22
1. Explain unit & non-unit protection of transmission line. The graded overcurrent systems described earlier do not meet the protection requirements of a power system. The grading is not possible to be achieved in long and thin networks and also it can be noticed that grading of settings may lead to longer tripping times closer to the sources, which are not always desired. These problems have given way to the concept of ‘unit protection’ where the circuits are divided into discrete sections without reference to the other sections. Ideally, to realize complete selectivity of protection, the power system is divided into discrete zones. Each zone is provided with relays and circuit breakers to allow for the detection and isolation of its own internal faults. The protection used in this manner – essentially for internal faults in a particular zone – is referred to as main or unit protection. 2. Explain with block diagram carrier-current protection of transmission line. 1

ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

1. Explain unit & non-unit protection of transmission line.

The graded overcurrent systems described earlier do not meet the protection requirements of a power system. The grading is not possible to be achieved in long and thin networks and also it can be noticed that grading of settings may lead to longer tripping times closer to the sources, which are not always desired. These problems have given way to the concept of ‘unit protection’ where the circuits are divided into discrete sections without reference to the other sections. Ideally, to realize complete selectivity of protection, the power system is divided into discrete zones. Each zone is provided with relays and circuit breakers to allow for the detection and isolation of its own internal faults. The protection used in this manner – essentially for internal faults in a particular zone – is referred to as main or unit protection.

2. Explain with block diagram carrier-current protection of transmission line.

1

Page 2: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

3. How are three phase motors protected from unbalance & single Phasing Protection?Unbalance protection

2

Page 3: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

4. Explain the different protective schemes used for protecting a bus zone

Differential protection

3

Page 4: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

Fault bus protection

5. (a) A 3Φ transformer of 220/11000 line volts is connected in star delta. The protective transformers on 220 V side have a current ratio of 600/5.What should be the CT ratio on 11000 V side? (8 Marks)

4

Page 5: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

(b) A 11 kV, 3Ф alternator has full load rated current of 200 A. Reactance of armature winding is 15 %. The differential protection system is set to operate on earth faults of more than 200 A. Find the neutral earthing resistance, which gives earth fault protection to 90% of stator winding. (8 Marks)

Refer principles of power systems - V.K.Metha& Rohit metha page no 529.

6. Explain the factors which cause difficulty in applying Merz-Price circulating current principle to a power transformers.(8) (nov/dec 2011)

For protection of generators, Merz-price circulating current system is unquestionably the most satisfactory. Though this is largely true of transformer protection, there are cases where circulating current system offers no particular advantage over other systems or impracticable on account of the troublesome conditions imposed by the wide variety of

5

Page 6: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

voltages, current and earthing conditions invariably associated with power transformers. Under such circumstances, alternative protective systems are used which in many cases are as effective as the circulating current system.

7. A three phase transformer of 220/11000 line volts is connected in star/delts. The protective transformers on 220 v side have a current ratio of 600/5. What should be the current transformer ratio on 11000 v side?(8) (nov/dec 2011)

Refer answer in Part B Unit III question no 10 (a).

8. Describe the differential pilot wire method of protection of feeder(16) (nov/dec 2011)

6

Page 7: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

Unit IV

1. Explain the phenomenon of arc and the various methods of arc extinction.

7

Page 8: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

2. Define the terms recovery voltage and RRRV. Explain the effect of above quantities on the operation of circuit breaker under fault conditions.

8

Page 9: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

3. Explain successive restrikes and current chopping as applied to the interruption of capacitive and low inductive currents.

9

Page 10: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

10

Page 11: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

4. Show schematic arrangements of a breaker with a resistor connected across the contacts and derive its Laplace equivalent.

5. A 50 Hz, 11KV, three-phase alternator with earthed neutral has a reactance of 5 ohms per phase, and is connected to bus bar through a circuit breaker. The capacitance to earth between the alternator and the circuit breaker is 0.02 micro farads per phase. Assuming the resistance of the generator to be negligible calculate the following (a) Maximum voltage across the contacts of the circuit breaker. (b) Frequency of oscillation (c) The average rate of rise of restriking voltage up to the first peak.

11

Page 12: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

Refer principles of power systems - V.K.Metha& Rohit metha page no 484.

6. What causes the initiation of electric arc at the instant of contact separation? Which of these is chiefly responsible for the creation of arc in circuit breakers and why?

Refer answer in Part B Unit IV question no 1.

7. In a short circuit test on a 130 kV ,3Φ system , the breaker gave the following results : p.f of fault 0.45 ,recovery voltage 0.95 times full line voltage , breaker current symmetrical , and restriking transient had a natural frequency 16 kHz .determine average RRRV .Assume fault is grounded.( 6 Marks ) In a 220 kV system , the reactance and capacitance up to the location of circuit breaker is 8Ω and 0.025 μF respectively. A resistance of 600 Ωis connected across the contacts of the circuit breaker. Determine the following: Natural frequency of oscillation Damped frequency of oscillation. Critical value of resistance which will give no transient oscillation. The value of resistance which will give damped frequency of oscillation, one fourth of the natural frequency of oscillation. (10 Marks )

Refer principles of power systems - V.K.Metha& Rohit metha page no 484.

8. Explain how arc is initiated and sustained when the circuit breaker contacts break(6) (nov/dec 2011)

Refer answer in Part B Unit IV question no 1.

9. Explain in detail various methods of arc extinction in a circuit breaker.(10) (nov/dec 2011)

Refer answer in Part B Unit IV question no 1.

10. What is current chopping? Explain how can the effect of current chopping be minimized?(8) (nov/dec 2011)

Refer answer in Part B Unit IV question no 4

11. Derive an expression for the rate of rise of restriking voltage in a circuit breaker(8) (nov/dec 2011)

Refer answer in Part B Unit IV question no 3.

12

Page 13: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

Unit V1. How is SF6 gas is used as an arc quenching medium? Describe the construction and

working of a SF6 circuit breaker. State its advantages and disadvantages and its applications.

13

Page 14: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

2. Explain the role of oil in arc quenching in oil circuit breakers. Show sectional view of working portion of a typical low –oil circuit breaker.

14

Page 15: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

3. What are the requirements of a contact material for a vacuum circuit breaker? Why current chopping is not a serious problem with this circuit breaker?

4. Describe with sketches one form of arc control device for an oil circuit breaker and explain its action. Why are such devices necessary in oil circuit breaker?

15

Page 16: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

5. Discuss testing of circuit breakers.

6. With neat sketch explain the principles of axial blast air circuit breaker. Enumerate the advantages and disadvantages of air blast circuit breakers.

16

Page 17: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

7. Explain with neat diagram the working principle of air blast circuit breakers

Refer answer in Part B Unit V question no 7.

8. Explain with neat diagram the working principle of minimum oil circuit breakers. Explain the advantages of Minimum oil circuit breakers.

Refer answer in Part B Unit V question no 2.

9. Explain with neat sketch, the construction and working of minimum oil circuit breaker. Also give its merits and demerits. (16) (nov/dec 2011)

Refer answer in Part B Unit V question no 2.

10. Describe the various types of rating of circuit breaker (8) (nov/dec 2011)

17

Page 18: ELECTRICAL AND ELECTRONICS ENGINEERING ...sk4education.com/engineering/Question/17227 2.doc · Web viewRefer principles of power systems - V.K.Metha& Rohit metha page no 529. Explain

11. Describe the various methods of testing of circuit breaker (8) (nov/dec 2011)

Refer answer in Part B Unit V question no 6.

18