ELECTRO HYDRAULICCONTROLLER
HEMANT KUMAR
7/31/2019 EHC 500 MW
2/55
EHC Speed measurement
Speed controller Load controller
Pressure controller Controller Selection
Position controller
7/31/2019 EHC 500 MW
3/55
SPEED MEASUREMENT Four Nos of hall probes mounted around a
disk containing 120 magnets (alternative60 N-pole & 60 S-pole)
One rotation will produce 60 pulses.
Three probes are used for measurement
0.8 mm gap is maintained b/w hall probeand disc.
Hall probe output is a sine wave with peakvoltage 700 to 800 mV.
7/31/2019 EHC 500 MW
4/55
SPEED MEASUREMENT Pulse converters will convert the sine waves tosquare wave of peak 10 V.
Each pulse converter card will generate three
isolated output out of which two are used. Speed measurement is done in two different
channels.
Both channels will receive signal from each pulseconverters. One channel is used for indication andLVM & the other one for controller. nACT is shownin digital indicator provided in UCB
range: (0- 3300 rpm)
7/31/2019 EHC 500 MW
5/55
SPEED CONTROLLER SC is used for increasing speed from
Barring speed to rated speed & to assist
auto synchronizer in synchronizing the m/c. SC can be used to load the m/c fully but it
is used only for loading upto 10% as
frequency variation will affect the v/vopening.
v/v opening is directly proportional to thediff. b/w grid freq and speed set point.
7/31/2019 EHC 500 MW
6/55
SPEED CONTROLLER Speed set point
Set point Tracking
Speed set point controller
Droop
dn/dt monitoring No load pressure correction
Speed controller loop.
7/31/2019 EHC 500 MW
7/55
SPEED CONTROLLER
Speedcontroller
49
7/31/2019 EHC 500 MW
8/55
Speed set point Speed reference nRCan be changed from
desk, auto synchronizer, ATRS, C&I cabinet& AVR console.
The set point changes at a gradient of2160 rpm/min up to a setting of 2820 rpm.
After 2820 rpm it changes at a rate of
360 rpm/min to have accurate control. Speed set point indicator is available in two
ranges 1) 0-3300 rpm
2) 2700-3300 rpm
7/31/2019 EHC 500 MW
9/55
Set point Tracking If the frequency is between 49 Hz & 51 Hzand LC or PC in action speed set point willtrack grid speed by +15 rpm.
This ensures that SC will not interfere innormal operation when frequency changes.
After turbine trips speed set point will followthe actual m/c speed by -120 rpm.
This ensures that speed set point is less thanactual speed (barring speed). So nxt timedurin rollin n has to be increased.
7/31/2019 EHC 500 MW
10/55
Speed set point controller nRwhich is a step signal will beconverted to time delayed ramp signaln
RTD
or nRLIM
by an integrator for whichgradient is decided by TSE upper margin.nRlim indicator is available in ucb(0-3300rpm)
This has three parts
1. Gradient
2. Stop reference
3. Fast balance
7/31/2019 EHC 500 MW
11/55
Speed set point controller1.Gradient
This is the rate at which the out put of SSPC
changes. Max rate is set at 600 rpm/min.
The rate also depends on TSE upper margin.
If it is 30ok then rate is maximum. Ratereduces as margin comes below 300k linearly.Min rate is 108 rpm/min.
This is to ensure minimum thermal stress
during rolling.
7/31/2019 EHC 500 MW
12/55
Speed set point controller2.Stop reference
The output of the SSPC will be blocked
under certain condition given below. Though nRcan be changed no change will
be there in nRTD.
The controller can be enabled again afterthe TSE influence is switched off and faultreset by C&I. Then made on and SPD set
point release push button is pressed in UCB.
7/31/2019 EHC 500 MW
13/55
Speed set point controllerStop reference logic
7/31/2019 EHC 500 MW
14/55
3. Fast balance
When the set point is in tracking mode
(follow up mode) there will beinstantaneous change in nRTD valuefor a change in nR.
The controller doesnt see the gradient inthis mode.
Speed set point controller
7/31/2019 EHC 500 MW
15/55
DroopAfter synchronization ifnR is increased
then actual speed will not increase.Instead the control will open more.
The droop is set at 5%. As the rated speedis 3000 rpm,5% is 150 rpm.
The deviation of 150 rpm will correspond
to full opening or full closing of control v/v(with the assumption that full opening ofCV will give full load at rated parameters).
7/31/2019 EHC 500 MW
16/55
Droop
Droop= %51003000
30003150
X
7/31/2019 EHC 500 MW
17/55
dn/dt monitoring KWU turbine got critical speeds between
700 rpm and 2850 rpm.
It is not advisable to run turbine forprolonged time in this speed zone.
For preventing low acceleration rate dn/dt
monitoring is provided. When following conditions satisfy dn/dt
monitoring actuates and will bring the speed
to 600rpm.
7/31/2019 EHC 500 MW
18/55
dn/dt monitoring nR is more than 600 rpm
ESVs open
G. bkr NOT ON
nact less than 2850 rpm
dn/dt less than 108 rpm/min SC in action
7/31/2019 EHC 500 MW
19/55
No load pressure correctionAs the speed controller loop is PD(P)
controller an error in input must be thereto keep the control V/Vs open.
As the v/v opening required for runningm/c at rated speed is directly proportionalto steam pressure, a pressure dependent
correction signal is give to the speedcontroller loop.
Correction is approximately 20 rpm for
100 bar.
7/31/2019 EHC 500 MW
20/55
7/31/2019 EHC 500 MW
21/55
LOAD CONTROLLER Load controller is used to maintain load set
by the operator or load dispatch center
(optional) LC comes into action only after
synchronization.
LC is also responsible for taking care offrequency changes and correcting load iffrequency influence is ON.
It is divided into following subsections.
7/31/2019 EHC 500 MW
22/55
LOAD CONTROLLER Load set point
Load set point controller
Frequency influence
Load limiter
Actual load measurement Load controller loop
Isolated grid
7/31/2019 EHC 500 MW
23/55
LOAD CONTROLLER
Loadcontroller
TSE & loadgradient
UCBATRS
C&I panelCMC
Stop fastbalance
Load setPoint
Controller
Gradient
PR
PACT
CMC ON
PR
LC output0 to +10V
FI ON/OFF
Frequencyinfluence
MIN
PRTD
Loadlimiter
+
_
droop
nACT set freq(51Hz)
PRf
PRCMC
Pressurecorrection
7/31/2019 EHC 500 MW
24/55
Load set point
Load set point can be changed from desk,C&I cabinet, ATRS & CMC
Set point changes at a gradient of 250MW/min
The gradient remains the same throughout
the range Load set point PR,indicator is available UCB
. range(0-600 MW).
7/31/2019 EHC 500 MW
25/55
Load set point controller PRwhich is a step signal will be converted to
time delayed ramp signal PRTD or PRLIM by
an integrator for which gradient is decided byload gradient and TSE influence .
PRLIM indicator is available in ucb (0-600MW)
LSPC has three parts
1. Load gradient and TSE influence
2. Stop reference
7/31/2019 EHC 500 MW
26/55
Load set point controller
1) Load gradient and TSE influence
Load gradient acts in parallel with TSE
margin with a minimum selector. Load gradient range is 0-60 MW/min and
can be set from UCB
TSE margin 0-30
0
k corresponds to0 to 60 MW/min
Both are having individual ON/OFF switch.The one which is ON will control the
output.
7/31/2019 EHC 500 MW
27/55
If both are OFF then PRTDchanges at a fixed rate of60 MW/min.
If both are ON min of two will be selected for
controlling the output. Load gradient setting is common for increasing as
well as decreasing.
But in case of TSE , upper margin controls theincreasing rate and lower margin controls thedecreasing rate.
If TSE fault occurs, the gradient will be 30 MW/min(50%)
Load set point controller
7/31/2019 EHC 500 MW
28/55
Load set point controller
2) Stop reference
The PRTD will freeze on any of following conditions.
i) TSE is ON and it develops fault. It can be resetby switching OFF TSE influence and fault resetby C&I. Then made ON and Load set point
release push button is pressed in UCB.ii) Limit pressure reached AND PC in action AND
Load set point raised.
iii) Load set point controller disabled
7/31/2019 EHC 500 MW
29/55
Load set point controller
3) Fast balance
In this mode output of LSPC, PRTD, will follo
the actual load if any of the followingcondition exists
i) generator breaker is OFF
ii) Load controller OFFiii) Load shedding to less than station aux
load AND MW error> 5%
7/31/2019 EHC 500 MW
30/55
Load set point controller
This ensures PRTD brought down to zeroafter GB opening.
After synchronization PRTD tracks the actualload so that more time is not wasted inbringing PRTD from zero to working value
7/31/2019 EHC 500 MW
31/55
Frequency influence Frequency influence is used to correct PRTD.
The MW correction corresponding to frequency
deviation is added to PRTD. FI has a droop of 5% (it can be changed 2.5%
to 8.0% in steps of 0.5%). ie, a deviation of0.5 Hz will cause a load change of 100 MW.
FI can be switched ON/OFF from UCB.
UCB indicator for the correction signal is knownas PRf.(range:-200 to +200 MW).
Pressure correction is similar as that of SC
7/31/2019 EHC 500 MW
32/55
Load limiter Load limiter is used to limit the load to a
certain value set by the operator. Load limitervalue is shown in UCB indicator.(range: 0-600 MW)
Final set point (sum of PRTD & PRf )is fed to aminimum selector with the load limiter.
As load limiter acts after PRTD it can be usedfor fast reduction of load in case ofemergency.
Final set point after load limiter is know as PR
7/31/2019 EHC 500 MW
33/55
Actual load measurement
Three load transducers are used formeasurement.
Actual load 0-600 MW corresponds to 4-20 mA.
Median value of the three will be selected forprocessing.
If any value drifts from the other value by morethan 5%, the selective card discards thedefective channel.
7/31/2019 EHC 500 MW
34/55
Load controller loop
Final control loop is a PI controller.
error signal= PRPACT.
Error is fed to a PI controller which producesan output of 0 to +10V which corresponds to0-600MW.
LC has provision for two follow modesi) follow above
ii) follow low
7/31/2019 EHC 500 MW
35/55
7/31/2019 EHC 500 MW
36/55
Load controller loop
Follow lowmode is present when the GB is ONand speed controller is still in action
During this mode LC tracks the SC out put withan error of -150mV.
The LC output can go more than SC output and
hence LC can be taken into service. Due to this follow mode, the LC can be taken
into service anytime without any delay after
synchronization.
7/31/2019 EHC 500 MW
37/55
Isolated grid
Isolated grid operation will act If,
i) PR Pact >10% (50MW) AND
ii) frequency > 51 Hz AND
iii) LC in action
In this condition the controller will be changed to
proportional (P) type for fast corrective action. This condition can be eliminated by adjusting
load set point near to actual load and pressing
the Isolated grid reset button in UCB desk.
7/31/2019 EHC 500 MW
38/55
PRESSURE CONTROLLER Pressure controller maintains the throttle
pressure within working range at all loads.
Deviation= actual (PrAct) - set pressure (PrR) The operating range of deviation is 0 to+150mV
As long as deviation is more than +150mV ,the PC output remains at max saturation(+12V).
ie, for a deviation of 0 to+150mV, PC willproduce an output of 0 to+12V.
PC has two modes of operation.
PC is a PI controller
7/31/2019 EHC 500 MW
39/55
PRESSURE CONTROLLER
PrAct
Pressurecontroller
&
PrR Limitpressureselected
15ksc
15ksc
+
+
_
Pr
Limitpressure
reached
PC output0V to +12V
+
_
Limitpressureselected
7/31/2019 EHC 500 MW
40/55
PRESSURE CONTROLLER1)Initial pressure mode
In initial pressure mode PC will try to
maintain the throttle pressure. Any deviation in pressure will be adjusted
by opening or closing the control v/v.
2)Limit pressure mode
In limit pressure mode boiler storagecapacity is utilized.
There wont be any change in PC out put
till Pr deviation becomes -15 ksc.
7/31/2019 EHC 500 MW
41/55
PRESSURE CONTROLLER
Once the throttle pressure falls below the setvalue (15 kgc) then further fall in pressure isprevented by varying the control v/v positionand hence load.
p indicator is provided in UCB
Range:(-30 to +30 kgc)
Minimum EHC output is set at 30% to avoidcomplete closing of the control v/v whendeviation isve.
7/31/2019 EHC 500 MW
42/55
PRESSURE CONTROLLER
Initial pressure mode will be selected on following
conditions.1. Boiler control on manual
2. Turbine follow mode
3. IP mode selected from console
Limit pressure mode will be selected on followingconditions.
1. Boiler follow mode
2. CMC selected3. LP mode selected from console
7/31/2019 EHC 500 MW
43/55
CONTROLLER SELECTION
M
A
X
A
D
D
M
I
N
M
I
N
+10V
SC out put
-10V to +10V
LC out put0V to +10V
PC out put0V to +12V
7/31/2019 EHC 500 MW
44/55
CONTROLLER SELECTION
SC output is -10V to +10V for 0 to 150 rpm.
LC out put is 0 to +10V for 0 to 600MW.
PC output is 0V to +12V for 0 to +150mV. SC output and LC output passes through a MAX
gate.
The value selected is passed to MIN-I gate. Theother input to the MIN-I gate is the adder outputgot by adding 10V(100%) to SC output.
The MIN-I output is fed to MIN-II gate for which
the other input is PC output.
7/31/2019 EHC 500 MW
45/55
CONTROLLER SELECTION
The MIN-II gate out put is fed to the positioncontroller.
Adder is provided to prevent over speeding ofthe turbo set.
In normal condition SC output will be +1V as
nR is tracking grid speed by 15 rpm. During over speeding, nRwill stop tracking at
3060 rpm(51 Hz). At this point nRwill be
3075 rpm.
7/31/2019 EHC 500 MW
46/55
CONTROLLER SELECTION If frequency further increases at 51.25 Hz
(3075 rpm) SC output will become 0V. From thispoint onwards SC output will beve for increase
in frequency which will reduce adder output.
Suppose if m/c is at 500MW (LC active), LC outputwill be 8.33 V. If adder output comes less than this
value SC will become active and m/c will startunloading.
At 53.75 Hz (3225 rpm) SC output will be -10Vand adder output will be 0V. ie, m/c will be fullyunloaded.
7/31/2019 EHC 500 MW
47/55
POSITION CONTROLLER Position controller is a PID controller
Error signal is generated by comparing the
selection circuit output with the positionfeedback obtained from Collins transformer.
There are two Collins transformers which givesoutput voltage corresponding to piston position.
The output of the two Collins transformer passesthrough a MIN gate (logical max selector as itsout put isve) and the selected value is fed to
the controller.
7/31/2019 EHC 500 MW
48/55
POSITION CONTROLLER
7/31/2019 EHC 500 MW
49/55
POSITION CONTROLLER
Plunger coil is an integrator type.
The balance position of the pilot v/v piston is
achieved if -1.0V is fed to the plunger coil. For moving the piston in open direction the voltage
has to be increased. Say -0.9V is fed to the coil,then piston will keep on moving towards openingdirection till the voltage again made -1.0V.
Similarly if the voltage is made -1.1V, then thepiston will keep on moving towards closing
direction till voltage is again brought back to -1V.
7/31/2019 EHC 500 MW
50/55
POSITION CONTROLLERPlunger coil
7/31/2019 EHC 500 MW
51/55
POSITION CONTROLLER
Collins transformer is a differential transformerand produces output from -8.0V to +8.0V which
is converted into 0.0 to -10.0V. 0.0V output corresponds to the position at which
first control v/v just starts opening.
-10.0V corresponds to the position at which lastcontrol v/v is just full open.
A constant bias of +200mV is given for secondCollins txr so as to avoid frequent changeover
from one Collins to the other.
7/31/2019 EHC 500 MW
52/55
POSITION CONTROLLER
If at any time the difference b/w the twoCollins exceeds 700mV a fault alarm isgenerated.
There is provision to switch ON/OFF thevoltage supply to plunger coil. This can bedone only if the output of position controller
is more than +5.0V. This ensures that at the time of switching
OFF, the piston is full open and there will
not any jump after switching OFF.
7/31/2019 EHC 500 MW
53/55
POSITION CONTROLLER
If at any time during operation plungercoil wire breaks, the piston will go to
full open position and plunger coil faultalarm will be generated.
As the piston goes to full open position,
the control v/vs also will open fully.
7/31/2019 EHC 500 MW
54/55
POSITION CONTROLLER
EHC fault will occur on following condition1. Starting device faulty
2.
Collins-1 faulty3. Collins-2 faulty
4. Plunger coil faulty
5. nAct-1 ~ nAct-2 >5%
6. Turbine tripped7. Power supply faulty
8. EHC faulty
9. Speed acquisition faulty