29
DATE: 30-01-15 PROJECT: ASPIRE INTERNATIONAL SHOOL SERVICES: ELECTRICAL SYSTEMS PRICE SUMMARY SR. NO. DESCRIPTION AMOUNT AMOUNT IN WORDS HT WORK A) RING MAIN UNIT B) SUBSTATION C) HT ABLE D) SUBSTATION AUXILARIES E) APFC PANEL F) DG SYSTEM G) LV SWITCHBOARDS H) LT CABLING I) POINT WIRING ### J) DISTRIBUTION BOARD K) ELV SYSTEM L) UPS M) LIFT N) EARTHING O) LIGHT FITTINGS P) LIGHTNING ARRESTOR In words: TOTAL

Electrical Boq

  • Upload
    aniket

  • View
    223

  • Download
    2

Embed Size (px)

DESCRIPTION

boq

Citation preview

Page 1: Electrical Boq

DATE: 30-01-15

PROJECT: ASPIRE INTERNATIONAL SHOOL

SERVICES: ELECTRICAL SYSTEMS

PRICE SUMMARY

SR. NO. DESCRIPTION AMOUNT AMOUNT IN WORDS

HT WORK

A) RING MAIN UNIT

B) SUBSTATION

C) HT ABLE

D) SUBSTATION AUXILARIES

E) APFC PANEL

F) DG SYSTEM

G) LV SWITCHBOARDS

H) LT CABLING

I) POINT WIRING 2,510,722.00

J) DISTRIBUTION BOARD

K) ELV SYSTEM

L) UPS

M) LIFT

N) EARTHING

O) LIGHT FITTINGS

P) LIGHTNING ARRESTOR

In words: TOTAL

Page 2: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

A 11KV RING MAIN GEAR PANEL

INCOMING-

Power frequency & Impulse voltage: 28KVBottom side Cable Entry.Mechanical ON/OFF/EARTH indication.Anti reflex operating handle.2 NO + 2 NC auxiliary contacts.Shunt Trip coil (230V AC) for external trip signal.Self powered O/C+E/F relay type VIP35.

disconnecting the cable termination.

Right angle boots (Push-On Type)

OUTGOING-

Type of Main Busbars: CopperRating of Main Busbars: 11KV, 630A, 25 KA/3sec

One Control Switch for TOD Operation. 1.No.1 No. Breaker Control SwitchEmergency Trip Push Button

Remote & Local switch for Circuit Breaker, Master Trip Relay

METERING:

CT:25/5A Core 1-15VA burden class 1.0 for metering.25/5A Core 2-15VA burden class 5P 10 for protection

PT Ratio:11000/22000/ √3 / 110 / √3 Volt. With class 0.5 , 100VA.

PROTECTIONS:Numerical Self Powered Relay with following protectionsa) Over Current (Instantaneous) 50b) Earth Fault (Instantaneous) 50Nc) Over Current ( IDMT) 51d) Earth Fault (IDMT) 51N

INDICATIONS :1 Set of fuses, ferrules, wiring etc. as required.1 set of following indicating lamps- Red, Yellow and Blue for phase Indication- Amber for trip indication- Red `ON’ & Green `OFF’- Earth & SF6 Gas Pressure Indication- Spring charge indication- 'Blue'Trip Circuit, Healthy IndicationAdequate no. of NO/NC contacts of Circuit Breaker shall be wired up to the terminal block for connection to controland relay panel.

No 1TOTAL CARRIED OVER TO SUMMARY

Supply.Installation,Testing,Commissioning of 11KV,630Amps,25KA outdoor type(IP54) ring main gear panel as per below specification.

2Nos. 11KV ,630A, 25kA Triple Pole load break switch with 3position (ON ,OFF,and Earth),and fully rated earth switch with provision for earth and test of the cable

Live Cable indicating LEDs energized thru capacitive voltage dividers.

Cable testing facility without opening cable compartment & without

Cable Box for termination of cable upto 1No. 3C X 95 sqmm. XLPE cable.

1 Nos VCB of 11KV, 25 KA , 3 sec,630 A, 50 Hz, Circuit Breaker with Earth Switch & Motorized Spring Charged 240V AC supply, Mechanical tripping & Closing arrangement

Shunt Tripping coil shall be at 30 V DC. With single & double core CT Epoxy Cast resin Insulation.

Mechanical ON , OFF, Earth Indications. Mechanical Spring Charging.

Cable Testing Facility without Opening the Compartment & Without Disconnecting the cable Terminations.

Live Cable Indications, Indicating LED's Energized through capacitive voltage divider

Cable Box Suitable For Cable Termination of 3C X 95 sq.mm XLPE Cable

Analog Voltmeter ( 0 - 12KV ) with selector switch - 1 No.Analog Ammeter ( 0 - 25 A ) with selector switch. - 1 No.

Page 3: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

B TRANSFORMER

1

Termination arrangements-HV Side - 3 Core, 95 Sq.mm XLPE CableLV Side - Provision for 2 runs of 240 Sq.mm XLPE Cable.

TOTAL CARRIED OVER TO SUMMARY

Supply, Installation, Testing and Commissioning of 315 kVA, 11 / 0.433 KV, 50 Hz., 5.0% impedance, vector symbol Dyn11, Indoor duty, oil cooled, copper wound, ONAN type transformers with tappings of +7.5% to –7.5% on primary side with Off load tap changing mechanism and all the standard accessories as required by the local electricity boards.

Note: Scope shall also include testing and inspection at works by the Electricity Board officials / Client / PMC / Consultants

Page 4: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

C HT CABLING

1 Rm 200

2 Rm 50

3 Nos. 4

4

i 150 mm dia ID Rm 250

ii 300 mm dia ID Rm 350

TOTAL CARRIED OVER TO SUMMARY

Supplying, laying, testing and commissioning of 11 kV earthed grade, 3 Core, 95 Sq.mm Cross Linked Polyethylene (XLPE) insulated, Aluminium Cable.The cables shall be laid in 150mm RCC hume pipe.The cost include all fixing accessories, excavation, back filling, sand & brick bedding etc. shall be included in the scope. (From MSEDCL to Substation)

Supplying, laying, testing and commissioning of 11 kV earthed grade, 3 Core, 95 Sq.mm Cross Linked Polyethylene (XLPE) insulated, Aluminium Cable.The cables shall be laid in existing cable trays,concrete trenches or buried hume pipe. (From HT Panel to Transformer )

Supplying and termination of 3 Core, 95 Sq.mm Cross Linked Polyethylene (XLPE) insulated, Aluminium Cable with cable gland, indoor type sealing kit, epoxy compound, heat shrinkable slews etc. complete as required for termination.

Supply and laying, installation of following RCC (NP-2 class) Hume pipe however all fixing accessories, excavation, back filling, sand & brick bedding etc. shall be included in the scope. This shall also include cost of required size chambers.

Page 5: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY RATE

D SUBSTATION AUXILLARIES

i No 1

ii No 1

iii No 2

iv Sets 1

v Sq.m 2

vi Nos. 1

vii Supply of first aid box of approved make as per specification. Nos. 1

viii Supply of tool kit with 1 pair 11 KV rubber hand gloves of approved make. Nos. 1

ix

RM 30

x

10 Core 2.5 sq.mm Control cable Nos. 6

xi

The work shall include the following:* Obtaining the feasibility report and spot inspection, etc.* Obtaining saction of H.T. connection of 2 nos.630 kVA Transformers.

* Obtaining necessary approvals and submitting to the clients.* Any other works related to MSEDCL and Electrical inspectorate. Lumpsum 1

TOTAL CARRIED OVER TO SUMMARY

Supply and fixing in position the best quality danger boards of approved shape and size as specified by the local electrical authorities written in English, Hindi and local language.

Providing and fixing in position approved shock treatment chart written in English and local language. The chart shall be framed in Teakwood and covered with glass.

Supply and fixing in position the fire extinguishers carbon-di-odide type 2.5 Kgs capacity..

Supply of fire buckets 5 nos. in each set duly filled with fine sand and fixed on an angle iron frame as per requirement of local authorities. Fire buckets shall be painted red from outside and white from inside with additional handle at the bottom

Supply and fixing in position 1000 mm wide rubber matting of 11 KV grade as per electricity rules.

Supply and fixing in position the approved single line diagram framed in 1000 x 800 mm size glass frame in the sub station.

Supplying, laying, testing and commissioning of 1100V grade PVC insulated PVC sheathed steel wire/ tape armoured aluminium / copper conductor control cables . The cables shall be laid in cable trays, clamped on walls and in concrete trenches, with suitable clamps and saddles fixing bolts etc. The cost of the cable trays or ladders, excavation and back filling of trenches not to be included in this scope. 10 Core 2.5 sq mm PVC insulated copper conductor armoured control cables

Supplying and Installation of cable terminations for the above cables including double compression type chrome plated brass glands and bimetallic lugs (crimping type), PVC taping as required and all accessories complete.

The professional charges for liason work and departmental procedures required for the above said work .

* Preparation and submission of all statutory drawings to MSEDCL and electrical inspectorate.

Page 6: Electrical Boq

AMOUNT

Page 7: Electrical Boq

SR.NO DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

E CONTACTOR BASED APFC PANELSWITH

2) Panels shall be free standing floor mounted.

8) All panel switches with locking arrangement.9) All types of switches,db mcb's require lockout mechanism

1 125 KVAR CONTACTOR BASED APFC PANELS as per schematic

Incomer

i

ii

iii

a. Currentb. Voltagec. Frequency / Harmonicsd. Instantaneous power factore. Total active energy (KWH/MWH)f. Maximum demand (KVA/MVA) (KW/MW)g. Maximum demand reset count.h. Eight time of a day energy.i. RS 485 Port as required for IBMS/BAS.

iv. R, Y & B Phase indicating lamps protected by 2 Amps MCBs.

v.

vi. Under voltage relay with timer

vii. Over voltage relay with timer

viii. Breaker control switch

2 Relay

3 Capacitors

4 Switching System

No 1TOTAL CARRIED OVER TO SUMMARY

Design, Assembling, Supply, Installation, Testing and Commissioning of following 125 KVAR Contactor based Auto Power Factor Correction Panels and Swithgears suitable for 415 Volts, 3 phase 4 wire, 50 Hz power distribution system. In conjunction with general specifications following points should also be considered and adhered to.

1) All the Switchboards shall be Indoor type, dust and vermin proof type compartmentalised design maintaining IP 54 degree of protection.

3) All hinged door shall be earthed through 2.5 sq mm tinned copper wire. Doors shall be pad locking type whereas for MCCB compartments they should be openable only in switch OFF mode.

4) All the busbars and links shall be of copper with color coded heat shrinkable insulating sleeves. Separate earth busbars shall be provided along the length of the switchboards.

5) All measuring instruments (Meters) shall be of digital electronic with LED display of approved make and compatible with IBMS / BAS.

6) Adequate additional sets of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for IBMS including space required for various transducers.

7) Adequate space for cable enteries and terminations shall be provided refering SLDs. Cable entries can be either from the top or bottom as required.

One(1) No 250 Amps, 415 Volts, 50 KA, TP ,MCCB releases for Short Circuit, Earth fault and Over Current protection along with adjustable setting. Each breaker shall be fitted vertical with following accessories, complete as required.

1 Nos. 96 x 96 sq.mm 0-250/ 1 amps CTR digital ammeter with 1 Nos. 250 / 5 amps, 15 VA Class I CT’s.

0-500 Volts, size 96 mm x 96 mm digital voltmeter with selector switch and protected by 2 amp TP MCB’s

Electronic energy meter of accuracy class-I, with 3 Nos. 250/1 amps 15VA CTs to measure and display the following electrical quantities :

Breaker indicating lamps for CB open, CB close, CB auto trip, Trip circuit healthy etc.

Microprocessor based APFC controller along with continuously monitor all three phases and displays various Electrical Parameters like voltage, input current, capacitive current, KVA demand,KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232C / 485 port as required. Controller should mounted on the front side of the panel.

Combination of Banks forming a 125 KVAr with mixed dielectric or MPP type dielectric medium.Capacitor banks shall be connected through appropriate sized MCCBs. Banks should be selected such that power factor should be close to unity.

Switching System shall be through high speed response Contactor with a response time less than 60 mill seconds. This should be complete with required firing cards.

Page 8: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

F DG SYSTEM

1 Diesel Generator set

ii Sets 2

Total for DG Sets

2 Cabling System

2.1

i 6 core 2.5 sq.mm Cu. Shielded & Armoured Control Cable Rm 50

2.2

i 6 core 2.5 sq.mm Cu. Shielded & Armoured Control Cable Rm 2

3 AMF PANEL/DG PANEL

3.1 DG Incomer

i Set 2

ii Set 2

iii Set 2

a. Currentb. Voltagec. Frequency / Harmonicsd. Instantaneous power factore. Total active energy (KWH/MWH)f. Maximum demand (KVA/MVA) (KW/MW)g. Maximum demand reset count.h. Eight time of a day energy.i RS 485 Port as required for IBMS/BAS.

iv. R, Y & B Phase indicating lamps protected by 2 Amps MCBs. Set 2

v. Set 2

vi. Under voltage relay with timer Set 2

vii. Over voltage relay with timer Set 2

viii. Breaker control switch Set 2

ix. Auto-manual selector switch Set 2

3.2 Bus Bar

3.3 Outgoing Feeders

i Nos 2

4 Lumpsum 1

TOTAL CARRIED OVER TO SUMMARY

Supply, Installation, testing and commissioning of 160 KVA Prime power rated Diesel Generator Set complete with Diesel Engine suitable for Generator application, developing 1500RPM with an overloading capacity of 10% for one hour in any 12 continuous hours operation coupled to 160 KVA at 0.8 Power factor, 415V, 3 Phase , 4 wires, 50 Hz. self excited, self regulated and brushless excitation complete with acoustic enclosure as per CPCB norms. DG set shall be radiator type with residential silencer, electronic governor, termination box, MS mounting frame, fuel piping, 24VDC Battery Charger & batteries, Battery mounting frame, oil level indicator with gauge board, The DG Set shall be suitable for auto-mains failure start.The cost shall include fuel piping & Exhaust pipeing with standard accessories and fuel oil required for testing DG Set at full load.

Supply, laying, testing and commissioning of 1100V grade PVC insulated PVC sheathed steel wire/ tape armoured aluminium / copper conductor cables. The cables shall be laid in cable trays, clamped on walls and in concrete trenches, with suitable clamps and saddles fixing bolts etc. The cost of the cable trays or ladders, excavation and back filling of trenches not to be included in this scope.

Supply,Installation of cable terminations for the above cables including double compression type chrome plated brass glands and bimetallic lugs (crimping type), PVC taping as required and all accessories complete.

Two(2) No 250Amps, 415 Volts, 50 KA, TPN, MCCB with Thermomagnetic releases for Short Circuit, Earth fault and Over Current protection along with adjustable setting. Each breaker shall be fitted vertical with following accessories, complete as required.

1 Nos. 96 x 96 sq.mm 250/ 5 amps CTR digital ammeter with 1 Nos. 250 / 5 amps, 15 VA Class I CT’s.

0-500 Volts, size 96 mm x 96 mm digital voltmeter with selector switch and protected by 2 amp TP MCB’s

Electronic energy meter of accuracy class-I, with 3 Nos. 250/5 amps 15VA CTs to measure and display the following electrical quantities :

Breaker indicating lamps for CB open, CB close, CB auto trip, Trip circuit healthy etc.

630 Amps, 415 Volts TPN, 50KA uniform Aluminium busbars with color coded heat shrinkable insulating sleeves.

630 Amps, 415 Volts, 50 KA, TPN, ACB with Thermomagnetic releases for Short Circuit, Earth fault and Over Current protection along with adjustable setting. Each breaker shall be fitted vertical with following accessories, complete as required.

The professional charges for liason work and departmental procedures required for the above said work .

Page 9: Electrical Boq

DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNTG

L.V SWITCHBOARDS

2) Switchboards shall be free standing floor mounted or wall mounted as required.

6) All measuring instruments (Meters) shall be of digital electronic with LED display of approved make.

1 MAIN LT PANEL as per Schematis Nos. 1

2 GROUND FLOOR PANEL as per Schematics Nos. 1

3 FIRST FLOOR PANEL as per Schematics

4 COMMON SERVIE PANEL as per schematics

5 PLUMBING PANEL as per Schematics

6 FIRE FIGHTING PANEL as per Schematics

TOTAL CARRIED OVER TO SUMMARY

Design, Assembling, Supply, Installation, Testing and Commissioning of following LV Switchboards and Swithgears suitable for 415 Volts, 3 phase 4 wire, 50 Hz power distribution system. In conjunction with general specifications following points should also be considered and adhered to.1) All the Switchboards shall be Indoor type, dust and vermin proof type compartmentalised design maintaining IP 52 degree of protection.

3) All the Switchboards shall be of compartmenttalised with entire fabrication in 14 Guage Sheet Steel and Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5.4) All hinged door shall be earthed through 2.5 sq mm tinned copper wire. Doors shall be pad locking type whereas for MCCB compartments they should be openable only in switch OFF mode.5) All the busbars and links shall be of copper with colour coded heat shrinkable insulating sleeves. Separate earth busbars shall be provided along the length of the switchboards.

7) Adequate space for cable entries and terminations shall be provided refering SLDs. Cable entries can be either from the top or bottom as required.

Page 10: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

H LT CABLING SYSTEM

1

a 3.5C x 240 sqmm A2XFY Rm 340

c 3.5Cx 150 sqmm A2XFY Rm 250

d 3.5Cx 50 sqmm A2XFY Rm 1450

for copper cables

a 4 C 16 sqmm 2XFY Rm 300

b 4 C 6 sqmm 2XFY Rm 250

c 4 C 4 sqmm 2XFY Rm 75

d 3 C 2.5 sqmm 2XFY Rm 20

e 3 C 4 sqmm 2XFY Rm 60

f 3 C 6 sqmm 2XFY Rm 20

2

a 3.5C x 240 sqmm A2XFY Nos. 8

b 3.5Cx 150 sqmm A2XFY Nos. 2

c 3.5Cx 50 sqmm A2XFY Nos. 10

f 4 C 16 sqmm 2XFY Nos. 4

g 4 C 6 sqmm 2XFY Nos. 12

h 4 C 4 sqmm 2XFY Nos. 8

i 3 C 2.5 sqmm 2XFY Nos. 4

j 3 C 4 sqmm 2XFY Nos. 12

k 3 C 6 sqmm 2XFY Nos. 4

3

a 150 mm wide single horizontal/vertical tier. Rm 250

TOTAL CARRIED OVER TO SUMMARY

Supplying, laying, testing and commissioning of 1100V grade XLPE type steel wire/ tape armoured aluminium / copper conductor cables. The cables shall be laid in cable trays, clamped on walls and in concrete trenches, with suitable clamps and saddles fixing bolts etc. The cost of the cable trays or ladders, excavation and back filling of trenches not to be included in this scope.

Supplying and Installation of cable terminations for the above cables including double compression type chrome plated brass glands and bimetallic lugs (crimping type), PVC taping as required and all accessories complete.

Supplying and Installation of Pregalvanised factory fabricated Perforated type cable trays with 50mm height & 1.5 mm thick. The tray shall be suspended from ceiling using anchor bolt and angle iron supports or mounted from wall. The rate shall include all accessories like radial bends, elbows, tees, coupler plates, etc., which will be measured as linear measurement and fixing accessories.

Page 11: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

1 POINT WIRING

a Rm 3,000 86.00 40.00 378,000.00

b Rm 3,600 86.00 40.00 453,600.00

c Rm 1,300 86.00 40.00 163,800.00

d Rm 2,000 86.00 40.00 252,000.00

2 Supply,Installation,Testing of following power points

a One 6 A Socket controlled by one 6 A Switch.(Half Point) No 168 290.00 80.00 62,160.00

b One 6 A Socket controlled by one 6 A Switch.(Individual Points) No 36 620.00 200.00 29,520.00

c One 16 A Socket controlled by one 16 A Switch. No 5 360.00 100.00 2,300.00

3

i No 172 470.00 150.00 106,640.00

ii No 17 700.00 230.00 15,810.00

iii No 84 940.00 300.00 104,160.00

iv No RO 1,175.00 375.00 1,550.00

v No 238 1,050.00 180.00 292,740.00

vi No 45 470.00 150.00 620.00

Note: 1) Client reserves the right to supply the lighting fixtures, where contractor shall be paid only for the installation.

Supply of following Cu PVC FRLS Wires for point wiring with Rmt(Quote for Wire Only)

Point wiring for all Light points using 2x2.5 + 1x1.5PE Cu PVC FRLS Wires in 25 mm PVC conduits contactor shall be consider three to four circuits in single conduits wherever possible from GF.LDB-1,GF LDB-2,FF LDB-1,FF LDB-2 including of submains wiring.(Wire rates only)

Point wiring for all Light points using 2x2.5 + 1x1.5PE Cu PVC FRLS Wires in 25 mm PVC conduits contactor shall be consider three to four circuits in single conduits wherever possible from COMMON AREA DB including of submains wiring.(Wire rates only)

Point wiring for all Light points using 2x2.5 + 1x1.5PE Cu PVC FRLS Wires in 25 mm PVC conduits contactor shall be consider three to four circuits in single conduits wherever possible from TERRAE LTG. DB including of submains wiring.(Wire rates only)

Point wiring for all Light points using 2x2.5 + 1x1.5PE Cu PVC FRLS Wires in 25 mm PVC conduits contactor shall be consider three to four circuits in single conduits wherever possible from EXTERNAL AREA DB including of submains wiring.(Wire rates only)

POINTWIRING-WING-A(Quote for Wire Only)Supply, Installation,Testing of One light point wiring from switchboard(1 switch controlled) to light point with 3x 1.5 insulated copper conductor 1100 volts grade stranded flexible FRLS wires in 25 mm PVC conduit concealed / embeded in walls. This shall include installation of 6 A single way modular switch, 2 mm thick GI concealed box and other accessories such as bends, junction boxses, saddles, spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.(Avg. point wiring length 6 mtr.)

Supply, Installation,Testing of Two light point wiring from switchboard (1

switch controlled) to light point with 3x 1.5 insulated copper conductor 1100

volts grade stranded flexible FRLS wires in 25 mm PVC conduit concealed /

embeded in walls. This shall include installation of 6 A single way modular

switch, 2 mm thick GI concealed box and other accessories such as bends,

junction boxses, saddles, spacers, switch plates, angle holders, ceiling

roses etc. as required to complete the wiring.

Supply, Installation,Testing of Three light point wiring from switchboard (1

switch controlled) to light point with 3x 1.5 insulated copper conductor 1100

volts grade stranded flexible FRLS wires in 25 mm PVC conduit concealed /

embeded in walls. This shall include installation of 6 A single way modular

switch, 2 mm thick GI concealed box and other accessories such as bends,

junction boxses, saddles, spacers, switch plates, angle holders, ceiling

roses etc. as required to complete the wiring.

Supply, Installation,Testing of Four light point wiring from switchboard (1

switch controlled) to light point with 3x 1.5 insulated copper conductor 1100

volts grade stranded flexible FRLS wires in 25 mm PVC conduit concealed /

embeded in walls. This shall include installation of 6 A single way modular

switch, 2 mm thick GI concealed box and other accessories such as bends,

junction boxses, saddles, spacers, switch plates, angle holders, ceiling

roses etc. as required to complete the wiring.

Supply, Installation & Testing of Ceiling Fan point wiring from switch

boards to fan points with 3 x 1.5 sq.mm PVC insulated copper conductor

1100 volts grade stranded flexible FRLS wires in 25 mm heavy duty

concealed PVC conduits.These points shall be controlled by 6 amps single

pole modular flush mounted switch from local switch board and an

electronic type regulator. This shall include 2 mm thick GI concealed box,

fan box with hook and other accessories such as socket type 5 step

electronic regulator, modular switches & switch boards, holders, ceiling rose,

etc. as required to complete the wiring. (Avg. Point Length 6 mtrs.)

Supply, Installation & Testing of Exhaust fan point wiring with 3 x 1.5

sq.mm PVC insulated copper conductor 1100 volts grade stranded

flexible FRLS wires in 25 mm heavy duty concealed PVC conduits. These

6 A sockets points shall be controlled by 6 amps single pole modular flush

mounted switch on the switchboard. This shall include 2 mm thick GI

concealed box and other accessories such as modular switches, sockets &

switch boards, holders, ceiling rose, etc. as required to complete the wiring.

(Avg. Point length 6 mtrs.)

Page 12: Electrical Boq

vii

a 1 LP controlled by 1 MCB No. RO 705.00 235.00 940.00

b 2 LP controlled by 1 MCB Nos. 1 1,055.00 353.00 1,408.00

c 3 LP controlled by 1 MCB Nos. 4 1,410.00 470.00 7,520.00

d 4 LP controlled by 1 MCB Nos. 3 1,760.00 588.00 7,044.00

e 5 LP controlled by 1 MCB Nos. 9 2,115.00 705.00 25,380.00

f 6 LP controlled by 1 MCB Nos. 12 2,465.00 823.00 39,456.00

g 7 LP controlled by 1 MCB Nos. 11 2,820.00 940.00 41,360.00

h 8 LP controlled by 1 MCB Nos. 19 3,170.00 1,058.00 80,332.00

i 9 LP controlled by 1 MCB Nos. 5 3,525.00 1,175.00 23,500.00

j 10 LP controlled by 1 MCB Nos. 4 3,878.00 1,293.00 20,684.00

viii

a 20 mm PVC Conduits Rm RO 49.00 16.00 65.00

b 25 mm PVC Conduits Rm 5000 62.00 18.00 400,000.00

c 32 mm PVC Conduits Rm RO 111.00 22.00 133.00

TOTAL CARRIED OVER TO SUMMARY 2,510,722.00

Supply, Installation and testing of Light point wiring from common lighting

DBs &External Ltg. DB. to light point with 2 x 2.5 + 1x 1.5 sq.mm PVC

insulated copper conductor 1100 volts grade stranded flexible FRLS

wires in concealed or on surface 25mm PVC conduits.These points shall be

controlled by MCB in distribution board. This shall include holders, holder

box, connectors etc. as required to complete the wiring. (for Staircase, ,

Ground ,Common area,External area ltg.)

Supply, laying and fixing of following Precision make (HMS) PVC conduits embedded in the RCC slab at the time of slab casting. This shall include all the accessories such as sockets, bends, binding wire, etc. and every thing as required to complete the conduiting.

Page 13: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

J DISTRIBUTION BOARDS

1

i Nos. 1

12 Way TPN DBIncomer -

63A, 10 KA, TPN ,MCB+ELCB(30mA) - 1 no.

Outgoing -

10 Amps, 10 KA, SP MCBs - 25 nos.

16 Amps, 10 KA, SP MCBs - 2 nos.

ii Nos. 1

12 Way TPN DBIncomer -

63A, 10 KA, TPN ,MCB+ELCB(30mA) - 1 no.

Outgoing -

10 Amps, 10 KA, SP MCBs - 36 nos.

iii No.s 1

4 WAY TPN DBIncomer -

20 Amps, TPN MCB+ELCB(30mA) - 1 nos.

Outgoing -

10 Amps, 10 KA, SP MCBs - 12 nos.

iv No.s 1

6 WAY TPN DBIncomer -

63 Amps, TPN MCB+ELCB, (30mA )- 1 nos.

Outgoing -

10 Amps, 10 KA, SP MCBs - 3 nos.

16 Amps, 10 KA, SP MCBs - 15 nos.

v No.s 1

8 WAY TPN DBIncomer -

63 Amps, TPN MCB+ELCB, (30mA )- 1 nos.

Outgoing -

10 Amps, 10 KA, SP MCBs - 8 nos.

16 Amps, 10 KA, SP MCBs - 14 nos.

vi No.s 1

6 WAY TPN DBIncomer -

63 Amps, TPN MCB+ELCB, (30mA )- 1 nos.

Outgoing -

10 Amps, 10 KA, SP MCBs - 2 nos.

16 Amps, 10 KA, SP MCBs - 16 nos.

vii No.s 1

8 WAY TPN DBIncomer -

63 Amps, TPN MCB+ELCB, (30mA )- 1 nos.

Outgoing -

10 Amps, 10 KA, SP MCBs - 4 nos.

16 Amps, 10 KA, SP MCBs - 16 nos.

TOTAL CARRIED OVER TO SUMMARY

Supply, Installation, Testing and Commissioning of the following Distribution Boards fabricated in sheet steel with phase copper bus bars, neutral and earth bar with tapped holes, cutouts for operating the MCB knobs in the inner cover, bakelite phase barriers, double door construction, powder coated with approved shade and partitions to segregate phases etc. DB's shall be suitable for single phase/3 phase operation. DB's shall be flush mounted to brick wall or surface mounted as required.(IP-43)

Distribution Board -(with separate neutral links) (For External Ltg.)

Distribution Board - (with separate neutral links) (For Common Area Ltg)

Distribution Board -(with separate neutral links) (For Terrace Ltg.)

Distribution Board -(with separate neutral links) (For Ground floor DB-1.)

Distribution Board -(with separate neutral links) (For Ground floor DB-2.)

Distribution Board -(with separate neutral links) (For First floor DB-1.)

Distribution Board -(with separate neutral links) (For First floor DB-2.)

Page 14: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

K ELV SYSTEMA TELEPHONE SYSTEM

1

a 30 Pair MDF Nos. 1

2

a 20 Pair krone Cable termination block Nos. 1b 5 Pair krone Cable termination block Nos. 1

3

a 20 pair Riser Cable Rm 30b 5 Pair Riser Cable Rm 35

4 Rm 200

i Single outlet faceplate with RJ-11 jack Nos. 10

B DATA NETWORKING SYSTEM

1 Nos. 1

2

a 16 Port Switch Nos. 1b 8 Port Switch Nos. RO

3

a 12 U Rack Nos. ROb 9 U Rack Nos. ROc 6 U Rack Nos. RO

4 Rm 250

5 Nos. 11

TOTAL CARRIED OVER TO SUMMARY

Supply, Installation, Testing and Commissioning of following Krone make Main Distribution Frame (MDF) protector panel for the service providers incoming lines.The panel shall have provision for both top and bottom cable entry.

Supply, installation, testing and commissioning of Krone make Cable termination block prepackaged with wiring block with legs, insert labels, label holders, jumper troughs, metal back panel, duct assembly, wire managers for distribution, screws, washers and an instruction sheet for termination of incoming pairs.

Supply, installation, testing and commissioning of Jelly filled Arm Telephone Riser cable consisting of multiple core solid copper conductors of 24 AWG size insulated with expanded polyethylene covered with a PVC skin and inner shielding for grounding. The core shall be covered by a layer of plastic tape and overlaid with a corrugated PVC plastic. The cable shall be as per specifications laid down in the tender.

Supply, installation, testing and commissioning of 4 pair Category 6 cable consisting of 24 AWG solid copper conductors through 25mm rigid pvc conduit and as per the specification. The cable shall have flexible jacket and ripcord for easy stripability

Supply, installation, testing and commissioning of 12 port Ethernet central switch(JACK PANEL) as per schematic

Supply, installation, testing and commissioning of following Ethernet work station switch as per specification.

Supply and installation of following sizes Racks with all accessories & wire managers

Supply, installation, testing and commissioning of Category 6 LAN cable consisting of 24 AWG solid copper conductors and as per the specification. The cable shall have flexible jacket and ripcord for easy Stripability(Laying of cable through tray)

Supply,Installaton,Testing and Commissioning of Single outlet faceplate with RJ-45 UTP information Outlets.The price shall include 2 mm thick GI boxes, inner plates, outer plates etc.

Page 15: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

L UPS SYSTEM

1 No 2

2

TOTAL CARRIED TO SUMMARY -

Supply, Installation, testing and commissioning of 7.5KVA UPS System complete with the required accessories as specified in the drawings & the specifications called for.

15 Minutes Battery Back-up for the 7.5KVA UPS system complete with the required accessories

Page 16: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

M LIFT SYSTEM

1 No 3

TOTAL CARRIED TO SUMMARY

Hoist way maintenance Lighting and Power for LIFT-1 including supply & intallation of I) 1# 5/15A Switch Socket per Floor ii)1# 60w Bulkhead Light Fixture iii)1# 5A switch to control Bulkhead Light Fixture iv) Conduit Wiring for above using 3# 2.5 Sq.mm Cu wires in PVC Conduit with termination of cables & junction box.

Page 17: Electrical Boq

CHEMICAL EARTHINGSR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

N CHEMICAL EARTHING

1 Nos. 6

2 Nos. 6

3 Nos. 17

4 Nos. 2

5

i 32 x 6 mm thick CU Strip Rm 120

ii 32 x 6 mm thick GI Strip Rm 120

iii 25 x 3 mm thick CU Strip Rm 85

iv 25 x 3 mm thick GI Strip Rm 400

v 8 SWG CU Wire Rm 320

TOTAL CARRIED OVER TO SUMMARY

Supply, Installing, Testing and Commissioning of CU earthing with 32 x 6 mm CU strips from earth electrode to inspection chamber, 50 mm dia CU pipe with 3 mtr long and surrounding area will be filled by BACKFILL COMPOUND. Prices should include 6'' dia bore, back filling, masonry chamber 500 x 500 mm with concrete base, cast Iron cover, test links, disconnecting link etc.

Supply, Installing, Testing and Commissioning of GI earthing station with 32 x 6 mm GI strips from earth electrode to inspection chamber, 50 mm dia GI pipe with 3 mtr long and surrounding area will be filled by BACKFILL COMPOUND. Prices should include 6'' dia bore, back filling, masonry chamber 500 x 500 mm with concrete base, cast Iron cover, test links, disconnecting link etc.

Supply, Installing, Testing and Commissioning of GI earthing station with 25 x 3 mm GI strips from earth electrode to inspection chamber, 50 mm dia GI pipe with 3 mtr long and surrounding area will be filled by BACKFILL COMPOUND. Prices should include 6'' dia bore, back filling, masonry chamber 500 x 500 mm with concrete base, cast Iron cover, test links, disconnecting link etc.

Supply, Installing, Testing and Commissioning of CU earthing with 25x 3 mm CU strips from earth electrode to inspection chamber, 50 mm dia CU pipe with 3 mtr long and surrounding area will be filled by BACKFILL COMPOUND. Prices should include 6'' dia bore, back filling, masonry chamber 500 x 500 mm with concrete base, cast Iron cover, test links, disconnecting link etc.

Supplying and laying earthing conductors of Copper / GI strips including necessary accessories, clamping to walls, cables etc.as required and interconnection between lengths as per specifications and as per good installation practice. Prices should include all supports, accessories and hardware necessary for proper installation.

Page 18: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

O LIGHTING FIXTURES

a 2X36 W TUBE LIGHT/CFL Nos. 804

b 1X 28W WALL LIGHT Nos. 139

c DOWN LIGHT Nos. 8

d 1x36 W WALL MOUNTED LIGHT Nos. 134

e 70 W POLE LIGHT Nos. 48

f FOOT LIGHT Nos. 72

TOTAL CARRIED OVER TO SUMMARY

Note: 1) Client reserves the right to supply the lighting fixtures, where contractor shall be paid only for the installation.

Installation, testing and commissioning of following type of light fixtures as per drawings and specifications with all other accessories such as supporting rods / frames, anchor fasteners, necessary hardware etc. The rate shall include for fittings along with transformers where required, diffuser, chokes, starter, power factor improvement capacitors, wires, downrods etc., complete with all accessories to complete the installation as required.

Page 19: Electrical Boq

SR. NO. DESCRIPTION UNIT QUANTITY SUPPLY INSTALLATION AMOUNT

P LIGHTNING PROTECTION

1 Nos. 2

TOTAL CARRIED OVER TO SUMMARY

Supply and Installation of Early strimer lightning arrestor for protection of building-Radius 79Mtr. This shall include the cost of mast of 5mtr height, lightning event counter, fixing hardware etc.