Electrical Service Types and Voltages This page describes various types of utility electrical services and supply voltages. The nominal system supply voltages listed below can vary by ±10% or more. WattNode ® meter models are available in seven different versions that cover the full range of electrical services types and voltages. Meters and current transformers are designed for use on either 50 or 60 Hz systems. Classification of Electrical Services Alternating current electric power distribution systems can be classified by the following properties: Frequency: 50 Hz or 60 Hz Number of phases: single or three phase Number of wires: 2, 3, or 4 (not counting the safety ground) Neutral present: Wye connected systems have a neutral Delta connected systems typically do not have a neutral Voltage levels: Low Voltage: 600 volts or less Medium Voltage: 601 volts to about 34,500 volts High Voltage: 46,000 volts and up Wye Line-to-Neutral Voltage Wye or Delta Line-to-Line Voltage 120 208 120 240 230 400 240 415 277 480 347 600 Line-to-line voltages are typically 1.732 times the phase-to-neutral voltages: In symmetrical three-phase electrical system, the phase-to-neutral voltages should be equal if the load is balanced. Common Electrical Services & Loads In the following drawings, the coil symbols represent the secondary winding of a utility service transformer or other step down transformer. Electrical code regulations in most jurisdictions require that the neutral conductor be bonded (connected) to the earth safety ground at the electrical service entrance. Single Phase Three Wire Also known as an Edison system, split-phase or center-tapped neutral. This is the most common residential service in North America. Line 1 to neutral and Line 2 to neutral are used to power 120 volt lighting and plug loads. Line 1 to Line 2 is used to power 240 volt single phase loads such as a water heater, electric range, or air conditioner. Three Phase Four Wire Wye The most common commercial building electric service in North America is 120/208 volt wye, which is used to power 120 volt plug loads, lighting, and smaller HVAC systems. In larger facilities the voltage is 277/480 volt and used to power single phase 277 volt lighting and larger HVAC loads. In western Canada 347/600V is common. Electrical Service Types and Voltages | Continental Control Sy... http://www.ccontrolsys.com/w/Electrical_Service_Types_an... 1 of 3 02/08/14 2:02 AM

Electrical Service Types and Voltages | Continental Control Systems

Embed Size (px)

DESCRIPTION

Electrical Services

Citation preview

Page 1: Electrical Service Types and Voltages | Continental Control Systems

Electrical Service Types and VoltagesThis page describes various types of utility electrical services and supply voltages. The nominal system supply voltages listed below canvary by ±10% or more. WattNode® meter models are available in seven different versions that cover the full range of electrical servicestypes and voltages. Meters and current transformers are designed for use on either 50 or 60 Hz systems.

Classification of Electrical ServicesAlternating current electric power distribution systems can be classified by the following properties:

Frequency: 50 Hz or 60 HzNumber of phases: single or three phaseNumber of wires: 2, 3, or 4 (not counting the safety ground)Neutral present:

Wye connected systems have a neutralDelta connected systems typically do not have a neutral

Voltage levels:Low Voltage: 600 volts or lessMedium Voltage: 601 volts to about 34,500 voltsHigh Voltage: 46,000 volts and up

Wye Line-to-NeutralVoltage

Wye or Delta Line-to-LineVoltage

120 208

120 240

230 400

240 415

277 480

347 600

Line-to-line voltages are typically 1.732 times the phase-to-neutral voltages: In symmetrical three-phase electrical system, the phase-to-neutral voltages should be equal if the load is balanced.

Common Electrical Services & LoadsIn the following drawings, the coil symbols represent the secondary winding of a utility service transformer or other step downtransformer. Electrical code regulations in most jurisdictions require that the neutral conductor be bonded (connected) to the earthsafety ground at the electrical service entrance.

Single Phase Three WireAlso known as an Edison system, split-phase or center-tapped neutral. This is the most commonresidential service in North America. Line 1 to neutral and Line 2 to neutral are used to power 120 voltlighting and plug loads. Line 1 to Line 2 is used to power 240 volt single phase loads such as a waterheater, electric range, or air conditioner.

Three Phase Four Wire WyeThe most common commercial building electric service in North America is 120/208 volt wye, which is used to power 120 volt plug loads,lighting, and smaller HVAC systems. In larger facilities the voltage is 277/480 volt and used to power single phase 277 volt lighting andlarger HVAC loads. In western Canada 347/600V is common.

Electrical Service Types and Voltages | Continental Control Sy... http://www.ccontrolsys.com/w/Electrical_Service_Types_an...

1 of 3 02/08/14 2:02 AM

Page 2: Electrical Service Types and Voltages | Continental Control Systems

Three Phase Three Wire DeltaUsed primarily in industrial facilities to provide power for three-phase motor loads, and in utilitypower distribution applications. Nominal service voltages of 240, 400, 480, 600, and higher aretypical.

Uncommon Electrical Services

Three Phase Four Wire DeltaAlso known as a high-leg or wild-leg delta system. Used in older manufacturing facilitieswith mostly three-phase motor loads and some 120 volt single-phase lighting and plugloads. Similar to the Three Phase Three Wire Delta discussed above but with acenter-tap on one of the transformer winding to create neutral for 120 volt single-phaseloads. Motors are connected to phase A, B, and C, while single-phase loads areconnected to either phase A or C and to neutral. Phase B, the high or wild leg, is notused as the voltage to neutral is 208 volt.

Three Phase Two Wire Corner-Grounded DeltaUsed to reduce wiring costs by using a service cable with only two insulated conductors ratherthen the three insulated conductors used in a convention three phase service entrance.

International Electrical Distribution Systems

DescriptionL–NVac

L–LVac

CountriesWattNode Models

(Wye or Delta–Voltage)

1-Phase, 2-Wire 120 V with neutral 120 - US 3Y-208

1-Phase, 2-Wire 230 V with neutral 230 - EU, Others 3Y-400

1-Phase, 2-Wire 208 V (No neutral) - 208 US 3D-240

1-Phase, 2-Wire 240 V (No neutral) - 240 US 3D-240

1-Phase, 3-Wire 120/240 V 120 240 US 3Y-208

3-Phase, 3-Wire 208 V Delta (No neutral) - 208 US 3D-240

3-Phase, 3-Wire 230 V Delta (No neutral) - 230 Norway 3D-240

3-Phase, 3-Wire 400 V Delta (No neutral) - 400 EU, Others 3D-400

3-Phase, 3-Wire 480 V Delta (No neutral) - 480 US 3D-480

3-Phase, 3-Wire 600 V Delta (No neutral) - 600 US, Canada none1

3-Phase, 4-Wire 208Y/120 V 120 208 US 3Y-208, 3D-240

3-Phase, 4-Wire 400Y/230 V 230 400 EU, Others 3Y-400, 3D-400

Electrical Service Types and Voltages | Continental Control Sy... http://www.ccontrolsys.com/w/Electrical_Service_Types_an...

2 of 3 02/08/14 2:02 AM

Page 3: Electrical Service Types and Voltages | Continental Control Systems

Copyright © 2009-2014 Continental Control Systems, LLC. All rights reserved. Page updated 7 April 2014

3-Phase, 4-Wire 415Y/240 V 230 415 Australia 3Y-400, 3D-400

3-Phase, 4-Wire 480Y/277 V 277 480 US 3Y-480, 3D-480

3-Phase, 4-Wire 600Y/347 V 347 600 US, Canada 3Y-600

3-Phase 4-Wire Delta 120/208/240Wild Phase

120,208

240 US 3D-240

3-Phase 4-Wire Delta 240/415/480Wild Phase

240,415

480 US 3D-480

1By using potential transformers (PTs), WattNode meters can measure 600 volt delta services as well as medium and high voltageservices.

QuestionsDo 3Y-600 and 3D-600 appear in the US or only in Canada?

Yes, wye and delta 600 volt services are used in both countries but in the US they are less common.What services are used in Canada?

Mostly 208Y/120 volt and 600Y/347 volt wye services and occasionally 600 volt delta too.

See AlsoTwo Phase Electrical ServiceThree-Phase Grounded Delta CircuitsFour Wire Delta CircuitsUsing Potential Transformers