Residential and Commercial Type Prepayment and Remote Open-Close Applications
Model B C D 245 87 178
A154A6
A C
B
D
Terminal Connection Diagram Model
METER READING PROGRAM
ELEKTROMED developed a software that reads data from meters and convert these data to meaningful tables.Clients may download this packet program free of charge at website.
Information grouped by program in table format:
• Readout Reading• Last 12 Months Consumption Values• Last 6 Months Demand Information• Cover Open Date • Connection Error Evet Logs• Phase Power Down Event Logs• Load Profile (Between Two Dates )
20
ww
w.e
lekt
rom
ed
.co
m.tr
www.elektromed.com.tr
www.elektromed.com.trOrganize Sanayi Bolgesi Uygurlar Cd.
No:4 06935 Sincan / ANKARA / TURKEY
T: (+90 312) 267 13 67 (pbx)
F: (+90 312) 267 13 66