10
PLAN NORTH KEY PLAN CHECKED BY: REVISIONS DRAWN BY: DATE: PROJECT NUMBER CLIENT ARCHITECTURE SACRAMENTO 2520 VENTURE OAKS DR, SUITE 440 SACRAMENTO, CA 95833 t: 916-682-9494 PBK.com MEPT PBK CONTACT: BRIAN HOOD 11 GREENWAY PLAZA, 22ND FLOOR HOUSTON, TX 77046 t: 713-965-0608 f: 713-961-4571 NO. C-17626 L I C E N S E D A R C H I T E C T R E N . 1 0 - 3 1 - 1 9 S T A T E O F C A L I F O R N I A G A R Y J. G E R Y SWL RS / DR 01.16.2018 17311 SANTA ROSA CS ISSUE FOR BID No. Description Date PB G E C W

EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833

  • Upload
    lyphuc

  • View
    218

  • Download
    3

Embed Size (px)

Citation preview

Page 1: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833

PLAN

NORTH

KEY PLAN

CHECKED BY:

REVISIONS

DRAWN BY:

DATE:

PROJECT NUMBER

CLIENT

ARCHITECTURE

SACRAMENTO

2520 VENTURE OAKS DR, SUITE 440

SACRAMENTO, CA 95833

t: 916-682-9494

PBK.com

MEPT

PBKCONTACT: BRIAN HOOD

11 GREENWAY PLAZA, 22ND FLOOR HOUSTON, TX 77046

t: 713-965-0608f: 713-961-4571

NO. C-17626

L

I

C

E

N

S

E

D

AR

C

H

I

T

E

C

T

R

E

N

.

10

-

3

1

-

1

9

S

T

A

T

E

O

F

CA

L

I

F

O

R

N

I

A

G

A

R

Y

J. G

E

R

Y

SWL

RS / DR

01.16.2018

17311

SANTA ROSA CS

ISSUE FOR BID

No. Description Date

EJ

PB

G

E

C

W

AutoCAD SHX Text
DRAMA BUILDING
AutoCAD SHX Text
BUILDING "B"
AutoCAD SHX Text
BUILDING "A"
AutoCAD SHX Text
BUNGALOW "A"
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
BUILDING "D1"
AutoCAD SHX Text
BUILDING "D2"
AutoCAD SHX Text
BUILDING "D3"
AutoCAD SHX Text
CLASS ROOM
AutoCAD SHX Text
EXERCISE BUILDING
AutoCAD SHX Text
CHARTER SCHOOL "A"
AutoCAD SHX Text
CHARTER SCHOOL "B"
AutoCAD SHX Text
CHARTER SCHOOL "C"
AutoCAD SHX Text
CHARTER SCHOOL "D"
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CCLA
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
SQ. FT.
AutoCAD SHX Text
APPROX.
AutoCAD SHX Text
AREA
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
ESTIMATE YEAR REPLACEMENT
AutoCAD SHX Text
126,481
AutoCAD SHX Text
2017
AutoCAD SHX Text
BUILDING "D2"
AutoCAD SHX Text
3,194
AutoCAD SHX Text
2017
AutoCAD SHX Text
BUILDING "D3"
AutoCAD SHX Text
4,138
AutoCAD SHX Text
2017
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
16,406
AutoCAD SHX Text
2026
AutoCAD SHX Text
DRAMA BUILDING
AutoCAD SHX Text
4,209
AutoCAD SHX Text
2026
AutoCAD SHX Text
EXERCISE BUILDING
AutoCAD SHX Text
1,748
AutoCAD SHX Text
2026
AutoCAD SHX Text
CLASS ROOM
AutoCAD SHX Text
1,335
AutoCAD SHX Text
2026
AutoCAD SHX Text
CHARTER SCHOOL "A"
AutoCAD SHX Text
1,264
AutoCAD SHX Text
2026
AutoCAD SHX Text
CHARTER SCHOOL "B"
AutoCAD SHX Text
3,311
AutoCAD SHX Text
2026
AutoCAD SHX Text
CHARTER SCHOOL "C"
AutoCAD SHX Text
667
AutoCAD SHX Text
2026
AutoCAD SHX Text
CHARTER SCHOOL "D"
AutoCAD SHX Text
1,275
AutoCAD SHX Text
2017
AutoCAD SHX Text
2017
AutoCAD SHX Text
BUILDING "A"
AutoCAD SHX Text
35,743
AutoCAD SHX Text
2017
AutoCAD SHX Text
BUILDING "B"
AutoCAD SHX Text
21,563
AutoCAD SHX Text
2017
AutoCAD SHX Text
BUILDING "C"
AutoCAD SHX Text
4,568
AutoCAD SHX Text
2017
AutoCAD SHX Text
BUILDING "D1"
AutoCAD SHX Text
8,110
AutoCAD SHX Text
CCLA
AutoCAD SHX Text
18,951
AutoCAD SHX Text
HILLIARD COMSTOCK MIDDLE SCHOOL ROOF AND MECHANICAL REPLACEMENT PROJECT
AutoCAD SHX Text
2750 W STEELE LANE SANTA ROSA, CA 95403
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
1
AutoCAD SHX Text
6
AutoCAD SHX Text
13
AutoCAD SHX Text
28
AutoCAD SHX Text
27
AutoCAD SHX Text
26
AutoCAD SHX Text
HILLARD COMSTOCK MIDDLE SCHOOL - COMPOSITE ROOF PLAN
AutoCAD SHX Text
17307-A300.dwg
AutoCAD SHX Text
1' = 1'-0"
AutoCAD SHX Text
NEW NOMENCLATURE
AutoCAD SHX Text
NEW MOD. BIT. BASE PLY
AutoCAD SHX Text
NEW MOD. BIT. FINISH PLY
AutoCAD SHX Text
NEW 1/2" SUBSTATE BOARD
AutoCAD SHX Text
A
AutoCAD SHX Text
NEW MOD. BIT. BASE PLY
AutoCAD SHX Text
NEW MOD. BIT. FINISH PLY
AutoCAD SHX Text
NEW 1" FLAT STOCK
AutoCAD SHX Text
NEW VAPOR BARRIER
AutoCAD SHX Text
EXISTING WOOD DECK
AutoCAD SHX Text
NEW 1/8":12 TAPERED INSULATION BOARD
AutoCAD SHX Text
B
AutoCAD SHX Text
NEW 3" INSULATION
AutoCAD SHX Text
EXISTING WOOD DECK
AutoCAD SHX Text
NEW VAPOR BARRIER
AutoCAD SHX Text
A. CONTRACTOR SHALL VISIT SITE TO ASCERTAIN EXACT EXISTING CONDITIONS AND COMPONENTS RELATED TO THE WORK DESCRIBED BY THESE DOCUMENTS. AFTER AWARD OF THE CONTRACT, CHANGE ORDER REQUEST FOR ADDITIONAL MONEY SHALL NOT BE APPROVED IF THE WORK COULD HAVE BEEN ANTICIPATED DURING THE SITE VISIT BY THE CONTRACTOR, ALL WORK SHALL BE COMPLETED IN ACCORDANCE WITH ACCEPTED MANUFACTURER'S PRINTED INSTRUCTIONS & WARRANTY REQUIREMENTS. B. DIMENSIONS,DETAILS, EQUIPMENT SIZE AND LOCATION SHOWN IN THESE DOCUMENTS ARE FOR INFORMATION AND REFERENCE ONLY. EXACT SIZE, LOCATION, TYPE OF MATERIAL AND TYPE OF CONSTRUCTION OF EXISTING CONDITIONS ARE THE RESPONSIBILITY OF THE CONTRACTOR TO ASCERTAIN & CONFIRM. C. ALL NEW CRICKETS AND TAPERED INSULATION SHALL BE INSTALLED WITH A FINISHED 1/4" PER FOOT MIN. SLOPE. CRICKET THE UP SLOPE SIDE OF ALL SQUARE CURBS AND PROJECTIONS. D. REMOVE ALL ABANDONED EQUIP. IDENTIFIED ON ROOF TOP AND AS SHOWN ON DRAWINGS -(PATCH DECK) HOLES LESS THAN 10" WIDE- SCREW 22 GA. STAINLESS STEEL SHEET METAL TO EXISTING DECK HOLES GREATER THAN 10" WIDE- SCREW NEW METAL DECK (MATCH EXISTING) SPAN FROM JOIST TO JOIST. E. ALL HVAC AND/OR DX UNITS, ELECTRICAL TRANSFORMERS, ROOF TOP EQUIPMENT, ETC. THAT ARE ON SLEEPERS SHALL BE DISCONNECTED/REMOVED, RAISED, & PLACED ON NEW CURBED PLATFORMS (RE: DETAIL), AND RECONNECTED/RE-INSTALLED. VERIFY ALL EXISTING CURB MOUNTED UNITS, EQUIPMENT, ETC. HAVE A MINIMUM 10" CURB HEIGHT (RAISED AS REQUIRED) - ALL DISCONNECTS AND RECONNECTS SHALL BE PERFORMED BY A LICENSED ELECTRICIAN. F. IF EXISTING ELECTRICAL/GAS/WATER/ETC. LINES ARE MODIFIED- ONLY LICENSED SUBCONTRACTORS SPECIALIZING IN HVAC, PLUMBING AND ELECTRICAL SHALL PERFORM THAT TYPE OF WORK. PERMITS AND INSPECTIONS REQUIRED- PROVIDE "MERCURY" GAS LINE TEST (COORDINATE OWNER/ARCHITECT WITNESS OF TEST), REPAIR ALL LEAKS AND RE-TEST G. REPLACE AND RAISE (AS REQUIRED) ALL EXISTING EXPANSION JOINTS/AREA DIVIDERS/ CURB MOUNTED EQUIPMENT/ SKYLIGHTS A MIN. 10" ABOVE ROOF DECK. (UNLESS INDICATED OTHER WISE ON DRAWING.) H. ENSURE ALL SOIL STACK FLASHING IS MIN. 10" ABOVE ROOF. COUPLE PVC PIPE ABOVE DECK, COUPLE CAST IRON PIPE UNDER DECK. I. PROVIDE SHEET METAL HOODED (w/METAL FACE CLOSURE), WOOD CURB, BOX COVER AT ALL GAS LINE AND WATER LINE ROOF PENETRATIONS (RE: DETAILS). ENSURE LINES SLOPE AWAY FROM FACE COVER. J. PROVIDE WALKWAY PROTECTION PADS (AS ACCEPTABLE TO MANUFACTURER-RE: SPECS.) AROUND ALL ROOF HATCHES, A/C UNITS, DOORS THAT OPEN ONTO ROOF, AND AT ALL ROOF TOP ACCESS LADDERS (TOP & BOTTOM) K. ISOLATE ALL HEAT PIPES/FLUES AS RECOMMENDED & OUTLINED IN THE NRCA MANUAL FOR ISOLATED STACK FLASHING- (RE:DETAILS) L. ALL OUTSIDE AIR INTAKES SHALL BE COVERED TO ELIMINATE ODORS AND FUMES FROM ENTERING INTO THE BUILDING DURING WORK. M. EXAMINE AND CLEAN EXISTING DRAIN LINES OF DEBRIS AND BLOCKAGE, FLUSH WITH WATER TO ENSURE THAT DRAINS FLOW FREELY. N. OWNER WILL VERIFY CORRECT OPERATION OF ALL ROOF TOP EQUIPMENT BEFORE AND AFTER PROJECT. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYING ALL INOPERABLE EQUIPMENT PRIOR TO RELEASE OF RETAINAGE. O. REPLACE ALL RUSTED/DETERIORATED EXISTING METAL VENT FLASHING AND FLUES. P. COORDINATE WALK OF ENTIRE ROOF (PRIOR TO STARTING) WITH ROOFING MANUFACTURER'S TECHNICAL REP. TO IDENTIFY AND LOCATE ALL AREAS OF HIGH SLOPE WHICH MIGHT REQUIRE SPECIAL PROCEDURES FOR SYSTEM ATTACHMENT.
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
INDEX
AutoCAD SHX Text
M1.0- MECHANICAL ROOF PLAN-COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
24
AutoCAD SHX Text
22
AutoCAD SHX Text
21
AutoCAD SHX Text
20
AutoCAD SHX Text
8
AutoCAD SHX Text
2
AutoCAD SHX Text
SITE MAP
AutoCAD SHX Text
POWER VENT
AutoCAD SHX Text
GOOSE NECK VENT
AutoCAD SHX Text
BOILER VENT
AutoCAD SHX Text
HEATER VENT
AutoCAD SHX Text
SPLASH BLOCK
AutoCAD SHX Text
CURB MOUNTED A/C
AutoCAD SHX Text
SPLASH PAN
AutoCAD SHX Text
A/C ON POSTS
AutoCAD SHX Text
TURBINE VENT
AutoCAD SHX Text
ABANDON EQUIP.
AutoCAD SHX Text
SKYLIGHT
AutoCAD SHX Text
ROOF HATCH
AutoCAD SHX Text
GUY WIRE
AutoCAD SHX Text
BE REMOVED/PATCHED
AutoCAD SHX Text
ABANDONED CURB TO
AutoCAD SHX Text
A
AutoCAD SHX Text
PLUMBING VENT
AutoCAD SHX Text
FLANGE VENT
AutoCAD SHX Text
EXIST. ROOF DRAIN
AutoCAD SHX Text
NEW ROOF DRAIN
AutoCAD SHX Text
PITCH PAN
AutoCAD SHX Text
OVERFLOW DRAIN
AutoCAD SHX Text
WALL DRAIN
AutoCAD SHX Text
CURB MOUNTED VENT
AutoCAD SHX Text
CURB MOUNTED VENT
AutoCAD SHX Text
ROOF AREA
AutoCAD SHX Text
OF WORK IDENTIFIED
AutoCAD SHX Text
DESIGNATES EXTENTS
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
WATER LINE
AutoCAD SHX Text
CONDINSATE LINE
AutoCAD SHX Text
A1
AutoCAD SHX Text
EXISTING AREAS TO
AutoCAD SHX Text
NEW TAPERED
AutoCAD SHX Text
ELEC. LINE
AutoCAD SHX Text
GAS LINE
AutoCAD SHX Text
SWING LADDER
AutoCAD SHX Text
DOWNSPOUT
AutoCAD SHX Text
WALL LADDER
AutoCAD SHX Text
SCUPPER
AutoCAD SHX Text
GUTTER
AutoCAD SHX Text
ANTENNA
AutoCAD SHX Text
SATELLITE DISH
AutoCAD SHX Text
DS
AutoCAD SHX Text
SC
AutoCAD SHX Text
G
AutoCAD SHX Text
TAPERED LIGHTWEIGHT
AutoCAD SHX Text
v
AutoCAD SHX Text
OF
AutoCAD SHX Text
PIPE BOX
AutoCAD SHX Text
GENERAL LEGEND
AutoCAD SHX Text
GENERAL INFO.
AutoCAD SHX Text
BASE SYSTEM
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
BY KEYED NOTES
AutoCAD SHX Text
DESIGNATION
AutoCAD SHX Text
INSULATION / CRICKET
AutoCAD SHX Text
REMAIN - NIC
AutoCAD SHX Text
RIDGE LINE
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
SL
AutoCAD SHX Text
SCOPE OF WORK
AutoCAD SHX Text
HILLIARD COMSTOCK MIDDLE SCHOOL 2750 W STEELE LANE, SANTA ROSA, CALIFORNIA 95403 BASE PROPOSAL: REMOVE AND PROPERLY DISPOSE OF EXISTING ROOFING / INSULATIONS DOWN TO AND PROPERLY DISPOSE OF EXISTING ROOFING / INSULATIONS DOWN TO AND PROPERLY DISPOSE OF EXISTING ROOFING / INSULATIONS DOWN TO PROPERLY DISPOSE OF EXISTING ROOFING / INSULATIONS DOWN TO PROPERLY DISPOSE OF EXISTING ROOFING / INSULATIONS DOWN TO DISPOSE OF EXISTING ROOFING / INSULATIONS DOWN TO DISPOSE OF EXISTING ROOFING / INSULATIONS DOWN TO OF EXISTING ROOFING / INSULATIONS DOWN TO OF EXISTING ROOFING / INSULATIONS DOWN TO EXISTING ROOFING / INSULATIONS DOWN TO EXISTING ROOFING / INSULATIONS DOWN TO ROOFING / INSULATIONS DOWN TO ROOFING / INSULATIONS DOWN TO / INSULATIONS DOWN TO / INSULATIONS DOWN TO INSULATIONS DOWN TO INSULATIONS DOWN TO DOWN TO DOWN TO TO TO EXISTING ROOF DECK AT ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD ROOF DECK AT ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD ROOF DECK AT ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD DECK AT ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD DECK AT ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD AT ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD AT ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD ROOF AREAS E AND F. REPAIR / PREPARE EXISTING WOOD AREAS E AND F. REPAIR / PREPARE EXISTING WOOD AREAS E AND F. REPAIR / PREPARE EXISTING WOOD E AND F. REPAIR / PREPARE EXISTING WOOD E AND F. REPAIR / PREPARE EXISTING WOOD AND F. REPAIR / PREPARE EXISTING WOOD AND F. REPAIR / PREPARE EXISTING WOOD F. REPAIR / PREPARE EXISTING WOOD F. REPAIR / PREPARE EXISTING WOOD REPAIR / PREPARE EXISTING WOOD REPAIR / PREPARE EXISTING WOOD / PREPARE EXISTING WOOD / PREPARE EXISTING WOOD PREPARE EXISTING WOOD PREPARE EXISTING WOOD EXISTING WOOD EXISTING WOOD WOOD WOOD DECK AND LOOSE LAY NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL AND LOOSE LAY NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL AND LOOSE LAY NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL LOOSE LAY NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL LOOSE LAY NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL LAY NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL LAY NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL NEW ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL ROSIN PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL PAPER AND 1” POLYISOCYANURATE INSULATION. INSTALL AND 1” POLYISOCYANURATE INSULATION. INSTALL AND 1” POLYISOCYANURATE INSULATION. INSTALL 1” POLYISOCYANURATE INSULATION. INSTALL 1” POLYISOCYANURATE INSULATION. INSTALL POLYISOCYANURATE INSULATION. INSTALL POLYISOCYANURATE INSULATION. INSTALL INSULATION. INSTALL INSULATION. INSTALL INSTALL INSTALL NEW 2X WOOD BLOCKING AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO 2X WOOD BLOCKING AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO 2X WOOD BLOCKING AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO WOOD BLOCKING AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO WOOD BLOCKING AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO BLOCKING AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO BLOCKING AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO AND SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO SHIM NAILERS AROUND PERIMETER OF ROOF EDGE TO NAILERS AROUND PERIMETER OF ROOF EDGE TO NAILERS AROUND PERIMETER OF ROOF EDGE TO AROUND PERIMETER OF ROOF EDGE TO AROUND PERIMETER OF ROOF EDGE TO PERIMETER OF ROOF EDGE TO PERIMETER OF ROOF EDGE TO OF ROOF EDGE TO OF ROOF EDGE TO ROOF EDGE TO ROOF EDGE TO EDGE TO EDGE TO TO TO MATCH NEW ROOF INSULATION AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH NEW ROOF INSULATION AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH NEW ROOF INSULATION AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH ROOF INSULATION AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH ROOF INSULATION AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH INSULATION AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH INSULATION AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH AND RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH RECOVERY BOARD ELEVATIONS. MECHANICALLY ATTACH BOARD ELEVATIONS. MECHANICALLY ATTACH BOARD ELEVATIONS. MECHANICALLY ATTACH ELEVATIONS. MECHANICALLY ATTACH ELEVATIONS. MECHANICALLY ATTACH MECHANICALLY ATTACH MECHANICALLY ATTACH ATTACH ATTACH NEW TAPERED INSULATION SLOPED 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND TAPERED INSULATION SLOPED 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND TAPERED INSULATION SLOPED 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND INSULATION SLOPED 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND INSULATION SLOPED 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND SLOPED 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND SLOPED 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND 1/8” PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND PER FOOT SLOPING TO RIDGE, EAVES, HIPS AND FOOT SLOPING TO RIDGE, EAVES, HIPS AND FOOT SLOPING TO RIDGE, EAVES, HIPS AND SLOPING TO RIDGE, EAVES, HIPS AND SLOPING TO RIDGE, EAVES, HIPS AND TO RIDGE, EAVES, HIPS AND TO RIDGE, EAVES, HIPS AND RIDGE, EAVES, HIPS AND RIDGE, EAVES, HIPS AND EAVES, HIPS AND EAVES, HIPS AND HIPS AND HIPS AND AND AND VALLEYS AS INDICATED ON ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED AS INDICATED ON ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED AS INDICATED ON ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED INDICATED ON ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED INDICATED ON ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED ON ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED ON ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED ROOF PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED PLAN. INSTALL NEW 1/4” RECOVERY BOARD SECURED INSTALL NEW 1/4” RECOVERY BOARD SECURED INSTALL NEW 1/4” RECOVERY BOARD SECURED NEW 1/4” RECOVERY BOARD SECURED NEW 1/4” RECOVERY BOARD SECURED 1/4” RECOVERY BOARD SECURED 1/4” RECOVERY BOARD SECURED RECOVERY BOARD SECURED RECOVERY BOARD SECURED BOARD SECURED BOARD SECURED SECURED SECURED TO EXISTING ROOF DECK, ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE EXISTING ROOF DECK, ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE EXISTING ROOF DECK, ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE ROOF DECK, ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE ROOF DECK, ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE DECK, ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE DECK, ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE ENSURE ALL FASTENERS ARE PROPERLY SECURED TO THE ALL FASTENERS ARE PROPERLY SECURED TO THE ALL FASTENERS ARE PROPERLY SECURED TO THE FASTENERS ARE PROPERLY SECURED TO THE FASTENERS ARE PROPERLY SECURED TO THE ARE PROPERLY SECURED TO THE ARE PROPERLY SECURED TO THE PROPERLY SECURED TO THE PROPERLY SECURED TO THE SECURED TO THE SECURED TO THE TO THE TO THE THE THE EXISTING ROOF DECK WITHOUT PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW ROOF DECK WITHOUT PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW ROOF DECK WITHOUT PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW DECK WITHOUT PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW DECK WITHOUT PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW WITHOUT PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW WITHOUT PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW PENETRATING THROUGH THE UNDERSIDE. INSTALL NEW THROUGH THE UNDERSIDE. INSTALL NEW THROUGH THE UNDERSIDE. INSTALL NEW THE UNDERSIDE. INSTALL NEW THE UNDERSIDE. INSTALL NEW UNDERSIDE. INSTALL NEW UNDERSIDE. INSTALL NEW INSTALL NEW INSTALL NEW NEW NEW SPECIFIED MODIFIED BITUMEN BASE PLY AND NEW FULLY ADHERED FLEECE-BACKED MODIFIED BITUMEN BASE PLY AND NEW FULLY ADHERED FLEECE-BACKED MODIFIED BITUMEN BASE PLY AND NEW FULLY ADHERED FLEECE-BACKED BITUMEN BASE PLY AND NEW FULLY ADHERED FLEECE-BACKED BITUMEN BASE PLY AND NEW FULLY ADHERED FLEECE-BACKED BASE PLY AND NEW FULLY ADHERED FLEECE-BACKED BASE PLY AND NEW FULLY ADHERED FLEECE-BACKED PLY AND NEW FULLY ADHERED FLEECE-BACKED PLY AND NEW FULLY ADHERED FLEECE-BACKED AND NEW FULLY ADHERED FLEECE-BACKED AND NEW FULLY ADHERED FLEECE-BACKED NEW FULLY ADHERED FLEECE-BACKED NEW FULLY ADHERED FLEECE-BACKED FULLY ADHERED FLEECE-BACKED FULLY ADHERED FLEECE-BACKED ADHERED FLEECE-BACKED ADHERED FLEECE-BACKED FLEECE-BACKED FLEECE-BACKED THERMOPLASTIC ROOF MEMBRANE FINISH PLY WITH ASSOCIATED ROOF RELATED SHEET ROOF MEMBRANE FINISH PLY WITH ASSOCIATED ROOF RELATED SHEET ROOF MEMBRANE FINISH PLY WITH ASSOCIATED ROOF RELATED SHEET MEMBRANE FINISH PLY WITH ASSOCIATED ROOF RELATED SHEET MEMBRANE FINISH PLY WITH ASSOCIATED ROOF RELATED SHEET FINISH PLY WITH ASSOCIATED ROOF RELATED SHEET FINISH PLY WITH ASSOCIATED ROOF RELATED SHEET PLY WITH ASSOCIATED ROOF RELATED SHEET PLY WITH ASSOCIATED ROOF RELATED SHEET WITH ASSOCIATED ROOF RELATED SHEET WITH ASSOCIATED ROOF RELATED SHEET ASSOCIATED ROOF RELATED SHEET ASSOCIATED ROOF RELATED SHEET ROOF RELATED SHEET ROOF RELATED SHEET RELATED SHEET RELATED SHEET SHEET SHEET METALS, GUTTERS, DOWNSPOUTS AND TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR GUTTERS, DOWNSPOUTS AND TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR GUTTERS, DOWNSPOUTS AND TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR DOWNSPOUTS AND TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR DOWNSPOUTS AND TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR AND TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR AND TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR TRIM. INSTALL NEW SPECIFIED PIPE SUPPORTS FOR INSTALL NEW SPECIFIED PIPE SUPPORTS FOR INSTALL NEW SPECIFIED PIPE SUPPORTS FOR INSTALL NEW SPECIFIED PIPE SUPPORTS FOR NEW SPECIFIED PIPE SUPPORTS FOR NEW SPECIFIED PIPE SUPPORTS FOR SPECIFIED PIPE SUPPORTS FOR SPECIFIED PIPE SUPPORTS FOR PIPE SUPPORTS FOR PIPE SUPPORTS FOR SUPPORTS FOR SUPPORTS FOR FOR FOR CONDUIT AND UTILITY PIPES WITH PROTECTION PADS. REPAIR / PATCH EXISTING ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, / PATCH EXISTING ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, / PATCH EXISTING ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, PATCH EXISTING ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, PATCH EXISTING ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, EXISTING ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, EXISTING ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, ROOF SYSTEM INCLUDING BLISTERS, DELAMINATION, SYSTEM INCLUDING BLISTERS, DELAMINATION, SYSTEM INCLUDING BLISTERS, DELAMINATION, INCLUDING BLISTERS, DELAMINATION, INCLUDING BLISTERS, DELAMINATION, BLISTERS, DELAMINATION, BLISTERS, DELAMINATION, DELAMINATION, DELAMINATION, DETERIORATION, EXCESSIVE MOISTURE CONTENT, ETC. AT ROOF AREAS C3. CLEAN / EXCESSIVE MOISTURE CONTENT, ETC. AT ROOF AREAS C3. CLEAN / EXCESSIVE MOISTURE CONTENT, ETC. AT ROOF AREAS C3. CLEAN / MOISTURE CONTENT, ETC. AT ROOF AREAS C3. CLEAN / MOISTURE CONTENT, ETC. AT ROOF AREAS C3. CLEAN / CONTENT, ETC. AT ROOF AREAS C3. CLEAN / CONTENT, ETC. AT ROOF AREAS C3. CLEAN / ETC. AT ROOF AREAS C3. CLEAN / ETC. AT ROOF AREAS C3. CLEAN / AT ROOF AREAS C3. CLEAN / AT ROOF AREAS C3. CLEAN / ROOF AREAS C3. CLEAN / ROOF AREAS C3. CLEAN / AREAS C3. CLEAN / AREAS C3. CLEAN / C3. CLEAN / C3. CLEAN / CLEAN / CLEAN / CLEAN / / / PREPARE EXISTING ROOF MEMBRANE, STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF EXISTING ROOF MEMBRANE, STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF EXISTING ROOF MEMBRANE, STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF ROOF MEMBRANE, STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF ROOF MEMBRANE, STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF MEMBRANE, STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF MEMBRANE, STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF STRIP IN ALL DRIP EDGES, DRAIN BOWLS, ROOF IN ALL DRIP EDGES, DRAIN BOWLS, ROOF IN ALL DRIP EDGES, DRAIN BOWLS, ROOF ALL DRIP EDGES, DRAIN BOWLS, ROOF ALL DRIP EDGES, DRAIN BOWLS, ROOF DRIP EDGES, DRAIN BOWLS, ROOF DRIP EDGES, DRAIN BOWLS, ROOF EDGES, DRAIN BOWLS, ROOF EDGES, DRAIN BOWLS, ROOF DRAIN BOWLS, ROOF DRAIN BOWLS, ROOF BOWLS, ROOF BOWLS, ROOF ROOF ROOF PENETRATIONS, ETC. WITH FLUID APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL ETC. WITH FLUID APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL ETC. WITH FLUID APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL WITH FLUID APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL WITH FLUID APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL FLUID APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL FLUID APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL APPLIED POLYURETHANE REINFORCING MASTIC. INSTALL POLYURETHANE REINFORCING MASTIC. INSTALL POLYURETHANE REINFORCING MASTIC. INSTALL REINFORCING MASTIC. INSTALL REINFORCING MASTIC. INSTALL MASTIC. INSTALL MASTIC. INSTALL INSTALL INSTALL INSTALL NEW FLUID APPLIED POLYURETHANE ROOF TOP BASE COAT PARTIALLY REINFORCED OVER FLUID APPLIED POLYURETHANE ROOF TOP BASE COAT PARTIALLY REINFORCED OVER FLUID APPLIED POLYURETHANE ROOF TOP BASE COAT PARTIALLY REINFORCED OVER APPLIED POLYURETHANE ROOF TOP BASE COAT PARTIALLY REINFORCED OVER APPLIED POLYURETHANE ROOF TOP BASE COAT PARTIALLY REINFORCED OVER POLYURETHANE ROOF TOP BASE COAT PARTIALLY REINFORCED OVER POLYURETHANE ROOF TOP BASE COAT PARTIALLY REINFORCED OVER ROOF TOP BASE COAT PARTIALLY REINFORCED OVER ROOF TOP BASE COAT PARTIALLY REINFORCED OVER TOP BASE COAT PARTIALLY REINFORCED OVER TOP BASE COAT PARTIALLY REINFORCED OVER BASE COAT PARTIALLY REINFORCED OVER BASE COAT PARTIALLY REINFORCED OVER COAT PARTIALLY REINFORCED OVER COAT PARTIALLY REINFORCED OVER PARTIALLY REINFORCED OVER PARTIALLY REINFORCED OVER REINFORCED OVER REINFORCED OVER OVER OVER EXISTING PREPARED ROOF SYSTEM PER MANUFACTURER'S REQUIREMENTS. AFTER BASE PREPARED ROOF SYSTEM PER MANUFACTURER'S REQUIREMENTS. AFTER BASE PREPARED ROOF SYSTEM PER MANUFACTURER'S REQUIREMENTS. AFTER BASE ROOF SYSTEM PER MANUFACTURER'S REQUIREMENTS. AFTER BASE ROOF SYSTEM PER MANUFACTURER'S REQUIREMENTS. AFTER BASE SYSTEM PER MANUFACTURER'S REQUIREMENTS. AFTER BASE SYSTEM PER MANUFACTURER'S REQUIREMENTS. AFTER BASE PER MANUFACTURER'S REQUIREMENTS. AFTER BASE PER MANUFACTURER'S REQUIREMENTS. AFTER BASE MANUFACTURER'S REQUIREMENTS. AFTER BASE MANUFACTURER'S REQUIREMENTS. AFTER BASE REQUIREMENTS. AFTER BASE REQUIREMENTS. AFTER BASE AFTER BASE AFTER BASE AFTER BASE BASE BASE COAT HAS PROPERLY CURED, APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. HAS PROPERLY CURED, APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. HAS PROPERLY CURED, APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. PROPERLY CURED, APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. PROPERLY CURED, APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. CURED, APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. CURED, APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. APPLY TOP COAT PER MANUFACTURER'S REQUIREMENTS. TOP COAT PER MANUFACTURER'S REQUIREMENTS. TOP COAT PER MANUFACTURER'S REQUIREMENTS. COAT PER MANUFACTURER'S REQUIREMENTS. COAT PER MANUFACTURER'S REQUIREMENTS. PER MANUFACTURER'S REQUIREMENTS. PER MANUFACTURER'S REQUIREMENTS. MANUFACTURER'S REQUIREMENTS. MANUFACTURER'S REQUIREMENTS. REQUIREMENTS. REQUIREMENTS. INSTALL NEW SAW-CUT REGLET AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING NEW SAW-CUT REGLET AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING NEW SAW-CUT REGLET AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING SAW-CUT REGLET AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING SAW-CUT REGLET AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING REGLET AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING REGLET AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING AND REMOVEABLE COUNTER FLASHING ABOVE EXISTING REMOVEABLE COUNTER FLASHING ABOVE EXISTING REMOVEABLE COUNTER FLASHING ABOVE EXISTING COUNTER FLASHING ABOVE EXISTING COUNTER FLASHING ABOVE EXISTING FLASHING ABOVE EXISTING FLASHING ABOVE EXISTING ABOVE EXISTING ABOVE EXISTING EXISTING EXISTING BASE FLASHING AT RISE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE FLASHING AT RISE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE FLASHING AT RISE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE AT RISE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE AT RISE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE RISE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE RISE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE WALLS. INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE INSTALL NEW PROTECTION PADS AT ALL EXISTING PIPE NEW PROTECTION PADS AT ALL EXISTING PIPE NEW PROTECTION PADS AT ALL EXISTING PIPE PROTECTION PADS AT ALL EXISTING PIPE PROTECTION PADS AT ALL EXISTING PIPE PADS AT ALL EXISTING PIPE PADS AT ALL EXISTING PIPE AT ALL EXISTING PIPE AT ALL EXISTING PIPE ALL EXISTING PIPE ALL EXISTING PIPE EXISTING PIPE EXISTING PIPE PIPE PIPE SUPPORTS FOR CONDUIT, UTILITY PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF FOR CONDUIT, UTILITY PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF FOR CONDUIT, UTILITY PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF CONDUIT, UTILITY PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF CONDUIT, UTILITY PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF UTILITY PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF UTILITY PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF PIPES AND DOWNSPOUT SPLASH PANS ABOVE ROOF AND DOWNSPOUT SPLASH PANS ABOVE ROOF AND DOWNSPOUT SPLASH PANS ABOVE ROOF DOWNSPOUT SPLASH PANS ABOVE ROOF DOWNSPOUT SPLASH PANS ABOVE ROOF SPLASH PANS ABOVE ROOF SPLASH PANS ABOVE ROOF PANS ABOVE ROOF PANS ABOVE ROOF ABOVE ROOF ABOVE ROOF ROOF ROOF AREAS.
AutoCAD SHX Text
GO
AutoCAD SHX Text
GENERAL INFORMATION
AutoCAD SHX Text
HILLARD COMSTOCK MS
AutoCAD SHX Text
NOTE: CONTRACTOR TO REFER TO MEP SHEETS FOR REFERENCE TO REMOVAL OF EXISTING ABANDONED CURB/ EQUIPMENT. LOCATIONS OF NEW CURB EQUIPMENT AND ASSOCIATED FLASHING, TRIM OR PENETRATIONS.
AutoCAD SHX Text
KEY NOTES 1 REMOVE EXISTING METAL WALL PANELS, INSTALL NEW WALL FLASHINGS AT MIN. 10" OF WALL, NEW STAINLESS STEEL COUNTER FLASHING. CUT EXISTING METAL WALL PANELS TO IT NEW WALL FLASHING HEIGHT IT NEW WALL FLASHING HEIGHT AND RE-INSTALL.
AutoCAD SHX Text
NEW NOMENCLATURE
AutoCAD SHX Text
14
AutoCAD SHX Text
ROOF AREAS
AutoCAD SHX Text
M2.0- MECHANICAL SCHEDULES-COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
M3.0- MECHANICAL DETAILS-COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
E1.0- ELECTRICAL PLAN- COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
E2.0- ELECTRICAL DETAILS- COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
P1.0- PLUMBING PLAN- COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
P2.0-PLUMBING DETAILS- COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
PLUMBING
AutoCAD SHX Text
GO-GENERAL INFORMATION -COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
A1- ROOF PLAN-COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
ARCHITECTURAL
AutoCAD SHX Text
A2-ROOF PLAN-COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
DRAWING INDEX
Page 2: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833

PLAN

NORTH

KEY PLAN

CHECKED BY:

REVISIONS

DRAWN BY:

DATE:

PROJECT NUMBER

CLIENT

ARCHITECTURE

SACRAMENTO

2520 VENTURE OAKS DR, SUITE 440

SACRAMENTO, CA 95833

t: 916-682-9494

PBK.com

MEPT

PBKCONTACT: BRIAN HOOD

11 GREENWAY PLAZA, 22ND FLOOR HOUSTON, TX 77046

t: 713-965-0608f: 713-961-4571

NO. C-17626

L

I

C

E

N

S

E

D

AR

C

H

I

T

E

C

T

R

E

N

.

10

-

3

1

-

1

9

S

T

A

T

E

O

F

CA

L

I

F

O

R

N

I

A

G

A

R

Y

J. G

E

R

Y

SWL

RS / DR

01.16.2018

17311

SANTA ROSA CS

ISSUE FOR BID

No. Description Date

AutoCAD SHX Text
DRAMA BUILDING
AutoCAD SHX Text
BUILDING "B"
AutoCAD SHX Text
BUILDING "A"
AutoCAD SHX Text
BUNGALOW "A"
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
BUILDING "D1"
AutoCAD SHX Text
BUILDING "D2"
AutoCAD SHX Text
BUILDING "D3"
AutoCAD SHX Text
CLASS ROOM
AutoCAD SHX Text
EXERCISE BUILDING
AutoCAD SHX Text
CHARTER SCHOOL "A"
AutoCAD SHX Text
CHARTER SCHOOL "B"
AutoCAD SHX Text
CHARTER SCHOOL "C"
AutoCAD SHX Text
CHARTER SCHOOL "D"
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CCLA
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
HILLIARD COMSTOCK MIDDLE SCHOOL ROOF AND MECHANICAL REPLACEMENT PROJECT
AutoCAD SHX Text
2750 W STEELE LANE SANTA ROSA, CA 95403
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
1
AutoCAD SHX Text
6
AutoCAD SHX Text
7
AutoCAD SHX Text
13
AutoCAD SHX Text
19
AutoCAD SHX Text
25
AutoCAD SHX Text
A1
AutoCAD SHX Text
ROOF PLAN
AutoCAD SHX Text
HILLIARD COMSTOCK MS
AutoCAD SHX Text
NOTE: CONTRACTOR TO REFER TO MEP SHEETS FOR REFERENCE TO REMOVAL OF EXISTING ABANDONED CURB/ EQUIPMENT. LOCATIONS OF NEW CURB EQUIPMENT AND ASSOCIATED FLASHING, TRIM OR PENETRATIONS.
AutoCAD SHX Text
KEY NOTES 1 REMOVE EXISTING METAL WALL PANELS, INSTALL NEW WALL FLASHINGS AT MIN. 10" OF WALL, NEW STAINLESS STEEL COUNTER FLASHING. CUT EXISTING METAL WALL PANELS TO IT NEW WALL FLASHING HEIGHT AND RE-INSTALL
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
11/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
11/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
11/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
11/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
5/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
13/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
13/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
13/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
22/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
22/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
22/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
22/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
1/A1
AutoCAD SHX Text
TYP.
Page 3: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833

PLAN

NORTH

KEY PLAN

CHECKED BY:

REVISIONS

DRAWN BY:

DATE:

PROJECT NUMBER

CLIENT

ARCHITECTURE

SACRAMENTO

2520 VENTURE OAKS DR, SUITE 440

SACRAMENTO, CA 95833

t: 916-682-9494

PBK.com

MEPT

PBKCONTACT: BRIAN HOOD

11 GREENWAY PLAZA, 22ND FLOOR HOUSTON, TX 77046

t: 713-965-0608f: 713-961-4571

NO. C-17626

L

I

C

E

N

S

E

D

AR

C

H

I

T

E

C

T

R

E

N

.

10

-

3

1

-

1

9

S

T

A

T

E

O

F

CA

L

I

F

O

R

N

I

A

G

A

R

Y

J. G

E

R

Y

SWL

RS / DR

01.16.2018

17311

SANTA ROSA CS

ISSUE FOR BID

No. Description Date

SYSTEMROOF

4" 4"MIN

HOT AIR WELDED

ROOF DECK

PIPE PENTRATION

ROOF SEALANT

PITCH PANMEMBRANE COATED METAL

SINGLE PENETRATION

COMPLETED ASSEMBLY

SPECIFIED

QUICK SETTING GROUT

ELASTOMERIC SEALANT &

METAL UMBRELLA FLASHING

STAINLESS STEEL DRAW BAND

POURABLE SEALER

MULTIPLE PENETRATIONS

SCREWS & SEALING WASHERSSHEET METAL HOOD & FACE COVER

PIPES (FORM DOWNWARDLOOP AWAY FROM HOOD)

MIN.6"

FLASHING MEMBRANEAPPROX. 4" BEYONDFLANGE

ELASTOMERIC SEALANT

S.S. METAL & STAINLESS STEEL

UMBRELLA FLASHINGDRAW BAND

AutoCAD SHX Text
HILLIARD COMSTOCK MIDDLE SCHOOL ROOF AND MECHANICAL REPLACEMENT PROJECT
AutoCAD SHX Text
2750 W STEELE LANE SANTA ROSA, CA 95403
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
A2
AutoCAD SHX Text
ROOF GENERAL DETAILS
AutoCAD SHX Text
HILLIARD COMSTOCK MS
AutoCAD SHX Text
5
AutoCAD SHX Text
12
AutoCAD SHX Text
13
AutoCAD SHX Text
17
AutoCAD SHX Text
19
AutoCAD SHX Text
20
AutoCAD SHX Text
11
AutoCAD SHX Text
6
AutoCAD SHX Text
1
AutoCAD SHX Text
16
AutoCAD SHX Text
18
AutoCAD SHX Text
7
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
10
AutoCAD SHX Text
4" MIN.
AutoCAD SHX Text
1 1/2"
AutoCAD SHX Text
CONTINUOUS SEALANT
AutoCAD SHX Text
FASTENERS AT APPROX.
AutoCAD SHX Text
3" O.C.; 1" STAGGER
AutoCAD SHX Text
EXTEND FINISH PLY TO
AutoCAD SHX Text
BELOW BLOCKING
AutoCAD SHX Text
MOD BIT BASE PLY
AutoCAD SHX Text
ROOF MEMBRANE
AutoCAD SHX Text
HOT AIR WELDED
AutoCAD SHX Text
FLASHING MEMBRANE
AutoCAD SHX Text
APPROX. 4" BEYOND FLANGE
AutoCAD SHX Text
4
AutoCAD SHX Text
MEMBRANE COATED
AutoCAD SHX Text
GRAVEL STOP.
AutoCAD SHX Text
MEMBRANE COATED METAL
AutoCAD SHX Text
JOINT COVER PLATE 6"
AutoCAD SHX Text
WIDE MIN. SET IN TWO
AutoCAD SHX Text
BEADS OF SEALANT
AutoCAD SHX Text
PERIMETER EDGE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
2x WOOD NAILERS
AutoCAD SHX Text
1/2"GAP
AutoCAD SHX Text
10' MAX.
AutoCAD SHX Text
LENGTH EA. PIECE OF
AutoCAD SHX Text
PERIMETER FLASHING
AutoCAD SHX Text
CONTINUOUS CLEAT
AutoCAD SHX Text
FASTENED APPROX. 6" O.C.
AutoCAD SHX Text
TOP OF WALL
AutoCAD SHX Text
1" MIN. BELOW
AutoCAD SHX Text
PITCH PAN
AutoCAD SHX Text
07M-FP01.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
BASE FLASHING
AutoCAD SHX Text
Bsflsh-Thruwall.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
3 COURSING
AutoCAD SHX Text
STAINLESS STEEL REGLET
AutoCAD SHX Text
PROVIDE NEW REMOVABLE COUNTER FLASHING.
AutoCAD SHX Text
UNLESS OTHERWISE NOTED, RE-USE EXISTING THRU WALL REICEIVER
AutoCAD SHX Text
FASTENERS APPROX. 24" O.C.
AutoCAD SHX Text
3" LAP AT JOINTS
AutoCAD SHX Text
COUNTERFLASHING
AutoCAD SHX Text
FASTENERS APPROX. 8" O.C.
AutoCAD SHX Text
REMOVABLE SHEET METAL
AutoCAD SHX Text
REINFORCING PLY - RE: SPEC
AutoCAD SHX Text
2" WIDE WIND CLIPS @ 3' O.C.
AutoCAD SHX Text
3" LAP W/ BEAD OF SEALANT
AutoCAD SHX Text
MOD. BIT. BASE PLY
AutoCAD SHX Text
EXISITNG DECK.
AutoCAD SHX Text
MIN. 8" HEIGHT
AutoCAD SHX Text
FINISH FLASHING MEMBRANE
AutoCAD SHX Text
FINISH PLY
AutoCAD SHX Text
WEEP HOLES @ 24" O.C.
AutoCAD SHX Text
THROUGH-WALL FLASHING
AutoCAD SHX Text
TOOLED POLYURETHANE SEALANT
AutoCAD SHX Text
CONTINUOUS FLEXIBLE MEMBRANE
AutoCAD SHX Text
ROOF EDGE W/ GUTTER
AutoCAD SHX Text
07M-PE02.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TURN-DOWN
AutoCAD SHX Text
SHEET METAL GUTTER
AutoCAD SHX Text
GUTTER SUPPORT RE: SPECS
AutoCAD SHX Text
FLEXIBLE MEMBRANE
AutoCAD SHX Text
FASTENERS AT APPROX
AutoCAD SHX Text
3" O.C. STAGGERED
AutoCAD SHX Text
STRIPPING
AutoCAD SHX Text
PLY RE: SPECS
AutoCAD SHX Text
GUTTER STRAPS
AutoCAD SHX Text
ALTERNATELY SPACED
AutoCAD SHX Text
FROM SUPPORTS
AutoCAD SHX Text
CLOSURE EXTEND
AutoCAD SHX Text
INTO GUTTER
AutoCAD SHX Text
BASE SHEET RE: SPECS
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
WOOD
AutoCAD SHX Text
NAILERS
AutoCAD SHX Text
EXTEND ONE PLY
AutoCAD SHX Text
FINISH PLY
AutoCAD SHX Text
SECURE TO WALL INDEPENDENT
AutoCAD SHX Text
FROM GUTTER
AutoCAD SHX Text
MOD BIT BASE PLY
AutoCAD SHX Text
BASE FLASHING @ EJ
AutoCAD SHX Text
07M-EJ03.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
BEVEL TOP TO
AutoCAD SHX Text
MEMBRANE
AutoCAD SHX Text
ROOF DECK-RE:SPECS
AutoCAD SHX Text
CONT. WATERPROOFING
AutoCAD SHX Text
DRAIN ROOFSIDE
AutoCAD SHX Text
12" O.C. W/ GASKETED SCREWS
AutoCAD SHX Text
E.J. FLASHING CLEAT FASTENED
AutoCAD SHX Text
FASTENERS 24" O.C.
AutoCAD SHX Text
FASTENERS 8" O.C.
AutoCAD SHX Text
SAW-CUT REGLET RE: SPECS
AutoCAD SHX Text
REMOVABLE SHEET METAL
AutoCAD SHX Text
COVER PIECE FASTENED 18" O.C.
AutoCAD SHX Text
FLEXIBLE VAPOR RETARDER WITH
AutoCAD SHX Text
COMPRESSIBLE INSULATION
AutoCAD SHX Text
LAP JOINT 3" W/ BEAD OF SEALANT
AutoCAD SHX Text
FINISH FLASHING MEMBRANE.
AutoCAD SHX Text
FINISH PLY
AutoCAD SHX Text
BASE PLY- MOD. BIT.
AutoCAD SHX Text
MOD. BIT. FLASHING PLY
AutoCAD SHX Text
W/ SEALED @ TOP
AutoCAD SHX Text
GRAVEL GUARD
AutoCAD SHX Text
NOTE: TAPER EXPANSION JOINT TO EDGE APPROX.
AutoCAD SHX Text
RAISED EXPANSION JOINT WITH COVER
AutoCAD SHX Text
07M-EJ01.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
EXPANSION NEEDS
AutoCAD SHX Text
TYPICAL FOR 1" EXPANSION
AutoCAD SHX Text
ADJUST AS NEEDED FOR ADDITIONAL
AutoCAD SHX Text
WOOD NAILERS.
AutoCAD SHX Text
TO TOP OF CURB.
AutoCAD SHX Text
SERVE AS INSULATION RETAINER
AutoCAD SHX Text
FLEXIBLE VAPOR RETARDER TO
AutoCAD SHX Text
NEW CANT. RE: SPEC'S.
AutoCAD SHX Text
COMPRESSIBLE INSULATION.
AutoCAD SHX Text
FLEXIBLE VAPOR RETARDER W/
AutoCAD SHX Text
1"
AutoCAD SHX Text
EXTEND BASE FLASHING.
AutoCAD SHX Text
BEVELED TOP OF BOTH WOOD CURBS
AutoCAD SHX Text
HIGH, DOMED, CAPPED, GASKETED
AutoCAD SHX Text
FLEXIBLE WATERPROOF MEMBRANE
AutoCAD SHX Text
MODIFIED BITUMEN MEMBRANE
AutoCAD SHX Text
BASE MODIFIED BITUMEN MEMBRANE.
AutoCAD SHX Text
MODIFIED BITUMEN REINFORCING
AutoCAD SHX Text
CLOSURE.
AutoCAD SHX Text
STANDING SEAM JOINT.
AutoCAD SHX Text
FASTENERS @ 8" O.C.
AutoCAD SHX Text
FASTENERS @ 16" O.C.
AutoCAD SHX Text
ROOF DECK. RE: SPEC'S.
AutoCAD SHX Text
PLY MEMBRANE
AutoCAD SHX Text
STRUCTURAL DRAWINGS.
AutoCAD SHX Text
STRUCTURE VARIES. SEE
AutoCAD SHX Text
TO DRAIN TO ONE SIDE.
AutoCAD SHX Text
6'-0" FROM EDGE.
AutoCAD SHX Text
ENLARGED HOLE
AutoCAD SHX Text
WASHER THROUGH
AutoCAD SHX Text
FASTENER W/
AutoCAD SHX Text
STANDING SEAM JOINT
AutoCAD SHX Text
IN PRE-FINISHED COLOR
AutoCAD SHX Text
TO MATCH FASCIA
AutoCAD SHX Text
NOTE: PROVIDE END COVER
AutoCAD SHX Text
CANT
AutoCAD SHX Text
BASE FLASHING
AutoCAD SHX Text
STAINLESS STEEL EXPANSION JOINT COVER.
AutoCAD SHX Text
CURBED PLATFORM -
AutoCAD SHX Text
SPECIFIED ROOF SYSTEM
AutoCAD SHX Text
REMOVABLE S.S. COUNTER
AutoCAD SHX Text
FLASHING W/ HEM & KICK OUT
AutoCAD SHX Text
FASTENERS 8" O.C.
AutoCAD SHX Text
BASE FLASHING
AutoCAD SHX Text
TREATED 3/4"
AutoCAD SHX Text
DECK RE:PLAN
AutoCAD SHX Text
2 STRUCTURAL MEMBERS
AutoCAD SHX Text
F.V. CURB SPANS AT LEAST
AutoCAD SHX Text
OVER FIELD OF ROOF SYSTEM
AutoCAD SHX Text
NOTE: INSTALL NEW PLATFORM
AutoCAD SHX Text
TREATED WD. CANT.
AutoCAD SHX Text
EXT. PLYWOOD
AutoCAD SHX Text
TREATED 2x
AutoCAD SHX Text
CROSS BRACING
AutoCAD SHX Text
@ 12" O.C. W/
AutoCAD SHX Text
TREATED
AutoCAD SHX Text
2x6 TYP.
AutoCAD SHX Text
TAPERED EDGE STRIP
AutoCAD SHX Text
RE:PLAN
AutoCAD SHX Text
FASTENERS 12"O.C.
AutoCAD SHX Text
DOMED GASKETED
AutoCAD SHX Text
FASTEN THRU TOP OF CAP.
AutoCAD SHX Text
WELD ALL JOINTS- DO NOT
AutoCAD SHX Text
TO CREATE POSITIVE SLOPE-
AutoCAD SHX Text
WATERPROOFING MEMBRANE
AutoCAD SHX Text
NOTE: PROVIDE "X" BREAK IN CAP
AutoCAD SHX Text
ROOF TOP EQUIPMENT
AutoCAD SHX Text
2" STANDING SEAMS
AutoCAD SHX Text
22 GA. S.S. COVER W/
AutoCAD SHX Text
EXIST. BEAMS ON NEW MOD. BIT. PADS
AutoCAD SHX Text
DRAIN DETAIL
AutoCAD SHX Text
07M-RD04.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
EXTEND UNDER
AutoCAD SHX Text
CLAMPING RING
AutoCAD SHX Text
STRIPPING PLIES ALL
AutoCAD SHX Text
LEAD FLASHING AND
AutoCAD SHX Text
MEMBRANE FIELD PLIES,
AutoCAD SHX Text
BASE SHEET
AutoCAD SHX Text
MOD. BIT. BASE PLY
AutoCAD SHX Text
ROOF MEMBRANE
AutoCAD SHX Text
DECK CLAMP
AutoCAD SHX Text
DRAIN BOWL
AutoCAD SHX Text
30" SQUARE MINIMUM, 4 lbs. LEAD
AutoCAD SHX Text
4" PAST LEAD
AutoCAD SHX Text
FINISH PLY
AutoCAD SHX Text
STRIPPING PLIES - EXTEND MIN.
AutoCAD SHX Text
BEFORE STRIPPING
AutoCAD SHX Text
ROOF CEMENT, PRIME TOP SURFACE
AutoCAD SHX Text
FLASHING SET ON FINISHED ROOF IN
AutoCAD SHX Text
FINISH FLASHING MEMBRANE
AutoCAD SHX Text
CAST IRON CLAMPING RING
AutoCAD SHX Text
CAST IRON DRAIN STRAINER
AutoCAD SHX Text
ROOF DRAIN (SUMP MIN. 1")
AutoCAD SHX Text
RE: SPEC
AutoCAD SHX Text
DRAIN SUMP DETAIL
AutoCAD SHX Text
OVERHEAD VIEW
AutoCAD SHX Text
PLAN VIEW
AutoCAD SHX Text
SUMP PERIMETER
AutoCAD SHX Text
4'-0"
AutoCAD SHX Text
4'-0"
AutoCAD SHX Text
LEAD DRAIN FLASHING
AutoCAD SHX Text
FLASHING
AutoCAD SHX Text
(prime and set in mastic)
AutoCAD SHX Text
(full adhere)
AutoCAD SHX Text
MOD. BIT. BASE PLY
AutoCAD SHX Text
lap a minimum of
AutoCAD SHX Text
(39" x 39", fully adhere,
AutoCAD SHX Text
STRIPPING PLY
AutoCAD SHX Text
4" beyond lead)
AutoCAD SHX Text
(48" x 48" min.)
AutoCAD SHX Text
FINISH FLASHING MEMBRANE
AutoCAD SHX Text
FINISH PLY
AutoCAD SHX Text
(fully adhere, heat weld
AutoCAD SHX Text
to flashing, lap min. 4")
AutoCAD SHX Text
MASTIC (set all roof
AutoCAD SHX Text
layers in mastic 6" around
AutoCAD SHX Text
drain perimeter)
AutoCAD SHX Text
CAST IRON STRAINER &
AutoCAD SHX Text
NOTE: USE EXTREME CAUTION NOT TO OVERTIGHTEN CLAMPING SCREWS TO PREVENT
AutoCAD SHX Text
BENDING AND PULLING /WRINKLING OF THE FLASHING MEMBRANES.
AutoCAD SHX Text
CLAMPING RING
AutoCAD SHX Text
SAW CUT REGLET
AutoCAD SHX Text
07M-WF03.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
STAINLESS STEEL SAW-CUT REGLET
AutoCAD SHX Text
FASTENERS APPROX. 24" O.C.
AutoCAD SHX Text
3" LAP AT JOINTS
AutoCAD SHX Text
COUNTERFLASHING
AutoCAD SHX Text
FASTENERS APPROX. 8" O.C.
AutoCAD SHX Text
REMOVABLE SHEET METAL
AutoCAD SHX Text
REINFORCING PLY - RE: SPEC
AutoCAD SHX Text
2" WIDE WIND CLIPS @ 3' O.C.
AutoCAD SHX Text
3" LAP W/ BEAD OF SEALANT
AutoCAD SHX Text
MOD. BIT. BASE PLY
AutoCAD SHX Text
EXISITNG DECK.
AutoCAD SHX Text
BASE SHEET - RE: SPEC
AutoCAD SHX Text
RE: SPEC - MIN. 8" HEIGHT
AutoCAD SHX Text
FINISH FLASHING MEMBRANE
AutoCAD SHX Text
FINISH PLY - RE: SPEC
AutoCAD SHX Text
TOOLED POLYURETHANE SEALANT
AutoCAD SHX Text
TOP OF WALL
AutoCAD SHX Text
NEW TREATED WOOD
AutoCAD SHX Text
PRIME WALL
AutoCAD SHX Text
NAILER SECURE TO
AutoCAD SHX Text
6" O.C.- MIN. 1" BELOW
AutoCAD SHX Text
TOP OF WALL CLADDING
AutoCAD SHX Text
WOOD SHIM SUPPORT
AutoCAD SHX Text
CONTINUOUS CLEAT FASTENED
AutoCAD SHX Text
CONTINUOUS TAPERED
AutoCAD SHX Text
10' MAX EA. CAP
AutoCAD SHX Text
1/2" SPACE
AutoCAD SHX Text
@ JOINT
AutoCAD SHX Text
MOD. BIT. BASE PLY
AutoCAD SHX Text
FINISH PLY
AutoCAD SHX Text
FASTENERS APPROX. 8"
AutoCAD SHX Text
FINISH FLASHING
AutoCAD SHX Text
MOD. BIT. REINFORCING PLY
AutoCAD SHX Text
NEW SHEET METAL JOINT COVER PLATE
AutoCAD SHX Text
SEALANT- 1 EA. SIDE OF JOINT.
AutoCAD SHX Text
MIN. 6" WIDE SET IN 2 BEADS OF
AutoCAD SHX Text
BY MANUFACTOR PER HGHT.
AutoCAD SHX Text
TERMINATION BAR AS REQ.
AutoCAD SHX Text
PRE FINISHED METAL PARAPET
AutoCAD SHX Text
PARAPET BASE & CAP
AutoCAD SHX Text
07M-WF02.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
CAP- RE: SPECS
AutoCAD SHX Text
MEMBRANE
AutoCAD SHX Text
HIGH DOMED, CAPPED,
AutoCAD SHX Text
GASKETED FASTENERS
AutoCAD SHX Text
MIN 8" -SEAL TOP
AutoCAD SHX Text
18" O.C. - MIN. TWO EA. SIDE
AutoCAD SHX Text
FINISH PLY
AutoCAD SHX Text
FINISH FLASHING MEMBRANE
AutoCAD SHX Text
REINFORCING PLY - RE: SPEC
AutoCAD SHX Text
CURB
AutoCAD SHX Text
ROOF DECK RE: SPECS
AutoCAD SHX Text
MOD. BIT. BASE PLY
AutoCAD SHX Text
SEALING MATERIAL
AutoCAD SHX Text
NOMINAL CURB
AutoCAD SHX Text
HEIGHT
AutoCAD SHX Text
10"
AutoCAD SHX Text
HIGH-DOMED, CAPPED,
AutoCAD SHX Text
GASKETED FASTENERS
AutoCAD SHX Text
MTL. COUNTERFLASHING
AutoCAD SHX Text
REMOVABLE SHEET
AutoCAD SHX Text
EQUIPMENT CURB
AutoCAD SHX Text
07M-CF01.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FASTENERS APPROX. 8" O.C.
AutoCAD SHX Text
1" MIN. BELOW TOP
AutoCAD SHX Text
MATERIAL @ TOP OF
AutoCAD SHX Text
REMOVABLE COUNTER
AutoCAD SHX Text
3 COURSING AT TOP
AutoCAD SHX Text
EXTENDS 1/2" MIN.
AutoCAD SHX Text
BEYOND TOP OF CURB
AutoCAD SHX Text
CURB RE: SPECS
AutoCAD SHX Text
OF CURB
AutoCAD SHX Text
TO CURB
AutoCAD SHX Text
FLASHING
AutoCAD SHX Text
MECH. UNIT,
AutoCAD SHX Text
HOOD, ETC.
AutoCAD SHX Text
CONT. SEALING
AutoCAD SHX Text
BASE OF UNIT
AutoCAD SHX Text
10" NOMINAL
AutoCAD SHX Text
FLASHING
AutoCAD SHX Text
HEIGHT
AutoCAD SHX Text
HOODED CURB
AutoCAD SHX Text
07M-CF02.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
STAINLESS STEEL HOOD / COVER
AutoCAD SHX Text
CROSSBREAK OF SLOPE FOR
AutoCAD SHX Text
DRAINAGE
AutoCAD SHX Text
INSULATE VOID TO PREVENT
AutoCAD SHX Text
CONDENSATION
AutoCAD SHX Text
SLOPE PIPES DOWN AND
AutoCAD SHX Text
AWAY FROM HOOD
AutoCAD SHX Text
HIGH-DOMED SS, CAPPED, GASKETED
AutoCAD SHX Text
FASTENERS APPROX. 18" O.C.
AutoCAD SHX Text
DEPENDING UPON WIND ZONE AND
AutoCAD SHX Text
CONDITIONS; MIN. TWO FASTENERS
AutoCAD SHX Text
PER SIDE)
AutoCAD SHX Text
FASTENERS APROX. 8" O.C.
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
MIN. 4" CLEARANCE FROM
AutoCAD SHX Text
PIPE TO TOP OF CURB;
AutoCAD SHX Text
MIN 2" BETWEEN PIPES
AutoCAD SHX Text
WOOD NAILERS
AutoCAD SHX Text
AND CURB
AutoCAD SHX Text
WOOD CANT TO
AutoCAD SHX Text
BRACE CURB
AutoCAD SHX Text
REMOVEABLE SHEET METAL
AutoCAD SHX Text
COUNTERFLASHING
AutoCAD SHX Text
12" MIN
AutoCAD SHX Text
12" MIN
AutoCAD SHX Text
FACE CLOSURE
AutoCAD SHX Text
RE: SPECS
AutoCAD SHX Text
SKYLIGHT CURB
AutoCAD SHX Text
07M-CF03.dwg
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FLASHING HEIGHT
AutoCAD SHX Text
10" NOMINAL
AutoCAD SHX Text
PER SIDE)
AutoCAD SHX Text
CONDITIONS, MIN. TWO FASTENERS
AutoCAD SHX Text
DEPENDING UPON WIND ZONE AND
AutoCAD SHX Text
SKYLIGHT RE: SPECS
AutoCAD SHX Text
SKYLIGHT FRAME WITH WEEP
AutoCAD SHX Text
HOLES
AutoCAD SHX Text
HIGH-DOMED, CAPPED, GASKETED
AutoCAD SHX Text
FASTENERS APPROX. 8" O.C.
AutoCAD SHX Text
FASTENERS (APPROX. 18" O.C.
AutoCAD SHX Text
REMOVABLE SHEET METAL
AutoCAD SHX Text
COUNTERFLASHING
AutoCAD SHX Text
ROOF DECK RE: SPECS
AutoCAD SHX Text
AND CURB
AutoCAD SHX Text
BRACE CURB
AutoCAD SHX Text
WOOD NAILERS
AutoCAD SHX Text
WOOD CANT TO
AutoCAD SHX Text
REINFORCING PLY - RE: SPEC
AutoCAD SHX Text
MOD. BIT. BASE PLY
AutoCAD SHX Text
RE: SPEC - MIN. 8" HEIGHT
AutoCAD SHX Text
FINISH FLASHING MEMBRANE
AutoCAD SHX Text
FINISH PLY - RE: SPEC
AutoCAD SHX Text
INFORMATION
AutoCAD SHX Text
GENERAL
AutoCAD SHX Text
HOT STACK -
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
FLASHING ASSEMBLY
AutoCAD SHX Text
ISOLATION COLLAR
AutoCAD SHX Text
REMOVABLE SHEET METAL
AutoCAD SHX Text
COUNTERFLASHING
AutoCAD SHX Text
STAINLESS STEEL CAP
AutoCAD SHX Text
STAINLESS STEEL
AutoCAD SHX Text
HOT FLUE/PIPE
AutoCAD SHX Text
WHERE APPLICABLE
AutoCAD SHX Text
TAPERED EDGE STRIP
AutoCAD SHX Text
CURB & CANT
AutoCAD SHX Text
TREATED WOOD
AutoCAD SHX Text
PER SIDE
AutoCAD SHX Text
MIN. 18" O.C.- MIN. 2
AutoCAD SHX Text
GASKETED FASTENERS
AutoCAD SHX Text
HIGH-DOMED CAPPED
AutoCAD SHX Text
SEALANT- AWR
AutoCAD SHX Text
DECK- RE:PLAN
AutoCAD SHX Text
10"
AutoCAD SHX Text
NOMINAL CURB HEIGHT
AutoCAD SHX Text
STAINLESS STEEL HOSE CLAMP
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
SEALANT
AutoCAD SHX Text
DRAWBAND
AutoCAD SHX Text
INSTALL SEALANT
AutoCAD SHX Text
BETWEEN PIPE AND
AutoCAD SHX Text
PREFABRICATED
AutoCAD SHX Text
MEMBRANE FLASHING
AutoCAD SHX Text
PREFABRICATED
AutoCAD SHX Text
MEMBRANE FLASHING
AutoCAD SHX Text
THERMOPLASTIC
AutoCAD SHX Text
ROOF MEMBRANE
AutoCAD SHX Text
PLUMBING VENT
AutoCAD SHX Text
STACK
AutoCAD SHX Text
SEALANT
AutoCAD SHX Text
(IF REQUIRED BY THE
AutoCAD SHX Text
SPECIFIC SYSTEM)
AutoCAD SHX Text
PLUMBING STACK
AutoCAD SHX Text
07P-FP01.dwg
AutoCAD SHX Text
1' = 1'-0"
AutoCAD SHX Text
EQUIPMENT SUPPORT CURB
AutoCAD SHX Text
07M-CF06
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
ISOLATION PAD
AutoCAD SHX Text
NEOPRENE
AutoCAD SHX Text
STEEL STRAPS 12" O.C.
AutoCAD SHX Text
18 GA. STAINLESS
AutoCAD SHX Text
UNISTRUT
AutoCAD SHX Text
TAPERED EDGE WHERE APP.
AutoCAD SHX Text
SPECIFIED ROOF SYSTEM
AutoCAD SHX Text
NEW 2x WOOD
AutoCAD SHX Text
RE:SPECS
AutoCAD SHX Text
FASTENERS AT 8" O.C.
AutoCAD SHX Text
GASKETED FASTENERS
AutoCAD SHX Text
18" O.C. - MIN. TWO EA. SIDE
AutoCAD SHX Text
HIGH-DOMED, CAPPED,
AutoCAD SHX Text
RECEIVER FOR COUNTER FLASH
AutoCAD SHX Text
NEW STAINLESS STEEL COVER W/
AutoCAD SHX Text
BASE FLASHING
AutoCAD SHX Text
FLASHING FASTENED 8" O.C.
AutoCAD SHX Text
REMOVABLE COUNTER
AutoCAD SHX Text
BLOCKING - AS REQ'D
AutoCAD SHX Text
MEMBRANE COATED GRAVEL STOP.
AutoCAD SHX Text
18" O.C.
AutoCAD SHX Text
ROOF HIGH/LOW
AutoCAD SHX Text
NTS
AutoCAD SHX Text
FOIL FACED FLASHING MEMBRANE RE: SPEC - MIN. 8" HEIGHT
AutoCAD SHX Text
REINFORCING PLY - RE: SPEC
AutoCAD SHX Text
CONTINUOUS CLEAT
AutoCAD SHX Text
MOD. BIT. FINISH PLY-RE: SPEC
AutoCAD SHX Text
MOD. BIT. BASE PLY
AutoCAD SHX Text
BASE SHEET - RE: SPEC
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
FASTENERS AT APPROX 3" O.C. STAGGERED
AutoCAD SHX Text
MOD BIT STRIPPING PLY RE: SPECS
AutoCAD SHX Text
MOD BIT FINISH PLY RE: SPECS
AutoCAD SHX Text
SHEET MTL. GRAVEL STOP SET IN ROOF CEMENT; BUFF SAND THEN PRIME FLANGE BEFORE STRIPPING.
AutoCAD SHX Text
BASE SHEET RE: SPECS
AutoCAD SHX Text
WOOD NAILERS
AutoCAD SHX Text
EXTEND ONE PLY
AutoCAD SHX Text
BACKUP WALL
AutoCAD SHX Text
AIR BARRIER
AutoCAD SHX Text
RIGID INSULATION
AutoCAD SHX Text
EXT. SHEATHING
AutoCAD SHX Text
FLEXIBLE FLASHING W/ SEALANT
AutoCAD SHX Text
22
AutoCAD SHX Text
EQUIPMENT CURB AS
AutoCAD SHX Text
DETAILED FOR SPECIFIED
AutoCAD SHX Text
ROOF SYSTEM
AutoCAD SHX Text
WALK PADS AROUND
AutoCAD SHX Text
PERIMETER OF ROOF TOP
AutoCAD SHX Text
EQUIPMENT, TYP. AT ALL
AutoCAD SHX Text
WALK PADS AT RTU
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ROOF TOP
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
RE: MEP
AutoCAD SHX Text
1'-0" MAX
AutoCAD SHX Text
GAP
AutoCAD SHX Text
23
AutoCAD SHX Text
3/8" STEEL SIDES
AutoCAD SHX Text
STD. CURB FLASHING
AutoCAD SHX Text
ROOF HATCH
AutoCAD SHX Text
07MC-LR01.dwg
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
ROOF SCUTTLE
AutoCAD SHX Text
PREFABRICATED
AutoCAD SHX Text
INSULATED CURB
AutoCAD SHX Text
3 x 3 x 1/4" CONT.
AutoCAD SHX Text
ALL AROUND
AutoCAD SHX Text
o
AutoCAD SHX Text
BLOCKING W/ 1/2"
AutoCAD SHX Text
LAG BOLT
AutoCAD SHX Text
ANCHOR TO DOUBLE
AutoCAD SHX Text
2 x 4 TREATED WOOD
AutoCAD SHX Text
STEEL BRACKET-
AutoCAD SHX Text
3/4" %%C GALV STEEL
AutoCAD SHX Text
FACE OF WALL
AutoCAD SHX Text
TYPICAL, EA. SIDE
AutoCAD SHX Text
1/2" %%C ANCHOR BOLT
AutoCAD SHX Text
18" WIDE ON 2 1/2"x
AutoCAD SHX Text
RUNGS @ 12" O.C. -
AutoCAD SHX Text
AROUND
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
2 1/2" METAL STUDS
AutoCAD SHX Text
5/8" GYP BD ON
AutoCAD SHX Text
@ 16" O.C. ALL
AutoCAD SHX Text
SCHEDULED
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
OVER FLOW DRAIN
AutoCAD SHX Text
NTS
AutoCAD SHX Text
NOTE: OVERFLOW DRAIN TO BE 2" ABOVE ROOF DRAIN
AutoCAD SHX Text
WD. BLOCKING
AutoCAD SHX Text
EXTEND OR LOWER AS REQUIRED - FIELD VERIFY.
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
EXTEND LEAD MIN.
AutoCAD SHX Text
SPECIFIED ROOF SYSTEM
AutoCAD SHX Text
OVERFLOW DRAIN
AutoCAD SHX Text
RE: PLUMBING
AutoCAD SHX Text
1" INTO PIPE
AutoCAD SHX Text
1"
AutoCAD SHX Text
STRIPPING PLIES
AutoCAD SHX Text
# 4 LEAD SUMP
AutoCAD SHX Text
STAINLESS
AutoCAD SHX Text
CLAMP
AutoCAD SHX Text
STEEL PIPE
AutoCAD SHX Text
STAINLESS
AutoCAD SHX Text
STEEL SCREEN
AutoCAD SHX Text
NOTE: CONTRACTOR TO REFER TO MEP SHEETS FOR REFERENCE TO REMOVAL OF EXISTING ABANDONED CURB/ EQUIPMENT. LOCATIONS OF NEW CURB EQUIPMENT AND ASSOCIATED FLASHING, TRIM OR PENETRATIONS.
Page 4: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833

PLAN

NORTH

KEY PLAN

CHECKED BY:

REVISIONS

DRAWN BY:

DATE:

PROJECT NUMBER

CLIENT

ARCHITECTURE

SACRAMENTO

2520 VENTURE OAKS DR, SUITE 440

SACRAMENTO, CA 95833

t: 916-682-9494

PBK.com

MEPT

PBKCONTACT: BRIAN HOOD

11 GREENWAY PLAZA, 22ND FLOOR HOUSTON, TX 77046

t: 713-965-0608f: 713-961-4571

SWL

RS / DR

01.16.2018

17311

SANTA ROSA CS

ISSUE FOR BID

No. Description Date

M

A

T

T

H

E

W

R. S

IC

K

O

R

E

Z

E

L

L

E

C

TR

I

C

A

E 20162

R

R

EG

IS

T

E

R

E

D

P

R

O

FESS

IO

N

A

L

E

N

G

I

N

E

E

S

A

T

A

T

E

O

F

CAL

I

F

O

R

N

I

PBK ENGINEERS

12 / 08 / 17

AutoCAD SHX Text
DRAMA BUILDING
AutoCAD SHX Text
BUILDING "B"
AutoCAD SHX Text
BUILDING "A"
AutoCAD SHX Text
BUNGALOW "A"
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
BUILDING "D1"
AutoCAD SHX Text
BUILDING "D2"
AutoCAD SHX Text
BUILDING "D3"
AutoCAD SHX Text
CLASS ROOM
AutoCAD SHX Text
EXERCISE BUILDING
AutoCAD SHX Text
CHARTER SCHOOL "A"
AutoCAD SHX Text
CHARTER SCHOOL "B"
AutoCAD SHX Text
CHARTER SCHOOL "C"
AutoCAD SHX Text
CHARTER SCHOOL "D"
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CCLA
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
DRAMA BUILDING
AutoCAD SHX Text
BUILDING "B"
AutoCAD SHX Text
BUILDING "A"
AutoCAD SHX Text
BUNGALOW "A"
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
BUILDING "D1"
AutoCAD SHX Text
BUILDING "D2"
AutoCAD SHX Text
BUILDING "D3"
AutoCAD SHX Text
CLASS ROOM
AutoCAD SHX Text
EXERCISE BUILDING
AutoCAD SHX Text
CHARTER SCHOOL "A"
AutoCAD SHX Text
CHARTER SCHOOL "B"
AutoCAD SHX Text
CHARTER SCHOOL "C"
AutoCAD SHX Text
CHARTER SCHOOL "D"
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
CCLA
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
SL
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
A/C
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
AC-5
AutoCAD SHX Text
AC-4
AutoCAD SHX Text
AC-43
AutoCAD SHX Text
AC-2
AutoCAD SHX Text
AC-3
AutoCAD SHX Text
AC-1
AutoCAD SHX Text
AC-44
AutoCAD SHX Text
AC-50
AutoCAD SHX Text
AC-45
AutoCAD SHX Text
AC-46
AutoCAD SHX Text
AC-47
AutoCAD SHX Text
AC-49
AutoCAD SHX Text
AC-48
AutoCAD SHX Text
AC-16
AutoCAD SHX Text
AC-1
AutoCAD SHX Text
%%UROOF PLAN GENERAL NOTES:
AutoCAD SHX Text
1.
AutoCAD SHX Text
CONTRACTOR TO PROVIDE CONNECTION FROM EXHAUST FANS TO ALL MOTORIZED BACKDRAFT DAMPERS AS REQUIRED, COORDINATE WITH MECHANICAL. DRAWINGS ARE FOR REFERENCE ONLY. CONTRACTOR SHALL FIELD VERIFY . CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITION PRIOR TO BID DATE. CONTRACTOR SHALL DOCUMENT EXISTING BRANCH CIRCUIT INFORMATION INCLUDING BUT NOT LIMITED TO CIRCUIT BREAKER, WIRES, CONDUIT, PHASE, VOLTAGE. PRIOR TO DEMOLITION. EXISTING BRANCH CIRCUITS MAY BE RE-USED TO THE EXTENT FEASIBLE IF THEY MATCH WITH THE NEW REQUIREMENTS. OTHERWISE, PROVIDE NEW BREAKER, CONDUIT, AND WIRE, AS REQUIRED ON ELECTRICAL SCHEDULES. CONDUIT SUPPORTS BY ROOFING CONTRACTOR. REFER TO ARCHITECTURAL ROOF PLANS FOR ADDITIONAL INFORMATION. ALL EXISTING LOW VOLTAGE CONNECTIONS TO MECHANICAL EQUIPMENTS BEING REPLACED SHALL REMAIN UNLESS NOTED OTHERWISE. RE-CONNECT TO NEW EQUIPMENT AS REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE AND OPERABLE SYSTEM. ELECTRICAL WORK SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL CODES AND REGULATIONS.
AutoCAD SHX Text
2.
AutoCAD SHX Text
3.
AutoCAD SHX Text
4.
AutoCAD SHX Text
5.
AutoCAD SHX Text
6.
AutoCAD SHX Text
7.
AutoCAD SHX Text
%%UROOF PLAN KEYED NOTES:
AutoCAD SHX Text
PROVIDE 120V CIRCUIT TO WEATHERPROOF/GFCI RECEPTACLES MOUNTED ON AC UNIT, WITH 2/12,1#12G, 3/4" CONDUIT. EXTEND CIRCUIT FROM EXISTING RECEPTACLE ON ROOF, IF AVAILABLE. OTHERWISE, PROVIDE 20A/1P BREAKER AND CIRCUIT TO NEAREST 120V PANEL. EXISTING EQUIPMENT TO BE DISCONNECTED, REMOVED, AND REPLACED. FIELD VERIFY EXISTING BRANCH CIRCUIT WIRING PRIOR TO DEMOLITION. COORDINATE WITH MECHANICAL FOR EXACT LOCATION, ORIENTATION, AND LOCATION OF FACTORY MOUNTED DISCONNECT. REFER TO ELECTRICAL EQUIPMENT SCHEDULES ON SHEET E-2 FOR ADDITIONAL INFORMATION. PROVIDE NEW 30AMP NEMA 3R DISCONNECT TO MATCH EXISTING. TYPICAL INDICATION OF EXISTING ELECTRICAL CONDUIT ROUTING. CONTRACTOR TO FIELD VERIFY ACTUAL CONDITION.
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
HILLIARD COMSTOCK MIDDLE SCHOOL ROOF AND MECHANICAL REPLACEMENT PROJECT
AutoCAD SHX Text
2750 W STEELE LANE SANTA ROSA, CA 95403
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
E1.0
AutoCAD SHX Text
ELECTRICAL PLAN
AutoCAD SHX Text
COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
COMSTOCK MS - ELECTRICAL PLAN
AutoCAD SHX Text
SCALE: 1/16"=1'-0"
AutoCAD SHX Text
1
Page 5: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833

PLAN

NORTH

KEY PLAN

CHECKED BY:

REVISIONS

DRAWN BY:

DATE:

PROJECT NUMBER

CLIENT

ARCHITECTURE

SACRAMENTO

2520 VENTURE OAKS DR, SUITE 440

SACRAMENTO, CA 95833

t: 916-682-9494

PBK.com

MEPT

PBKCONTACT: BRIAN HOOD

11 GREENWAY PLAZA, 22ND FLOOR HOUSTON, TX 77046

t: 713-965-0608f: 713-961-4571

SWL

RS / DR

01.16.2018

17311

SANTA ROSA CS

ISSUE FOR BID

No. Description Date

M

A

T

T

H

E

W

R.S

IC

K

O

R

E

Z

E

L

L

E

C

TR

I

C

A

E 20162

R

R

EG

IS

T

E

R

E

D

P

R

O

FES

S

IO

N

A

L

E

N

G

I

N

E

E

S

A

T

A

T

E

O

F

CAL

IF

O

R

N

I

PBK ENGINEERS

12 / 08 / 17

AutoCAD SHX Text
CIRCUITING IS REQUIRED.
AutoCAD SHX Text
WIRING" FOR REQUIREMENTS.
AutoCAD SHX Text
PANELS, WIRING, ETC.
AutoCAD SHX Text
SCHEDULES, REFER TO SPECIFICATIONS FOR MINIMUM SIZE REQUIRED.
AutoCAD SHX Text
ACCOMPLISH CIRCUITING AND SWITCHING REQUIREMENTS SHOWN.
AutoCAD SHX Text
2. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL HVAC AND PLUMBING EQUIPMENT.
AutoCAD SHX Text
A. BRANCH CIRCUITING IS SCHEMATIC IN NATURE AND IS INTENDED TO INDICATE CIRCUIT LOADING AND
AutoCAD SHX Text
CONTROL, NOT METHODS OF INSTALLATION. REFER TO SPECIFICATIONS FOR METHODS OF
AutoCAD SHX Text
INSTALLATION AND MATERIALS, INCLUDING WHETHER OR NOT BX IS ALLOWED AND WHETHER
AutoCAD SHX Text
"THROUGH-FIXTURE" OR "OCTOPUS (EMT WITH FLEXIBLE WHIPS)" TYPE LIGHTING BRANCH
AutoCAD SHX Text
B. WHERE WIRE SIZE AND CONDUIT SIZE IS NOT INDICATED ON THE DRAWINGS AND/OR PANEL
AutoCAD SHX Text
C. BRANCH CIRCUITS ON THE DRAWINGS ARE GENERALLY NOT SHOWN GROUPED IN SINGLE
AutoCAD SHX Text
RACEWAYS. HOWEVER, GROUPING IS ALLOWED UNDER CERTAIN
AutoCAD SHX Text
CONDITIONS. REFER TO DIVISION 26 SPECIFICATIONS UNDER SECTION ENTITLED "ELECTRICAL
AutoCAD SHX Text
D. THE DRAWINGS GENERALLY INDICATE QUANTITY OF CONDUCTORS ON BRANCH CIRCUIT HOME RUNS
AutoCAD SHX Text
ONLY. ELSEWHERE WITHIN CIRCUITS, PROVIDE QUANTITY OF CONDUCTORS AS NEEDED TO
AutoCAD SHX Text
6. FIELD VERIFY CONDITION OF, AND MODIFICATIONS AND ADDITIONS TO, ALL EXISTING ELECTRICAL FIXTURES,
AutoCAD SHX Text
CONTRACTOR SHALL REMOVE FROM JOB SITE ALL MATERIAL NOT RETAINED BY OWNER.
AutoCAD SHX Text
5. ALL ITEMS NOTED TO BE REMOVED ARE TO REMAIN THE PROPERTY OF THE OWNER; HOWEVER,
AutoCAD SHX Text
CONTRACTOR SHALL TAKE WHATEVER STEPS ARE NECESSARY TO MAINTAIN CIRCUIT CONTINUITY.
AutoCAD SHX Text
4. WHEN REMOVING EXISTING ELECTRICAL WORK WHERE OTHER ITEMS REMAIN ON THE SAME CIRCUIT, THE
AutoCAD SHX Text
ADDING NEW LOAD, AND SHALL TIE NEW LOAD INTO THAT CIRCUIT.
AutoCAD SHX Text
BE RESET AS NECESSARY TO PROVIDE FLUSH MOUNTING FOR BOXES.
AutoCAD SHX Text
STEPS ARE NECESSARY TO COMPLY WITH NEC 314-19.
AutoCAD SHX Text
UNDER WORK COVERED IN OTHER SECTIONS.
AutoCAD SHX Text
UNDERSTANDING OF SCOPE OF PROJECT PRIOR TO COMMENCEMENT OF WORK.
AutoCAD SHX Text
BOXES. WHERE THIS WORK IS DONE, THE WALLS, FLOOR, AND CEILING SHALL BE PATCHED AS NECESSARY
AutoCAD SHX Text
REMOVED BACK TO CIRCUIT BREAKER(S). BLANK COVER PLATES SHALL BE PROVIDED FOR RECESSED
AutoCAD SHX Text
BOXES ALONG WALLS, FLOOR AND CEILING SHALL BE REMOVED. BRANCH CIRCUIT WIRES SHALL BE
AutoCAD SHX Text
10. WHEN EXISTING ELECTRICAL WORK IS REMOVED, ALL EXPOSED CONDUIT, WIRING, CONTROL AND JUNCTION
AutoCAD SHX Text
SHALL LOCATE ANOTHER EXISTING CIRCUIT (THE CLOSEST), WHICH WOULD NOT BE OVERLOADED UPON
AutoCAD SHX Text
AND/OR ADDITIONS TO THAT CIRCUIT. IF NEW WORK WOULD OVERLOAD EXISTING CIRCUIT, CONTRACTOR
AutoCAD SHX Text
9. CONTRACTOR SHALL FIELD VERIFY EXISTING BRANCH CIRCUIT LOADING WHEN MAKING MODIFICATIONS
AutoCAD SHX Text
8. EXISTING ELECTRICAL BOXES TO REMAIN IN AREAS WHERE NEW WALL FINISHES ARE TO BE APPLIED SHALL
AutoCAD SHX Text
7. WHERE EXISTING JUNCTION BOXES ARE COVERED OR REMOVED, CONTRACTOR SHALL TAKE WHATEVER
AutoCAD SHX Text
11. CONTRACTOR TO REFER TO ARCHITECTURAL DEMOLITION PLANS ANS PHASING PLANS AND HAVE A GOOD
AutoCAD SHX Text
3. CIRCUITING
AutoCAD SHX Text
GENERAL ELECTRICAL NOTES
AutoCAD SHX Text
1 ENCLOSURE UNLESS OTHERWISE NOTED. PROVIDE FUSED BUSWAY PLUG WHEN SWITCH IS INDICATED
AutoCAD SHX Text
DISCONNECT SWITCH. FRAME SIZE/FUSE SIZE/POLES AS INDICATED, "NF" INDICATES NON-FUSIBLE. NEMA
AutoCAD SHX Text
A NOTATION INDICATING THE MOUNTING HEIGHT OF A DEVICE AS MEASURED FROM FINISHED FLOOR OR
AutoCAD SHX Text
MAGNETIC MOTOR CONTROLLER. NUMBER INDICATES NEMA SIZE. STARTER NEMA SIZE SHALL BE "NEMA 1"
AutoCAD SHX Text
ON BUSWAY. ALL DISCONNECT SWITCHES SHALL BE 30/NF/3 UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
GROUNDING CONNECTION TO GROUNDING ELECTRODE AS DEFINED IN NEC ARTICLE 250.
AutoCAD SHX Text
SWITCHBOARD/DP
AutoCAD SHX Text
MOTOR.
AutoCAD SHX Text
SINGLE CIRCUIT BREAKER IN INDIVIDUAL ENCLOSURE.
AutoCAD SHX Text
GRADE TO CENTER LINE OF DEVICE.
AutoCAD SHX Text
COMBINATION DISCONNECT SWITCH/MOTOR CONTROLLER.
AutoCAD SHX Text
UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
T
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
PANELBOARD
AutoCAD SHX Text
CONTACTOR
AutoCAD SHX Text
+42"
AutoCAD SHX Text
EQUIPMENT:
AutoCAD SHX Text
ELECTRICAL SYMBOL LEGEND
AutoCAD SHX Text
1. EVERY SYMBOL SHOWN ON LEGEND MAY NOT APPEAR ON DRAWINGS.
AutoCAD SHX Text
2. DASHED ELECTRICAL EQUIPMENT GENERALLY INDICATES EXISTING EQUIPMENT.
AutoCAD SHX Text
3. LONG-SHORT-SHORT-LONG DASHING GENERALLY INDICATES MATCH LINE OR DEFINES AREA FOR
AutoCAD SHX Text
LIGHTING OR POWER CIRCUIT(S). ARROW INDICATES HOME RUN, LONGER TICK(S) INDICATE NEUTRAL
AutoCAD SHX Text
WIRE(S), SHORTER STRAIGHT TICK(S) INDICATE PHASE WIRE(S), SLANTED SHORTER TICK(S) INDICATE
AutoCAD SHX Text
SWITCH LEG(S), DOT(S) INDICATE GROUNDING CONDUCTOR(S), DASHED WIRING (LONG-SHORT-LONG
AutoCAD SHX Text
DASHES) INDICATES WIRING BELOW SLAB OR GRADE, DASHED WIRING (SERIES OF SHORT DASHES)
AutoCAD SHX Text
INDICATES EXISTING WIRING, SLASH THROUGH ARROW INDICATES PARTIAL CIRCUIT, "D" ON HOMERUN
AutoCAD SHX Text
ARROW INDICATES DEDICATED CIRCUIT: PROVIDE A SEPARATE NEUTRAL FOR EACH PHASE CONDUCTOR
AutoCAD SHX Text
FOR ENTIRE LENGTH OF CIRCUIT FROM PANEL TO OUTLET; COUNT EACH NEUTRAL AS CURRENT-CARRYING
AutoCAD SHX Text
AND GROUP A MAXIMUM OF SIX THHN/THWN CONDUCTORS IN A SINGLE RACEWAY; GROUNDING
AutoCAD SHX Text
TELEPHONE CONDUIT SYSTEM. DASHED WIRING (LONG-SHORT-LONG DASHES) INDICATES WIRING IN OR
AutoCAD SHX Text
BELOW SLAB OR GRADE, DASHED WIRING (SERIES OF SHORT DASHES) INDICATES EXISTING WIRING.
AutoCAD SHX Text
JUNCTION BOX. "J" MAY BE OMITTED IF BOX IS WITHIN OR ATTACHED TO FLUORESCENT LIGHT FIXTURE
AutoCAD SHX Text
POINT OF BRANCH CIRCUIT TAP FOR SEPARATELY SWITCHED FIXTURE GROUP. REFERENCE CATEGORY "B"
AutoCAD SHX Text
GROUNDING ELECTRODE.
AutoCAD SHX Text
POWER OUTLETS:
AutoCAD SHX Text
CIRCUIT RELATED:
AutoCAD SHX Text
SYMBOL ON PLANS.
AutoCAD SHX Text
CONDUCTOR IS NOT COUNTED.
AutoCAD SHX Text
LIGHTING SYMBOLS FOR FURTHER INFORMATION.
AutoCAD SHX Text
T
AutoCAD SHX Text
SPECIAL NOTE.
AutoCAD SHX Text
J
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
01
AutoCAD SHX Text
%%UCONDUIT PENETRATION DETAIL - EXTERIOR WALL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
CONDUIT PENETRATING WALL
AutoCAD SHX Text
AS REQUIRED TO FIT CONDUIT PENETRATION.
AutoCAD SHX Text
THUNDERLINE LINKSEAL. SELECT SIZE/MODEL
AutoCAD SHX Text
WITH ANCHOR AND WATERSTOP COLLAR.
AutoCAD SHX Text
TO THUNDERLINE CENTURY-LINE SLEEVE
AutoCAD SHX Text
PENETRATION SLEEVE TO BE SIMILAR
AutoCAD SHX Text
WALL
AutoCAD SHX Text
LUMINAIRE SUPPORT IN SUSPENDED CEILINGS: A. PROVIDE MEANS OF SUPPORT FOR LUMINAIRES PER NEC 410-16. T BAR CLIPS SHALL BE INSTALLED ON THE LUMINAIRE PROVIDE MEANS OF SUPPORT FOR LUMINAIRES PER NEC 410-16. T BAR CLIPS SHALL BE INSTALLED ON THE LUMINAIRE LUMINAIRE AND SHALL BE FIELD SECURED TO THE INVERTED CEILING TEES SO THAT THE LUMINAIRE IS SECURELY FASTENED TO THE FASTENED TO THE CEILING SYSTEM FRAMING MEMBERS. B. CEILING TILES SHALL NOT BEAR THE WEIGHT OF LUMINAIRES. SURFACE MOUNT LUMINAIRES, RECESSED DOWNLIGHTS, CEILING TILES SHALL NOT BEAR THE WEIGHT OF LUMINAIRES. SURFACE MOUNT LUMINAIRES, RECESSED DOWNLIGHTS, LIGHT TRACK, EXIT SIGNS, ETC. SHALL BE SUPPORTED BY PROPER FRAMES OR OTHER ATTACHMENT TO MAIN CEILING SYSTEM GRID OR BUILDING STRUCTURE ABOVE CEILING. C. LUMINAIRES SHALL BE CENTERED IN CEILING TILE. LUMINAIRES SHALL BE CENTERED IN CEILING TILE. D. LUMINAIRE SHALL HAVE FLANGE OR TRIM RING FOR CLOSURE OF CEILING CUTOUT OR OPENING. LUMINAIRE SHALL HAVE FLANGE OR TRIM RING FOR CLOSURE OF CEILING CUTOUT OR OPENING. E. FIRE-RATED CEILING ASSEMBLY: FOR LUMINAIRES TO BE FLUSH-MOUNTED INTO A FIRE-RATED CEILING OR SURFACE FIRE-RATED CEILING ASSEMBLY: FOR LUMINAIRES TO BE FLUSH-MOUNTED INTO A FIRE-RATED CEILING OR SURFACE MOUNTED TO A FIRE-RATED CEILING, INSTALL WITH INDEPENDENT, SECURE SUPPORT. RACEWAY, CABLE ASSEMBLIES, BOXES BOXES AND FITTINGS LOCATED ABOVE A FIRE-RATED FLOOR/CEILING OR ROOF CEILING ASSEMBLY SHALL NOT BE SECURED TO, OR SECURED TO, OR SUPPORTED BY, THE CEILING ASSEMBLY INCLUDING THE CEILING SUPPORT WIRES. PROVIDE AN INDEPENDENT MEANS OF INDEPENDENT MEANS OF SECURE SUPPORT. INDEPENDENT SUPPORT WIRES SHALL BE DISTINGUISHABLE BY COLOR, TAGGING, OR OTHER EFFECTIVE TAGGING, OR OTHER EFFECTIVE MEANS FROM THOSE THAT ARE PART OF THE FIRE-RATED DESIGN.
AutoCAD SHX Text
12.
AutoCAD SHX Text
CIRCUIT DESIGNATION NEXT TO RECEPTACLE DEVICES INDICATES BRANCH CIRCUIT NUMBER. RE: PANEL
AutoCAD SHX Text
INDICATES RECEPTACLE SHALL BE MOUNTED ABOVE COUNTER TOP. REFER TO
AutoCAD SHX Text
SAME AS FOURPLEX RECEPTACLE EXCEPT ISOLATED GROUND TYPE RECEPTACLE.
AutoCAD SHX Text
SCHEDULES FOR INFORMATION.
AutoCAD SHX Text
ARCHITECT FOR EXACT HEIGHT ABOVE COUNTER.
AutoCAD SHX Text
LC1-X
AutoCAD SHX Text
AC
AutoCAD SHX Text
SINGLE DUPLEX. PROVIDE CARPET FLANGE WHERE APPLICABLE.
AutoCAD SHX Text
SPECIAL PURPOSE SINGLE POWER RECEPTACLE. RATED AS INDICATED (IF NO RATING INDICATED,
AutoCAD SHX Text
RECEPTACLE RATING SHALL MATCH BRANCH CIRCUIT OVERCURRENT PROTECTIVE DEVICE SIZE AND SHALL
AutoCAD SHX Text
MEET REQUIREMENTS OF EQUIPMENT BEING CONNECTED), "C" INDICATES CLOCK OUTLET.
AutoCAD SHX Text
20A-125V FLUSH FLOOR DUPLEX RECEPTACLE. 20A WHEN INDICATED OR IF BRANCH CIRCUIT SERVES ONLY
AutoCAD SHX Text
20A-125V DUPLEX TAMPER RESISTANT RECEPTACLE WITH (2) USB CHARGING PORTS.
AutoCAD SHX Text
20A-125V DUPLEX RECEPTACLE.
AutoCAD SHX Text
"GF" INDICATES GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE.
AutoCAD SHX Text
"WP" INDICATES WEATHER PROOF DEVICE.
AutoCAD SHX Text
SAME AS DUPLEX RECEPTACLE EXCEPT ISOLATED GROUND TYPE RECEPTACLE.
AutoCAD SHX Text
CONTRACTOR SHALL FIELD VERIFY ANY EXISTING UNDERGROUND PIPING, WIRING, OR OTHER FACILITIES PRIOR TO TRENCHING, AND SHALL BE RESPONSIBLE FOR ANY DAMAGE CAUSED BY INSTALLATION OF NEW WORK.
AutoCAD SHX Text
13.
AutoCAD SHX Text
ADA VISUAL ALARM 80" AFF TO BOTTOM OF LENS OR 6" BELOW CEILING,
AutoCAD SHX Text
SPECIAL PURPOSE WALL OUTLETS 15" AFF TO BOTTOM OF BOX (OR HIGHER AS REQUIRED TO
AutoCAD SHX Text
INTERIOR BELLS, BUZZERS, HORNS 1'-0" BELOW CEILING, OR IN CEILING, AS REQUIRED*
AutoCAD SHX Text
FIRE ALARM SPEAKER/HORN 1'-0" BELOW CEILING, OR IN CEILING, AS REQUIRED*
AutoCAD SHX Text
WALL CLOCK OUTLETS 7'-0" AFF (OR ABOVE CHALKBOARDS WHERE REQUIRED)*
AutoCAD SHX Text
WALL DATA/VOICE OUTLETS 15" AFF TO BOTTOM OF BOX
AutoCAD SHX Text
WALL CONVENIENCE RECEPTACLES 15" AFF TO BOTTOM OF BOX
AutoCAD SHX Text
ELECTRICAL OUTLETS SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. DIMENSIONS ARE TO CENTER OF
AutoCAD SHX Text
1. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THE ARCHITECT,
AutoCAD SHX Text
AFG = ABOVE FINISHED GRADE
AutoCAD SHX Text
AFF = ABOVE FINISHED FLOOR
AutoCAD SHX Text
MANUAL FIRE ALARM PULL STATIONS
AutoCAD SHX Text
WALL OUTLETS FOR WALL MTD. TELEPHONE
AutoCAD SHX Text
BOX UNLESS OTHERWISE NOTED:
AutoCAD SHX Text
PUSH BUTTONS
AutoCAD SHX Text
WALL SWITCHES
AutoCAD SHX Text
VERIFY EXACT HEIGHT WITH ARCHITECT.
AutoCAD SHX Text
FRONTAL APPROACH AND 48" AFF MAX. FOR SIDE APPROACH.
AutoCAD SHX Text
TOP OF BOX SHALL BE 42" AFF MAX. FOR WHEELCHAIR
AutoCAD SHX Text
WHICHEVER IS LOWER. ENTIRE LENS TO BE WITHIN 80" TO 96"
AutoCAD SHX Text
AFF*
AutoCAD SHX Text
SERVE EQUIPMENT)
AutoCAD SHX Text
7'-0" AFF TO BOTTOM OF DEVICE IF DEVICE PROTRUDES
AutoCAD SHX Text
MORE THAN 4" FROM WALL (PER ADA)
AutoCAD SHX Text
*
AutoCAD SHX Text
THE ELECTRICAL CONTRACTOR SHALL COMPLY WITH ALL AUTHORITIES HAVING JURISDICTION, NEC, ALL STATE AND LOCAL CODES AND AMENDMENTS.
AutoCAD SHX Text
14.
AutoCAD SHX Text
CH
AutoCAD SHX Text
MANUAL MOTOR RATED SWITCH
AutoCAD SHX Text
S
AutoCAD SHX Text
M
AutoCAD SHX Text
HILLIARD COMSTOCK MIDDLE SCHOOL ROOF AND MECHANICAL REPLACEMENT PROJECT
AutoCAD SHX Text
2750 W STEELE LANE SANTA ROSA, CA 95403
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
E2.0
AutoCAD SHX Text
ELECTRICAL DETAILS
AutoCAD SHX Text
COMSTOCK MIDDLE SCHOOL
AutoCAD SHX Text
COMSTOCK MS - ELECTRICAL DETAILS
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
1
Page 6: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833
Page 7: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833
Page 8: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833
Page 9: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833
Page 10: EJ - srcs.k12.ca.us · plan north. key plan. checked by: revisions drawn by: date: project number client. architecture. sacramento 2520 venture oaks dr, suite 440 sacramento, ca 95833