Upload
vaithy1990
View
230
Download
1
Embed Size (px)
Citation preview
7/30/2019 Electrical Standarts
1/33
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD002.U07
Page1/33
Rev.A
LIST OF ELECTRICAL STANDARD SPECIFICATIONS
01 Codes for electrical equipment
02 Preparation of electrical documents03 Incoming substations04 Departmental substations05 Medium voltage switchboards06 Power transformers
07 Power control centres, motor control centres
08 Large motors09 Small motors10 Starters11 Variable speed drives12 Erection, cabling, earthing connections, lightning protection13 Production and distribution of auxiliary voltages
14 Electrical cabinets and marshalling cabinets15 Instrumentation16 Process Control System : equipment and configuration17 Process Control System: application software and integration18 Lighting and power outlets19 Electrical devices for mechanical equipment20 Earthing grid21 Process Control System : basic functional objects22 Visible Cut-off Switches23 Incoming transformers
Key codes: Low voltage, Power, Motor Control Centre, MCC, Cabinet
F
E
D
C
B
A 21/10/05 General revision I. MOCANU M. MAHAUX
0 07/10/02 Document edition I. MOCANU M. MAHAUX
Rev Date Scope of revision Issued Approved CTI ApprovedCTEC
LAFARGE CENTRE TECHNIQUE INTER-UNITESLIsle dAbeau Parc de Chesnes B.P. 70F-38291 ST QUENTIN-FALLAVIER CedexPhone : + 33 474 82 16 16 / Fax + 33 474 94 30 07
LAFARGE CENTRE TECHNIQUE EUROPE CENTRALEGumpendorfer Strasse 19-21,A-1060 WIEN, Postfach 264Phone : + 43 1 811 42 0 / + 43 1 811 42 44 09
ASIA TECHNICAL CENTRELevel 3,Wisma Lafarge N2 Jalan Kilang46050 PETALING JAYA SELANGOR DARUL EHSANMY-MALAYSIAPhone : + 603 77874800 / Fax : + 603 77874890
Reproduction & usage strictly forbidden without Lafarge
explicite agreement (Law March 11th
, 1957)
ELECTRICAL STANDARD
SPECIFICATION
7/30/2019 Electrical Standarts
2/33
CONTENT
1. GENERAL REQUIREMENTS 4
1.1. APPLICABILITY 41.2. APPLICABLE STANDARDS 41.3. LOCAL CONDITIONS 41.4. GLOSSARY 41.5. SIGNS USED 41.6. ENCLOSURE AND DEGREE OF PROTECTION 51.7. RATED VOLTAGES 5
1.7.1. Main voltage......................................................................................................................51.7.2. Auxiliary voltages..............................................................................................................5
1.8. RATED INSULATING VOLTAGE 5
1.9. RATED CURRENTS 51.10. SHORT CIRCUIT WITHSTAND STRENGTH 6
2. SWITCHBOARD CONSTRUCTION 6
2.1. COMMON REQUIREMENTS 62.1.1. General arrangement........................................................................................................62.1.2. Switchboard structure........................................................................................................62.1.3. Incoming circuit(s).............................................................................................................72.1.4. Busbars............................................................................................................................. 72.1.5. Control and measuring circuits..........................................................................................82.1.6. Remote Input/Output modules...........................................................................................82.1.7. Wiring................................................................................................................................8
2.1.8. Labels................................................................................................................................92.2. DRAW-OUT / FIXED TYPES 9
2.2.1. Draw-out type....................................................................................................................92.2.2. Fixed type........................................................................................................................10
3. POWER SWITCHGEAR 11
3.1. INCOMERS AND BUS-TIE BREAKERS 113.2. OUTGOING CIRCUITS 11
4. CONTROL SWITCHGEAR AND MEASURING DEVICES 12
4.1. CONTROL CIRCUITS 124.2. PROTECTIONS 13
4.3. MEASURING DEVICES 14
5. PCC/MCC SUPPLYING VSDS 14
6. POWER FACTOR CORRECTION UNITS 15
7. DOCUMENTS 17
7.1. DOCUMENTS TO BE SUPPLIED BY THE OWNER 17
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page2/33
Rev.A
7/30/2019 Electrical Standarts
3/33
7.2. DOCUMENTS TO BE PREPARED BY THE SUPPLIER 177.3. DOCUMENTS TO BE SUBMITTED WITH THE OFFER 18
8. FACTORY TESTS 18
9. GUARANTEE 19
10. DATA SHEETS 19
11. SWITCHGEAR SELECTION TABLES 22
11.1. SWITCHGEAR SELECTION FOR 400 V MOTORS USING LINE STARTERS 2211.2. SWITCHGEAR SELECTION FOR 500 V MOTORS USING LINE STARTERS 24
12. DIAGRAMS 24
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page3/33
Rev.A
7/30/2019 Electrical Standarts
4/33
1. GENERAL REQUIREMENTS
1.1. APPLICABILITY
This specification is applicable to Power Control Centres (Low Voltage Distribution Boards) aswell as to Motor Control Centres operating in 3-phase AC under a voltage not exceeding 1000 V.
1.2. APPLICABLE STANDARDS
The panels shall comply with the requirements of IEC and ISO standards. In particular, they shallbe prefabricated, type-tested assemblies according to IEC 60439-1 standard.
1.3. LOCAL CONDITIONS
Local conditions are given in the Site Specification. Equipment subject to this specification will beinstalled in electrical rooms protected from the dust. The ambient air temperature will not exceed+ 40C nor be less than - 5C and its average over a period of 24 h will not exceed + 35C.
If required by climatic conditions, anti-condensation heaters shall be installed.
1.4. GLOSSARY
ACC Auxiliary Control Centre
MCB Miniature circuit breaker
MCC Motor Control Centre
PCC Power Control Centre
PCS Process Control System
UPS Uninterruptible Power Supply
VCS Visible Cut-Off Switch
VSD Variable Speed Drive
1.5. SIGNS USED
Asign in the margin will mark up in the text of this specification each clause to be mandatorilyspecified by the Site Specification.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page4/33
Rev.A
7/30/2019 Electrical Standarts
5/33
A
1.6. ENCLOSURE AND DEGREE OF PROTECTION
Switchboards enclosures shall ensure in normal service (doors closed) a protection degree IP31according to IEC 60529, IP20 with door open or drawer in test or drawn-out position.
1.7. RATED VOLTAGES
1.7.1. Main voltage
This voltage is mentioned in the Site Specification, as well as the condition of the neutral point.The default value for a new plant with a frequency of 50 Hz is 400 V, three-phase.Unless otherwise mentioned, the neutral will be solidly earthed and not distributed.
1.7.2. Auxiliary voltages
These voltages are mentioned in the Site Specification. The default values for a new plant are :
230 V AC Normal for contactor coils and anti-condensation heaters.
230 V AC UPS for electronic modules and contactor coils when protection against feeder
voltage dips is required.
24 V DC for auxiliary relays and signalling lamps.
All these auxiliary voltages will be supplied by the ACC (out of this supply), as developed inSpecification STD.002.U13.
1.8. RATED INSULATING VOLTAGE
The insulation voltage for the busbars and power switchgear as well as for any circuit of theswitchboard shall not be less than:
Busbars: 1 000 V
Power switchgear: 690 V
Power circuits: 750V
Control switchgear and circuits: 500 V
1.9. RATED CURRENTS
The rating of the incoming circuit(s) shall be in accordance with the feeding transformer,
and at least equal to the total load of the users supplied, if the power of the feedingtransformer is not known.
The rating of the main busbar(s) shall not be less than this one of the incoming circuit(s).
Same rating shall be considered for the full length of each main busbar (no reduced crosssection at ends).
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page5/33
Rev.A
7/30/2019 Electrical Standarts
6/33
A
Unless otherwise specified, every switchboard shall be designed for a continuous service.
1.10.SHORT CIRCUIT WITHSTAND STRENGTH
The rated short-time withstand current of the switchboard shall at least be equal to the short-
circuit current mentioned in the particular specification and shall in no case be less than50 kA rms during 1 s.
This shall also apply to the incoming circuit breaker, to bus-tie breakers and to outgoing
circuit breakers (please refer to section 3).
2. SWITCHBOARD CONSTRUCTION
2.1. COMMON REQUIREMENTS
2.1.1. General arrangement
The switchboard shall be defined with access to switchgear and to cables from the front
only. The switchboard shall be designed so that its sections (columns) can be installed eitherin one line or back to back (busbars shall be independent and segregated).
The main busbarshall be positioned on top or on the back of the switchboard and cables
shall enter from the bottom. If an incoming bus duct is used, this could enter from the top.
The switchboard shall be designed to be installed directly above the cable channel or on
technical floor without the addition of any part not supplied by the Supplier.
The switchboard shall be designed foreasy extension at least at one end.
All the switchboard components: busbars, outgoing feeders and its dimensions shall be
standardized as much as possible.
A minimum of 10% empty spare space shall be provided.
2.1.2. Switchboard structure
The switchboard shall be of modular and prefabricated type, assembled and equipped in
the factory. No section shall be higher than 2200 mm and access to each piece of equipment
and device shall be easy, especially for resetting thermal overload protection relays or formanoeuvring MCBs protecting auxiliary circuits.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page6/33
Rev.A
7/30/2019 Electrical Standarts
7/33
A
A
A
Anticorrosion protection of the metal structure (internal and external sides) shall be
ensured as follows:
Continuous hot dip galvanised sheet metal shall be used for non visible internal metal
parts. Visible metal parts shall be prepared by phosphatisation-cleaning treatment and
painted with either epoxy-polyester powder (minimum thickness 50 m) or acrylo-
urethane lacquer (minimum thickness 20 m). The finish shall be semi-gloss; the colour
will be the Manufacturers standard shade unless otherwise specified.
Ample passage shall be designed for the cables arriving from below, and supporting clamps
shall be available for fixing power and control cables. Cable channel width shall not be lessthan 300 mm.
Dust ingress and fire transmission will be stopped by closing these cable passages,after cables installation, with fire resisting materials (operation performed by the cabling
contractor).
Each switchboard section shall be equipped with a vertical copperearth collectorconnected
to an horizontal copper earth collecting bar. This shall terminate to an earthing tail,accessible when the board is alive and suitable for connecting a copper earthing cable. Thecross section of this earth collector shall be such that it will withstand the switchboards short-circuit current during 1 s, with a minimum cross section of 200 mm.
Switchboards shall be form 2 with doors open. At the minimum, Plexiglass (perspex)
screens will be provided in order to avoid contacts with live conductors (busbars and powerconnections).
Each access doorshall be locked by a single handle without key nor need of using any tool
as these switchboards will be installed in locked electrical rooms.
2.1.3. Incoming circuit(s)
The incoming section(s) shall be designed for connection to incoming feeder(s) either bybusbar provided with flexible connection or by cables.
2.1.4. Busbars
Main busbars (horizontal) and vertical busbars shall be ofelectrolytic coppertype Cu ETP
according to ISO 1337 standard.
Busbars which do not require maintenance shall be provided.
Metal sheets near high current busbars (1 600 A or more) shall be of aluminium or of other
non magnetic material.
All bolted connections shall be checked by using a torque wrench.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page7/33
Rev.A
7/30/2019 Electrical Standarts
8/33
A
A
2.1.5. Control and measuring circuits
Every control equipment shall be accessible from the front ofthe switchboard. Every signallingswitchgear and every indicator shall be visible from the front of the switchboard.
2.1.6. Remote Input/Output modules
Unless otherwise mentioned in the Site Specification, digital remote Input/Output modules
and their associated communication modules shall be installed by the Supplier on top ofeach switchboard section, in a compartment separate by a metal sheet from the portiondevoted to switchgears installation. Unless otherwise provided in the Site Specification,these I/O modules are not a part of this supply.
Every device of these modules shall be accessible directly from the front of the switchboard,
without having to remove any part.
Indication LEDs of I/O modules and of communication modules shall be perfectly visible to
a person standing in front of the switchboard, with its doors closed.
2.1.7. Wiring
The switchboard wiring shall be performed in accordance with the Lafarge standard
schematic diagrams included in section 12 of this document.
Terminal strips shall allow easy maintenance access to each wire terminal. They shall be
segregated between:
Power circuits
AC control circuits
DC control circuits.
Terminals:
Power terminals : screw type up to 16 mm core section, with a cable lug for largercables ;
Control terminals : shall be of insulation displacement type (needing no special tool forcompleting the connection) or of spring type.
Connectors with plug and sockets (several stages if necessary) shall be provided forcontrol terminals of plug-in modules.
Auxiliary voltages distribution to the different circuits will preferably be by adequate
prefabricated busbars. These busbars shall be adequately insulated to prevent anyaccidental contact.
Control wires shall be flexible, 500 V PVC insulated with a minimum core section of 1 mm.
Each wire shall be labelled or marked up at each end with the number of the terminal it isconnected to, according to manufacturers standard procedures. Wires shall be installed intrunkings of adequate sections.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page8/33
Rev.A
7/30/2019 Electrical Standarts
9/33
A
2.1.8. Labels
Following labels shall be provided and installed :
Switchboard main label installed at the upper left front part of the switchboard andindicating the tag (Lafarge code) and the description of the switchboard.
Switchboard indicating plate installed just under the main label and indicating :manufacturer, year, rated voltage, rated insulating voltage, incoming and main bus barrated currents, short circuit withstand current.
Section (column) number label installed on the upper middle front part of each sectionor of its door.
Module (plug-in type) or drawer (draw-out type) tag label to be secured to the fixed partfacing to corresponding module or drawer, indicating the tag (Lafarge code) and thedescription of the circuit.
Labels shall be engraved in black - cored white dilophane and fixed by screws or rivets (glue
not accepted). Letters height shall be at least :
15 mm for the switchboard main label
6 mm for the incoming, bus-tie and outgoing circuits labels
4 mm for the auxiliary circuits.
2.2. DRAW-OUT / FIXED TYPES
The Owner will specify whether the switchboard shall be of draw-out or plug-in type.
2.2.1. Draw-out type
The switchboard shall be form 3b (at least).
Each outgoing circuit shall be at least Service Index 333:
Operation: control circuits can be tested with the power circuit off
Maintenance: after switching it off, any outgoing circuit module can be removed andinserted without switching off the switchboard
Evolution: new outgoing circuits can be installed without switching off the switchboard.
Each drawer shall have 4 positions:
Connected (power and control on)
Test (power of, control on)
Disconnected (power and control off)
Removed.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page9/33
Rev.A
7/30/2019 Electrical Standarts
10/33
A
It shall be possible to lock out each drawer in disconnected position by up to 3 padlocks.
Power circuits shall be automatically disconnected in disconnected positions, as well on
upstream side than on downstream side.
Control circuits shall be disconnected in removed position either automatically ormanually by disconnecting a plug where pass all the control circuits through. Suchdisconnection/reconnection operation shall not need the use of any tool.
A contact from the drawer shall inform the PCS (and the operator) that this circuit is
unavailable when the drawer is in disconnected or removed position.
A defeater (mechanical interlocking system) shall be installed on each fixed part and on
each drawer to prevent from introducing a drawer of an inappropriate type or rating.
Signalling lamps and instruments (current and active power indicators) shall be installed in
front of drawers.
2.2.2. Fixed type
The switchboard shall be of modular type form 2b (at least), except sections housing
incomers and bus-tie breakers which shall be form 3b.
Each outgoing circuit shall be mounted and wired on an individual metal sheet plate, also
modular and standardized. It shall be possible to install or remove such modules fullyequipped without dismantling the adjacent modules or other cubicle parts or accessories.
Each outgoing circuit shall be at least Service Index IS 322, which means :
Operation : control circuits can be tested with the power circuit switched off.
Maintenance : after switching it off any outgoing circuit module can be removed withoutswitching off the switchboard.
Evolution : new outgoing circuits can be installed, if spare spaces exist, withoutswitching off the switchboard.
This plate shall support power connectors to be plugged in the busbar. It shall also support a
connector for connecting all the control circuits of the module. No connection with anotheroutgoing circuit or with switchboard common circuits shall be performed without passingthrough these plugs and connectors.
Each modular plate shall also support signalling lamps and instruments (current and
active power indicators). Alternatively, these items can be installed and wired to the front
door. If signalling lamps and instruments are mounted on the plates, each switchboardsection supporting outgoing circuits shall be equipped with a safety glass door with a rubberseal.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page10/33
Rev.A
7/30/2019 Electrical Standarts
11/33
A
3. POWER SWITCHGEAR
3.1. INCOMERS AND BUS-TIE BREAKERS
The incomers and bus-tie breakers shall have their protection devices co-ordinated with
the outgoing circuit breakers to guarantee a good selectivity. On feeders already protectedon upstream side (for instance by a circuit breaker connected to the secondary winding of thefeeding transformer) power switches (or circuit breakers without protection relays) shall beinstalled to avoid unnecessary selectivity steps.
Each circuit breaker or power switch shall be of draw-out type. It shall be equipped with a
system for locking out with 3 padlocks.
Each circuit breaker or power switch shall also have a closing auxiliary contact (normally
open) for initiating an alarm when in open position.
Emergency busbar (when applicable) shall be supplied in normal condition from the mainbusbar; in case of power failure from the emergency generator. Changeover shall be by2 circuit breakers or contactors mechanically interlocked to avoid paralleling these 2 sources.
If neutral is isolated, an insulation check metershall be installed on incoming circuit, with
an alarm contact open on low insulation resistance.
An emergency shut-down push button (red mushroom to be turned for unlatching) shall be
installed on the incoming section (column) of the switchboard and wired to switchboardsterminals.
3.2. OUTGOING CIRCUITS
Each outgoing circuit shall be protected by a circuit breaker from short circuits and
instantaneous overcurrents; fuses are not accepted. This circuit breaker shall be capable towithstand the full short circuit current. Its protection system shall be co-ordinated with cablescore section and cables length according to IEC rules (short-circuit condition, overloadcondition, voltage drop, installation conditions, protections against indirect contacts, ...).
Its handle shall provide forlocking it out with up to 3 padlocks.
Each outgoing circuit to a motor shall be protected by a thermal overload protection. Such
protection can be provided by a separate overload relay tripping the contactor coil. It can alsobe integrated in the above mentioned circuit breaker. If separate from the circuit breaker, it
shall also be co-ordinated according to IEC rules (overload condition).
For protecting motors driving large inertia equipment with long start-up time such as fans with
a power of 11 kW or more, heavy duty starters orelectronic soft starters shall be used.
Each motor shall be operated by a contactor (or two contactors for two directions motors
and two speeds motors).
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page11/33
Rev.A
7/30/2019 Electrical Standarts
12/33
A
Each contactor shall be dimensioned for an AC-3 service according to IEC 60947-4 withfollowing derating: the contactor rated current shall be at least equal to :
150% of users rated current for motors up to 55 kW
130% of users rated current for larger motors.
Switchgear items of each outgoing circuit shall have a type 2 co-ordination according to
IEC standard, resulting in the absence of contacts welding and of damage on protectionsystem after any electrical failure.
The Supplier shall also check the compliance of equipment supplied with starting conditions
(magnetisation current, long starting time, )
Outgoing circuits shall be standardised in order to reduce quantities of spare parts to be
kept in the warehouse.
Protection functions (magnetic and thermal overload) and operating function can be grouped
in a combined equipment provided that the operated motor power does not exceed 22 kW. Considering all the switchboards included in the Supply, following spare outgoing circuits
shall be supplied (fully equipped) :
2 units for each rating of 1 direction motor feeder up to 15 kW
1 unit for each rating of:
- 1 direction motor feeder above 15 kW ;
- 2 directions motor feeder ;
- circuit breaker outgoing feeder.
The approval of the Owner shall be required on the choice of the switchboards where thesespare circuits will be installed.
4. CONTROL SWITCHGEAR AND MEASURING DEVICES
4.1. CONTROL CIRCUITS
On each incoming, bus-tie or outgoing circuit shall be installed two Miniature Circuit
Breakers :
1 MCB for protecting AC control circuits ;
1 MCB for protecting DC control circuits.
In case of a double busbar with a bus-tie, the three incoming/bus-tie circuit breakers/switches
shall have their trip coils interlocked to prevent any paralleling of sources.
The KA relay that controls the contactor kW shall be of safety relay type (IEC).
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page12/33
Rev.A
7/30/2019 Electrical Standarts
13/33
A
A
A no-volt relay shall be installed in the incomer compartment; this relay equipped with a timer
(0 to 1 sec) shall cut off the contactors auxiliary voltage 230 VAC (recommended setting 0.5sec). The contact of this relay shall be connected in the series with the emergency shut-downcontacts.
In case of an emergency busbar an automatic switchover system shall be supplied to
change the sources in case of power failure and when the power is back. Auxiliary contactsof the switchboard system shall be wired to switchboards terminals in order to inform thePCS.
Each outgoing circuit shall be equipped with signalling lamps indicating :
Green:
- running direction 1 / speed 1
- running direction 2 / speed 2 (if applicable)
Yellow: Circuit available (drawer in operation position, power switch and/or circuitbreaker closed, thermal overload protection in normal position, auxiliary voltages MCBs
closed)
Red: Trip (circuit breaker and thermal relay).
These lamps shall use Light Emitting Diodes (bulbs with a filament are not accepted).Lamp colours are shown on Lafarge standard schematic diagrams (please refer to section12).
Unless otherwise mentioned in the Site Specification, each control circuit (and each alarm
circuit) shall be connected to Remote Digital Input/Output modules to be installed on top of
each switchboard section (column) in a closed compartment isolated by a metal sheet fromthe rest of the section. These modules will communicate with the PCS. Unless otherwisementioned, the supply of these RI/O modules and their associated devices (power supply,connectors, ...) is not included in this scope of work. This in order to minimise site cablingand be able to perform a maximum of tests at the workshop.
Alternatively, for incoming circuits, the metering units mentioned in section 4.2 can beused for the transmission of their control signals to the plant control system.
When required by the Site Specification, the switchboard shall be intelligent. Each incoming
and each outgoing circuit shall be controlled by a fieldbus connected to the PCS. It shall bepossible to modify the parameters of these circuits through this fieldbus.
Each outgoing circuit shall be wired up in accordance with the Lafarge standard schematic
diagrams under section 12. Inter allia, terminals shall be supplied for connecting local STARTand STOP commands from the VCS supplied by others.
4.2. PROTECTIONS
Following alarms shall be made available to the PCS :
Incoming/bus-tie breaker is in off position (please refer to section 3.1);
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page13/33
Rev.A
7/30/2019 Electrical Standarts
14/33
A
MCB protecting AC control circuits is in off position (please refer to section 4.1);
MCB protecting DC control circuits is in off position (please refer to section 4.1);
Insulation resistance too low if an insulation checkmeter is installed at the incoming feeder
(please refer to section 3.1).
The emergency shut-down push-button installed on incoming section (please refer to section 3.1)will trip the MV circuit breaker feeding the transformer supplying this switchboard (cabling to beperformed by the cabling contractor).
4.3. MEASURING DEVICES
Every current transformershall have a secondary winding rated for 1 A, and shall withstand
the maximum possible short circuit current.
An electrical parameters metering unit shall be installed on each incoming circuit. Thisshall measure at least following parameters : 3U, 3V, 3I, P, Q, S, f and PF and display theseparameters (according to operator selection).This unit shall also meter active and reactive energies and provide a pulse output for activeenergy.
This metering unit shall also monitor the presence of the three phases and send analarm through the fieldbus (see below) in the absence of one or several phases, or in case offailure of this device.It shall include communication with the PCS by a fieldbus PROFIBUS DP. On this fieldbusshall be made available all above measurements and alarms.
Every outgoing circuit supplying a motor with a power of 30 kW or more or a material
handling equipment (screw conveyor, bucket elevator, chain conveyor, belt conveyor, ) ofany power shall be equipped with a current transducer converting the full motor currentrange in a 4-20 mA DC signal connected to the plant control system through outgoingterminals and to a current indicatorinstalled on the drawer front/plate or adjacent to it.
The current transducer and the current indicator shall be replaced by an active power
transducerand an active power indicatorfor bucket elevators and for cooler drag chains.
5. PCC/MCC SUPPLYING VSDS
These LV boards shall be provided with two motorised incoming circuit breakers supplying
two separate 3-phase busbars (please refer to the diagram indicated in section 12). Theirsimultaneously switching-on and switching-off shall be ensured by a dedicated control circuit.
Each 3-phase incoming feeder shall be provided with following protections :
A surge protection on each phase
An insulation check meter
The outgoing circuits supplying VSDs shall be equipped with fast fuses.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page14/33
Rev.A
7/30/2019 Electrical Standarts
15/33
A
A
The loads of each bus barshall be balanced as far as possible. A single line diagram of the
switchboard shall be submitted to the Owners approval.
6. POWER FACTOR CORRECTION UNITS Unless otherwise specified, a power factor correction unit shall be supplied with each set of
PCC/MCC. The reactive power of this unit shall be calculated so to increase the power factorof the switchboard from natural value (typically 0.7) up to 0.92 unless more stringentrequirements from the Site Specification.
Following table indicates the minimum rated power required for power factor correction units
according to the transformer rated power supplying this set of PCC / MCC:
Feeding transformer ratedpower(kVA)
Power factor correctionunit rated power required
(kVAR)
630 275
1000 425
1250 520
1600 675
2000 850
2500 1050
This power factor correction unit shall be of automatic type, connecting or disconnecting thecapacitor banks by steps according to power factor fluctuations. Steps shall not exceed50 kVAR each. All the capacitor banks shall be identical.
It shall be housed in a separate cabinet to be installed either at the end of the PCC or MCC
or behind their incoming section. This cabinets look shall match as much as possible withthe PCC or MCC.
It shall be connected to corresponding PCC or MCC by an outgoing circuit breaker of
appropriate rating.
It shall be designed in order to be remotely turned on and off.
The protection against harmonic currents will be considered taking into account the ratio kbetween the power of harmonics generated and the power of the transformer feeding thePCC/MCC :
k < = 15% : no harmonic protection required
k > 15% and < = 25% : reinforced type is required
k > 25% and < = 50% : anti-harmonic inductances are required
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page15/33
Rev.A
7/30/2019 Electrical Standarts
16/33
k > 50% : anti-harmonic filters are required
The type of protection against harmonic currents shall be submitted to the Owners approval.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page16/33
Rev.A
7/30/2019 Electrical Standarts
17/33
A
The protection fuses shall be provided with a trigger , with trip local signalisation and one
NC contact for remote alarm.
Each unit shall be equipped with discharge resistors for operators safety.
Note: For new department electrical distribution, at least, reinforced type is required.
7. DOCUMENTS
7.1. DOCUMENTS TO BE SUPPLIED BY THE OWNER
Site Specification which details site conditions, voltages,
Particular Specification : this document, complemented with a single line diagram if
required, shall specify, when not mentioned in the Site Specification :
draw-out or plug-in type
sections arrangement back-to-back or in one row
incoming (stand-by) rated currents
short circuit current to be considered for each board
emergency busbar rated current (if applicable)
power factor correction unit rated power required or power factor to be achieved withall the users in operation.
Consumers List specifying for each user : rated power
rated current
rated voltage
type of circuit (with/without contactor, one way/two ways, normal/heavy start)
accessories (current/active power transducer and indicator)
power cable core section (the Supplier to mention when it needs this document).
7.2. DOCUMENTS TO BE PREPARED BY THE SUPPLIER
Following documents shall be prepared in English (unless otherwise stated in the SiteSpecification) in accordance with the requirements of specification STD.002.U02.
Single Line Diagram giving references of upstream equipment : feeders tag numbers,
upstream single line diagrams, ...
Selectivity Study demonstrating that protections are effective and co-ordinated.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page17/33
Rev.A
7/30/2019 Electrical Standarts
18/33
A
A
Lay-Out of each switchboard with dimensions and position of each circuit.
Lay-Out of each module(Typical)
Civil Works Guide Drawing for each switchboard.
Typical Detailed Schematic Diagrams for each circuit type (including auxiliary circuits).
These diagrams shall also mention the number of every terminal.
Interlocking Diagrams if applicable.
Equipment list of Switchgear installed with technical details.
Application software of each programmable equipment.
Interface tables of exchange (addresses clearly indicated) of each programmable
equipment.
Manufacturing Time Schedule.
Installation and Maintenance leaflets.
Recommended Spare Parts Lists :
for commissioning
for 2 years operation.
7.3. DOCUMENTS TO BE SUBMITTED WITH THE OFFER
Following documents shall be submitted in English with bid:
Detailed specification of the proposed equipment
Technical characteristics of each switchboard
Front face and dimensions of each switchboard
Type tests certificates according IEC 60439-1 for:
Icc 50 kA 1s
Ingress protection certificate.
8. FACTORY TESTS
The Supplier shall notify the Owner not less than 14 days prior to the testing period, in order thatthe Owner may, should he think it necessary, delegate a representative to witness these tests.
Following tests shall be performed on each switchboard, according to IEC 60439-1 standard,completely assembled except main busbars connections between sections which are to beseparately packed for despatch and a detailed test procedure be submitted to the Owner priorstarting the tests.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page18/33
Rev.A
7/30/2019 Electrical Standarts
19/33
Measuring insulation resistances (power and control circuits)
Dielectric tests (power and control circuits)
Operation tests
Check of interlockings and safety devices
Check of drawers interchangeability (if applicable)
Check of dimensions and accessories.
The Supplier shall also supply copies of type test reports proving the short circuit withstand of theswitchboard.
All these factory tests/type tests will be performed at the Supplier's expenses.A detailed test report shall be prepared by the Supplier and handed over to the Ownersrepresentative or mailed to the Owner if it has not witnessed the tests.
9. GUARANTEE
Minimum required guarantee is 24 months after commissioning, with a maximum of 30 monthsafter the switchboards are ready for factory tests.
10. DATA SHEETS
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page19/33
Rev.A
7/30/2019 Electrical Standarts
20/33
CUSTOMER: SUPPLIER :PROJECT:
DATA SHEET PROJECT No:POWER CONTROL CENTRE, MOTORCONTROL CENTRE
OFFER:
EQUIPMENT: DATE :
Type
1
Draw-out/Plug-in
2 Protection degree IP
3 Segregation Form
4 Service index ISManufacturer
5 Cabinets
6 Switchgear
Service conditions
7
Rated voltage V
8
Insulation voltage V
9 Short-time withstand current kA
Incoming circuit
10
Rated current of main circuit breaker A
11 Short circuit current of main circuit breaker kA12 Feeder by busbar/cables
13 Measurement device14 Insulation checkmeter (if applicable)
Busbars15 Main busbars (horizontal) rated current A
16 Material / cross section17 Secondary busbars (vertical) rated current A
18 Material / cross section19 Maintenance required
Control
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page20/33
Rev.A
7/30/2019 Electrical Standarts
21/33
20 Remote I/O modules / intelligent switchboard
Accessories
21 Anti-condensation heaters required Yes/No22 Others Yes/No
Dimensions23 Switchboard height mm24 Switchboard depth mm
25 Switchboard length mm26 Cable channel width mm
Painting27 Preparation
28 Finish
29 Deviations from this specification
CUSTOMER: SUPPLIER :PROJECT:
DATA SHEET PROJECT No:LV POWER FACTOR CORRECTION UNIT OFFER:
EQUIPMENT: DATE :
1 Type
2 Manufacturer
3 Rated voltage V
4 Insulation voltage V
5 Total capacity kVAr
6 Capacity of each step kVArPower factor regulation V
7 Regulation load relays in each unit Yes/No8 Remote turn on and off Yes/No
Protection against harmonic currents9 Reinforced protection Yes/No10 Anti-harmonic inductance Yes/No
11 Anti-harmonic filters Yes/No
Dimensions12 Cabinet height mm13 Cabinet depth mm
14 Cabinet length mmPainting
15 Preparation
16
Finish
17 Deviations from this specification
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page21/33
Rev.A
7/30/2019 Electrical Standarts
22/33
Notes:
1. Values to be mentioned in boxes marked with sign are to be given by the Owner or bythe main Contractor.
2. The Supplier is requested to fill in a data sheet for each type of equipment proposed andto return it with its proposal.
11. SWITCHGEAR SELECTION TABLES
11.1.SWITCHGEAR SELECTION FOR 400 V MOTORS USING LINE STARTERS
P (kW)Current
(A)Contactor Thermal C-breaker* CT Ratio
0.25 0.8 25 0.63 to 10.37 1.1 25 1.00 to 1.6
0.55 1.6 25 1.00 to 1.6
0.75 2 25 1.60 to 2.5
1.1 2.5 25 1.60 to 2.5
1.5 3.3 25 2.50 to 4.0
2.2 4.6 25 4.00 to 6.0
3 6.0 25 4.00 to 6.0
4 8.4 25 7.00 to 10
5.5 11 25 10.0 to 13
7.5 15 25 13.0 to 18
11 20 40 18.0 to 25 15 28 40 23.0 to 32
18.5 34 63 30.0 to 40
22 40 63 38.0 to 50
25 47 80 0.63 to 1 50/1
30 55 80 " 60/1
37 66 115 " 100/1
55 100 185 " 125/1
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page22/33
Rev.A
7/30/2019 Electrical Standarts
23/33
75 128 185 " 150/1
90 156 265 " 200/1
110 205 265 " 250/1
132 224 400 " 250/1
160 280 400 " 300/1200 349 400 400/1
250 434 630 630/1
Up to 63 A, circuit breakers are equipped with thermal overload and magnetic protection circuitsrated for standard motors.
* to be filled by MCC Supplier for type 2 co-ordination (please refer to section 7.2). Thenumber of circuit breaker sizes will be limited to reduce spare part stock.
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page23/33
Rev.A
7/30/2019 Electrical Standarts
24/33
11.2.SWITCHGEAR SELECTION FOR 500 V MOTORS USING LINE STARTERS
P (kW) Current(A)
contactor Thermal C-breaker* CT ratio
0,25 0,8 25 0,63 to 1
0,37 1,1 25 1,00 to 1,6
0,55 1,6 25 1,00 to 1,6
0,75 2 25 1,60 to 2,5
1,1 2,5 25 1,60 to 2,5
1,5 3,3 25 2,50 to 4
2,2 4,6 25 4,00 to 6
3 6 25 4,00 to 6
4 8,4 25 7,00 to 10
5,5 11 25 10,00 to 137,5 15 25 13,00 to 18
11 20 40 18,00 to 25
15 28 40 23,00 to 32
18,5 34 63 30,00 to 40
22 40 63 38,00 to 50
25 47 80 0,63 to 1 50/1
30 55 80 " 60/1
37 66 115 " 80/1
45 80 185 " 100/1
55 100 185 " 125/1
75 128 185 " 150/190 156 265 " 200/1
132 224 400 " 250/1
160 280 400 " 300/1
Up to 63 A, circuit breakers are equipped with thermal overload and magnetic protection circuitsrated for standard motors.
* to be filled by MCC Supplier for type 2 co-ordination (please refer to section 7.2). Thenumber of circuit breaker sizes will be limited to reduce spare part stock.
12. DIAGRAMS
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page24/33
Rev.A
7/30/2019 Electrical Standarts
25/33
MCC single line diagrams in 2 versions :
Either the emergency generator feeds the essential users through the normal busbar ofthe MCC and the load shedding of the other users is controlled by the PCS.
Or the MCC is equipped with an emergency busbar for feeding the essential usersfrom the emergency generator, the other users being connected to the normal busbarnot fed from the emergency generator.
Lafarge standard schematic diagrams of 5 types :
K1 : motor one direction
K2 : motor two directions
KM : actuator 2 positions
VS : variable speed drive (VSD installed inside the MCC)
Q : circuit breaker supplying a package such as a crane panel,
For each schematic diagram following facilities shall be specified by following suffixes:
E : emergency shut-down (pull-rope, push-button)
I : current measurement
J : power measurement
S : speed monitor
H : heavy start.
Examples :
Belt conveyor : K1 EIS
Fan, Pmot > 30 kW, direct start : K1 IH
Kiln motor : VS I
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page25/33
Rev.A
7/30/2019 Electrical Standarts
26/33
MOTORCONTROLCENTRE
TypicalsinglelinediagramwithoutLVemergencysupply
I
PE
MODULE(KY)
MEASURING
3
By-Pass
CONSUMERS
FEEDINGESSENTIAL
230Vac
400V
Auxiliary
Transformer 2
30Vac
UPS(UP)
STEPREGULATIONACCORDINGTOPF&LOAD
CAPACITORBANK
MOTORSTARTERMODULES
MEDIUM/LOW
VOLTAGE
DISTRIBUTIONTRANSFORMER(TF)
PACKAGE
(TF)
MainHorizontalBusbars
NOTDISTRIBUTED
NEUTRALCONDUCTOR
TN-SNETWORK
INCOMINGFEEDER
I
I
I
I
I
I
I
I
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page26/33
Rev.A
7/30/2019 Electrical Standarts
27/33
V
G3
EMERGENCY
GENERATOR
Emergency
HorizontalBusbars
I
I
I
I
I
I
I
I
MOTORCONTROLCENTRE
TypicalsinglelinediagramwithLVemergencysupply
I
PE
MODULE(KY)
MEASURING
3
By-Pass
CONSUMERS
FEEDINGESSENTIAL
230Vac
400V
Auxiliary
Transform
er
2
30Vac
UPS(UP)
STEPREGULATION
ACCORDINGTOPF&LOAD
CAPACITORBANK
MOTORSTARTERMODULES
NOTDISTRIBUTED
NEUTRALCONDUCTOR
TN-SNETWORK
MEDIUM/LOWV
OLTAGE
DISTRIBUTIONTRANSFORMER(TF)
PACKAGE
(TF)
MainHorizontalBusbars
INCOMINGFEEDER
PE
3
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page27/33
Rev.A
7/30/2019 Electrical Standarts
28/33
Fastfuses
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
3
3
IM
Surgearrester
3
3
1000A
1000A
MV/LV
transformer
MOTORCONTROLCENTRE
MCC316MC13-V
SDKilnDownstream(example)
318HE01MT21
318HE01MT18
318HE01MT15
318HE01MT12
IM-I
nsulationMonitoring
Note:fastfusesforVSDprotection
110kW
317FA07MT10
IM
3*30kW
318HE01MT19
318HE01MT20
Busbar1
Busbar2
3*30kW
3*30kW
3*30kW
132kW
75kW
75kW
316AB13MT10
318HE01MT10
318HE01MT13
318HE01MT16
318HE01MT11
318HE01MT14
318HE01MT17
317FA05MT10
317FA03MT10
400V
M
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page28/33
Rev.A
7/30/2019 Electrical Standarts
29/33
MOTORCONTROLCENTRE
Typicalschematicdiagram-Motor1direction-K1type
DrawerorPla
te
I/OCompartment
MarshallingBoard
Othermachinesensors
MotorCurrentorPower
XXnn
YI
Digitalinput
Analogueinput
Speedswitch
XS
2
4Vdc
S
Speedmonitor
230Vac
-Q1
-KB
400V
-KM1
-F1
/
3M
Cable-Loop
Field
VisibleCut-offSwitch
-KM1
-KA1
Heavystart(ifany)
H I J
Currentmeasureor
Powermeasure
3Padlocks
ToQ1Trip
+24Vdc
0V
-KA1
-KB
-KM1
-F1
Yellow
Green
Red
HS
L1
LS
E
EmergencyShut-Down
1
3
44
3
1
8
7
Pre-Cutoff
LocalStart
Availability
Feedback
B1
AV
L1
Digitaloutput
Digitalinput
LS
EmergencyShut-Down
HS
LocalStop
MotorOperatingMode:
ChoiceofSequential/Localmodeismadebyoperator
ontheOperatorStation
StartCommand
C1
2
-Q1
Trip
2
pullrope
-Q11
-Q12
Precut-off
Available
Running
Failure
3 247110
12
(ifapplicable)
1
3
4
7
4
3
1
2
3 247110
12
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page29/33
Rev.A
7/30/2019 Electrical Standarts
30/33
LocalStop
MotorOperatingMode:
ChoiceofSequential/Localmodeismadebyoperator
ontheOperatorStation
S
Speedmonitor
Heavystart(ifany)
H I J
Currentmeasureor
Powermeasure
E
EmergencyShut-Down
1
4
55
4
1
10
11
10
11
3 2
3
2
8
7
3Padlocks
Pre-Cutoff
ToQ1Trip
0V
-Q11
-Q12
Precut-off
Available
Running
Direction1
Failure
pullrope
23 541
1
1
0
RunningDirection2
1
3
1
2 1 87
(ifapplicable)
1
4
5
10
11
3 2
7
-KM1
-KA1
-KM2
MOTORCONTROLCENTRE
Typicalschematicdiagram-Motor2directions-K2type
230Vac
-Q1
-KM2
-KB
400V
-KA2
-KM1
-F1
/
+24Vdc
-KA2
-KB
-KM1
-F1
-Q1
Trip
Yellow
Green
Red
DrawerorPlate
I/O
Compartment
StartCommandDirection1
LocalStartDirection1
Availability
FeedbackDirection1
LocalStartDirection2
B1
AVC
1L1
L2
3M
Cable-Loop
HS
Digitaloutput
Digitalinput
MarshallingBoard
Othermachinesensors
MotorCurrentorPower
XXnn
YI
Digitalinput
Analogueinput
Field
VisibleCut-offSwitch
Speedswitch
XS
-KM1
-KM2
-KM2
Green
FeedbackDirection2
B2
LS
-KA1
StartCommandDirection2
C2
Emergency
Shut-Down
HS
L1
L2
LS
24Vdc
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page30/33
Rev.A
7/30/2019 Electrical Standarts
31/33
MOTORCONTROLCENTRE
Typicalschematicdiagram-Actuator2positions-KMtype
230Vac
-Q1
400V
-F1
+24Vdc
-KA2
-KB
-KM1
-F1
-Q1
Trip
Yellow
Green
Red
DrawerorPlate
I/O
Compartment
StartCommandDirection1
(open)
LocalStartDirection1(open)
Availability
LocalStartDirection2(close)
AVC
1L1
L2
-KM2
Precut-off
1
3
1
2
1
47 8115
4
5
10
119 3
8
71
-KM2
-KB
-KA2
-KM1-
KM1
-KA1
-KM2
3M
Cable-Loop
Digitaloutput
Digitalinput
MarshallingBoard
Othermachinesensors
XXnn
Digitalinput
Analoginput
Field
VisibleCut-offSwitch
-KM2
Green
LS
XZ20
XZ10
-KA1
StartCommandDirection2
(close)
C2
XX10
L1
L2
LS
24Vdc
XZ10
Position1
XZ20
Position2
Torque
switch
Position1switch(open)
Torqueswitch(ifany)
LocalStop
Position2switch(close)
MotorOperatingMode:
ChoiceofSequential/Localmodeismadebyoperator
ontheOperatorStation
1
4
55
4
1
10
11
9
10
119 3
3
8
7
Actuator
3Padlocks
Pre-Cutoff
ToQ1Trip
0V
Analogueoutput
Positionsetpoint
ZC
PositionFeedback
YZ10
FeedbackDirection1
B1
FeedbackDirection2
B2
34
591
1
1
0
Available
Running
Direction1
Failure
RunningDirection2
-KM1
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page31/33
Rev.A
7/30/2019 Electrical Standarts
32/33
LocalStart
Availability
Feedback
B1
AV
L1
Digitaloutput
Digitalinput
LS
Emergency
Shut-Down
HS
LocalStop
MotorOperatingMode:
ChoiceofSequential/Localmodeismadebyoperator
ontheOperatorStation
StartCommand
C1
2
-Q1
Trip
2
-KA1
-C1
Speedfeedback
YS
Speedset-point
SC
ToVSD
insideMCC
LU
LocalSpeed-up
LD
LocalSpeed-down
LU
161
6 LD
66
FieldbustoPCScontroller
230VUPS
-Q11
-Q13
-Q12
-KM1
Available
Running
Failure
Precut-off
pullrope
261641
0
Note:fastfusesforVSDprotection
31 712
MOTORCONTROLCENTRE
Typicalschematicdiagram-Motorspeedvariation-VStype
DrawerorPlate
I/OCompartment
MarshallingBoard
MotorCurrentorPower
YI
Analoginput
Analogueoutput
230Vac
-Q1
-KB
400V
-F1 3
M
Cable-Loop
Field
VisibleCut-offSwitch
-KM1
-KA1
3Padlocks
ToQ1Trip
+24Vd
c0V
-KA1
-KB
-KM1
-F1
Yellow
Green
Red
HS
L1
LS
E
EmergencyShut-Down
1
3
44
3
1
8
7
Pre-Cutoff
(ifapplicable)
POWER CONTROL CENTRES,MOTOR CONTROL CENTRES
DocumentSTD.002.U07
Page32/33
Rev.A
7/30/2019 Electrical Standarts
33/33
MOTORCONTROLCENTRE
Typicalschematicdiagram-Packagecircuitbreaker-Qtype D
rawerorPlate
I/OCompartment
M
arshallingBoard
CurrentorPower
YI
Analogueinput
Q1
400Vac
/
Field
VisibleCut-offSwitch
I J
Currentmeasureor
Powermeasure
3Padlocks
Availability
AV
Digitalinput
PACKAGE
2
4Vdc