  • Electrical Engineering Ins�tute Nikola Tesla Koste Glavinica 8a, Belgrade, Serbia

    www.ieent.org [email protected]

    Decontamination of PCB Contaminated Electrical Equipment Using INT Process for Simultaneous Dechlorination, Desulphurization and Regeneration of Mineral Insulating Oils

    Implementation period: 2015-2018 Location: Republic of Serbia, Power Sector Task: Eliminate PCB’s in RS acc. to NIPPCB’s in Electrical Equipment

    C(PCB) = 50-500 mg/kg

    C (PCB) >500 mg/kgStockholm Convention PCB limited to 50 mg/kg in electrical equipment in service New equipment and oils PCB free

    Sources of PCB Contamination • Oil treatments (oil tanks, machines for oil

    treatment) • Oil change and topping up (oil tanks, machines

    for oil treatment) • Repair of transformers (TR workshops and

    factories, oil tanks) Section 1 Section 2 Section 3 Section 4 Section 5

    WWaassttee

    11

    ((uusseedd

    rreeaaggeennttss

    aanndd

    iinnoorrggaanniicc

    cchhlloorriiddeess,,

    wwiitthhoouutt

    PPCCBB))

    WWaassttee

    22

    ((uusseedd

    aaddssoorrbbeenntt

    wwiitthh

    ttrraacceess

    ooff

    ooiill

    wwiitthhoouutt

    PPCCBB))

    MMiixxiinngg

    &&HHeeaattiinngg

    PPCCBB

    CCoonnttaammiinnaatteedd

    OOiill

    OOiill

    wwiitthhoouutt

    PPCCBB

    rree--rreeffiinneedd,,

    rreeaaddyy

    ttoo

    uussee

    iinn

    eell..eeqquuiippmmeenntt

    RReeaaggeennttss

    pprreeppaarraattiioonn

    SSeeppaarraattiioonn

    ((ooiill

    ffrroomm

    rreeaaggeennttss))

    OOiill

    rreeggeenneerraattiioonn

    ((ppuurriiffiiccaattiioonn

    bbyy

    aaddssoorrbbeennttss))

    OOiill

    rreeccoonnddiittiioonniinngg

    ((rreemmoovvaall

    ooff

    mmooiissttuurree

    aanndd

    ppaarrttiicclleess))

    CChheemmiiccaall

    RReeaaccttiioonnss

    DDeecchhlloorriinnaattiioonn

    pprroocceessss

    DDeessuullffuurriizzaattiioonn,,

    ooiill

    rree--rreeffiinniinngg

    INT patented technology (RS 53510) for Simultaneous Oil Dechlorination, Desulphurization and Regeneration of Mineral Insulating Oils • Removal of PCB, Corrosive Sulphur

    and Oil ageing products • Improved Oil properties after

    treatment

    PCB Decontamination Unit

    Capacity: 1500 -2000 kg/day

    PCB Conversion

    0

    100

    200

    300

    400

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

    oil batch

    P C

    B in

    it ia

    l, p

    p m

    0

    5

    10

    15

    20

    25

    30

    35

    40

    45

    50

    P C

    B fi

    n a

    l, p

    p m

    C PCBo, ppm

    C PCB fin., ppm

    Results of PCB Decontamination

    Process flow

    On Site Laboratory PCB BDV DDF IFT

    CONCLUSION • INT process is efficient in the removal of PCB,

    corrosive sulphur and ageing products from mineral insulating oils

    • After treatment Oils and transformers have “extended life” and improved properties for further use

    • INT process can be used for treatment of mineral oils and equipment after “end of life” (waste treatment)

    J. Lukić*, J. Janković, D. Mihajlović, V. Vasović, S. Milosavljević

    *[email protected], +381648259711